Sie sind auf Seite 1von 17

Service Manual

Generator Set
with PowerCommand 3201 Controller
DFEG (Spec C−H)
DFEH (Spec C−H)
DFEJ (Spec C−H)
DFEK (Spec C−F)
DQCA (Spec A−F)
DQCB (Spec A−F)
DQCC (Spec A−F)

English − Original Instructions 1−2011 960−0521 (Issue 8)


Table of Contents

SECTION TITLE PAGE


1 INTRODUCTION
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
How To Obtain Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2 CONTROL OPERATION
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Control Panel Power On/Off Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Menu Display and Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Main Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Controller Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Engine Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Alternator Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Adjust Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Faults Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
History Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20
About Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Power Transfer Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-24
3 CIRCUIT BOARDS AND MODULES
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Base Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
4 TROUBLESHOOTING
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
InPower Service Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Network Application and Customer Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3

i
SECTION TITLE PAGE
5 POWER TRANSFER CONTROL (PTC) TROUBLESHOOTING
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
PTC Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Sequence of Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Troubleshooting using Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
PTC Fault Code Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . 5-3
Troubleshooting with Symptoms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Source 1 Power Fails, But Genset Does Not Start . . . . . . . . . . . . . . . . . . 5-9
Genset Starts, But Does Not Assume Load . . . . . . . . . . . . . . . . . . . . . . . 5-11
PTC Module Does Not Retransfer When Source 1 Utility Power
Is Restored After A Power Failure Or On Initial Installation . . . . . . . 5-13
Genset Continues To Run After Retransfer Of Load To S1 Utility . . . . . 5-15
Genset Starts During Normal Power Service . . . . . . . . . . . . . . . . . . . . . . 5-15
Generator Test Runs But Genset Does Not Assume Load . . . . . . . . . . 5-15
6 CONTROL ADJUSTMENT AND SERVICE
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Circuit Board Removal/Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Modifying Setup Submenus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Password Submenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Crank/Idle Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Governor/Regulator Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Power Transfer Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
PCC Control Panel Box Components (Standard/Optional) . . . . . . . . . . 6-12
Engine Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Magnetic Speed Pickup Unit (MPU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-17
Current Transformer (CT) Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-18
7 SERVICING THE GENERATOR
Testing the Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Generator Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10
Generator Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
Servicing the PMG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
8 GOVERNORS
Electric Governor Throttle Lever/Linkage Adjustment . . . . . . . . . . . . . . . . 8-1
Mechanical Governor Throttle Lever/Linkage Adjustment . . . . . . . . . . . . 8-2
9 FUEL TRANSFER PUMP AND CONTROL
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
Fuel Transfer Pump Motor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
Testing the Float Switch Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-7
10 WIRING DIAGRAMS
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1

ii
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS − This manual contains EXHAUST GASES ARE DEADLY
important instructions that should be followed during
installation and maintenance of the generator set and  Provide an adequate exhaust system to properly
batteries. expel discharged gases away from enclosed or
sheltered areas and areas where individuals are
Before operating the generator set (genset), read the likely to congregate. Visually and audibly inspect
Operator’s Manual and become familiar with it and the the exhaust daily for leaks per the maintenance
equipment. Safe and efficient operation can be schedule. Make sure that exhaust manifolds are se-
achieved only if the equipment is properly operated cured and not warped. Do not use exhaust gases to
and maintained. Many accidents are caused by failure heat a compartment.
to follow fundamental rules and precautions.
 Be sure the unit is well ventilated.
The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the oper-
 Engine exhaust and some of its constituents are
ator, service personnel, or the equipment. known to the state of California to cause cancer,
birth defects, and other reproductive harm.
This symbol warns of immediate
MOVING PARTS CAN CAUSE SEVERE
hazards which will result in severe personal in-
jury or death. PERSONAL INJURY OR DEATH
 Keep your hands, clothing, and jewelry away from
WARNING This symbol refers to a hazard or un-
moving parts.
safe practice which can result in severe person-
al injury or death.  Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis-
CAUTION This symbol refers to a hazard or un- connect starting batteries, negative (−) cable first.
safe practice which can result in personal injury This will prevent accidental starting.
or product or property damage.  Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards
FUEL AND FUMES ARE FLAMMABLE in position over fans, drive belts, etc.
Fire, explosion, and personal injury or death can result  Do not wear loose clothing or jewelry in the vicinity of
from improper practices. moving parts, or while working on electrical equip-
ment. Loose clothing and jewelry can become
 DO NOT fill fuel tanks while engine is running, un- caught in moving parts.
less tanks are outside the engine compartment.
Fuel contact with hot engine or exhaust is a potential  If adjustment must be made while the unit is run-
fire hazard. ning, use extreme caution around hot manifolds,
moving parts, etc.
 DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source DO NOT OPERATE IN FLAMMABLE AND
near the generator set or fuel tank.
EXPLOSIVE ENVIRONMENTS
 Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be Flammable vapor can cause an engine to overspeed and
made with an approved flexible line. Do not use zinc become difficult to stop, resulting in possible fire, explo-
coated or copper fuel lines with diesel fuel. sion, severe personal injury and death. Do not operate a
genset where a flammable vapor environment can be
 Be sure all fuel supplies have a positive shutoff created by fuel spill, leak, etc., unless the genset is
valve. equipped with an automatic safety device to block the air
 Be sure battery area has been well-ventilated prior intake and stop the engine. The owners and operators of
to servicing near it. Lead-acid batteries emit a highly the genset are solely responsible for operating the gen-
explosive hydrogen gas that can be ignited by arc- set safely. Contact your authorized Cummins Power
ing, sparking, smoking, etc. Generation distributor for more information.

