Sie sind auf Seite 1von 76

Operator: Project address: Date:

Darwin A. Bernardo 19-053 2/28/2019

Advanced Lighting Company


Almadar Industrial, Ibn Sena
Al Khobar, Kingdom of Saudi
Arabia

darwin.bernardo@alc.sa

Al Ramaniah Commercial Building & Offices


Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Table of contents

Table of contents
Al Ramaniah Commercial Building & Offices
Luminaire parts list.................................................................................................................................................................................................... 4
Views.........................................................................................................................................................................................................................6
Site 1
Results summary of surfaces............................................................................................................................................................................. 16
Parking Driveway / Horizontal illuminance..........................................................................................................................................................17
Parking Slot / Horizontal illuminance.................................................................................................................................................................. 18
Parking Slot / Horizontal illuminance.................................................................................................................................................................. 20
Parking Driveway / Horizontal illuminance..........................................................................................................................................................21
Parking Slot / Horizontal illuminance.................................................................................................................................................................. 22
Building Side / Horizontal illuminance.................................................................................................................................................................23
Rooftop / Horizontal illuminance......................................................................................................................................................................... 24
Rooftop / Horizontal illuminance......................................................................................................................................................................... 26
Building 2
Ground Floor
Corridor
Room summary..................................................................................................................................................................................... 28
Corridor
Room summary..................................................................................................................................................................................... 29
Staircase
Room summary..................................................................................................................................................................................... 30
Staircase
Room summary..................................................................................................................................................................................... 31
Results summary of surfaces................................................................................................................................................................ 32
Staircase
Room summary..................................................................................................................................................................................... 33
Results summary of surfaces................................................................................................................................................................ 34
First Floor
1 Office
Room summary..................................................................................................................................................................................... 35
1 Toilet
Room summary..................................................................................................................................................................................... 36
10 Office
Room summary..................................................................................................................................................................................... 37
10 Office
Room summary..................................................................................................................................................................................... 38
2 Office
Room summary..................................................................................................................................................................................... 39
2 Toilet
Room summary..................................................................................................................................................................................... 40
3 Office
Room summary..................................................................................................................................................................................... 41
3 Toilet
Room summary..................................................................................................................................................................................... 42
4 Office
Room summary..................................................................................................................................................................................... 43
4 Toilet
Room summary..................................................................................................................................................................................... 44
5 Office
Room summary..................................................................................................................................................................................... 45
5 Toilet
Room summary..................................................................................................................................................................................... 46
6 Office
Room summary..................................................................................................................................................................................... 47
6 Toilet
Room summary..................................................................................................................................................................................... 48
7 Office

Page 2
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Table of contents

Room summary..................................................................................................................................................................................... 49
7 Toilet
Room summary..................................................................................................................................................................................... 50
8 Office
Room summary..................................................................................................................................................................................... 51
8 Toilet
Room summary..................................................................................................................................................................................... 52
9 Office
Room summary..................................................................................................................................................................................... 53
9 Office
Room summary..................................................................................................................................................................................... 54
Corridor
Room summary..................................................................................................................................................................................... 55
Corridor
Room summary..................................................................................................................................................................................... 56
Staircase
Room summary..................................................................................................................................................................................... 57
Results summary of surfaces................................................................................................................................................................ 58
Staircase
Room summary..................................................................................................................................................................................... 59
Results summary of surfaces................................................................................................................................................................ 60
Staircase
Room summary..................................................................................................................................................................................... 61
Results summary of surfaces................................................................................................................................................................ 62
Second Floor
11 Office
Room summary..................................................................................................................................................................................... 63
11 Toilet
Room summary..................................................................................................................................................................................... 64
12 Office
Room summary..................................................................................................................................................................................... 65
12 Toilet
Room summary..................................................................................................................................................................................... 66
13 Office
Room summary..................................................................................................................................................................................... 67
13 Toilet
Room summary..................................................................................................................................................................................... 68
14 Office
Room summary..................................................................................................................................................................................... 69
14 Toilet
Room summary..................................................................................................................................................................................... 70
Corridor
Room summary..................................................................................................................................................................................... 71
Corridor
Room summary..................................................................................................................................................................................... 72
Staircase
Room summary..................................................................................................................................................................................... 73
Staircase
Room summary..................................................................................................................................................................................... 74
Building 3
SEC
SEC RM
Room summary..................................................................................................................................................................................... 75
SEC RM
Room summary..................................................................................................................................................................................... 76

