Sie sind auf Seite 1von 4

STATION SURGE ARRESTERS

• switching surges (frequently a consideration Continuous System Voltage


in transmission systems of 345 kV
Arresters in service 'are s contintJally exposed to
and aboye, and for capacitor banks and
system operating voltage: For . 'éach arrester
cable applications).
rating, there is .recommended limit to the
The arrester selected must have aufficient magnitude of voltage which may be continuously
capability to meet the anticipated service reguire- applied. This has been termed the "maximum
ments in all categories. continuous operating voltage" (MCOV), of the ar-

TABLE 2
(1) (2)
(MCOV)
MAXIMUM
CONTINUOUS
OPE

5.0 kA

160
200
2131.
232 240
269
5 ,•285 295
170 309 320
198 360 373 394
203. 457 353 382 404 448
212 477 369 399 422 468
226 509 394 426 4 499
22 289 604, 467 505 592
240, „„ 233 635 491 531 562 623
3b4 683 528 551 604 641 670 755
214. 311 699 540 564 618 655 685 773
1 4 730 565 589 646 685 716 808
288 23 340 762 589 615 674 715 747 843
294 238 347 778 602 628 688 730 763 860
,100 243 354 795 615 641 .703 745 779 879
,41.4,, I . 253 36.8 826 639 667 731 775 810 914
1318 n• ..3 272 396 890 688 718 787 835 872 984
.-).ON. ‘. ' 292 424 953 737 769 843 894 934 1054

6
rester. The MCOV of each TRANQUELL XE ar- Temporary Overvoltages
rester is contained in Table 2, Column 2. These
values meet or exceed those values contained in Temporary overvoltages (TOV) can be caused by
the referenced standard. a number of system events such as line-to-ground
The arrester rating must be selected such that faults, circuit backfeeding, load rejection, fer-
the maximum continuous power system voltage roresonance, and others. The system configura-
applied to the arrester is less than, or equal to, the tion and operating practices should be reviewed
arrester's continuous voltage capability. Atten- to identify the most probable forms of temporary

`lát,
...umnineuzunnumzulumuumme 111111112111111•1111111111111
g11:11111111111111=1111111111111111111111111111111111111•1111111 AMBIENT TEMPERATURE 45°C;
111n511111i! 11111111 MIIIIIIIIIIIIIINIM11111111111111•11
gui -91 • mummiulimumminfiffinfiffig. INITIAL ARRESTEFI TEMPERATURE 60°C I
1
9 Miiiiiilliiii!Imminimuliammummulam
10.gumiwoommunnumunuquiplumpunimunuin~liiiiiiii
n1111111111b
ffilIKTI IIIIIIIIIIZIWAIIIIIIIIIIZZI1r
Ammommig i onolinimggic — 111111~1111111111111111
NO PRIOR ENERGY 1111111111111111111111111~111111111.
111111111111110.1111111111101110111PEdinumunewmanu 1111•1111n1111111111111111n11111111111t

,'''1111111111111111111WRIMMIK911:.11111•111111111111111111li1111111111111•••111111111„.
MI111111111111111011111111:1110E11111111111111 0.50 P.U. RATED 111111111111MM1111111111?
MIE1111111111111111n0111111111~11111111O 11111111111••111111111111
1•1111111111111111•1111111111011111111011 g 11111% PRIOR ENERGY iiiiiiiiIMMIWIEN111
11111111111111111111111•11M11111W i mmainur III nifin ginw 11111111111~1111111111
+ 1111•111111111111111111M111111111 WII n11111101110. 111 nn11111111111111• nn111111111111111111n1111111111
' ';11111111U11111111111111111211111111111Mn241111111~11111111111MMIWINNME1111111111
,IINZIIMIIIIIIIIIMMINIIIIIIIIIIM11110111111111 n0111110111111111MIW 1.0 P.U. RATED 1 1111111111ii,
.11111111111111111111M1111111111111111111111111119" 1:91101111111112 PRIOR ENERGY 111111111111V
Mzunuelumunnunimuzunialmunwhimig__________ zulinwr:
i IMIIIIIIIIIIIIIMMIIIIIII11111111•111111111111111 nM1111110.5∎ nn•~=111111111111111111P
iIMMIIIIIIIIIIIMIEN111111111•1=1111111111111111Z1M11111W•041111111M11•11111111111Ir
íffiEll111111111•1•11111111111111111E11111111111111•1111111111011111•11%11111111•IMINI11111111 1
EI MIIIIIIIIIIIIMIIIIIIIIIIIIIIIIIIMIIIIIIIIIIIIIIIIIIIIIIIMMIMII01111011M•11111111111111:
1 w111111111111111111•11111111111111111111111111M11111111111•11111111111101101111a9110111111111111111
ZZIMIIIIII1111111111111111111M.•111111111111111111M1111111111111MiMIIIIIili: n011111111111fi
7P ' 715 '111.2! 11"'

