Sie sind auf Seite 1von 12

CV.

TEHNIK POMPA CONTRACTOR :

PROJECT NO: LOCATION : RUMAH SAKIT UNGARAN


PROJECT NAME : RUMAH SAKIT UNGARAN
CONTENTS:

SL.# DESCRIPTION

A Hydrolic calculations for potable water booster pumps.

A-1 Table of total fixtures.

A-2 Potable water booster pump demand.

A-3 Flow rate through the piping system to the farthest point.

A-4 Head loss calculations.

A-5 Conclusion of the hydrolic calculations for potable water booste pumps.

B Hydrolic calculations for flush water booster pumps.

B-1 Table of total fixtures.

B-2 Flush water booster pump demand.

B-3 Flow rate through the piping system to the farthest point.

B-4 Head loss calculations.

B-5 Conclusion of the hydrolic calculations for flush water booste pumps.

C Refrence sheets from Uniform Plumbing Code

D Water supply layout showing the farthest point.


PROJECT NAME : RUMAH SAKIT UNGARAN

Table of total fixtures


Fixture type : PUBLIC
Total
FIXTURES / POINT NO. B1 G.F. F.F 2nd.F 3rd F 4th F. 5th F 6th F 7th F 8th F 9th F 10th F 11th F 12th F 13th F
fixtures

Water closet (flush valve) 0


Water closet (flush tank) 3 6 10 12 27 23 25 31 137
Water Bidet 0
Hose for W.C 3 6 10 12 27 23 25 31 137
Lavatory (& H.B.) 1 12 41 36 26 25 27 31 199
Janitor Sink 7 1 1 1 1 11
Service sink 0 27 0 4 31
Shower 0 0 2 27 23 25 31 108
Bath tub 0
Kitchen sink 0 1 0 0 1
Drinking water cooler 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Dishwashing machine
Laundry 0
Ablution (Public) 0
Urinal (1" flush valve) 4 4 4 12
Urinal (3/4" flush valve) 0
Urinal (flush tank) 0
PROJECT NAME : RUMAH SAKIT UNGARAN

POTABLE WATER BOOSTER PUPM DEMAND


TOTAL DOMESTIC WATER DEMAND CALCULATION Fixtures type : PUBLIC
Weight in Fixture units Total weight in fixture units
FIXTURES Quantity
Cold Hot Total Cold Hot Total
Water closet (flush valve) 10 0 10 0 0 0 0
Water closet (flush tank) 5 0 5 137 685 0 685
Water Bidet 1.5 1.5 2 0 0 0 0
Hose for W.C 1.5 1.5 2 137 205.5 205.5 274
Lavatory (& H.B.) 1.5 1.5 2 199 298.5 298.5 398
Janitor Sink 1.5 1.5 2 11 16.5 16.5 22
Service sink 2.25 2.25 3 31 69.75 69.75 93
Shower 3 3 4 108 324 324 432
Bath tub 3 3 4 0 0 0 0
Kitchen sink 3 3 4 1 3 3 4
Drinking water cooler 1 1 0 0 0 0
Dishwashing machine 0 1 1 0 0 0 0
Laundry 3 3 4 0 0 0 0
Ablution (Public) 1 1 1.5 0 0 0 0
Urinal (1" flush valve) 10 0 10 12 120 0 120
Urinal (3/4" flush valve) 5 0 5 0 0 0 0
Urinal (flush tank) 3 0 3 0 0 0 0
Total Fixture Units 1722.25 917.25 2028
WATER DEMAND ( GPM ) 291.0 GPM 195.4 GPM 324.0 GPM
WATER DEMAND ( m3/ h ) 66.06 m3/h 44.36 m3/h 73.55 m3/h

Booster pump capacity 324.0 gpm ( Assuming three pumps with 70 gpm )
73.55 m3/h
20.43 l/s
Shower

Laundry
Bath tub
Water Bidet

Janitor Sink

Service sink

Kitchen sink
Hose for W.C

SUM Total f.u.


Ablution (Public)
Lavatory (& H.B.)