LS-16L
v
ELECTRICAL SHOCK CAN CAUSE  Keep multi-class ABC fire extinguishers handy.
SEVERE PERSONAL INJURY OR DEATH Class A fires involve ordinary combustible materials
such as wood and cloth; Class B fires, combustible
 Remove electric power before removing protective and flammable liquid fuels and gaseous fuels; Class
shields or touching electrical equipment. Use rub- C fires, live electrical equipment. (ref. NFPA No. 10).
ber insulative mats placed on dry wood platforms
over floors that are metal or concrete when around  Make sure that rags or combustible material are not
electrical equipment. Do not wear damp clothing left on or near the generator set.
(particularly wet shoes) or allow skin surface to be
damp when handling electrical equipment. Do not  Make sure generator set is mounted in a manner to
wear jewelry. Jewelry can short out electrical con- prevent combustible materials from accumulating
tacts and cause shock or burning. under or near the unit.
 Use extreme caution when working on electrical
components. High voltages can cause injury or  Remove all unnecessary grease and oil from the
death. DO NOT tamper with interlocks. unit. Accumulated grease and oil can cause over-
heating and engine damage which present a poten-
 Follow all applicable state and local electrical tial fire hazard.
codes. Have all electrical installations performed by
a qualified licensed electrician. Tag and lock open  Keep the generator set and the surrounding area
switches to avoid accidental closure. clean and free from obstructions. Remove any de-
 DO NOT CONNECT GENERATOR SET DIRECT- bris from the set and keep the floor clean and dry.
LY TO ANY BUILDING ELECTRICAL SYSTEM.
Hazardous voltages can flow from the generator set  Do not work on this equipment when mentally or
into the utility line. This creates a potential for elec- physically fatigued, or after consuming any alcohol
trocution or property damage. Connect only or drug that makes the operation of equipment un-
through an approved isolation switch or an ap- safe.
proved paralleling device.
 Substances in exhaust gases have been identified
GENERAL SAFETY PRECAUTIONS by some state or federal agencies as causing can-
 Coolants under pressure have a higher boiling point cer or reproductive toxicity. Take care not to breath
than water. DO NOT open a radiator or heat ex- or ingest or come into contact with exhaust gases.
changer pressure cap while the engine is running.  Do not store any flammable liquids, such as fuel,
To prevent severe scalding, let engine cool down
cleaners, oil, etc., near the generator set. A fire or
before removing coolant pressure cap. Turn cap
explosion could result.
slowly, and do not open it fully until the pressure has
been relieved.  Wear hearing protection when near an operating
 Used engine oils have been identified by some state generator set.
or federal agencies as causing cancer or reproduc-
tive toxicity. When checking or changing engine oil,  To prevent serious burns, avoid contact with hot
take care not to ingest, breathe the fumes, or con- metal parts such as radiator system, turbo charger
tact used oil. system and exhaust system.

KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE

vi
1. Introduction
ABOUT THIS MANUAL TEST EQUIPMENT
This manual provides PowerCommand Control To perform the test procedures in this manual, the
3201 (PCC) calibration and adjustment proce- following test equipment must be available
dures, control operation, alternator test and repair  True RMS meter for accurate measurement of
procedures. small AC and DC voltages.
 Battery Hydrometer
Operating and maintenance instructions are in the
 Jumper Leads
applicable Operator’s Manual. Generator set trou-
bleshooting and repair (control and engine) infor-  Tachometer or Frequency Meter
mation is provided in the following manual.  Wheatstone Bridge or Digital Ohmmeter
 Variac
 Troubleshooting and Repair Manual Power-
Command Control QSX15, (QSK23), QSK45,  Load Test Panel
QSK60 Generator Sets, Bulletin No. 402-1419  Megger or Insulation Resistance Meter
(Not shown on front cover, but includes QSK23  InPower Service Tool (PC based genset ser-
information.) vice tool)
Read Important Safety Instructions and carefully HOW TO OBTAIN SERVICE
observe all instructions and precautions in this Always give the complete Model, Specification and
manual. Serial number of the generator set as shown on the
nameplate when seeking additional service infor-
mation or replacement parts. The nameplate is lo-
cated on the side of the generator output box.
WARNING Incorrect service or replacement of
parts can result in severe personal injury or
death, and/or equipment damage. Service per-
sonnel must be trained and experienced to per-
form electrical and mechanical service. Read
and follow Important Safety Instructions, on
pages iii and iv.

1-1
2. Control Operation
GENERAL present, it will wait for a pulse from a remote Master
First Start Sensor. On receiving that pulse, the con-
The following describes the function and operation trol will signal the paralleling breaker to close.
of the PowerCommand Control 3200 (PCC). All in-
dicators, control switches/buttons and graphical If bus voltage is present, the control will check for
display are located on the face of the control panel proper phase rotation, adjust the generator set to
as illustrated in Figure 2-1. the bus voltage and frequency level, and then syn-
Normally, generator set configuration options are chronize the generator set to the system bus. When
set at the factory. When a new control is installed on a synchronous condition is achieved, the control will
a generator set or when parts are replaced, the con- send a signal to close the paralleling breaker.
trol must be configured for that generator set. Setup
and calibration procedures are described in Sec- When the paralleling breaker is closed, the genera-
tion 3. tor set will assume it’s proportional share of the total
load on the system bus.
SEQUENCE OF OPERATION
CONTROL PANEL POWER ON/OFF
When the PowerCommand control is in the AUTO
MODES
mode, it will cause the generator set to start on re-
ceiving a signal from a remote device. The control
The power on/off modes of the control panel and op-
will initiate a starter cranking signal and verify that
erating software are Power On, Screen Saver and
the engine is rotating. The control will provide suffi-
Sleep/Awake.
cient fuel to the engine to accelerate to start discon-
nect speed. On reaching that speed, the control will
ramp the generator set to idle (warm-up) or rated Power On Mode: In this mode, power is continu-
speed and voltage. ously supplied to the control panel. The control’s
operating software and control panel LEDs/graphi-
On reaching rated speed and voltage, the control cal display will remain active until the Screen Saver
checks the system bus voltage. If no bus voltage is mode is activated.

2-1
Screen Saver Mode: Power to the graphical dis- If these conditions are not met, Sleep mode is dis-
play will be removed after 10 minutes (generator set abled in Auto mode.
not running or running). The 10 minute timer resets
and begins after each control panel action (any but- The graphical display can enter Screen Saver mode
ton or switch selection) or signal received by the op- even if Sleep mode is disabled.
erating software. The bottom LEDs of the Analog
AC Metering Panel (bar graphs) may remain on dur- If Sleep mode is enabled in Auto mode, Sleep mode
ing Screen Saver mode, indicating that the operat- is activated when there are no unacknowledged
ing software is active (Awake mode). faults and Screen Saver mode is active.
When a “Warning” signal is sensed by the PCC (for
example, low coolant temp), the control will display The operating software is initialized and the control
the warning message. The control will remain active panel LEDs and graphical display are turned on in
until the Fault Acknowledge button is pressed to response to one of the following:
clear the warning message and start the 10 minute
timer.  Moving/pressing any control panel switch/but-
ton. (If Sleep mode is enabled in Auto mode,
Sleep/Awake Mode: In the Sleep mode, the con- the control will remain asleep if Sleep mode
trol’s operating software is inactive and the LEDs was previously active in Off mode.)
and the graphical display on the control panel are all  Receiving a remote start input signal (genera-
off. Sleep mode is a feature that is used to reduce tor set in Auto mode)
battery power consumption when the control is not
being used.  Receiving an active DCD signal on the RS-232
port.
In Off mode, Sleep mode is activated when there
are no unacknowledged faults and Screen Saver  Modem RI latch becoming active.
mode is active.  Digital display waking up.
In Auto mode, Sleep mode can be enabled or dis-  Lonworks (backplane) wakeup becoming ac-
abled. When shipped from the factory, it is disabled. tive.
You can enable Sleep mode by making these
changes:  Customer fault 2 or 3 only (shutdown or warn-
ing indicator is on).
 Use InPower service tool to set Auto Sleep En-
able to Sleep in Auto.  Dial Out process becoming active.
 Set switch S1 on the Genset/Paralleling Card To activate the control and view the menu display
to Sleep/Off. This switch is located next to con- without starting the generator set, press any button
nector J8 and relay K9. on the control panel.

