Element C Interiors

Interior Finishes
C3020 Floor Finishes

PART 1 - GENERAL
1.01 OVERVIEW

A. Includes carpet, terrazzo, stone, resilient flooring, quarry tile, ceramic tile, concrete, and,
hardeners and sealers.

PART 2 - DESIGN CRITERIA


2.01 GENERAL

A. The following table indicates finishes for various room types within Owner’s facilities.
Confirm finishes with Owner’s Project Manager/Planner Designers

Room Type Floor Finish


Conference Rooms, Corridors, Offices, Carpet tile. (Provide seamless sheet vinyl
Waiting Areas, Family Lounges, Break flooring adjacent to counters in Break Rooms)
Rooms
Dining Areas Confirm with Owner’s Project Manager/ Planner
Designer.
Public Lobbies Confirm with Owner’s Project Manager /Planner
Designer.
Toilet Rooms, Shower Rooms, Patient Porcelain ceramic tile with solid surface material
Toilets/Showers, Public/Staff Toilets door threshold. Refer to Typical Restroom Door
Threshold detail located on the Owner’s Design
Guidelines website. At patient toilets, provide a
seamless floor system in toilet rooms for
radioactive patients. Provide non-slip flooring at
patient shower areas. At Shower Rooms and
Patient Toilets/Showers, provide a waterproof
membrane under the floor finish in the entire
room.
Storage, Building Services, Security, Vinyl composition tile (VCT).
Mechanical/Electrical Equipment Sealed concrete. (Antistatic sealer at
Rooms, Shops, Telecommunications Telecommunications Rooms)
Rooms
Food Preparation Quarry tile.
Nurse Station Corridors, Public Seamless sheet vinyl flooring with heat welded
Corridors in Clinical Areas seams. Accent colors of same seamless sheet
vinyl used for wayfinding purposes. Confirm
with Owner’s Project Manager/ Planner
Designer.
Patient Rooms, Nurse Stations, Clean Seamless sheet vinyl flooring with heat welded
Workrooms/Clean Supply, Soiled seams. Confirm with Owner’s Project Manager/
Workrooms/Soiled Holding, Storage, Planner Designer

The University of Texas FLOOR FINISHES


MD Anderson Cancer Center C3020
ODG041712 1 OF 4
Element C Interiors
Interior Finishes
C3020 Floor Finishes

Room Type Floor Finish


Locker Rooms, Staff Corridors, Staff
Elevator Lobbies, Service Elevator
Lobby, Janitor Closets, Work Rooms,
Clinical Corridors, Isolation Rooms,
Procedure Rooms, Pharmacy, Clinical
Areas, Operating Rooms
Freight Elevator Lobby, Dock Receiving, Fluid-applied epoxy resin or sealed concrete.
Material Movement Corridor
Laboratories, Lab Support Areas, Tissue Seamless sheet vinyl flooring with heat welded
Culture Rooms, Dark Rooms, Flex seams
Rooms and Shared Equipment Areas
Research Laboratory Special Function Fluid applied epoxy resin
Rooms (Glasswash, Liquid Nitrogen
Storage Rooms)
Vivarium and Vivarium Support Fluid applied epoxy resin
Functions
Shell Space No finish
Selected Imaging Equipment Rooms Raised access flooring vinyl finish.

PART 3 - SPECIAL CONTRACT DOCUMENT REQUIREMENTS


3.01 GENERAL

A. In addition to incorporating all applicable life safety and building code requirements,
provisions described within this Element shall be included within the Project Contract
Documents.

B. Where terrazzo is the scheduled finish for an area occupying more than one structural bay, a
“sand cushion” terrazzo system with depressed floor slab shall be utilized. Depressed slab
and all membranes/materials beneath the terrazzo shall be fully detailed. Confirm use of
sand cushion system with Owner’s Project Manager.

C. Indicate that flooring materials shall be installed using adhesives/products which are
recommended for use by the manufacturer. Require that shop drawing submittals for flooring
material include information on the proposed installation product(s) and substantiate that they
are as recommended for use by the manufacturer. Indicate that in cases where products
differ from those recommended by the manufacturer, the installer/contractor shall bear sole
responsibility for any resulting deficiencies.

D. Require that flooring materials be installed as late in the construction schedule as practical,
and be protected from damage from construction operations and placement of equipment
and fixtures during the remainder of the construction period. Require use of protection
methods recommended in writing by manufacturer and installer that ensure the flooring
material is without damage or deterioration at time of Substantial Completion.

The University of Texas FLOOR FINISHES


MD Anderson Cancer Center C3020
ODG041712 2 OF 4
Element C Interiors
Interior Finishes
C3020 Floor Finishes

E. Indicate that immediately prior to Substantial Completion inspections, resilient flooring (sheet
vinyl and vinyl composition tile) is to have a floor finish applied and be buffed/burnished as
recommended by the manufacturer to a level acceptable to Owner.

F. Schedule walk off carpet in lieu of using recessed mats at building entrances. 

G. Select floor joint assemblies that are appropriate for expected traffic.

PART 4 - PRODUCTS
4.01 GENERAL

A. Obtain approval from Owner’s Project Manager/Planner Designer for all finish schedules prior
to issuance of Construction Documents.

B. For renovation projects, refer to Owner’s Master Construction Specifications and Interior
Finishes Standards. These are available on the Owner’s Design Guidelines website:
Construction Specifications - http://www2.mdanderson.org/depts/cpm/standards/specs.html
Interior Finish Standards - http://www2.mdanderson.org/depts/cpm/standards/interiors.html

PART 5 - DOCUMENT REVISION HISTORY

Issue Date Revision Description Reviser


01-01-07 Initial Adoption of Element
Rev. 1 08-14-08 Various revisions throughout document incorporating interior LN, JC, DB
standards and eliminating project specific requirements.
Rev. 2 07-08-10 Revised finish at Laboratories, and added more types of KB
spaces to the category; Added Research Laboratory Special
Function Rooms; Deleted Special Function Room.
Rev. 3 09-16-10 Added 3.01 B. JRC
Rev. 4 08-02-11 Deleted "Non-static" from the floor finish type for Storage, JRC
Building Services, Security and Telecommunications Rooms.
Paragraph 2.01 A.
Rev. 5 11-22-11 Added 3.01 C, D, and E related to installation product JRC
approval, protection during construction, and final finish
application prior to inspection. Changed finishes for telecom
and break rooms.
Rev. 6 04-17-12 Added Operating Rooms in table; Added 2.01 F and 2.01 G. JRC

The University of Texas FLOOR FINISHES


MD Anderson Cancer Center C3020
ODG041712 3 OF 4
Element C Interiors
Interior Finishes
C3020 Floor Finishes

END OF ELEMENT C3020