Urinal (flush tank)

Flow rate ( gpm )


Drinking water cooler

Urinal (1" flush valve)


Dishwashing machine

Urinal (3/4" flush valve)


Water closet (flush tank)
Water closet (flush valve)
FIXTURES / POINT NO.
POTABLE WATER PUMPS

3 5 10 1 3 0 1 3 3 3 2.25 1.5 1.5 1.5 1.5 5 10 cold


Load

0 0 0 1 3 1 3 3 3 2.25 1.5 1.5 1.5 1.5 0 0 hot


PUBLIC

3 5 10 1.5 4 1 1 4 4 4 3 2 2 2 2 5 10 Total
PROJECT NAME : RUMAH SAKIT UNGARAN

0 0 0.8 0 0 0 0 0 0 0 1.4 1 0 0 2 0 Add

T.Fix.
p-o
Total

0 0 0.8 0 0 0 0 0 0 0 1.4 1 0 0 2 0
Flow rate through the piping system to the farthest point

16 22.8 0 0 8 0 0 0 0 0 0 0 2.8 2 0 0 10 0 Total f.u

0 0 0 0 0 0 0 0 1 0 1 0 0 0 27 0 Add

T.Fix.
o-n
Total

0 0 0.8 0 0 0 0 0 1 0 2.4 1 0 0 29 0

58 163.8 0 0 8 0 0 0 0 0 4 0 4.8 2 0 0 145 0 Total f.u

0 0 0.8 0 0 0 0 0 1 1 0 Add

T.Fix.
Total
n-m

0 0 1.6 0 0 0 0 0 1 0 2.4 2 1 0 29 0

60 175.8 0 0 16 0 0 0 0 0 4 0 4.8 4 2 0 145 0 Total f.u

0 0 0.8 0 0 0 0 1 2 1 0 Add

T.Fix.
m-l
Total

0 0 2.4 0 0 0 0 0 2 0 2.4 4 2 0 29 0

64 193.8 0 0 24 0 0 0 0 0 8 0 4.8 8 4 0 145 0 Total f.u

0 0 0.8 0 0 0 2 4 2 0 Add
l-k

T.Fix.
Total

0 0 3.2 0 0 0 0 0 4 0 2.4 8 4 0 29 0

69 221.8 0 0 32 0 0 0 0 0 16 0 4.8 16 8 0 145 0 Total f.u

0 0 0.8 0 0 0 0 2 4 2 0 Add
k-j

T.Fix.
Total

0 0 4 0 0 0 0 0 6 0 2.4 12 6 0 29 0

75 249.8 0 0 40 0 0 0 0 0 24 0 4.8 24 12 0 145 0 Total f.u

0 0 0.8 0 0 0 0 2 4 2 0 Add
j-i

T.Fix.
Total

0 0 4.8 0 0 0 0 0 8 0 2.4 16 8 0 29 0

50 128 0 0 48 0 0 32 32 16 0 Total f.u


Fixture type : PUBLIC

0 0 0 0 0 0 0 2 0 0 4 2 0 0 0 Add

T.Fix.
i-h
Total

0 0 4 0 0 0 0 0 10 0 2.4 20 10 0 29 0

83 289.8 0 0 40 0 0 0 0 0 40 0 4.8 40 20 0 145 0 Total f.u

0 0 0 0 0 0 5 0 0 0 Add

T.Fix.
h-g
Total

0 0 4 0 0 0 5 0 10 0 2.4 20 10 0 29 0

87 309.8 0 0 40 0 0 0 20 0 40 0 4.8 40 20 0 145 0 Total f.u

0 0 0 0 0 0 10 20 10 0 0 0 Add

T.Fix.
g-f
Total

0 0 4 0 0 0 5 0 20 0 2.4 40 20 0 29 0

107 409.8 0 0 40 0 0 0 20 0 80 0 4.8 80 40 0 145 0 Total f.u

0 0 0 0 0 0 10 20 10 0 0 0 Add

T.Fix.
f-e
Total

0 0 4 0 0 0 5 0 30 0 2.4 60 30 0 29 0

127 509.8 0 0 40 0 0 0 20 0 120 0 4.8 120 60 0 145 0 Total f.u

0 0 0 0 0 0 20 39 20 0 0 0 Add

T.Fix.
e-d
Total

0 0 4 0 0 0 5 0 50 0 2.4 99 50 0 29 0

162 707.8 0 0 40 0 0 0 20 0 200 0 4.8 198 100 0 145 0 Total f.u

0 0 4 0 0 0 6 45 93 48 0 6 0 Add

T.Fix.
d-c
Total

0 0 8.8 0 0 0 11 0 95 0 2.4 192 98 0 35 0

242 1271.8 0 0 88 0 0 0 44 0 380 0 4.8 384 196 0 175 0 Total f.u

0 0 0 0 0 0 5 50 99 50 0 3 0 Add

T.Fix.
c-b
Total

0 0 8.8 0 0 0 16 0 145 0 2.4 291 148 0 38 0

300 1804.8 0 0 88 0 0 0 64 0 580 0 4.8 582 296 0 190 0 Total f.u

0 0 0 0 0 0 25 5 0 45 2 0.5 93 48 0 15.5 0 Add

T.Fix.
b-a
Total

0 0 8.8 0 0 0 25 21 0 190 2 2.9 384 196 0 53.5 0

364 2396.3 0 0 88 0 0 0 25 84 0 760 6 5.8 768 392 0 267.5 0 Total f.u


PROJECT NAME : RUMAH SAKIT UNGARAN

Head loss calculation using (1) COLBROOK Formula For###

Total head (DH+GH) / pipe


Local factors of fittings