Page 3
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Luminaire parts list

Al Ramaniah Commercial Building & Offices


Quantity Luminaire (Luminous emittance)
26 Advanced Lighting Company - AL-CD38-10W-X-8-40
Luminous emittance 1
Fitting: 1x10W LED/840
Light output ratio: 100%
Lamp luminous flux: 902 lm
Luminaire luminous flux: 902 lm See our luminaire catalog for
Power: 10.2 W an image of the luminaire.
Luminous efficacy: 88.5 lm/W

Colorimetric data
1x: CCT 4000 K, CRI 80

34 Advanced Lighting Company - AL-CD38-25W-X-8-40


Luminous emittance 1
Fitting: 1x25W LED/840
Light output ratio: 100%
Lamp luminous flux: 2745 lm
Luminaire luminous flux: 2745 lm See our luminaire catalog for
Power: 25.4 W an image of the luminaire.
Luminous efficacy: 108.1 lm/W

Colorimetric data
1x: CCT 4000 K, CRI 80

14 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-


40-MB
Luminous emittance 1
Fitting: 1x10W LED/840
Light output ratio: 100%
Lamp luminous flux: 1044 lm See our luminaire catalog for
Luminaire luminous flux: 1044 lm an image of the luminaire.
Power: 10.5 W
Luminous efficacy: 99.4 lm/W

Colorimetric data
1x: CCT 4000 K, CRI 80

64 Advanced Lighting Company - AL-DS59-6-18W-X-8-40


Luminous emittance 1
Fitting: 1x18W LED/840
Light output ratio: 100%
Lamp luminous flux: 1904 lm
Luminaire luminous flux: 1904 lm See our luminaire catalog for
Power: 17.7 W an image of the luminaire.
Luminous efficacy: 107.6 lm/W

Colorimetric data
1x: CCT 4000 K, CRI 80

4 Advanced Lighting Company - AL-IN01-12-40W-X-8-40


Luminous emittance 1
Fitting: 1x40W LED/840
Light output ratio: 100%
Lamp luminous flux: 4292 lm
Luminaire luminous flux: 4292 lm See our luminaire catalog for
Power: 41.4 W an image of the luminaire.
Luminous efficacy: 103.7 lm/W

Colorimetric data
1x: CCT 4000 K, CRI 80

Page 4
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Luminaire parts list

Quantity Luminaire (Luminous emittance)


246 Advanced Lighting Company - AL-PLM1-22-36W-X-8-
40
Luminous emittance 1
Fitting: 1x36W LED/840
Light output ratio: 100%
Lamp luminous flux: 4072 lm See our luminaire catalog for
Luminaire luminous flux: 4072 lm an image of the luminaire.
Power: 36.3 W
Luminous efficacy: 112.2 lm/W

Colorimetric data
1x: CCT 4000 K, CRI 80

9 Advanced Lighting Company - AL-SL01-30W-X-7-40-


3M
Luminous emittance 1
Fitting: 1x30W LED/740
Light output ratio: 100%
Lamp luminous flux: 3711 lm See our luminaire catalog for
Luminaire luminous flux: 3711 lm an image of the luminaire.
Power: 29.4 W
Luminous efficacy: 126.2 lm/W

Colorimetric data
1x: CCT 4000 K, CRI 70

34 Advanced Lighting Company - AL-WL01-18W-X-8-40


Luminous emittance 1
Fitting: 1x18W LED/840
Light output ratio: 100%
Lamp luminous flux: 1632 lm
Luminaire luminous flux: 1632 lm See our luminaire catalog for
Power: 16.8 W an image of the luminaire.
Luminous efficacy: 97.1 lm/W

Colorimetric data
1x: CCT 4000 K, CRI 80

14 Advanced Lighting Company - AL-WP02-30W-X-7-50


Luminous emittance 1
Fitting: 1x30W LED/750
Light output ratio: 100%
Lamp luminous flux: 3300 lm
Luminaire luminous flux: 3300 lm See our luminaire catalog for
Power: 30.0 W an image of the luminaire.
Luminous efficacy: 110.0 lm/W