2-2
OPERATOR PANEL SWITCH PANEL

REMOTE START,
NOT IN AUTO,
SHUTDOWN,
WARNING
STATUS INDICATORS
ANALOG AC PANEL LAMP/ FAULT EMERGENCY
METERING LAMP TEST ACKNOWLEDGE STOP PUSH
PANEL BUTTON BUTTON BUTTON

DISPLAY MENU EXERCISE MANUAL RUN/


SELECTION BUTTONS BUTTON & STOP BUTTON
(1 of 6) INDICATOR & INDICATOR

GRAPHICAL 0/MANUAL/AUTO
DISPLAY SWITCH

FIGURE 2-1. CONTROL PANEL ASSEMBLY (FULL-FEATURED)

2-3
CONTROL PANEL ASSEMBLY Scales for each function are in % of nominal values.
Resolution is 1% for values close to nominal, and in-
The control panel assembly (Figure 2-1) consist of creases at values further from nominal.
two panels, the Operator Panel and the Switch Pan-
el. Graphical Display: The graphical display is capa-
ble of displaying up to 9-lines of data with approxi-
Dependent on site requirements, the Operator Pan- mately 27 characters per line. The display is used to
el is either mounted on the control panel assembly view the menus of the menu-driven operating sys-
(full-featured) as shown in Figure 2-1 or contained tem.
in a separate enclosure and mounted remotely of
the control panel assembly. The top three lines of the graphical display contain
the following control information in the order de-
The function of several buttons on the control panel scribed:
will vary dependent on the location of the control
panel (remote or local of the control panel assem-  State Line − modes of operation, such as
bly). If the function differs, it is noted as either “re- Stopped, Time Delay To Start, Warm Up At
mote” or “local operator panel” in the button de- Idle, etc. (see Figure 2-2), and paralleling op-
scription. erations, such as Standby, Dead BUS Close,
Synchronize, Load Share and Load Govern.
Operator Panel
 Action Line − system actions, such as Warning,
The operator panel contains the following compo- Derate, Shutdown Cool-down and Shutdown,
nents: and fault codes.
Analog AC Metering Panel: This panel simulta-  Description Line − Fault code messages.
neously displays 3-phase line to line AC volts and
current, kW, power factor and frequency. Display Menu Selection Buttons: Six momentary
buttons—three on each side of the graphical dis-
The meter panel is composed of a series of LEDs, play window—are used to navigate through the sys-
that are configured in bar graphs for each function. tem control menus and to adjust generator set pa-
The LEDs are color coded, with green indicating rameters. The button is active when the message
normal range values, amber for warning levels and adjacent to the button is highlighted (displayed in in-
red for shutdown conditions. verse video).

