Instrument
Tr a n s f o r m e r s
page
Main characteristics 2
A certified quality system 3
Current transformers 4
Current transformers types 4
Specifications 6
Standardized current transformers 8
Order form 34
Voltage transformers 35
Voltage transformers types 35
Specifications 36
Standardized voltage transformers 38
Order form 53
c Their standard shape, top electric performance, c Extremely good ageing behaviour both to heat mass ageing according to IEC 216
reduced weight and overall dimensions make these (over 20 years at 120 °C) and to surface ageing obtained in salty mist
devices suitable for use in:
v metalclad units c In case of fire, no toxic substances are released in accordance with standards
v metal enclosed units IEC 20-37, IEC 20-22 and ASTM D 3286.
v large motor terminal strips
v environments with potentially explosive c Extremely effective behaviour in tropical climates.
atmosphere (Eex).
c High strength even at the highest working temperatures
(Martens point exceeding 105 °C).
F2 Forces applied
not simultaneously
up to 100°C
F1 F1 = 500 daN
F2 = 300 daN
Quality is obtained by planning and implementing Magrini Galileo, brand of Schneider Electric can prove its Guaranteed Quality via:
every phase, from the initial design all through c documentations explaining the company quality policy
production and testing to product delivery and c the planning of each individual product development phase
after-sales service. c continuous assessment of special indicators showing any possible quality faults
This means operating in full application of the Quality throughout the production process
Guarantee. By this procedure it is possible to supply a c a set of technical/quality papers providing evidence of what has been done all
product with all the design characteristics on the one through the production and testing process in order to guarantee the required
hand, and to show the Customer all that is planned quality level.
and implemented in order to come up with a good
product on the other hand. Production process applies standard Guarantee and Quality Control methods.
Quality Control Plans ensure that established procedures are applied to product
checking from construction material reception all the way to product delivery.
The earliest phases of product design and industrialization are also set up and
verified according to Guaranteed Quality principles.
CSQ is an independent
organisation for the
certification of company
management system,
member of the CISQ
(Italian Certifiers of
Company Quality Systems),
it’s active within the scope
of IMQ with the support of
CESI, these being
internationally
acknowledged boards in the
electrical engineering
industry.
Post type
type reference short-circuit max possible refer notes
voltage thermal current primary number to
(kV) in multiple of rated of CT page
Ipn x 1 s current cores (n°)
(max 60 kA x 1s) (A) (no.)
ARM1 7.2 - 12 100÷400 SR 800 1-2 8
ARM1 ARM2 ARQ1 17.5 - 24 DR 800-400 compact
ARM2 7.2 - 12 100÷630 SR 800 1-2-3 9 size
ARQ2 17.5 - 24 DR 800-400
ARM6 ARM7
Note
(1) SR = single ratio - DR = double ratio,
(2) All the apparatus have a 120% extended range, which means that the transformers can
be overloaded 20%beyond their rated current without exceeding the class.
ARM9
Support type
type reference short-time max possible reter notes
voltage thermal current primary number to
(kV) (A) rated current of CT page
cores (n°)
ARO1a 7.2-12 max 60 kA x Ipn SR 5000 1-2-3 24 without
primary for
ARO1b 17.5 DR 5000-2500 mounting
ARO2 24-36 max 60 kA x 1s SR 4000 1-2-3 25 directly on
ARO1 ARO2 busbar
DR 4000-2000
Warning:
This equation is only guaranteed during CT selection phase.
266 160
Dimensions (mm)
8
8
Type A B C
ARM1 250 290 310
Ø 14
50
P1
P2
220
P1
VA = nominal output
Isn = secondary rated current
Ze = measuring instrument impedance (ohm)
Table reading:
1) Define multiple: Iter x 1s
Ipn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Iter indicate a point within the blue area.
If such point should fall within the white area, a larger CT type
should be used: ARM2, ARM3, ARM4,ARM8
Dimensions (mm)
Type ARQ1/N1-N2 Type ARM1/N1-N2
Weight 13.5 kg Weight 14 kg
110 43 M 12
287
282
279
75
274
248
243
240
235
P2
5
130
158
110
85
20
P1
65
115
115 97 200
N°4 holes
158 225 Ø 11
M6 screw type 212 M6 screw type
secondary and earthing terminals
secondary and earthing terminals
Table reading:
1) Define multiple: Iter x 1s
Ipn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Iter indicate a point within the blue area.
If such point should fall within the white area, a larger CT type
should be used: ARM3, ARM4, ARM8
If such point should fall within the grey area, choose a smaller CT type:
ARM1.