Colorimetric data
1x: CCT 5000 K, CRI 70

Total lamp luminous flux: 1407221 lm, Total luminaire luminous flux: 1407221 lm, Total Load: 12759.8 W, Luminous efficacy: 110.3 lm/W

Page 5
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Views

Al Ramaniah Commercial Building & Offices

Site Render_01

Page 6
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Views

Site False Color Render_01, Illuminance values in [lx]

0.10 0.16 0.25 0.40 0.63 1.00 1.25 1.58 1.99 2.51 3.16 3.97 5.00 6.30 7.93

9.98 13 16 20 25 32 40 50 208 866 [lx]

Page 7
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Views

Site Render_02

Page 8
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Views

Site False Color Render_02, Illuminance values in [lx]

0.10 0.16 0.25 0.40 0.63 1.00 1.25 1.58 1.99 2.51 3.16 3.97 5.00 6.30 7.93

9.98 13 16 20 25 32 40 50 208 866 [lx]

Page 9
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Views

Ground Floor Render

Page 10
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Views

Ground Floor False Color Render, Illuminance values in [lx]

0.10 0.16 0.25 0.40 0.63 1.00 1.25 1.58 1.99 2.51 3.16 3.97 5.00 6.30 7.93

9.98 13 16 20 25 32 40 50 208 [lx]

Page 11
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Views

First Floor Render

Page 12
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Views

First Floor False Color Render, Illuminance values in [lx]

0.10 0.16 0.25 0.40 0.63 1.00 1.25 1.58 1.99 2.51 3.16 3.97 5.00 6.30 7.93

9.98 13 16 20 25 32 40 50 208 866 [lx]

Page 13
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Views

Second Floor Render

Page 14
Al Ramaniah Commercial Building & Offices 2/28/2019

Al Ramaniah Commercial Building & Offices / Views

Second Floor False Color Render, Illuminance values in [lx]

0.10 0.16 0.25 0.40 0.63 1.00 1.25 1.58 1.99 2.51 3.16 3.97 5.00 6.30 7.93

9.98 13 16 20 25 32 40 50 208 [lx]

Page 15
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Results summary of surfaces

Site 1

Light loss factor: 0.80

General
Surface Result Average Min Max Min/average Min/max

1 Parking Driveway Horizontal illuminance [lx] 12.0 9.18 14.9 0.77 0.62
Height: 0.000 m

2 Parking Slot Horizontal illuminance [lx] 20.9 13.9 28.7 0.67 0.48
Height: 0.000 m

3 Parking Slot Horizontal illuminance [lx] 18.8 6.22 40.2 0.33 0.15
Height: 0.000 m

4 Parking Driveway Horizontal illuminance [lx] 11.9 3.49 44.1 0.29 0.079
Height: 0.000 m

5 Parking Slot Horizontal illuminance [lx] 28.1 8.40 59.5 0.30 0.14
Height: 0.000 m

6 Building Side Horizontal illuminance [lx] 20.4 0.000 41.3 0.00 0.00
Height: 0.000 m

7 Rooftop Horizontal illuminance [lx] 19.6 4.92 114 0.25 0.043


Height: 7.800 m

8 Rooftop Horizontal illuminance [lx] 39.8 7.89 308 0.20 0.026


Height: 7.800 m

Page 16
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Parking Driveway / Horizontal illuminance

Parking Driveway / Horizontal illuminance

Light loss factor: 0.80

Parking Driveway: Horizontal illuminance (Grid)


Light scene: Light scene 1
Average: 12.0 lx, Min: 9.18 lx, Max: 14.9 lx, Min/average: 0.77, Min/max: 0.62
Height: 0.000 m

Value grid [lx]

Scale: 1 : 500

Page 17
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Parking Slot / Horizontal illuminance

Parking Slot / Horizontal illuminance

Light loss factor: 0.80

Parking Slot: Horizontal illuminance (Grid)


Light scene: Light scene 1
Average: 20.9 lx, Min: 13.9 lx, Max: 28.7 lx, Min/average: 0.67, Min/max: 0.48
Height: 0.000 m

