TR Supply CFM Deh CFM

Women Secondary Change Room 5.94 1,117 1,117


Men Secondary Change Room 2.91 528 528
Women Airlock 0.63 147 131
men Airlock 0.63 147 131
Airlock for Visitors 0.38 200 99
Sec. Airlock for Visitors 0.35 109 83

10.84 2,248.00 2,089.00

As per Encon 11.42 2261 1401


Return CFM Fresh Air CFM Fan CFM Bleed CFM Reheat kW
927 600 3.04
338 300 1.09
318 60 0.27
318 60 0.27
0 30 0.18
280 30 0.17

2,180.58 1,080.00 3,261 1,013 5.02

1661 1080 2741 480 3.73


Table : 1 :: Building Constructions & "U"-Factors

Id. Summer U- Winter U-


Item Material of Construction Remarks (if any)
No Factor Factor
Exp. Glass Exp. Glass 5.5 mm thk. Clear Sheet Glass 1.13 1.13
Exp. Glass (R) Exp. Glass (R) 5.5 mm thk. Clear Sheet Glass 1.00 1.00 Radiation Factor
Part. Glass Part. Glass 5.5 mm thk. Toughened / Clear Sheet Glass 1.13 1.13
Exp. Wall Exp. Wall 225 mm thk. Brick Wall + 10 mm thk. Sand Plaster on 0.34 0.35
both sides.
Part. Wall Part. Wall 100mm thk. Brick Wall + 10 mm thk. Sand Plaster on 0.42 0.42
both sides.
Part. Wall 2 Part. Wall2 450 mm thk. Brick Wall + 20 mm thk. Sand Plaster on 0.20 0.20
both sides.
Roof Exposed 150 mm thk. RC Slab + 10 mm thk. Plaster on both 0.13 0.13
sides.50mm EPS insulation
Ceiling Ceiling 150 mm thk. RC Slab + 10 mm thk. Plaster on both 0.31 0.31
sides.
Floor Floor 150 mm thk. RC Slab + 10 mm thk. Plaster on both 0.35 0.35
sides.

Table : 2 :: Solar Heat Gain Thru' Glass


Solar Gain (FPS Unit)
Direction
For Summer-(May) For Monsoon-(July) For Winter-(January)
East Exp. GlassEast 12.00 12.00 8.00
West Exp. GlassWest 163.00 163.00 128.00
North Exp. GlassNorth 23.00 23.00 8.00
South Exp. GlassSouth 12.00 12.00 69.00
NE Exp. GlassNE 12.00 12.00 8.00
SE Exp. GlassSE 12.00 12.00 8.00
NW Exp. GlassNW 138.00 138.00 26.00
SW Exp. GlassSW 113.00 113.00 144.00
SW Exp. GlassSW 113.00 113.00 144.00