2-4
Switch Panel Fault Acknowledge: Press this button to acknowl-
edge warning and shutdown messages after the
The switch panel contains the following compo- fault has been corrected.
nents:
To acknowledge a Warning message, the 0/Manu-
Emergency Stop Button: Push the button in for al/Auto switch can be in any position. (It is not nec-
emergency shutdown of the engine. If the engine is essary to stop the generator set to acknowledge an
not running, pushing the button in will prevent the inactive Warning condition.) To acknowledge a
starting of the engine, regardless of the start signal shutdown message with this button, the 0/Manual/
source (local or remote). Auto switch must be in the 0 (Off) position.
To reset: This button is also used to blink a fault code if the
1. Pull the button out. Shutdown or Warning Status Indicator is lit. (This
2. Move the 0/Manual/Auto switch to 0. function is used when the control does not contain a
3. Press the front panel Fault Acknowledge graphical display.) Refer to Reading Fault Codes in
button. this section, which describes how to use this button
4. Select Manual or Auto, as required. for interpreting fault codes.
Remote Start Indicator: This green lamp is lit Panel Lamp/Lamp Test Button: Press this button
whenever the control is receiving a remote run sig- to turn on or off the panel lamp. Press and hold
nal. When flashing, it indicates a load demand stop down this button for three seconds or more to turn
mode. all control panel LEDs on to make sure all lamps illu-
minate. The illumination will shut off after releasing
Not in Auto Indicator: This red lamp flashes con- the button.
tinuously when the 0/Manual/Auto switch is not in
the Auto position. (If in Auto position and lamp is Exercise Button: Press this button to initiate a pre-
flashing, service is required.) programmed exercise sequence. To start the exer-
cise sequence, press and hold down the Exercise
Shutdown Status Indicator: This red lamp is lit button and move the O/Manual/Auto switch from
whenever the control detects a shutdown condition. Auto to Manual and back to Auto or from Manual to
The generator set can not be started when this lamp Auto.
is on. After the condition is corrected, shutdown in-
dicators can be reset by turning the 0/Manual/Auto Manual Run/Stop Button: This button starts and
switch to the 0 position, and pressing the Fault Ac- stops the set locally and will bypass Time Delay to
knowledge button. Start and Stop sequences. The 0/Manual/Auto
switch must be in the Manual position to enable this
Dependent upon the specific fault that occurs, the button.
engine may or may not shut down immediately. A
fault that could cause engine damage, causes an 0/Manual/Auto Switch: Manual position enables
immediate engine shutdown (bypasses engine the use of the switch panel Manual Run/Stop but-
cool-down sequence). All other faults would allow ton.
the engine to run during the cool-down sequence Auto position enables start/stop control of the en-
before engine shutdown. In this case, the Shutdown gine from a remote location. (Disables the use of the
Status Indicator blinks during the cooldown period. switch panel Manual Run/Stop button.)
Warning Status Indicator: This yellow lamp is lit 0 (Off) position prevents the starting of the set (local
whenever the control detects a warning condition. or remote). If moved to 0 during set operation, will
After the condition is corrected, warning indicators cause an immediate engine shutdown (bypasses
can be reset by pressing the Fault Acknowledge cool-down timers). This hot shutdown should be
button. (It is not necessary to stop the generator set avoided, if possible, to help prolong the life of the
if the fault becomes inactive during genset opera- engine. Hot shutdowns are logged by the system
tion.) software.

2-5
READING FAULT CODES A three digit fault code is indicated by three sets of
blinks separated by a two second pause. The first
If the genset contains the optional graphical display set corresponds to the hundreds position, the sec-
and a fault occurs, the fault code/message will be ond to the tens position and the third to the ones dig-
displayed in the display Description Line (Figure it. Example for Code No. 213:
2-2). If the control does not contain the graphical
display, the fault code is read from the Warning and Shutdown LED:
Shutdown status indicators. blink-blink-pause-blink-pause-blink-blink-blink

Reading Fault codes Using Warning/Shutdown Warning LED:


Indicators: If the Warning or Shutdown status indi- blink (2 seconds)
cator is lit, press and hold the Fault Acknowledge The light will display the fault codes (active or inac-
button and release after one second or more. After tive) in succession, starting with the most recent. Up
one second, the Shutdown lamp will begin to blink to 32 (unacknowledged) fault codes can be stored
the active fault code(s) as follows. in control panel memory.
The Warning lamp is used to indicate the start of a To return the control to the most recent fault code,
new code. The Warning lamp will remain on for 2 press and release the Fault Acknowledge button
seconds, followed by the Shutdown lamp blinking (less than one second) and repeat procedure.
the fault code. This sequence occurs three times for
each code. The fourth flash of the Warning lamp in- When the fault code is acknowledged and cor-
dicates the beginning of the second fault code. rected, the recorded fault will be deleted from the
LED fault log, but will remain in a data log that main-
There are distinct pauses between repetitions of the tains a fault code history. (The InPower service tool
code blink transmissions of the Shutdown lamp. is required to view this data log.)