Page 18
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Parking Slot / Horizontal illuminance

Value grid [lx]

Scale: 1 : 200

Page 19
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Parking Slot / Horizontal illuminance

Parking Slot / Horizontal illuminance

Light loss factor: 0.80

Parking Slot: Horizontal illuminance (Grid)


Light scene: Light scene 1
Average: 18.8 lx, Min: 6.22 lx, Max: 40.2 lx, Min/average: 0.33, Min/max: 0.15
Height: 0.000 m

Value grid [lx]

Scale: 1 : 200

Page 20
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Parking Driveway / Horizontal illuminance

Parking Driveway / Horizontal illuminance

Light loss factor: 0.80

Parking Driveway: Horizontal illuminance (Grid)


Light scene: Light scene 1
Average: 11.9 lx, Min: 3.49 lx, Max: 44.1 lx, Min/average: 0.29, Min/max: 0.079
Height: 0.000 m

Value grid [lx]

Scale: 1 : 500

Page 21
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Parking Slot / Horizontal illuminance

Parking Slot / Horizontal illuminance

Light loss factor: 0.80

Parking Slot: Horizontal illuminance (Grid)


Light scene: Light scene 1
Average: 28.1 lx, Min: 8.40 lx, Max: 59.5 lx, Min/average: 0.30, Min/max: 0.14
Height: 0.000 m

Value grid [lx]

Scale: 1 : 500

Page 22
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building Side / Horizontal illuminance

Building Side / Horizontal illuminance

Light loss factor: 0.80

Building Side: Horizontal illuminance (Grid)


Light scene: Light scene 1
Average: 20.4 lx, Min: 0.000 lx, Max: 41.3 lx, Min/average: 0.00, Min/max: 0.00
Height: 0.000 m

Value grid [lx]

Scale: 1 : 500

Page 23
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Rooftop / Horizontal illuminance

Rooftop / Horizontal illuminance

Light loss factor: 0.80

Rooftop: Horizontal illuminance (Grid)


Light scene: Light scene 1
Average: 19.6 lx, Min: 4.92 lx, Max: 114 lx, Min/average: 0.25, Min/max: 0.043
Height: 7.800 m

Page 24
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Rooftop / Horizontal illuminance

Value grid [lx]

Scale: 1 : 100

Page 25
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Rooftop / Horizontal illuminance

Rooftop / Horizontal illuminance

Light loss factor: 0.80

Rooftop: Horizontal illuminance (Grid)


Light scene: Light scene 1
Average: 39.8 lx, Min: 7.89 lx, Max: 308 lx, Min/average: 0.20, Min/max: 0.026
Height: 7.800 m

Page 26
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Rooftop / Horizontal illuminance

Value grid [lx]

Scale: 1 : 200

Page 27
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Ground Floor / Corridor / Room summary

Corridor

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (Corridor) Perpendicular illuminance (adaptive) [lx] 175 97.7 224 0.56 0.44
Height: 0.100 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

9 Advanced Lighting Company - AL-DS59-6-18W-X-8-40 1904 17.7 107.6

Total via all luminaires 17136 159.3 107.6

Lighting power density: 3.49 W/m² = 1.99 W/m²/100 lx (Floor area of room 45.66 m²)

Consumption: 440 kWh/a of maximum 1600 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 28
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Ground Floor / Corridor / Room summary

Corridor

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (Corridor) Perpendicular illuminance (adaptive) [lx] 172 99.1 212 0.58 0.47
Height: 0.100 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

9 Advanced Lighting Company - AL-DS59-6-18W-X-8-40 1904 17.7 107.6

Total via all luminaires 17136 159.3 107.6

Lighting power density: 3.49 W/m² = 2.03 W/m²/100 lx (Floor area of room 45.66 m²)

Consumption: 440 kWh/a of maximum 1600 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 29
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Ground Floor / Staircase / Room summary

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

2 Advanced Lighting Company - AL-CD38-25W-X-8-40 2745 25.4 108.1

Total via all luminaires 5490 50.8 108.1

Lighting power density: 2.30 W/m² (Floor area of room 22.12 m²)

Consumption: 140 kWh/a of maximum 800 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 30
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Ground Floor / Staircase / Room summary