Table : 3 :: Equivalent Temp. Diff. Thru' Wall & Roof


Solar Gain (FPS Unit)
Item / Direction
For Summer For Monsoon For Winter
Exp. Wall
East Exp. WallEast 25.00 20.00 -22.00 Shaded Walls
West Exp. WallWest 19.00 14.00 -20.00 Shaded Walls
North Exp. WallNorth 11.00 6.00 -27.00 Shaded Walls
South Exp. WallSouth 23.00 18.00 -23.00 Shaded Walls
NE Exp. WallNE 17.00 12.00 -23.00
SE Exp. WallSE 25.00 20.00 -21.00
NW Exp. WallNW 13.00 8.00 -23.00
SW Exp. WallSW 21.00 16.00 -23.00
Roof
Shaded RoofShaded 15.00 10.00 -30.00
Exposed RoofExposed 57.00 44.00 -37.25
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Women Secondary Change Room Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
 Specified Inside / Room Data
Floor Area 43.64 m² Height 3.0 m Volume 4,621 ft³ Eq. Load 0 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 600 cfm ST. PR 5 inch
Exhaust Air From Room cfm Exhaust Thru' DE System Min. Air Changes 10.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 22.0 ± 2.0 °C Relative Humidity 65.0 ± 5 % Pressure Level 20.0 Pa Cleanliness Class D
 Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 10.0 Pa 86 cfm Exfiltration1
Door Area m² m Percentage Free 100.0 % Pa 0 cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door 1 Area m² m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
86
 Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 5 Pa 105 cfm Exfiltration1
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa
105
 Selected Fresh Air Qty : 600 cfm
 Outside & Inside Conditions
PARAMETER DB, °F WB, °F RH, % DP, °F Gr / lb TIME OF DAY D.RANGE,°F MONTH REMARKS
Outside
Summer 96.8 78.7 45.4 119.7 16.00 hrs 27.0 May
Monsoon 16.00 hrs 16.0 August
Winter 62.0 40.0 2.12 1.8 5.00 hrs 20.0 j$anuary
Inside 72.0 64.0 65.0 76.0 24 Hrs  All Months
Differences
Summer 24.8    43.8   
Monsoon      
Winter -10.0    -74.2   
 Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Ë Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x 0.80 0.80
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling Ceiling 469.6 ft² x 24.80 0.00 -10.00 x 0.15 0.15 1,747 -704
Part. Wall Part. Wall 267.28 ft² x 24.80 0.00 -10.00 x 0.35 0.35 2,320 -935
Part. Glass Part. Glass ft² x 24.80 0.00 -10.00 x
Floor Floor ft² x 24.80 0.00 -10.00 x
Gain From Internal Sources
People People 40 nos x 269.0 10,760 10,760
Equipment Equipment 0.00 kW 0.80 0.80 0.80 x 3400.0 xUF 0 0
Lights Lights 939 W x 3.4 xBl.F 1.25 3,991 3,991
Hot Surface Hot Surface W x 1.00 1.00 1.00 x 3.41 0
Infiltration Infiltration cfm x x 1.08 0
Infiltration Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 18,818 13,111
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 1,411 983
Draw Thru' AHU Motor Draw Thru' AHU Motor 1.1 kW x % 3,748 3,748
Bypassed FA Bypassed FA 600 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.06 964 -389
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 24,941 17,454
Ë Latent Heat
People People 40 nos x 231.0 9,240 9,240
Appliances Appliances kW x 3400.0 xUF
Steam Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 Infiltration0 cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 9,240 9,240
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 693 693
Bypassed FA Bypassed FA 600 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.06 1,071 -1,816
EFFECTIVE ROOM LATENT HEAT (ERLH) : 11,004 8,117
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 35,945 25,570
Ë Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x

4
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Women Secondary Change Room Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 600 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 15,106 -6,091
Bypassed FA Bypassed FA 600 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 16,779 -28,457
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 31,885 -34,548
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 67,830 -8,978
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 3,392 -449
GRAND TOTAL HEAT (GTH) IN BTU / HR : 71,222 -9,427
GRAND TOTAL HEAT (GTH) IN TR : 5.94 -0.79
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.69 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 1,117 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 770 
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 1,117 
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No Yes
Reheater Capacity for Winter Heating RH ‹winter› kW   5.03
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW 
Reheat 3.04
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 5.94 0.00 0.64
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 1,117 0 
Ë FINAL SYSTEM SELECTION
Tonnage TR 5.94
Supply Air Qty CFM 1,117
Dehumidified Air Qty CFM 1,117
Return Air Qty CFM 927
Fresh Air Qty CFM 600
Reheater / Heating Coil Capacity kW 3.04

