JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Women Secondary Change Room Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 600 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 15,106 -6,091
Bypassed FA Bypassed FA 600 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 16,779 -28,457
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 31,885 -34,548
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 67,830 -8,978
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 3,392 -449
GRAND TOTAL HEAT (GTH) IN BTU / HR : 71,222 -9,427
GRAND TOTAL HEAT (GTH) IN TR : 5.94 -0.79
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.69 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 1,117 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 770
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 1,117
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No Yes
Reheater Capacity for Winter Heating RH ‹winter› kW 5.03
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW
Reheat 3.04
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 5.94 0.00 0.64
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 1,117 0
Ë FINAL SYSTEM SELECTION
Tonnage TR 5.94
Supply Air Qty CFM 1,117
Dehumidified Air Qty CFM 1,117
Return Air Qty CFM 927
Fresh Air Qty CFM 600
Reheater / Heating Coil Capacity kW 3.04
5
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Men Secondary Change Room Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Specified Inside / Room Data
Floor Area 26.51 m² Height 3.0 m Volume 2,807 ft³ Eq. Load 0 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 300 cfm ST. PR 5 inch
Exhaust Air From Room cfm Exhaust Thru' DE System Min. Air Changes 10.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 ± 2.0 °C Relative Humidity 55.0 ± 5 % Pressure Level 20.0 Pa Cleanliness Class D
Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 10.0 Pa 86 cfm Exfiltration1
Door Area m² m Percentage Free 100.0 % Pa 0 cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door 1 Area m² m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
86
Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 5 Pa 105 cfm Exfiltration1
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa
105
Selected Fresh Air Qty : 300 cfm
Outside & Inside Conditions
PARAMETER DB, °F WB, °F RH, % DP, °F Gr / lb TIME OF DAY D.RANGE,°F MONTH REMARKS
Outside
Summer 96.8 78.7 45.4 119.7 16.00 hrs 27.0 May
Monsoon 16.00 hrs 16.0 August
Winter 62.0 40.0 2.12 1.8 5.00 hrs 20.0 j$anuary
Inside 72.0 64.0 65.0 76.0 24 Hrs All Months
Differences
Summer 24.8 43.8
Monsoon
Winter -10.0 -74.2
Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Ë Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x 0.80 0.80
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling Ceiling 285.2 ft² x 24.80 0.00 -10.00 x 0.15 0.15 1,061 -428
Part. Wall Part. Wall ft² x 24.80 0.00 -10.00 x 0.35 0.35
Part. Glass Part. Glass ft² x 24.80 0.00 -10.00 x
Floor Floor ft² x 24.80 0.00 -10.00 x
Gain From Internal Sources
People People 20 nos x 269.0 5,380 5,380
Equipment Equipment 0.00 kW 0.80 0.80 0.80 x 3400.0 xUF 0 0
Lights Lights 570 W x 3.4 xBl.F 1.25 2,425 2,425
Hot Surface Hot Surface W x 1.00 1.00 1.00 x 3.41 0
Infiltration Infiltration cfm x x 1.08 0
Infiltration Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 8,866 7,377
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 665 553
Draw Thru' AHU Motor Draw Thru' AHU Motor 0.5 kW x % 1,771 1,771
Bypassed FA Bypassed FA 300 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.06 482 -194
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 11,784 9,507
Ë Latent Heat
People People 20 nos x 231.0 4,620 4,620
Appliances Appliances kW x 3400.0 xUF
Steam Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 Infiltration0 cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 4,620 4,620
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 347 347
Bypassed FA Bypassed FA 300 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.06 536 -908
EFFECTIVE ROOM LATENT HEAT (ERLH) : 5,502 4,058
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 17,286 13,565
Ë Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
6
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Men Secondary Change Room Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 300 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 7,553 -3,046
Bypassed FA Bypassed FA 300 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 8,390 -14,229
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 15,943 -17,274
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 33,229 -3,709
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 1,661 -185
GRAND TOTAL HEAT (GTH) IN BTU / HR : 34,890 -3,894
GRAND TOTAL HEAT (GTH) IN TR : 2.91 -0.32
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.68 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 528 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 468
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 528
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No Yes
Reheater Capacity for Winter Heating RH ‹winter› kW 2.28
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW
Reheat 1.09
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 2.91 0.00 0.32
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 528 0
Ë FINAL SYSTEM SELECTION
Tonnage TR 2.91
Supply Air Qty CFM 528