2-6
MENU DISPLAY AND SWITCHES Menu Buttons: Six momentary buttons—three on
each side of the graphical display window—are
Figure 2-2 shows the graphical display and the used to navigate through the system control menus
menu selection buttons. and to adjust generator set parameters. The button
Graphical Display: The graphical display is capa- is active when the message or symbol adjacent to
ble of displaying up to 9-lines of data with approxi- the switch is highlighted (displayed in inverse vid-
mately 27 characters per line. The display is used to eo). The displayed message or symbol indicates
view the menus of the menu-driven operating sys- the function of the button.
tem. Refer to the menu trees later in this section.
The display is also used to show the following sys- In the graphical display, the “B” symbol indicates
tem information: that selecting the adjacent button causes the operat-
ing program to go to the next menu display—as
 State Line − modes of operation, such as shown in the menu diagrams.
Stopped, Time Delay To Start, Warm Up At
Idle, etc., and paralleling operations, such as
Standby, Dead BUS Close, Synchronize, etc. In the graphical display, the “Y” symbol indicates
that selecting the adjacent button causes the operat-
 Action Line − system actions, such as Warning, ing program to go back to the previous menu display.
Derate, Shutdown Cool-down and Shutdown,
and fault codes.
In the graphical display, the “ ” symbol indicates
 Description Line − Fault code/status mes- that selecting the adjacent button causes the operat-
sages. ing program to go back to Main Menu A (Figure 2-4).

STATE LINE
ACTION LINE
DESCRIPTION LINE

MENU DISPLAY
AREA

GRAPHICAL
DISPLAY

MENU MENU
BUTTONS BUTTONS

FIGURE 2-2. GRAPHICAL DISPLAY AND MENU SELECTION BUTTONS

2-7
LANGUAGE/UNITS SELECTION MENU Temp: Used to select F or C for temperature read-
ings.
During any control panel operation, you can select
one of three languages and change how units are Pressure Fluid: Used to select PSI, KPA, BAR or
displayed by pressing the two lower menu buttons IN for pressure readings.
(one on each side of display). When pressing these
two buttons simultaneously, the language/units Pressure Gas: Used to select INHG or MMHG for
menu will appear (Figure 2-3). After making desired pressure readings.
selections, press the ENTER button in this menu to
change and save the selections. Flow Air: Used to select CFM or CMM for air flow
readings.
Use the + buttons to select the desired option for
each field. Use the arrow () button to move to the
next field. Selected field is highlighted.

Language: Used to select desired language (de-


fault = English). LANGUAGE ENGLISH
+ LOCATION LOCAL
Location: This selection must be set to Local when TEMP F ENTER
the graphical display is mounted on the generator PRESS FLD PSI
 PRESS GAS INHG
set front control panel or Remote when mounted re- FLOW AIR CFM
motely from the generator set.
The Local/Remote selection determines which but-
tons in the Control submenu (page 2-13) are active
(displayed). FIGURE 2-3. LANGUAGE/UNITS MENU

2-8
MAIN MENU _\_ Button (Paralleling Applications Only)
Figure 2-4 shows the main menus (Menu A and When displayed, indicates that the feature for gen-
Menu B) of the system control. The two main menus erator set paralleling applications is installed. This
are used to divide the system submenus into major button is used to open and close the generator set
categories, such as, Engine Data, Alternator Data, circuit breaker (CB). The symbol indicates if the CB
Control, etc. is opened or closed. Opened _\_, push to close.
To view system data, simply press the appropriate Closed _−_, push to open.
menu button to select the category. After pressing
the desired menu button, refer to the page number With the control panel 0/Manual/Auto switch in the
shown in Figure 2-4 for detailed information related Auto position, the opening and closing of the CB is
to the selected category. controlled by the control system software. The CB
symbol will indicate an open or closed CB, but the
In the following figures, the boxed/highlighted field button will be inactive when the control is in Auto.
indicates that the adjacent menu button is active.
Also, the submenus are shown in the order in which In the Manual position, the CB can only be closed
they are displayed when scrolling up Y or down B. by using this button. When manually closed and the
CB opens, it must be closed again by using this but-
Adjust Button ton. To close the CB, press and hold the button until
The Adjust submenu is intended for qualified site the symbol indicates a closed CB. (CB close will oc-
personnel only. Note that a password may be as- cur only when setup conditions allow − dead bus or
signed to allow only authorized operators to modify generator synchronized with bus.)
this data. (Password is not required if not assigned.)
Power Trans Button (Power Transfer
Setup Button Control Applications Only)
The Setup submenu is described in Section 3. When displayed, indicates that the Power Transfer
The “Adjust” and “Setup” submenus can be viewed, Control (PTC) feature is installed. Refer to page
but not modified without entering the correct pass- 2-17 for PTC Data submenu description. The PTC
words. setup submenu is described in Section 3.

2-9
Thank you very much
for your reading.
Please Click Here
Then Get More
Information.

Das könnte Ihnen auch gefallen