5
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Men Secondary Change Room Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
 Specified Inside / Room Data
Floor Area 26.51 m² Height 3.0 m Volume 2,807 ft³ Eq. Load 0 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 300 cfm ST. PR 5 inch
Exhaust Air From Room cfm Exhaust Thru' DE System Min. Air Changes 10.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 ± 2.0 °C Relative Humidity 55.0 ± 5 % Pressure Level 20.0 Pa Cleanliness Class D
 Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 10.0 Pa 86 cfm Exfiltration1
Door Area m² m Percentage Free 100.0 % Pa 0 cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door 1 Area m² m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
86
 Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 5 Pa 105 cfm Exfiltration1
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa
105
 Selected Fresh Air Qty : 300 cfm
 Outside & Inside Conditions
PARAMETER DB, °F WB, °F RH, % DP, °F Gr / lb TIME OF DAY D.RANGE,°F MONTH REMARKS
Outside
Summer 96.8 78.7 45.4 119.7 16.00 hrs 27.0 May
Monsoon 16.00 hrs 16.0 August
Winter 62.0 40.0 2.12 1.8 5.00 hrs 20.0 j$anuary
Inside 72.0 64.0 65.0 76.0 24 Hrs  All Months
Differences
Summer 24.8    43.8   
Monsoon      
Winter -10.0    -74.2   
 Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Ë Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x 0.80 0.80
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling Ceiling 285.2 ft² x 24.80 0.00 -10.00 x 0.15 0.15 1,061 -428
Part. Wall Part. Wall ft² x 24.80 0.00 -10.00 x 0.35 0.35
Part. Glass Part. Glass ft² x 24.80 0.00 -10.00 x
Floor Floor ft² x 24.80 0.00 -10.00 x
Gain From Internal Sources
People People 20 nos x 269.0 5,380 5,380
Equipment Equipment 0.00 kW 0.80 0.80 0.80 x 3400.0 xUF 0 0
Lights Lights 570 W x 3.4 xBl.F 1.25 2,425 2,425
Hot Surface Hot Surface W x 1.00 1.00 1.00 x 3.41 0
Infiltration Infiltration cfm x x 1.08 0
Infiltration Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 8,866 7,377
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 665 553
Draw Thru' AHU Motor Draw Thru' AHU Motor 0.5 kW x % 1,771 1,771
Bypassed FA Bypassed FA 300 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.06 482 -194
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 11,784 9,507
Ë Latent Heat
People People 20 nos x 231.0 4,620 4,620
Appliances Appliances kW x 3400.0 xUF
Steam Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 Infiltration0 cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 4,620 4,620
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 347 347
Bypassed FA Bypassed FA 300 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.06 536 -908
EFFECTIVE ROOM LATENT HEAT (ERLH) : 5,502 4,058
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 17,286 13,565
Ë Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x

6
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Men Secondary Change Room Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 300 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 7,553 -3,046
Bypassed FA Bypassed FA 300 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 8,390 -14,229
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 15,943 -17,274
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 33,229 -3,709
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 1,661 -185
GRAND TOTAL HEAT (GTH) IN BTU / HR : 34,890 -3,894
GRAND TOTAL HEAT (GTH) IN TR : 2.91 -0.32
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.68 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 528 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 468 
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 528 
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No Yes
Reheater Capacity for Winter Heating RH ‹winter› kW   2.28
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW 
Reheat 1.09
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 2.91 0.00 0.32
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 528 0 
Ë FINAL SYSTEM SELECTION
Tonnage TR 2.91
Supply Air Qty CFM 528
Dehumidified Air Qty CFM 528
Return Air Qty CFM 338
Fresh Air Qty CFM 300
Reheater / Heating Coil Capacity kW 1.09

7
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Women Airlock Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
 Specified Inside / Room Data
Floor Area 8.31 m² Height 3.0 m Volume 880 ft³ Eq. Load 0 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 60 cfm ST. PR 5 inch
Exhaust Air From Room cfm Exhaust Thru' DE System Min. Air Changes 10.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 ± 2.0 °C Relative Humidity 55.0 ± 5 % Pressure Level 10.0 Pa Cleanliness Class D
 Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20.0 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa 0 cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door 1 Area m² m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
-86
 Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa
(86)
 Selected Fresh Air Qty : 60 cfm
 Outside & Inside Conditions
PARAMETER DB, °F WB, °F RH, % DP, °F Gr / lb TIME OF DAY D.RANGE,°F MONTH REMARKS
Outside
Summer 96.8 78.7 45.4 119.7 16.00 hrs 27.0 May
Monsoon 16.00 hrs 16.0 August
Winter 62.0 40.0 2.12 1.8 5.00 hrs 20.0 j$anuary
Inside 72.0 64.0 65.0 76.0 24 Hrs  All Months
Differences
Summer 24.8    43.8   
Monsoon      
Winter -10.0    -74.2   
 Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Ë Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x 0.80 0.80
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling Ceiling 89.4 ft² x 24.80 0.00 -10.00 x 0.15 0.15 333 -134
Part. Wall Part. Wall ft² x 24.80 0.00 -10.00 x 0.35 0.35
Part. Glass Part. Glass ft² x 24.80 0.00 -10.00 x
Floor Floor ft² x 24.80 0.00 -10.00 x
Gain From Internal Sources
People People 4 nos x 269.0 1,076 1,076
Equipment Equipment 0.00 kW 0.80 0.80 0.80 x 3400.0 xUF 0 0
Lights Lights 179 W x 3.4 xBl.F 1.25 760 760
Hot Surface Hot Surface W x 1.00 1.00 1.00 x 3.41 0
Infiltration Infiltration cfm x x 1.08 0
Infiltration Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 2,169 1,702
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 163 128
Draw Thru' AHU Motor Draw Thru' AHU Motor 0.1 kW x % 493 493
Bypassed FA Bypassed FA 60 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.06 96 -39
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 2,921 2,284
Ë Latent Heat
People People 4 nos x 231.0 924 924
Appliances Appliances kW x 3400.0 xUF
Steam Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 Infiltration0 cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 924 924
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 69 69
Bypassed FA Bypassed FA 60 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.06 107 -182
EFFECTIVE ROOM LATENT HEAT (ERLH) : 1,100 812
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 4,021 3,096
Ë Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x