Dehumidified Air Qty CFM 528
Return Air Qty CFM 338
Fresh Air Qty CFM 300
Reheater / Heating Coil Capacity kW 1.09
7
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Women Airlock Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Specified Inside / Room Data
Floor Area 8.31 m² Height 3.0 m Volume 880 ft³ Eq. Load 0 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 60 cfm ST. PR 5 inch
Exhaust Air From Room cfm Exhaust Thru' DE System Min. Air Changes 10.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 ± 2.0 °C Relative Humidity 55.0 ± 5 % Pressure Level 10.0 Pa Cleanliness Class D
Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20.0 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa 0 cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door 1 Area m² m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
-86
Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa
(86)
Selected Fresh Air Qty : 60 cfm
Outside & Inside Conditions
PARAMETER DB, °F WB, °F RH, % DP, °F Gr / lb TIME OF DAY D.RANGE,°F MONTH REMARKS
Outside
Summer 96.8 78.7 45.4 119.7 16.00 hrs 27.0 May
Monsoon 16.00 hrs 16.0 August
Winter 62.0 40.0 2.12 1.8 5.00 hrs 20.0 j$anuary
Inside 72.0 64.0 65.0 76.0 24 Hrs All Months
Differences
Summer 24.8 43.8
Monsoon
Winter -10.0 -74.2
Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Ë Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x 0.80 0.80
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling Ceiling 89.4 ft² x 24.80 0.00 -10.00 x 0.15 0.15 333 -134
Part. Wall Part. Wall ft² x 24.80 0.00 -10.00 x 0.35 0.35
Part. Glass Part. Glass ft² x 24.80 0.00 -10.00 x
Floor Floor ft² x 24.80 0.00 -10.00 x
Gain From Internal Sources
People People 4 nos x 269.0 1,076 1,076
Equipment Equipment 0.00 kW 0.80 0.80 0.80 x 3400.0 xUF 0 0
Lights Lights 179 W x 3.4 xBl.F 1.25 760 760
Hot Surface Hot Surface W x 1.00 1.00 1.00 x 3.41 0
Infiltration Infiltration cfm x x 1.08 0
Infiltration Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 2,169 1,702
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 163 128
Draw Thru' AHU Motor Draw Thru' AHU Motor 0.1 kW x % 493 493
Bypassed FA Bypassed FA 60 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.06 96 -39
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 2,921 2,284
Ë Latent Heat
People People 4 nos x 231.0 924 924
Appliances Appliances kW x 3400.0 xUF
Steam Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 Infiltration0 cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 924 924
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 69 69
Bypassed FA Bypassed FA 60 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.06 107 -182
EFFECTIVE ROOM LATENT HEAT (ERLH) : 1,100 812
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 4,021 3,096
Ë Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
8
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Women Airlock Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 60 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 1,511 -609
Bypassed FA Bypassed FA 60 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 1,678 -2,846
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 3,189 -3,455
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 7,210 -359
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 360 -18
GRAND TOTAL HEAT (GTH) IN BTU / HR : 7,570 -377
GRAND TOTAL HEAT (GTH) IN TR : 0.63 -0.03
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.73 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 131 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 147
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 147
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No Yes
Reheater Capacity for Winter Heating RH ‹winter› kW 0.34
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW
Reheat 0.27
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 0.63 0.00 0.07
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 131 0
Ë FINAL SYSTEM SELECTION
Tonnage TR 0.63
Supply Air Qty CFM 147
Dehumidified Air Qty CFM 131
Return Air Qty CFM 318
Fresh Air Qty CFM 60
Reheater / Heating Coil Capacity kW 0.27
9
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : men Airlock Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Specified Inside / Room Data
Floor Area 8.31 m² Height 3.0 m Volume 880 ft³ Eq. Load 0 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 60 cfm ST. PR 5 inch
Exhaust Air From Room cfm Exhaust Thru' DE System Min. Air Changes 10.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 ± 2.0 °C Relative Humidity 55.0 ± 5 % Pressure Level 10.0 Pa Cleanliness Class D
Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20.0 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa 0 cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door 1 Area m² m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
-86
Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa
(86)
Selected Fresh Air Qty : 60 cfm
Outside & Inside Conditions
PARAMETER DB, °F WB, °F RH, % DP, °F Gr / lb TIME OF DAY D.RANGE,°F MONTH REMARKS
Outside
Summer 96.8 78.7 45.4 119.7 16.00 hrs 27.0 May
Monsoon 16.00 hrs 16.0 August
Winter 62.0 40.0 2.12 1.8 5.00 hrs 20.0 j$anuary
Inside 72.0 64.0 65.0 76.0 24 Hrs All Months
Differences
Summer 24.8 43.8
Monsoon
Winter -10.0 -74.2
Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Ë Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x 0.80 0.80