Dimensions (mm)
Type ARQ2/N1-N2-N3 Type ARM2/N1-N2-N3
Weight kg 19 Weight kg 19.5
N°4 fixing holes
M 8 x 12 50
50 110 86
43 M 12
82
287
279
248
240
20
110
P2
130
158
282
274
85
5
243
235
90
P1
145
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARM1 - ARM2.
If such point should fall within the white area, a larger CT type
should be used: ARM4 - ARM8.
110
P1
175
200
52
82
P2
338
330
333
325
300
292
295
110
287
23
120
90
225
5
N°4 holes
Ø 11
260
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area..
If such point should fall within the grey area, choose a smaller CT type:
ARM1 - ARM2 - ARM3.
If such point should fall within the white area, a larger CT type
should be used: ARM8.
110
175
200
52
82
338
333
330
325
300
295
292
287
110
23
225
90
N°4 holes
5
148
Ø 11
260
1000
1200
1250
800-400
1000-500
1200-600
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARJP3/N1-N2-N3
Weight kg 22
72 M 12 x 23
P2
20
120
148
P1
5
270
240
120
185 137 184
175 100 N°4 slot
Ø 11
322 295
M6 screw type
secondary and earthing terminals
1000
1200
1250
1600
800-400
1000-500
1200-600
1500-750
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARJM3/N1-N2-N3
Weight kg 25
M 12 x 23
260
20
178
P2
120
148
P1
185 137
120
322
M6 screw type 184 N°4 slot
secondary and earthing terminals Ø 11
175 100
295
1200
1250
1500
1600
1800
2000
2500
1000-500
1500-750
2000-1000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARJP3.
Dimensions (mm)
type ARJA1/N1-N2-N3
Weight kg 30
175
200
P1
40
45
160 148
58
70
M6 screw type
secondary and earthing terminals 120
308
60
184 60
N°4 holes 70
225 Ø 11
260
Table reading:
1) Define multiple: Iter x 1s
Ipn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Iter indicate a point within the blue area.
Dimensions (mm)
TypeAD12/N1-N2-N3
Weight kg 20
12.5
11
C1
P1
C1
P1
223
C2
P2
C2
P2
P1
P2
125
100
148
DIN 1030
M8 c c
Pg 16
18.5
254
184
20
177 150
270
350
1000
1200
1250
800-400
1000-500
1200-600
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type AD13/N1-N2-N3
Weight kg 20
M12 x 23
DIN 40430
M8
Pg 16
223
125
148
100
31
M5 screw type
secondary and earthing terminals
177 150
20
350
184
270
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the white area, a larger CT type should be
used: AD22.
Dimensions (mm)
type AD21/N1-N2
Weight kg 23
P1
P1
11
280
P2
P2
C2
C2
M8
178
DIN 40430
150
100
Pg 16 18.5
319
184
163 160
20
280
370
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
AD21.
Dimensions (mm)
type AD22/N1-N2-N3
Weight kg 28
1 x Ipn 2 x Ipn
280
150
178
100
DIN 40430 M8
Pg 16
311
184
178 160
20
280
370
1000
1200
1250
1500
1600
2000
2500
DR
800-400
1000-500
1200-600
1500-750
1600-800
2000-1000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type AD23/N1-N2-N3
Weight kg 30
178
100
40
31
45
58
70
M5 screw type
178 160 120 secondary and earthing terminals
20
60
370 184 N˚4 holes Ø 14 60
70
280
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the white area, a larger CT type
should be used: ARM7 - ARM8.
Dimensions (mm)
type ARM6/N1-N2
Weight kg 22
86 50 43 M 12
P1
175
200
52
P2
408
400
370
362
225
N°4 holes
23
Ø 11
260
5
122 102
M6 screw type
secondary and earthing terminals
224
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARM6
If such point should fall within the white area, a larger CT type
should be used: ARM8.
Dimensions (mm)
type ARM7/N1-N2-N3
Weight kg 30
86 50 43 M 12
P1
175
200
52
P2
408
400
370
362
260
157 150
M6 screw type
secondary and earthing terminals
307
Table reading:
1) Define multiple: Iter x 1s
lpn
2) Fix line according to Ipn primary current and its multiple.
3) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
If such point should fall within the grey area, choose a smaller CT type:
ARM1 - ARM2 - ARM3 - ARM4 for Um ≤ 24 kV;
ARM6 - ARM7 for Um = 36 kV.