8
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Women Airlock Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 60 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 1,511 -609
Bypassed FA Bypassed FA 60 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 1,678 -2,846
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 3,189 -3,455
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 7,210 -359
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 360 -18
GRAND TOTAL HEAT (GTH) IN BTU / HR : 7,570 -377
GRAND TOTAL HEAT (GTH) IN TR : 0.63 -0.03
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.73 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 131 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 147 
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 147 
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No Yes
Reheater Capacity for Winter Heating RH ‹winter› kW   0.34
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW 
Reheat 0.27
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 0.63 0.00 0.07
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 131 0 
Ë FINAL SYSTEM SELECTION
Tonnage TR 0.63
Supply Air Qty CFM 147
Dehumidified Air Qty CFM 131
Return Air Qty CFM 318
Fresh Air Qty CFM 60
Reheater / Heating Coil Capacity kW 0.27

9
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : men Airlock Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
 Specified Inside / Room Data
Floor Area 8.31 m² Height 3.0 m Volume 880 ft³ Eq. Load 0 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 60 cfm ST. PR 5 inch
Exhaust Air From Room cfm Exhaust Thru' DE System Min. Air Changes 10.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 ± 2.0 °C Relative Humidity 55.0 ± 5 % Pressure Level 10.0 Pa Cleanliness Class D
 Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20.0 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa 0 cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door 1 Area m² m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
-86
 Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa
(86)
 Selected Fresh Air Qty : 60 cfm
 Outside & Inside Conditions
PARAMETER DB, °F WB, °F RH, % DP, °F Gr / lb TIME OF DAY D.RANGE,°F MONTH REMARKS
Outside
Summer 96.8 78.7 45.4 119.7 16.00 hrs 27.0 May
Monsoon 16.00 hrs 16.0 August
Winter 62.0 40.0 2.12 1.8 5.00 hrs 20.0 j$anuary
Inside 72.0 64.0 65.0 76.0 24 Hrs  All Months
Differences
Summer 24.8    43.8   
Monsoon      
Winter -10.0    -74.2   
 Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Ë Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x 0.80 0.80
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling Ceiling 89.4 ft² x 24.80 0.00 -10.00 x 0.15 0.15 333 -134
Part. Wall Part. Wall ft² x 24.80 0.00 -10.00 x 0.35 0.35
Part. Glass Part. Glass ft² x 24.80 0.00 -10.00 x
Floor Floor ft² x 24.80 0.00 -10.00 x
Gain From Internal Sources
People People 4 nos x 269.0 1,076 1,076
Equipment Equipment 0.00 kW 0.80 0.80 0.80 x 3400.0 xUF 0 0
Lights Lights 179 W x 3.4 xBl.F 1.25 760 760
Hot Surface Hot Surface W x 1.00 1.00 1.00 x 3.41 0
Infiltration Infiltration cfm x x 1.08 0
Infiltration Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 2,169 1,702
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 163 128
Draw Thru' AHU Motor Draw Thru' AHU Motor 0.1 kW x % 493 493
Bypassed FA Bypassed FA 60 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.06 96 -39
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 2,921 2,284
Ë Latent Heat
People People 4 nos x 231.0 924 924
Appliances Appliances kW x 3400.0 xUF
Steam Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 Infiltration0 cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 924 924
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 69 69
Bypassed FA Bypassed FA 60 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.06 107 -182
EFFECTIVE ROOM LATENT HEAT (ERLH) : 1,100 812
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 4,021 3,096
Ë Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x