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling Ceiling 89.4 ft² x 24.80 0.00 -10.00 x 0.15 0.15 333 -134
Part. Wall Part. Wall ft² x 24.80 0.00 -10.00 x 0.35 0.35
Part. Glass Part. Glass ft² x 24.80 0.00 -10.00 x
Floor Floor ft² x 24.80 0.00 -10.00 x
Gain From Internal Sources
People People 4 nos x 269.0 1,076 1,076
Equipment Equipment 0.00 kW 0.80 0.80 0.80 x 3400.0 xUF 0 0
Lights Lights 179 W x 3.4 xBl.F 1.25 760 760
Hot Surface Hot Surface W x 1.00 1.00 1.00 x 3.41 0
Infiltration Infiltration cfm x x 1.08 0
Infiltration Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 2,169 1,702
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 163 128
Draw Thru' AHU Motor Draw Thru' AHU Motor 0.1 kW x % 493 493
Bypassed FA Bypassed FA 60 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.06 96 -39
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 2,921 2,284
Ë Latent Heat
People People 4 nos x 231.0 924 924
Appliances Appliances kW x 3400.0 xUF
Steam Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 Infiltration0 cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 924 924
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 69 69
Bypassed FA Bypassed FA 60 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.06 107 -182
EFFECTIVE ROOM LATENT HEAT (ERLH) : 1,100 812
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 4,021 3,096
Ë Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
10
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : men Airlock Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 60 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 1,511 -609
Bypassed FA Bypassed FA 60 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 1,678 -2,846
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 3,189 -3,455
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 7,210 -359
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 360 -18
GRAND TOTAL HEAT (GTH) IN BTU / HR : 7,570 -377
GRAND TOTAL HEAT (GTH) IN TR : 0.63 -0.03
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.73 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 131 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 147
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 147
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No Yes
Reheater Capacity for Winter Heating RH ‹winter› kW 0.34
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW
Reheat 0.27
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 0.63 0.00 0.07
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 131 0
Ë FINAL SYSTEM SELECTION
Tonnage TR 0.63
Supply Air Qty CFM 147
Dehumidified Air Qty CFM 131
Return Air Qty CFM 318
Fresh Air Qty CFM 60
Reheater / Heating Coil Capacity kW 0.27
11
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Airlock for Visitors Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Specified Inside / Room Data
Floor Area 6.43 m² Height 3.0 m Volume 681 ft³ Eq. Load 0 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 30 cfm ST. PR 5 inch
Exhaust Air From Room cfm Exhaust Thru' DE System Min. Air Changes 10.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 ± 2.0 °C Relative Humidity 55.0 ± 5 % Pressure Level 20.0 Pa Cleanliness Class D
Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 10.0 Pa 86 cfm Exfiltration1
Door Area m² m Percentage Free 100.0 % Pa 0 cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door 1 Area m² m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
86
Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 5 Pa 105 cfm Exfiltration1
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa
105
Selected Fresh Air Qty : 30 cfm
Outside & Inside Conditions
PARAMETER DB, °F WB, °F RH, % DP, °F Gr / lb TIME OF DAY D.RANGE,°F MONTH REMARKS
Outside
Summer 96.8 78.7 45.4 119.7 16.00 hrs 27.0 May
Monsoon 16.00 hrs 16.0 August
Winter 62.0 40.0 2.12 1.8 5.00 hrs 20.0 j$anuary
Inside 72.0 64.0 65.0 76.0 24 Hrs All Months
Differences
Summer 24.8 43.8
Monsoon
Winter -10.0 -74.2
Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Ë Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x 0.80 0.80
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling Ceiling 69.2 ft² x 24.80 0.00 -10.00 x 0.15 0.15 257 -104
Part. Wall Part. Wall ft² x 24.80 0.00 -10.00 x 0.35 0.35
Part. Glass Part. Glass ft² x 24.80 0.00 -10.00 x
Floor Floor ft² x 24.80 0.00 -10.00 x
Gain From Internal Sources
People People 2 nos x 269.0 538 538
Equipment Equipment 0.00 kW 0.80 0.80 0.80 x 3400.0 xUF 0 0
Lights Lights 138 W x 3.4 xBl.F 1.25 588 588
Hot Surface Hot Surface W x 1.00 1.00 1.00 x 3.41 0
Infiltration Infiltration cfm x x 1.08 0
Infiltration Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 1,383 1,022
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 104 77
Draw Thru' AHU Motor Draw Thru' AHU Motor 0.2 kW x % 671 671
Bypassed FA Bypassed FA 30 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.06 48 -19
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 2,206 1,751
Ë Latent Heat
People People 2 nos x 231.0 462 462
Appliances Appliances kW x 3400.0 xUF
Steam Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 Infiltration0 cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 462 462
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 35 35
Bypassed FA Bypassed FA 30 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.06 54 -91
EFFECTIVE ROOM LATENT HEAT (ERLH) : 550 406