Accumulative Pressure
ID Pipe Inner diameter

RE Reynolds number
DN Nominal diameter

Loss m per 100 m


K Pipe roughness

F Liner loss factor


Total local factors

V Mean Velocity

dh(2) Local loss


dh(1) Liner loss
1.0 discharge outlet
no. part of pipe

GH Static head
1.0 Multimedia filter

0.3 elbow ( 45 leg.)


0.3 elbow ( 90 leg.)
L Pipe length

DH Total loss
Q Flow rate

2.0 check valve


1.0 Foot valve
0.2 gate valve

2.0 Strainer
0.5 reducer
0.9 tee
no. DN mm m mm GPM l/s 1/1 m m/s 1/1 1/1 m m m m m m

A TO B 110 PVC 93.6 8 0.01 364 22.9 1 0 0 1 0 1 4 0 6.1 3.3309 311772.63 0.0154 9.31 0.74 3.449 4.19 4.19 4.194
B TO C 110 PVC 93.6 27 0.01 300 18.9 1 1 1 1.4 0 2.74601 257026.52 0.01584 6.5 1.76 0.538 2.29 2.29 6.488
C TO D 90 PVC 76.6 10 0.01 242 15.3 1 0 1 0 1.1 0 3.31317 253789.01 0.01605 11.7 1.17 0.615 1.79 1.79 8.276
D TO E 90 PVC 76.6 11 0.01 162 10.2 0 1 1 1.4 0 2.22019 170066.44 0.01705 5.59 0.62 0.352 0.97 0.97 9.243
E TO F 75 PVC 63.8 20 0.01 127 7.99 1 1 1 1.7 0 2.49807 159377.1 0.01739 8.67 1.73 0.541 2.27 2.27 11.52
F TO G 63 PVC 53.6 6 0.01 107 6.74 1 1 1.4 0 2.98636 160069.02 0.01756 14.9 0.89 0.636 1.53 1.53 13.05
G TO H 63 PVC 53.6 3.5 0.01 87 5.48 1 0.9 2.42795 130138.38 0.01813 10.2 0.36 0.27 0.63 0.63 13.67
H TO I 50 PVC 42.6 7 0.01 83 5.23 1 3 1 1 2.5 3.66691 156210.35 0.0179 28.8 2.02 1.713 3.73 3.73 17.4
I TO J 40 PVC 34 3.5 0.01 50 3.14 3 1 3.2 3.45559 117490.05 0.01897 34 1.19 1.948 3.14 3.14 20.54
J TO K 40 PVC 34 3.5 0.01 75 4.72 2 1.8 5.20143 176848.48 0.01795 72.8 2.55 2.482 5.03 5.03 25.57
K TO L 40 PVC 34 3.5 0.01 69 4.37 2 1.8 4.81285 163636.75 0.01812 62.9 2.2 2.125 4.33 4.33 29.9
L TO M 32 PVC 27.2 3.5 0.01 64 4.02 2 1 2.3 6.91291 188031.27 0.01823 163 5.71 5.602 11.3 11.3 41.21
M TO N 25 PVC 21.2 1.5 0.01 60 3.79 1 1 2 1 2.8 10.7371 227626.4 0.01845 511 7.67 16.45 24.1 24.1 65.33
N TO O 25 PVC 21.2 2 0.01 58 3.64 1 0.9 10.3088 218545.56 0.01851 473 9.46 4.875 14.3 14.3 79.67
O TO P 20 PVC 17 2.5 0.01 16 0.99 3 1 1.4 4.3521 73985.703 0.02151 122 3.05 1.352 4.4 4.4 84.07

TOTAL 113 5 0 0 1 0 10 23 8 0 0 30.7 0 68.9703 2764613.7 0.26705 1535 41 43 84 84.07

Static head = 41.00 m


Outlet pressure 20 PSI = 14.00 m
total friction loss = 84.07 m
total dynamic head = 139.07 m
Add 10 % safety 0.00 = 152.98 m , 502 ft
POTABLE WATER BOOSTER PUMP

PROJECT NAME : RUMAH SAKIT UNGARAN

Head Loss Calculations:

The total friction loss Hs Consist of:

Hs = Hs1 + Hs2 …………………………………………………….…… (1)

Where: Hs1 : Friction loss Inside pipes


Hs2 : Friction loss inside fittings

Linear friction loss equation:

Hs = J . L …………………………………… ……………………………………... .... (2)

J = l . V² / ( 2 g D ) ………..…………………………………………………………….. (3)

Where: J : linear loss factor


L : length Of the pipe (m.)
l : friction loss factor (COLBROOK-WHITE formula)
V : velocity of water (m/s)
g : gravity acceleration (9.81 m/s²)
D : pipe inside diameter (m.)

