PDVSA

ENGINEERING DESIGN MANUAL


VOLUME 18–STD

ENGINEERING SPECIFICATION

PDVSA N° TITLE

0602.1.045 ACID PROOF BRICK LINED TRENCH


DETAILS

1 JUN.90 GENERAL REVISION 2 L.T. R.P. R.R.

0 DEC.85 FOR APPROVAL 2 J.S. J.G. E.S.

REV. DATE DESCRIPTION PAG. REV. APPD. APPD.

APPD.BY José Gilarranz DATE DEC.85 APPD.BY Eduardo Santamaria DATE DEC.85

E1994 ESPECIALISTAS
ENGINEERING SPECIFICATION PDVSA 0602.1.045

PDVSA
REVISION FECHA
ACID PROOF BRICK LINED TRENCH DETAILS
1 JUN.90
Página 1
.Menú Principal Indice manual Indice volumen Indice norma

ACID PROOF (AP) BRICK LINED TRENCHES


GRATING COVERS

COVER

AP BRICK FULL BRICK


INVT OF TRENCH COURSE
SEE PLAN FOR EL

1 BRICK + 1 JT ACID PROOF MORTAR FILL

LONGITUDINAL SECTION

ACID PROOF AP FLOOR


GRATING SEE PLAN
DEPTH OF TRENCH

DEPTH OF TRENCH
SEE PLAN

SEE PLAN

WIDTH OF TRNCH
WIDTH OF TRNCH CHEMICAL RESISTANT CHEMICAL RESISTANT
MEMBRANE SEE PLAN MEMBRANE
SEE PLAN

SECTION A–A SECTION A–A


AP BRICK CURB & CONC FLOOR AP BRICK CRB & AP FLOOR

NOTES:
1. PROTECTION OF CONCRETE, TYPE OF BRICK, MORTAR, GRATING AND
MEMBRANE, SHALL BE SPECIFIED IN PURCHASE ORDER DOCUMENT AND/OR
SUPPLEMENTED BY A SPECIFICATION IF REQUIRED.
2. FOR TRENCH LAYOUT, DIMENSIONS AND REINFORCING, SEE DESIGN DRAWINGS.
3. FOR MATERIAL SELECTION, REFER TO MANUFACTURER.
4. ALL DIMENSION ARE IN mm UNLESS OTHERWISE NOTED.
ENGINEERING SPECIFICATION PDVSA 0602.1.045

PDVSA
REVISION FECHA
ACID PROOF BRICK LINED TRENCH DETAILS
1 JUN.90
Página 2
.Menú Principal Indice manual Indice volumen Indice norma

ACID PROOF (AP) BRICK LINED TRENCHES


CHECKERED PLATE OR PRECAST CONCRETE COVER

CURB ANGLE

INVT OF TRENCH SEE AP BRICK FULL BRICK COUR-


PLAN FOR EL SES

1 BRICK + 1 JT ACID PROOF MORTAR FILL

LONGITUDINAL SECTION

CHKD PLATE W/HOLES 300 OC EACH


WAY IF REQ D FOR FLOOR DRAINAGE

SEE DET 1 STD 2.041 SEE DET 1 STD 2.041


DEPTH OF TRENCH

DEPTH OF TRENCH
SEE PLANT

SEE PLANT

WIDTH OF TRENCH WIDTH OF TRENCH


CHEMICAL RESISTANT CHEMICAL RESISTANT
SEE PLAN MEMBRANE SEE PLAN MEMBRANE

SECTION A–A SECTION A–A


PRECAST CONCRETE COVER
CHECKERED PLATE COVER

NOTES:
1. PROTECTION OF CONCRETE, TYPE OF BRICK, MORTAR, GRATING AND
MEMBRANE, SHALL BE SPECIFIED IN PURCHASE ORDER DOCUMENT AND/OR
SUPPLEMENTED BY A SPECIFICATION IF REQUIRED.
2. FOR TRENCH LAYOUT, DIMENSIONS AND REINFORCING, SEE DESIGN DRAWINGS.
3. FOR MATERIAL SELECTION, REFER TO MANUFACTURER.
4. ALL DIMENSION ARE IN mm UNLESS OTHERWISE NOTED.