Dimensions (mm)
type ARM8/N1-N2-N3
Weight kg 45
86 50 43 M 12
P1
175
200
249
52
P2
408
400
370
362
23
Ø 11
260
152 150
M6 screw type
secondary and earthing terminals
302
1200
1250
1500
1600
1800
2000
2500
1000-500
1500-750
2000-1000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARM9/N1-N2-N3
Weight kg 35
Ipn Ipn
800 ÷ 1600 A 1800 ÷ 2500 A
200
P2
175
362
P1
40
45
23
70
120
5
184
70
225 N°4 holes
157 150 M6 screw type 260 Ø 11 70
secondary and earthing terminals
307
1200
1500
2000
3000
4000
5000
2000-1000
3000-1500
4000-2000
5000-2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARO1a/N1-N2-N3 and ARO1b/N1-N2-N3
Weight kg 27
L
Ø
175
200
P1 P2
369
230
23
225
5
N°4 holes
Ø 11
260
c type ARO1a/N1-N2-N3
M6 screw type secondary
L = 238 mm Ø = 110 mm and earthing terminals
c type ARO1b/N1-N2-N3
Connection between primary
L = 248 mm Ø = 130 mm and shielding (lenght 300 mm)
1200
1500
2000
3000
4000
2000-1000
3000-1500
4000-2000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
Dimensions (mm)
type ARO2/N1-N2-N3 248
Weight kg 32
110
175
200
P1 P2
420
280
Ø 11
5
260
400 400-800
600 600-1200
800 800-1600
1000 1000-2000
1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15
3) In case of double (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF1/N1-N2
Weight kg 8
85
25
100
M6 secondary
terminals
140
170
198
7
P1
170
N°4 slot
198 Ø 9 x 11
130
229
400 400-800
600 600-1200
800 800-1600
1000 1000-2000
1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15
If such point should fall within the grey area, choose a smaller CT type:
ARF1.
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF2/N1-N2-N3
Weight kg 12
85
25
150
M6 secondary
140
170
198
7
terminals
P1
130
229
100 200-100 * **
150 300-150 * ** *
200 400-200 ** **** **
300 600-300
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1200
1500
2000
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF3/N1
Weight kg 7
105
30
100
M6 secondary
terminals
198
83
113
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1250 2500-1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF4/N1-N2
Weight kg 14
105
25
100
M6 secondary
terminals
140
200
238
7
P1
200
238 N°4 slot
Ø 9 x 11
152
271
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1250 2500-1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF5/N1-N2
Weight kg 12
125
25
100
M6 secondary
terminals
140
200
238
7
P1
200
238 N°4 slot
Ø 9 x 11
152
271
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1250 2500-1250
1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARF6/N1-N2
Weight kg 10
150
25
100
M6 secondary
terminals
140
200
238
7
P1
200
238 N°4 slot
Ø 9 x 11
152
271
Schneider Instrument Transformers
Electric Merlin Gerin 31
Toroidal type Current transformers
AOP-C/N1 - AOP-C/N2
400 800-400
600 1200-600
800 1600-800
1000 2000-1000
1250 2500-1250
1500 3000-1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
* cl. 1 Fs≤15 ** cl. 0.5 Fs≤15 *** cl. 10P
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type AOP-C/N1-N2
Weight kg 15
200
25
100
M6 secondary
terminals
373
7
P1
140
290
330
225
N°4 slot
264 Ø 9 x 11
208
800 1600-800
1000 2000-1000
1250 2500-1250
1500 3000-1500
2000
2500
Table reading:
1) Fix line according to Ipn primary current.
2) A CT is feasible if the coordinates corresponding to the required
performance and Ipn indicate a point within the blue area.
3) In case of double ratio (DR) CT, rated outputs are guaranteed on low ratio and are
doubled on high ratio.
Dimensions (mm)
type ARL4/N1-N2
Weight kg 30
25
100
220
90
M6 secondary
terminals
400
557
Part 1
Type: _________________________________________________________________________________________________________
Number of secondaries: 1¨ 2¨ 3¨
2nd secondary Output: ________________ Class: ___________ Security factor/Accuracy limit factor ______________________
3rd secondary Output: ________________ Class: ___________ Security factor/Accuracy limit factor ______________________
Capacitive tap: ¨
Frequency: 60 Hz ¨ Others ¨
Others:
Note
Apparatus with the following features are defined as standard:
n electrical features, max. reference voltage, rated current, output and class strictly as indicated in the table of option from page 8 to 33
n primary contacts and terminals, if requested, are tin plated
n pickled copper secondary terminals
n fixtures, if any, are zinc-plated steel.