10
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : men Airlock Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 60 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 1,511 -609
Bypassed FA Bypassed FA 60 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 1,678 -2,846
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 3,189 -3,455
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 7,210 -359
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 360 -18
GRAND TOTAL HEAT (GTH) IN BTU / HR : 7,570 -377
GRAND TOTAL HEAT (GTH) IN TR : 0.63 -0.03
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.73 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 131 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 147 
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 147 
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No Yes
Reheater Capacity for Winter Heating RH ‹winter› kW   0.34
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW 
Reheat 0.27
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 0.63 0.00 0.07
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 131 0 
Ë FINAL SYSTEM SELECTION
Tonnage TR 0.63
Supply Air Qty CFM 147
Dehumidified Air Qty CFM 131
Return Air Qty CFM 318
Fresh Air Qty CFM 60
Reheater / Heating Coil Capacity kW 0.27

11
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Airlock for Visitors Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
 Specified Inside / Room Data
Floor Area 6.43 m² Height 3.0 m Volume 681 ft³ Eq. Load 0 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 30 cfm ST. PR 5 inch
Exhaust Air From Room cfm Exhaust Thru' DE System Min. Air Changes 10.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 ± 2.0 °C Relative Humidity 55.0 ± 5 % Pressure Level 20.0 Pa Cleanliness Class D
 Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 10.0 Pa 86 cfm Exfiltration1
Door Area m² m Percentage Free 100.0 % Pa 0 cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door 1 Area m² m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
86
 Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 5 Pa 105 cfm Exfiltration1
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa
105
 Selected Fresh Air Qty : 30 cfm
 Outside & Inside Conditions
PARAMETER DB, °F WB, °F RH, % DP, °F Gr / lb TIME OF DAY D.RANGE,°F MONTH REMARKS
Outside
Summer 96.8 78.7 45.4 119.7 16.00 hrs 27.0 May
Monsoon 16.00 hrs 16.0 August
Winter 62.0 40.0 2.12 1.8 5.00 hrs 20.0 j$anuary
Inside 72.0 64.0 65.0 76.0 24 Hrs  All Months
Differences
Summer 24.8    43.8   
Monsoon      
Winter -10.0    -74.2   
 Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Ë Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x 0.80 0.80
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling Ceiling 69.2 ft² x 24.80 0.00 -10.00 x 0.15 0.15 257 -104
Part. Wall Part. Wall ft² x 24.80 0.00 -10.00 x 0.35 0.35
Part. Glass Part. Glass ft² x 24.80 0.00 -10.00 x
Floor Floor ft² x 24.80 0.00 -10.00 x
Gain From Internal Sources
People People 2 nos x 269.0 538 538
Equipment Equipment 0.00 kW 0.80 0.80 0.80 x 3400.0 xUF 0 0
Lights Lights 138 W x 3.4 xBl.F 1.25 588 588
Hot Surface Hot Surface W x 1.00 1.00 1.00 x 3.41 0
Infiltration Infiltration cfm x x 1.08 0
Infiltration Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 1,383 1,022
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 104 77
Draw Thru' AHU Motor Draw Thru' AHU Motor 0.2 kW x % 671 671
Bypassed FA Bypassed FA 30 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.06 48 -19
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 2,206 1,751
Ë Latent Heat
People People 2 nos x 231.0 462 462
Appliances Appliances kW x 3400.0 xUF
Steam Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 Infiltration0 cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 462 462
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 35 35
Bypassed FA Bypassed FA 30 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.06 54 -91
EFFECTIVE ROOM LATENT HEAT (ERLH) : 550 406
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 2,757 2,156
Ë Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x