tion must be given to both the circuit connection overvoltages which may occur at the arrester
(single phase, wye or delta) and the arrester con- location. The arrester temporary overvoltage
nection (line-to-ground, line-to-line). In most capability must meet or exceed the expected tem-
cases, the arrester is connected line-to-ground porary overvoltages. Table 2, Column 3, defines
and therefore must withstand line-to-ground the one-second temporary overvoltage capability
system operating voltage. If an arrester is to be of each TRANQUELL XE arrester.
connected line-to-line, phase-to-phase voltage If detailed transient system studies or calcula-
must be considered. In addition, attention should tions are not available, ít is traditional to consider
be given to an arrester application on the delta as a minimum, the overvoltages due to single line-
tertiary winding of a transformer where one corner to-ground faults. The arrester application stan-
of the delta is permanently grounded. In such cir- dard ANSI C62.2 gives some guidance in deter-
cuits, the normal voltage continuously applied to mining the magnitude of single line-to-ground
the arrester will be the full phase-to-phase fault overvoltages. These overvoltages depend on
voltage even though the arresters are connected details of system grounding.
line-to-ground. The primary effect of temporary overvoltages

7
STATION SURGE ARRESTERS

on metal oxide arresters is increased current these conditions is less than permitted for an ar-
and • Rower dissipation, and a rising arrester rester with no initial energy. Lightning energies
temperature. Curves óf recommended temporary can be neglected when applying the temporary
overvoltage capabilities for all TRANQUELL XE overvoltage curves because the energy content of
station arresters are shown in Figure 1 in per unit- -a single lightning discharge reaching the arrester
of .the -arresters i- one-second temporary ovbrf in a shielded station is low.
voltage capability. These. • curves define the dura- In applications involving voltages of distorted
.tion and magnitude of temporary overvoltages Waveshapes, a conservative approach is to divide
that may be applied tddhe arrester before the ` "the crest of the actual system voltage by 1.414
rester voltage must bereduded to the arresters' and use it as if it were rms in conjunctíon with the
tinuous operating voltage capability. These temporary overvoltage curves.
'rtapábilities have been defined independent of As an exercise in using Figure 1, suppose it is
', 'system impedance and are- therefore valid for desired to determine the rmagnitude of temporary
, -voltages applied at location. overvoltage a 258-kV rated arrester can withstand
-Tttp permislible durationá are a function of. the for a 0.5-second period (with no initial energy).
- energy•that 'may have been discharged in the ar- Referring to Figure 1, the arrester can op'erate at
restet just prior to the, temporary overvoltage 1.014 per unit of its one-second temporary over-
period. Any ipitin4 energy, most likely due to a voltage capability or 1.014 x 304 kV = 308 .kV rms.
discharge associated with a switching surge, witl This transiates into
raise the teriiíSerature' pf the metal oxide vale
elements. Th initial 'arrester energy can be 308kV rms - 1.55 p.u.
estirrieted frorn Figures 2 through 7 for arresters 345/3
connected to''ovérheac) tra4inission lines as on a 345-kV base. If the temporary overvoltage
described in theiyottowintítsection on SWITCHINd cannot be cleared before the arrester capability is
SyRGES. Thd. pemissible TOV applied under exceeded, a faster means to clear the source of

8
Eli 100 MI RIE1111111
11111111/111111111111
11111 200 Ml

DREINE0111111111
1111111
n 1111111111FEsTER2w,T71
276.kVini

.'"'"Irk" 'tí"` .11"59-v` *Ileffr

Das könnte Ihnen auch gefallen