1 2 3 4 5 6 7 8 9 10 11

C1.00 X 2.00 BASE EXTENSION FOR


1.00" SLOT 6X CONTROLLER (OPTIONAL)
A A
1 Raw Water-Inlet 1" NPTF

2 Heater Junction Box HEATER VOLTAGE REQUIREMENTS:


230 VAC 2500 WATT, 115 VAC OPTIONAL
(Flexible Hose)
17"
3 Fuel Return Conn. (Shipped Loose)
3/8" NPTF Farside
9.97"
4 Fuel Supply Conn. (Flexible Hose)
(Shipped Loose)
1/2" NPTF Farside 36"

B 5 Raw Water-Outlet 1-1/4" NPTF B

6 Flexible Exhaust Outlet 5" Class 150 Flanged


Conn.
7 Drive Shaft CDS50-SC
5.00" 49" 49" 5.00"
108" 25.00"
C C

73.38"

36.85"
D D

21.75"
41.14"

23.03"
E 46.98" E
20.08" 17.72"

FUEL PUMP
0.45 ± 0.11 CENTERLINE 75.43"
16.29"
SEE NOTE 1
5.98"

10.63" 10.63"
F 21.26" F
8" SUCTION 6" DISCHARGE 28.00"

6" CHANNEL

32.70"
16.97"
G APPROX. EQUIPMENT WT. [LBS.] 34.70" G

39.27"
4962

NOTES:
DRN : AZC 03/03/14
1) THE DRIVESHAFT IS DESIGNED TO OPERATE AT A 2) FLANGE DRILLING AS PER ANSI B16.1 CLASS 250 FF PUMP MODEL: TF15H
2° ANGLE WITH THE INPUT AND OUTPUT SHAFTS APP'D : RLM 03/03/14
IN PARALLEL. THE ENGINE CRANKSHAFT 3) ALL DIMENSIONS IN INCHES. ENGINE MODEL: DP6H-UFAA50
DRAWN SCALE : N/A
IS TO BE SET WITH A PARALLEL OFFSET OF 4) BASE MUST BE COMPLETELY FILLED WITH GROUT PER NFPA 20.
H 0.45±0.11 INCHES VERTICALLY ABOVE DIESEL DRIVEN HORIZONTAL SPLIT CASE
H
THE PUMP SHAFT AND 0.00±0.11 INCHES PARALLEL 5) PUMP IS CW (CLOCKWISE) ROTATION WHEN VIEWED FROM SPP PUMPS LP FIRE PUMP SET
OFFSET HORIZONTALLY RIGHT OR LEFT OF THE COUPLING END. 2905 PACIFIC DRIVE
THE PUMP SHAFT. REFER TO THE ENGINE MANUAL NORCROSS, GA. 30071
SHOP ORDER
NUMBER
BORDER
SIZE A2
FOR ALIGNMENT. (770)409-3280 DRAWING
NUMBER TF15H - DP6H-UFAA50 SHEET 1 OF 1