VRCR VRC3
produce resonance.
in the immediate vicinity of the VT. We suggest to use 10A/500V fuses for "earth
70 pole" devices and 6A/500V fuses for "insulated poles" devices.
Fairleadbush Ø 12
Fixing slots 20 x 8
20
120
354
Rated performance calculation one secondary (instrument or protection) double primary ratio (with tap at secondary)
a1 - b small ratio; a2 - b high ratio
table
Power absorbed by measuring instruments and Maximum Single (grounded) pole Two (insulated) poles
protection relays reference
(alternating current 50 to 60 Hz) voltage for
Type of instrument or relay insulation
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRFRn/S1-S2
VRFR/S1-S2
Weight kg 15
M 10
125
148
A
221
30
270
5
N°4 holes
M6 screw type secondary Ø 11
and earthing terminals 300
140 117
257
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRF1n/S1-S2
VRF1/S1-S2-S3
Weight kg 21
M 10 170
155
180
240
30
155
5
N°4 holes
Ø 11
225
177 155
M6 screw type secondary
and earthing terminals
332
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRF2n/S1-S2
VRF2/S1-S2
Weight kg 29
M 10 186
175
200
A A
300
30
Ø 11
260
177 155
M6 screw type secondary
332 and earthing terminals
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRQ1n/S1-S2-S3
VRQ1n/S1-S2-S3
Weight kg 30
M 10 158 N°4 holes M 6 x 8
144
82
275
25
180
187 170
M6 screw type secondary
357 and earthing terminals
VRQ2n
VRQ2
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary and
separate operation for 3rd secondary.
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRQ2n/S1-S2-S3
VRQ2/S1-S2-S3
Weight kg 19
M 10 170 N°4 holes
M6x8
A
265
135
82
25
115
160 138
M6 screw type secondary
298 and earthing terminals
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary
and separate operation for 3rd secondary.
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRF3n/S1-S2-S3
VRF3/S1-S2-S3
VRF/S1-S2-S3
Weight kg 45
M 10 230
225
255
A
390
300
30
N°4 holes
Ø 11
5
325
192 170
M6 screw type secondary
362 and earthing terminals
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRF3Zn/S1-S2-S3
VRF3Z/S1-S2-S3
Weight kg 65
M 10
230
225
255
A
390
300
30
N°4 holes
Ø 11
5
325
197 175
M6 screw type secondary
372 and earthing terminals
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VDF11/S1-S2
VDF11n/S1-S2
Weight kg 15
M 10
100
125
148
DIN 40430
Pg 16 M8
221
168 150
20
VRQ2n
VRQ2
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
(2) Output with separate operation means that precision class of the 2nd secondary is
guaranted with 1st secondary under load. In this case, class 3P remains guaranteed with a
simultaneous operation.
(3) In case of three secondaries it is simultaneous operation between 1st and 2nd secondary
and separate operation for 3rd secondary.
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VDF21/S1-S2-S3
VDF21n/S1-S2-S3
Weight kg 21
M 10
DIN 40430
M8
A
Pg 16
100
150
178
280
280
n° 4 holes ø14
370
20
31
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRCR/S1-S2
Weight kg 15
100 110 A
125
148
M 10
B
270
221
N°4 holes
30
Ø 11
5
300
257
(1) Output with simultaneous operation means that accuracy class of the 1st secondary is
guaranteed with the 2nd secondary under load and vice versa
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRC1/S1-S2
Weight Kg 23
M 10 195
150
155
180
30
A B
Ø 11
225
161 139
300
M6 screw type secondary
and earthing terminals
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRC2/S1-S2
Weight Kg 28
M 10 270
210
175
200
30
A B
5
300
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VRC3/S1-S2
Weight Kg 45
M 10 380
320
225
255
390
30
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VDC11/S1-S2
Weight Kg 15
100 110
M 10
DIN 40430
Pg 16 M8
100
125
148
221
31
Table reading:
1) VT is feasible if the coordinates corresponding to the selected line and
required output indicate a point within the blue area.
Dimensions (mm)
type VDC21/S1-S2
Weight Kg 21
165 130
M 10
DIN 40430
Pg 16 M8
100
150
178
280
Part 1
Type: _________________________________________________________________________________________________________
Number of secondaries: 1¨ 2¨ 3¨
Frequency: 60 Hz ¨ Others ¨
Others:________________________________________________________________________________________________
Note
Apparatus with the following features are defined as standard:
n electrical features, max. reference voltage, rated voltages, output and classes strictly as indicated in the table of options from page 38
to page 52
n pickled copper primary holds and secondary terminals
n fixtures, if any, are zinc-plated steel.
04/2000