12
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Airlock for Visitors Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 30 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 755 -305
Bypassed FA Bypassed FA 30 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 839 -1,423
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 1,594 -1,727
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 4,351 429
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 218 21
GRAND TOTAL HEAT (GTH) IN BTU / HR : 4,568 450
GRAND TOTAL HEAT (GTH) IN TR : 0.38 0.04
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.80 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 99 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 113 
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 113 
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No No
Reheater Capacity for Winter Heating RH ‹winter› kW  
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW 
Reheat 0.18
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 0.38 0.00 0.04
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 99 0 
Ë FINAL SYSTEM SELECTION
Tonnage TR 0.38
Supply Air Qty CFM 200
Dehumidified Air Qty CFM 99
Return Air Qty CFM 0
Fresh Air Qty CFM 30
Reheater / Heating Coil Capacity kW 0.18

13
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Sec. Airlock for Visitors Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
 Specified Inside / Room Data
Floor Area 6.17 m² Height 3.0 m Volume 653 ft³ Eq. Load 0 kW
FA Qty (if given) cfm Min.FA Circulation 1.0 ac / hr Min. FA Qty 30 cfm ST. PR 5 inch
Exhaust Air From Room cfm Exhaust Thru' DE System Min. Air Changes 10.0 per hr Lighting 2 W/sqft
Dry Bulb Temperature 23.0 ± 2.0 °C Relative Humidity 55.0 ± 5 % Pressure Level 10.0 Pa Cleanliness Class D
 Infiltration / Exfiltration Calculations Within System
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20.0 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa 0 cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door 1 Area m² m Percentage Free 100.0 % 0.0 Pa 0 cfm ###
-86
 Infiltration / Exfiltration Calculations & Fresh Air Selection
ADj$ACENT AREA AT
THRU' NOS. DIMENSIONS & DETAILS INFIL'N / EXFIL'N AIR QTY
PRESSURE DB (°F) Gr / lb
Door 1 1 Area 0.0100 m² m Percentage Free 100.0 % 20 Pa 86 cfm Infiltration1
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa cfm
Door Area m² m Percentage Free 100.0 % Pa
(86)
 Selected Fresh Air Qty : 30 cfm
 Outside & Inside Conditions
PARAMETER DB, °F WB, °F RH, % DP, °F Gr / lb TIME OF DAY D.RANGE,°F MONTH REMARKS
Outside
Summer 96.8 78.7 45.4 119.7 16.00 hrs 27.0 May
Monsoon 16.00 hrs 16.0 August
Winter 62.0 40.0 2.12 1.8 5.00 hrs 20.0 j$anuary
Inside 72.0 64.0 65.0 76.0 24 Hrs  All Months
Differences
Summer 24.8    43.8   
Monsoon      
Winter -10.0    -74.2   
 Heat Gain / Loss Calculations
SUN GAIN / OTHER DIFF. FACTORS HEAT GAIN
HEAT GAIN THRU' AREA / QTY. (In FPS Units) (In FPS Units) (BTU / Hr)
Summer Mons'n Winter Sum. / Mon. Winter Summer Monsoon Winter
Ë Sensible Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x 0.80 0.80
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Ceiling Ceiling 66.4 ft² x 24.80 0.00 -10.00 x 0.15 0.15 247 -100
Part. Wall Part. Wall ft² x 24.80 0.00 -10.00 x 0.35 0.35
Part. Glass Part. Glass ft² x 24.80 0.00 -10.00 x
Floor Floor ft² x 24.80 0.00 -10.00 x
Gain From Internal Sources
People People 2 nos x 269.0 538 538
Equipment Equipment 0.00 kW 0.80 0.80 0.80 x 3400.0 xUF 0 0
Lights Lights 133 W x 3.4 xBl.F 1.25 564 564
Hot Surface Hot Surface W x 1.00 1.00 1.00 x 3.41 0
Infiltration Infiltration cfm x x 1.08 0
Infiltration Infiltration cfm x x 1.08
Room Sensible Heat Sub-Total (RSH) : 1,349 1,003
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 101 75
Draw Thru' AHU Motor Draw Thru' AHU Motor 0.1 kW x % 366 366
Bypassed FA Bypassed FA 30 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.06 48 -19
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) : 1,864 1,424
Ë Latent Heat
People People 2 nos x 231.0 462 462
Appliances Appliances kW x 3400.0 xUF
Steam Steam kg/hr x 1050.0 x CF 1.00
Infiltration 0 Infiltration0 cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Infiltration Infiltration cfm x x 0.68
Room Latent Heat Sub-Total (RLH) : 462 462
SA Duct Heat Gain & Leak Loss (%) : 2.50 % Safety : 5.00 % 35 35
Bypassed FA Bypassed FA 30 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.06 54 -91
EFFECTIVE ROOM LATENT HEAT (ERLH) : 550 406
EFFECTIVE ROOM TOTAL HEAT (ERTH) : 2,415 1,830
Ë Return Air & AHU Room Heat
Solar Gain Thru' Exposed Glasses
Exp. Glass Exp. Glass ft² x x
Exp. Glass Exp. Glass ft² x x