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 66.9%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-CD38-25W-X-8-40 2745 25.4 108.1

Total via all luminaires 2745 25.4 108.1

Lighting power density: 1.85 W/m² (Floor area of room 13.75 m²)

Consumption: 70 kWh/a of maximum 500 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 31
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Ground Floor / Staircase / Results summary of surfaces

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 66.9%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

General
Surface Result Average Min Max Min/average Min/max

1 Platform Perpendicular illuminance [lx] 188 160 207 0.85 0.77


Height: 1.581 m

2 Platform Perpendicular illuminance [lx] 261 181 347 0.69 0.52


Height: 0.000 m

Page 32
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Ground Floor / Staircase / Room summary

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Lighting power density: 0.00 W/m² (Floor area of room 13.68 m²)

Consumption: 0 kWh/a of maximum 50 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 33
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Ground Floor / Staircase / Results summary of surfaces

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

General
Surface Result Average Min Max Min/average Min/max

1 Platform Perpendicular illuminance [lx] 274 251 296 0.92 0.85


Height: 2.100 m

2 Platform Perpendicular illuminance [lx] 283 258 303 0.91 0.85


Height: 1.100 m

Page 34
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 1 Office / Room summary

1 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (1 Office) Perpendicular illuminance (adaptive) [lx] 522 203 685 0.39 0.30
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

16 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 65152 580.8 112.2

Lighting power density: 6.70 W/m² = 1.28 W/m²/100 lx (Floor area of room 86.67 m²)

Consumption: 1600 kWh/a of maximum 3050 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 35
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 1 Toilet / Room summary

1 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (1 Toilet) Perpendicular illuminance (adaptive) [lx] 232 77.6 408 0.33 0.19
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 3.89 W/m² = 1.68 W/m²/100 lx (Floor area of room 2.70 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 36
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 10 Office / Room summary

10 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (10 Office) Perpendicular illuminance (adaptive) [lx] 523 191 687 0.37 0.28
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

16 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 65152 580.8 112.2

Lighting power density: 6.70 W/m² = 1.28 W/m²/100 lx (Floor area of room 86.68 m²)

Consumption: 1600 kWh/a of maximum 3050 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 37
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 10 Office / Room summary

10 Office

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (10 Office) Perpendicular illuminance (adaptive) [lx] 232 76.4 408 0.33 0.19
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 3.89 W/m² = 1.68 W/m²/100 lx (Floor area of room 2.70 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 38
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 2 Office / Room summary

2 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (2 Office) Perpendicular illuminance (adaptive) [lx] 492 174 653 0.35 0.27
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

14 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 57008 508.2 112.2

Lighting power density: 6.44 W/m² = 1.31 W/m²/100 lx (Floor area of room 78.91 m²)

Consumption: 1400 kWh/a of maximum 2800 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 39
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 2 Toilet / Room summary

2 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (2 Toilet) Perpendicular illuminance (adaptive) [lx] 231 77.4 408 0.34 0.19
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 3.89 W/m² = 1.68 W/m²/100 lx (Floor area of room 2.70 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 40
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 3 Office / Room summary

3 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (3 Office) Perpendicular illuminance (adaptive) [lx] 490 171 652 0.35 0.26
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

14 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 57008 508.2 112.2

Lighting power density: 6.44 W/m² = 1.31 W/m²/100 lx (Floor area of room 78.91 m²)

Consumption: 1400 kWh/a of maximum 2800 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 41
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 3 Toilet / Room summary

3 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (3 Toilet) Perpendicular illuminance (adaptive) [lx] 232 77.4 407 0.33 0.19
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 3.89 W/m² = 1.68 W/m²/100 lx (Floor area of room 2.70 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 42
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 4 Office / Room summary

4 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (4 Office) Perpendicular illuminance (adaptive) [lx] 457 172 603 0.38 0.29
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

10 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 40720 363.0 112.2

Lighting power density: 6.64 W/m² = 1.45 W/m²/100 lx (Floor area of room 54.70 m²)

Consumption: 1000 kWh/a of maximum 1950 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 43
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 4 Toilet / Room summary

