REFRIGERACION Y AIRE ACONDICIONADO MEC 3338 A

RESOLUCION PRACTICA N 10

condiciones ambientales

AUX: UNIV. WILMER IGNACIO I. ORURO-BOLIVIA MAYO 2015


REFRIGERACION Y AIRE ACONDICIONADO MEC 3338 A

condiciones ambientales
Ti ≔ 25 C Te ≔ 5 C
HR ≔ 40% HR ≔ 60%
areas de pared
Pared norte
2
An ≔ 5.75 m ⋅ 4 m = 23 m considerando que no es pared solo las
dos ventanas
Pared oeste
2
Ao ≔ (5.12 m + 3.47 m − 2.5 m) ⋅ 4 m = 24.36 m
ventanas
2
Av ≔ 2 ⋅ (1.5 m ⋅ 1.5 m)) + 2.5 m ⋅ 1.5 m = 8.25 m
2
Apared ≔ An + Ao − Av = 39.11 m

coeficiente global de transferencia segun Stoker tabla 22.1


kcal km
he = 9.8 + 1.2 ⋅ vexterior ―――― donde la velocidad esta en ――
2
hr ⋅ m ⋅ C hr

kcal km
hi = 10.3 + 1.5 ⋅ vinterior ―――― donde la velocidad esta en ――
2
hr ⋅ m ⋅ C hr

tomando valores de:


km cm
vexterior = 13 ―― vinterio = 20 ――
hr s

kcal kcal
he ≔ 25.4 ―――― hi ≔ 11.38 ――――
2 2
hr ⋅ m ⋅ C hr ⋅ m ⋅ C

kcal
x1 ≔ 0.02 m k1 ≔ 0.81 ―――
hr ⋅ m ⋅ C
x2 ≔ 0.15 m
kcal kcal
k2 ≔ 0.6 ――― k3 ≔ 0.4 ―――
x3 ≔ 0.015 m hr ⋅ m ⋅ C hr ⋅ m ⋅ C

1 kW kcal
U ≔ ―――――――― = 0.003 ――― U = 2.558 ――――
2 2
1 x1 x2 x3 1 m ⋅C hr ⋅ m ⋅ C
+ +
― ― ― ― ― + +
he k1 k2 k3 he

Qpared ≔ U ⋅ Apared (Te − Ti)

Qpared = −2.327 kW el signo representa perdias hacia el aire exterior,


eso se debido a que el aire interior esta mas
caliente

Transferencia de calor debido al vidrio:

AUX: UNIV. WILMER IGNACIO I. ORURO-BOLIVIA MAYO 2015


REFRIGERACION Y AIRE ACONDICIONADO MEC 3338 A

Transferencia de calor debido al vidrio:

W
Uv ≔ 5.8 ――― coeficiente global de transferencia de calor del vidrio
2
m ⋅C

Qvidrio ≔ Uv ⋅ Av ⋅ (Te − Ti) Qvidrio = −0.957 kW


ya se explico el vidrio
anteriormente

Transferencia de calor debido a la readiacion


W W
Rnorte ≔ 81 ―― Roeste ≔ 41 ――
2 2
m m

f ≔ 0.62 ⋅ 1.17 = 0.725 factores que se obtienen de tabla 5 y 6

Qrad ≔ ⎛⎝Rnorte ⋅ 1.5 m ⋅ 1.5 m ⋅ 2 + Roeste ⋅ 2.5 m ⋅ 1.5 m⎞⎠ ⋅ f

2 ventanas al 1 ventana al lado


lado norte oeste

Qrad = 0.376 kW

Transferencia de calor por paredes interioresParedes interiores

W
Uint ≔ 1.86 ――― ΔT = 3 ‥ .5C solo para paredes interiores
2
m ⋅C
pared sud pared este
2
area de paredes interiores Aint ≔ 7.64 m ⋅ 4 m + 7.89 m ⋅ 4 m = 62.12 m

Qparedes.int ≔ Uint ⋅ Aint ⋅ (4 C))

Qparedes.int = 0.462 kW

Calor sencible y calor latente generado por perzonas

Csensible ≔ 70 W Clatente ≔ 50 W

Qperzonas ≔ Csensible ⋅ 150 + Clatente ⋅ 150 150 es el numero de


perzonas en el salon
Qperzonas = 18 kW

calor generado por iluminacion

AUX: UNIV. WILMER IGNACIO I. ORURO-BOLIVIA MAYO 2015


REFRIGERACION Y AIRE ACONDICIONADO MEC 3338 A

calor generado por iluminacion


potencia instalada 0.9 es debido a la irregularidad que
tiene el area del piso del esquema
Ailuminar ≔ (7.64 m ⋅ 7.89 m − 2 m ⋅ 2.5 m) ⋅ 0.9

W
Pins ≔ 8 ―― ⋅ Ailuminar = 0.398 kW
2
m

Qilum ≔ Pins ⋅ 1.25 Qilum = 0.498 kW

calor sensible y latente procedente de la ventilacion

Qs1 = f ⋅ ρ ⋅ V ⋅ Nperzonas ⋅ cp ⋅ (Te − Ti)) kW f es el factor de By-pass =0.3


3
kg m J
Qs1 ≔ 0.3 ⋅ 1.2 ―― ⋅ 85 ―― ⋅ 150 ⋅ 1004.66 ――⋅ (−20 C))
3
m hr kg ⋅ C
Qs1 = −25.619 kW

con la formula directa valido solo para el nivl del mar


Qs = 0.33 ⋅ f ⋅ V ⋅ Nperzonas ⋅ ΔT

Qs ≔ 0.33 ⋅ 0.3 ⋅ 85 ⋅ 150 ⋅ −20 W = −25.245 kW

Ql1 = f ⋅ ρ ⋅ V ⋅ Nperzonas ⋅ Δω ⋅ hfg


3
kg m J
Ql1 ≔ 0.3 ⋅ 1.2 ―― ⋅ 85 ―― ⋅ 150 ⋅ (0.002176 − 0.01188)) ⋅ 2512200 ―
3
m hr kg

Ql1 = −31.082 kW

o con la formula directa (valido solo para nivel del mar)


kgw kgw
ω1 ≔ 0.002176 ―― ω2 ≔ 0.01188 ――
kga kga
Ql ≔ 0.84 ⋅ 0.3 ⋅ 85 ⋅ 150 ⋅ ⎛⎝ω1 − ω2⎞⎠ kW

Ql = −31.179 kW

Qventilacion ≔ Qs1 + Ql1

Qventilacion = −56.701 kW

Sumatoria de la carga termica total

AUX: UNIV. WILMER IGNACIO I. ORURO-BOLIVIA MAYO 2015


REFRIGERACION Y AIRE ACONDICIONADO MEC 3338 A

Sumatoria de la carga termica total

Qpared = −2.327 kW

Qrad = 0.376 kW

Qparedes.int = 0.462 kW

Qperzonas = 18 kW

Qilum = 0.498 kW

Qventilacion = −56.701 kW

Qtotal ≔ ⎛⎝Qventilacion + Qilum + Qperzonas + Qparedes.int + Qrad + Qpared⎞⎠ ⋅ 1.1

Qtotal = −43.662 kW

NOTA: se debe tomar en cuenta que:

Texterior < Tinterior se trata de un proceso de calentamiento, la carga


termica representa perdidas, por tanto sera negativa

Texterior > Tinterior se tratara de un proceso de enfriamiento por tanto la


garga termica representa ganancia de calor, por lo cual
sera positiva.