14
JOB REF. NO. :
CUSTOMER CONSULTANT
DATE :
AIR-CONDITIONING HEAT LOAD :
Rooms : Sec. Airlock for Visitors Room No AHU NO. :
Site Data : Location Latitude (°N) Altitude (mt) Estimate by :
Exp. Glass Exp. Glass ft² x x
Solar & Trans. Gain Thru' Walls & Roofs
Exp. Wall Exp. Wall ft² x x
Roof Roof ft² x x
Trans. Gain Thru' All Except Walls & Roofs
Exp. Glass Exp. Glass ft² x x
Part. Wall Part. Wall ft² x x
Ceiling Ceiling ft² x x
RA & AHU Room Heat Sub-Total : 0 0
RA Duct Heat Gain & Leak Loss (%) : % Safety : %
RA & AHU ROOM HEAT (RAH) : 0 0
Ë Outside (Fresh) Air Heat on Coil
Sensible Part Sensible Part 30 cfm x 24.80 0.00 -10.00 x 1.08 x BF 0.94 755 -305
Bypassed FA Bypassed FA 30 cfm x 43.75 0.00 -74.20 x 0.68 x BF 0.94 839 -1,423
OUTSIDE (FRESH) AIR HEAT ON COIL (OAH) : 1,594 -1,727
SUB-TOTAL OF ALL ABOVE HEAT GAINS : 4,009 103
Deh.Heat Gain By Air Deh.Heat Gain By Air kW x 3400.0
Blow Thru' AHU Motor Blow Thru' AHU Motor x 10.0 % 0
CHW Pump Motor/Dehum.Pipe Loss % GTH Safety : 5.00 % 200 5
GRAND TOTAL HEAT (GTH) IN BTU / HR : 4,209 108
GRAND TOTAL HEAT (GTH) IN TR : 0.35 0.01
RESULTS
PARAMETERS & EQUATIONS ABBREVIA-TIONS UNITS
Summer Monsoon Winter
Ë Dehumidified Air Quantity
Eff. Sensible Heat Factor = (ERSH / ERTH) ESHF - 0.77 -
Min. Possible ESHF w/o Reheat From Psychrometric Chart ESHF‹min› - -
Indicated Apparatus Dew Point From Psychrometric Chart °F -
Selected Apparatus Dew Point ADP °F 50.00 -
Dehumidified Rise = (1 - BF) x (Inside DB - ADP) DR °F 20.68 -
Dehumidified air qty = ERSH / (1.08 * DR) DA cfm 83 -
Ë Reheater Calculations
Supply Air Qty.on Air Change Basis = Vol. x No. of Air Change / 60 SA ‹ac› cfm 109 
Preliminary Selected Air Qty = Highest of DA‹sum›, DA‹mon›, SA‹ac› DA ‹max› cfm 109 
Is Reheater Reqd. in Summer & Monsoon for High Latent Load & in Winter for Heating Yes / No No No Yes
Reheater Capacity for Winter Heating RH ‹winter› kW   0.09
Reheater to Increase ESHF to Achievable Limit RH ‹latent› kW 
Reheat 0.17
Ë Revised Tonnage & Supply Air Qty
Tonnage GTH (in TR) + S {RH * 3400 / 12000} TR ‹rev› TR 0.35 0.00 0.03
Correctd De-Humidified Air Qty = {ERSH + (SRH * 3400)} / (1.08 * DR) DA ‹rev› cfm 83 0 
Ë FINAL SYSTEM SELECTION
Tonnage TR 0.35
Supply Air Qty CFM 109
Dehumidified Air Qty CFM 83
Return Air Qty CFM 280
Fresh Air Qty CFM 30
Reheater / Heating Coil Capacity kW 0.17