4 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (4 Toilet) Perpendicular illuminance (adaptive) [lx] 232 77.0 409 0.33 0.19
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 3.89 W/m² = 1.68 W/m²/100 lx (Floor area of room 2.70 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 44
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 5 Office / Room summary

5 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (5 Office) Perpendicular illuminance (adaptive) [lx] 515 150 688 0.29 0.22
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

17 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 69224 617.1 112.2

Lighting power density: 7.10 W/m² = 1.38 W/m²/100 lx (Floor area of room 86.89 m²)

Consumption: 1700 kWh/a of maximum 3050 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 45
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 5 Toilet / Room summary

5 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (5 Toilet) Perpendicular illuminance (adaptive) [lx] 241 85.1 410 0.35 0.21
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 4.12 W/m² = 1.71 W/m²/100 lx (Floor area of room 2.55 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 46
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 6 Office / Room summary

6 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (6 Office) Perpendicular illuminance (adaptive) [lx] 514 141 690 0.27 0.20
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

17 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 69224 617.1 112.2

Lighting power density: 7.10 W/m² = 1.38 W/m²/100 lx (Floor area of room 86.89 m²)

Consumption: 1700 kWh/a of maximum 3050 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 47
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 6 Toilet / Room summary

6 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (6 Toilet) Perpendicular illuminance (adaptive) [lx] 241 87.9 409 0.36 0.21
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 4.12 W/m² = 1.71 W/m²/100 lx (Floor area of room 2.55 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 48
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 7 Office / Room summary

7 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (7 Office) Perpendicular illuminance (adaptive) [lx] 458 171 605 0.37 0.28
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

10 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 40720 363.0 112.2

Lighting power density: 6.64 W/m² = 1.45 W/m²/100 lx (Floor area of room 54.70 m²)

Consumption: 1000 kWh/a of maximum 1950 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 49
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 7 Toilet / Room summary

7 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (7 Toilet) Perpendicular illuminance (adaptive) [lx] 231 76.6 408 0.33 0.19
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 3.89 W/m² = 1.68 W/m²/100 lx (Floor area of room 2.70 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 50
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 8 Office / Room summary

8 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (8 Office) Perpendicular illuminance (adaptive) [lx] 492 175 651 0.36 0.27
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

14 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 57008 508.2 112.2

Lighting power density: 6.44 W/m² = 1.31 W/m²/100 lx (Floor area of room 78.91 m²)

Consumption: 1400 kWh/a of maximum 2800 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 51
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 8 Toilet / Room summary

8 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (8 Toilet) Perpendicular illuminance (adaptive) [lx] 231 77.0 407 0.33 0.19
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 3.89 W/m² = 1.68 W/m²/100 lx (Floor area of room 2.70 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 52
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 9 Office / Room summary

9 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (9 Office) Perpendicular illuminance (adaptive) [lx] 490 167 651 0.34 0.26
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

14 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 57008 508.2 112.2

Lighting power density: 6.44 W/m² = 1.32 W/m²/100 lx (Floor area of room 78.91 m²)

Consumption: 1400 kWh/a of maximum 2800 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 53
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / 9 Office / Room summary

9 Office

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (9 Office) Perpendicular illuminance (adaptive) [lx] 231 76.3 407 0.33 0.19
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 3.89 W/m² = 1.68 W/m²/100 lx (Floor area of room 2.70 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 54
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / Corridor / Room summary

Corridor

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (Corridor) Perpendicular illuminance (adaptive) [lx] 159 83.4 258 0.52 0.32
Height: 0.100 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

18 Advanced Lighting Company - AL-DS59-6-18W-X-8-40 1904 17.7 107.6

Total via all luminaires 34272 318.6 107.6

Lighting power density: 3.28 W/m² = 2.06 W/m²/100 lx (Floor area of room 97.16 m²)

Consumption: 880 kWh/a of maximum 3450 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 55
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / Corridor / Room summary

Corridor

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (Corridor) Perpendicular illuminance (adaptive) [lx] 159 81.1 256 0.51 0.32
Height: 0.100 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

18 Advanced Lighting Company - AL-DS59-6-18W-X-8-40 1904 17.7 107.6

Total via all luminaires 34272 318.6 107.6

Lighting power density: 3.28 W/m² = 2.06 W/m²/100 lx (Floor area of room 97.16 m²)