COLBROOK WHITE formula:……………………………………………………………….. ( 4 )

1 k 2.51
= - 2 x log [ + )
sqr(l) 3.7 x D Re x sqr( l )

Where: K : pipe inside Surface roughness (m.)


D : pipe inside diameter (m.)
RE : REYNOLD’S no. is given as follows: (1/1)

RE = V x D / n …………………………………………………………………………. ( 5 )

Where: n : water viscosity= ( n = 1E-06 m2/s)


V : velocity of water (m/s)
D : pipe inside diameter (m.)

V = Q/A ………………………………………...………………………………………. ( 6 )

Where: Q : flow rate (m³/s)


A : cross section are of the pipe (m²)
Apply the equations 110 PVC Pipe type & size 110
for the First pipe : 110 mm Out side diameter (mm)
8.2 mm Wall thickness (mm)

D = 0.0936 m : pipe inside diameter (m.)


K = 0.00001 m : pipe inside Surface roughness (m.)

Flow : Q = 363.8 GPM = 22.919 l/s = 0.02292 m �/sec

A = p x D2 / 4 = 3.14 x 0.094 � / 4 = 0.00688 m�

V = Q/A = 3.331 m/s

Re = V x D / n = 3.331 x 0.0936 / 0.000001 = 311772.63

1 0.00001 2.51
= - 2 log [ + ]
sqr(l) 3.7 x 0.094 311772.6 x sqr( l )

By solving above equation :

l= 0.01540

0.0154 x 3.3309 x 3.331


J = l . V² / ( 2 g D ) = = 0.09307 m/m
2 x 9.81 x 0.0936

Loss m per 100 m = J x 100 = 0.09307 x 100 m = 9.307 m / 100m

Pipe length L = 8.0 m

dh(1) Liner loss = J x L = 0.09307 x 8.0 = 0.745 m


Local losses equation is given as follows:

HS2 = SUM ZE . V ² / ( 2 . G ) …..…………………………………………………….. (7)

Where: G : Gravity acceleration (9.81 m/s²)


V : Velocity of water (m/s)
SUM ZE : Sum of local loss factors

SUM ZE = gate valve 1 x 0.2 = 0.2


Multimedia filter 0 x 1 = 0
Foot valve 0 x 1 = 0
check valve 1 x 2 = 2
elbow ( 45 leg.) 0 x 0.3 = 0
elbow ( 90 leg.) 1 x 0.3 = 0.3
tee 4 x 0.9 = 3.6
reducer 0 x 0.5 = 0
Strainer 0 x 2 = 0
discharge outlet 0 x 1 = 0
Total local factors = 6.10

HS2 = SUM ZE . V ² / ( 2 . g )

3.3309 X 3.3309
HS(2) = SUM ZE.x V² / ( 2 g ) = 6.1 x = 3.4495 m
2 x 9.81

DH Total loss = HS1 + HS2 = 0.745 + 3.449 = 4.194 m

Total head (DH+GH) / pipe = Static head + Friction losses ………………………. ( 8 )

= 0.0 + 4.194 = 4.194 m


PROJECT NAME : TAIF UNIVERSITY HOUSING (MALE).

POTABLE WATER BOOSTER PUMP :

Based on the previous calculations and refering to tender documents,

The potable water booster pump will be a set of three pumps

Each: 70 GPM @ 80 FT head


ZUHAIR FAYEZ PARTNERSHIP MINISTRY OF HIGHER EDUCATION CONTRACTOR :

RMC
AL-RASHID & AL-MANGOUR CO

PROJECT NO: 357 LOCATION : TAIF UNIVERSITY - TAIF(K.S.A)


PROJECT NAME : TAIF UNIVERSITY HOUSING (MALE).

HYDRAULIC CALCULATION FOR

POTABLE & FLUSH WATER BOOSTER PUMPS

( 1 ) WATER DEMAND

( 2 ) TOTAL DYNAMIC HEAD

Prepared By Checked By

Eng. Ahmed Hikal Eng. Aboobucker Sediq


Mechanical Project Engineer Chief of Mechanical Dept.

Das könnte Ihnen auch gefallen