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 2,757 2,156
Ë Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
12
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Airlock for Visitors Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 30 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 755 -305
Bypassed FA Bypassed FA 30 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 839 -1,423
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 1,594 -1,727
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 4,351 429
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 218 21
GRAND TOTAL HEAT (GTH) IN BTU / HR : 4,568 450
GRAND TOTAL HEAT (GTH) IN TR : 0.38 0.04
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.80 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 99 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 113
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 113
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No No
Reheater Capacity for Winter Heating RH ‹winter› kW
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW
Reheat 0.18
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 0.38 0.00 0.04
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 99 0
Ë FINAL SYSTEM SELECTION
Tonnage TR 0.38
Supply Air Qty CFM 200
Dehumidified Air Qty CFM 99
Return Air Qty CFM 0
Fresh Air Qty CFM 30
Reheater / Heating Coil Capacity kW 0.18
13
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Sec. Airlock for Visitors Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Specified Inside / Room Data
Floor Area 6.17 m² Height 3.0 m Volume 653 ft³ Eq. Load 0 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 30 cfm ST. PR 5 inch
Exhaust Air From Room cfm Exhaust Thru' DE System Min. Air Changes 10.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 ± 2.0 °C Relative Humidity 55.0 ± 5 % Pressure Level 10.0 Pa Cleanliness Class D
Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20.0 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa 0 cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door 1 Area m² m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
-86
Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa
(86)
Selected Fresh Air Qty : 30 cfm
Outside & Inside Conditions
PARAMETER DB, °F WB, °F RH, % DP, °F Gr / lb TIME OF DAY D.RANGE,°F MONTH REMARKS
Outside
Summer 96.8 78.7 45.4 119.7 16.00 hrs 27.0 May
Monsoon 16.00 hrs 16.0 August
Winter 62.0 40.0 2.12 1.8 5.00 hrs 20.0 j$anuary
Inside 72.0 64.0 65.0 76.0 24 Hrs All Months
Differences
Summer 24.8 43.8
Monsoon
Winter -10.0 -74.2
Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Ë Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x 0.80 0.80
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling Ceiling 66.4 ft² x 24.80 0.00 -10.00 x 0.15 0.15 247 -100
Part. Wall Part. Wall ft² x 24.80 0.00 -10.00 x 0.35 0.35
Part. Glass Part. Glass ft² x 24.80 0.00 -10.00 x
Floor Floor ft² x 24.80 0.00 -10.00 x
Gain From Internal Sources
People People 2 nos x 269.0 538 538
Equipment Equipment 0.00 kW 0.80 0.80 0.80 x 3400.0 xUF 0 0
Lights Lights 133 W x 3.4 xBl.F 1.25 564 564
Hot Surface Hot Surface W x 1.00 1.00 1.00 x 3.41 0
Infiltration Infiltration cfm x x 1.08 0
Infiltration Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 1,349 1,003
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 101 75
Draw Thru' AHU Motor Draw Thru' AHU Motor 0.1 kW x % 366 366
Bypassed FA Bypassed FA 30 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.06 48 -19
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 1,864 1,424
Ë Latent Heat
People People 2 nos x 231.0 462 462
Appliances Appliances kW x 3400.0 xUF
Steam Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 Infiltration0 cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 462 462
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 35 35
Bypassed FA Bypassed FA 30 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.06 54 -91
EFFECTIVE ROOM LATENT HEAT (ERLH) : 550 406
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 2,415 1,830
Ë Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
14
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Sec. Airlock for Visitors Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 30 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 755 -305
Bypassed FA Bypassed FA 30 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 839 -1,423
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 1,594 -1,727
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 4,009 103
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 200 5
GRAND TOTAL HEAT (GTH) IN BTU / HR : 4,209 108
GRAND TOTAL HEAT (GTH) IN TR : 0.35 0.01
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.77 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 83 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 109
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 109
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No Yes
Reheater Capacity for Winter Heating RH ‹winter› kW 0.09
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW
Reheat 0.17
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 0.35 0.00 0.03
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 83 0
Ë FINAL SYSTEM SELECTION
Tonnage TR 0.35
Supply Air Qty CFM 109
Dehumidified Air Qty CFM 83
Return Air Qty CFM 280
Fresh Air Qty CFM 30
Reheater / Heating Coil Capacity kW 0.17
15