Consumption: 880 kWh/a of maximum 3450 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 56
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / Staircase / Room summary

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

4 Advanced Lighting Company - AL-CD38-25W-X-8-40 2745 25.4 108.1

Total via all luminaires 10980 101.6 108.1

Lighting power density: 4.59 W/m² (Floor area of room 22.13 m²)

Consumption: 280 kWh/a of maximum 800 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 57
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / Staircase / Results summary of surfaces

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

General
Surface Result Average Min Max Min/average Min/max

1 Platform Perpendicular illuminance [lx] 293 194 375 0.66 0.52


Height: 0.000 m

Page 58
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / Staircase / Room summary

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

2 Advanced Lighting Company - AL-CD38-25W-X-8-40 2745 25.4 108.1

Total via all luminaires 5490 50.8 108.1

Lighting power density: 3.71 W/m² (Floor area of room 13.68 m²)

Consumption: 140 kWh/a of maximum 500 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 59
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / Staircase / Results summary of surfaces

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

General
Surface Result Average Min Max Min/average Min/max

1 Platform Perpendicular illuminance [lx] 330 293 360 0.89 0.81


Height: 2.100 m

2 Platform Perpendicular illuminance [lx] 261 236 283 0.90 0.83


Height: 1.100 m

Page 60
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / Staircase / Room summary

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 24.5%, Light loss factor: 0.80

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

3 Advanced Lighting Company - AL-CD38-25W-X-8-40 2745 25.4 108.1

Total via all luminaires 8235 76.2 108.1

Lighting power density: 5.54 W/m² (Floor area of room 13.75 m²)

Consumption: 210 kWh/a of maximum 500 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 61
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / First Floor / Staircase / Results summary of surfaces

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 24.5%, Light loss factor: 0.80

General
Surface Result Average Min Max Min/average Min/max

1 Platform Perpendicular illuminance [lx] 296 211 354 0.71 0.60


Height: 0.000 m

Page 62
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / 11 Office / Room summary

11 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (11 Office) Perpendicular illuminance (adaptive) [lx] 513 141 680 0.27 0.21
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

32 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 130304 1161.6 112.2

Lighting power density: 6.21 W/m² = 1.21 W/m²/100 lx (Floor area of room 187.02 m²)

Consumption: 3000 - 3200 kWh/a of maximum 6550 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 63
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / 11 Toilet / Room summary

11 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (11 Toilet) Perpendicular illuminance (adaptive) [lx] 232 76.4 408 0.33 0.19
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 3.89 W/m² = 1.68 W/m²/100 lx (Floor area of room 2.70 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 64
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / 12 Office / Room summary

12 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (12 Office) Perpendicular illuminance (adaptive) [lx] 505 156 683 0.31 0.23
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

20 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 81440 726.0 112.2

Lighting power density: 6.44 W/m² = 1.28 W/m²/100 lx (Floor area of room 112.68 m²)

Consumption: 1700 - 2000 kWh/a of maximum 3950 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 65
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / 12 Toilet / Room summary

12 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (12 Toilet) Perpendicular illuminance (adaptive) [lx] 291 137 430 0.47 0.32
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 5.83 W/m² = 2.01 W/m²/100 lx (Floor area of room 1.80 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 66
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / 13 Office / Room summary

13 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (13 Office) Perpendicular illuminance (adaptive) [lx] 505 149 684 0.30 0.22
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

20 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 81440 726.0 112.2

Lighting power density: 6.44 W/m² = 1.28 W/m²/100 lx (Floor area of room 112.68 m²)

Consumption: 1700 - 2000 kWh/a of maximum 3950 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 67
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / 13 Toilet / Room summary

13 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (13 Toilet) Perpendicular illuminance (adaptive) [lx] 290 134 429 0.46 0.31
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 5.83 W/m² = 2.01 W/m²/100 lx (Floor area of room 1.80 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 68
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / 14 Office / Room summary

14 Office

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (14 Office) Perpendicular illuminance (adaptive) [lx] 513 139 679 0.27 0.20
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

32 Advanced Lighting Company - AL-PLM1-22-36W-X-8-40 4072 36.3 112.2

Total via all luminaires 130304 1161.6 112.2

Lighting power density: 6.21 W/m² = 1.21 W/m²/100 lx (Floor area of room 187.02 m²)

Consumption: 3000 - 3200 kWh/a of maximum 6550 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 69
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / 14 Toilet / Room summary

14 Toilet

Clearance height: 2.400 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (14 Toilet) Perpendicular illuminance (adaptive) [lx] 232 76.5 408 0.33 0.19
Height: 0.800 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

1 Advanced Lighting Company - AL-DC10-3-10W-B-X-8-40-MB 1044 10.5 99.4

Total via all luminaires 1044 10.5 99.4

Lighting power density: 3.89 W/m² = 1.68 W/m²/100 lx (Floor area of room 2.70 m²)

Consumption: 29 kWh/a of maximum 100 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 70
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / Corridor / Room summary

Corridor

Clearance height: 3.000 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (Corridor) Perpendicular illuminance (adaptive) [lx] 149 71.7 197 0.48 0.36
Height: 0.100 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

5 Advanced Lighting Company - AL-DS59-6-18W-X-8-40 1904 17.7 107.6

Total via all luminaires 9520 88.5 107.6

Lighting power density: 3.25 W/m² = 2.19 W/m²/100 lx (Floor area of room 27.20 m²)

Consumption: 240 kWh/a of maximum 1000 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 71
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / Corridor / Room summary

Corridor

Clearance height: 3.000 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (Corridor) Perpendicular illuminance (adaptive) [lx] 147 75.1 196 0.51 0.38
Height: 0.100 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

5 Advanced Lighting Company - AL-DS59-6-18W-X-8-40 1904 17.7 107.6

Total via all luminaires 9520 88.5 107.6

Lighting power density: 3.25 W/m² = 2.21 W/m²/100 lx (Floor area of room 27.20 m²)

Consumption: 240 kWh/a of maximum 1000 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 72
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / Staircase / Room summary

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

5 Advanced Lighting Company - AL-CD38-25W-X-8-40 2745 25.4 108.1

Total via all luminaires 13725 127.0 108.1

Lighting power density: 9.28 W/m² (Floor area of room 13.68 m²)

Consumption: 350 kWh/a of maximum 500 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 73
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 2 / Second Floor / Staircase / Room summary

Staircase

Clearance height: 3.300 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

5 Advanced Lighting Company - AL-CD38-25W-X-8-40 2745 25.4 108.1

Total via all luminaires 13725 127.0 108.1

Lighting power density: 9.28 W/m² (Floor area of room 13.68 m²)

Consumption: 350 kWh/a of maximum 500 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 74
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 3 / SEC / SEC RM / Room summary

SEC RM

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (SEC RM) Perpendicular illuminance (adaptive) [lx] 304 211 361 0.69 0.58
Height: 0.100 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

2 Advanced Lighting Company - AL-IN01-12-40W-X-8-40 4292 41.4 103.7

Total via all luminaires 8584 82.8 103.7

Lighting power density: 9.67 W/m² = 3.19 W/m²/100 lx (Floor area of room 8.56 m²)

Consumption: 230 kWh/a of maximum 350 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.

Page 75
Al Ramaniah Commercial Building & Offices 2/28/2019

Site 1 / Building 3 / SEC / SEC RM / Room summary

SEC RM

Clearance height: 2.800 m, Reflection factors: Ceiling 70.0%, Walls 50.0%, Floor 20.0%, Light loss factor: 0.80

Workplane
Surface Result Average Min Max Min/average Min/max

1 Workplane (SEC RM) Perpendicular illuminance (adaptive) [lx] 260 175 308 0.67 0.57
Height: 0.100 m, Wall zone: 0.000 m

# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]

2 Advanced Lighting Company - AL-IN01-12-40W-X-8-40 4292 41.4 103.7

Total via all luminaires 8584 82.8 103.7

Lighting power density: 7.52 W/m² = 2.89 W/m²/100 lx (Floor area of room 11.01 m²)

Consumption: 230 kWh/a of maximum 400 kWh/a

The energy consumption quantities do not take into account light scenes and their dimming levels.