Sie sind auf Seite 1von 2

H05VV-F

JUS mark: PP/J

01
standards: HRN HD 21.5 S3
IEC 60227-5 (mark 227 IEC 53)
DIN VDE 0281 part 5 PVC insulated and sheathed fine wired cable

H - harmonized cable (conforming with European standards)

cables and conductors


PVC-insulated installation
05 - U0 /U = 300/500 V
V - PVC insulation
V - PVC sheath
F - fine wired flexible conductor

ø
Technical data Construction
Temperature range: 1. Conductor: bare copper conductor, fine wired stranded,
• during installation and application with class 5 acc. to IEC 60228 / HD 383 / DIN VDE 0295
bending: +5 °C up to +70 °C 2. Insulation: PVC compound TI2 acc. to DIN VDE 0207 part
• fixed installed: -30 °C up to +70 °C 4/ HD 21.1 S4
• at short circuit of max. 5 s: up to 150 °C • concentrically stranded cores colour marked acc. to HRN
HD 308 S2 / DIN VDE 0293-308
• ambient temperature at storage: up to 40 °C (under direct
sun exposure conductor surface up to 60 °C) • with or without green - yellow protective conductor
Nominal voltage: U0 /U = 300/500 V 3. Sheath: PVC compound TM2 for flexible cables acc. to
DIN VDE 0207 part 5 / HD 21.1 S4
Test voltage: 2000 V
• sheath colours: white or black
Minimal inner bending radius: (D = external cable
diameter)
Core colour marking: acc. to HRN HD 308 S2 / VDE 0293-308
• 4D for D < 8 mm
Number With protective conductor Without protective
• 5D for 8 mm < D < 12 mm of cores conductor
• 6D for D > 12 mm 2 - bu ●, bn ●
3 gn/ye , bu ●, bn ● -
Behaviour in fire: Flame retardant (self-extinguishing) 4 gn/ye , bn ●, bk ●, gy ● -
cable acc. to IEC 60332-1 / EN 60332-1 (earlier EN 50265-2- 5 gn/ye , bu ●, bn ●, bk ●, gy ● -
1) / VDE 0482-332-1 (earlier VDE 0482-265-2-1, also DIN VDE >5 gn/ye , black cores with white -
0472 part 804 test method B) numbering

Application
Flexible cable for medium mechanical stresses. Permitted frequent bending and twisting.
Specially suitable for application in household, kitchens and offices in dry and damp conditions, for inst. washing-machines, dryers,
refrigerators etc., as long as the cable is adapted to essential specifications of the device. Also suitable for cookers, i.e. hot devices, on
condition that it does not get in direct contact with hot parts of the device and is not exposed to heat irradiation. Suitable for fixed
installation in furniture, partition walls, decorative linings and cavities in prefabricated construction elements.
Not suitable for permanent outdoor use (only temporary) or application for industrial or agricultural machines (except for sewing-
machines and similar).

31

TKgroup_01.indd 31 1/5/11 2:59 PM


H05VV-F
01 PVC insulated and sheathed fine wired cable
PVC-insulated installation

Dimensions - Construction of indi- External Insulation Sheath thick- Conductor resis- Specific. el. resis- Cu weight Cable weight Packing**
cables and conductors

number vidual conductor (No. of diameter thickness ness tance at 20 °C tance of insulation
of cores x wires x diameter) at 70°C
conductor
cross-section
nominal min-max. nominal nominal max. min. approx .
mm2 n x mm mm mm mm Ω/km MΩkm kg/km kg/km
2 x 0,75 24 x 0,20 5,7 - 7,2 0,6 0,8 26,0 0,011 14,4 52 c.100
2x1 32 x 0,20 5,9 - 7,5 0,6 0,8 19,5 0,010 19,2 65 c.100
2 x 1,5 30 x 0,25 6,8 - 8,6 0,7 0,8 13,3 0,010 28,8 90 c.100
2 x 2,5 50 x 0,25 8,4 - 10,6 0,8 1,0 7,98 0,0095 48,0 115 c.100

3 G 0,75 24 x 0,20 6,0 - 7,6 0,6 0,8 26,0 0,011 21,6 70 c.100
3G1 32 x 0,20 6,3 - 8,0 0,6 0,8 19,5 0,010 28,8 80 c.100
3 G 1,5 30 x 0,25 7,4 - 9,4 0,7 0,9 13,3 0,010 43,2 115 c.100
3 G 2,5 50 x 0,25 9,2 - 11,4 0,8 1,1 7,98 0,0095 72,0 175 c.100
3G4 56 x 0,30 10,5 - 13,1 0,8 1,2 4,95 0,0078 115,2 235 CUT

4 G 0,75 24 x 0,20 6,6 - 8,3 0,6 0,8 26,0 0,011 28,8 75 c.100
4G1 32 x 0,20 7,1 - 9,0 0,6 0,9 19,5 0,010 38,4 92 c.100
4 G 1,5 30 x 0,25 8,4 - 10,5 0,7 1,0 13,3 0,010 57,6 145 c.100
4 G 2,5 50 x 0,25 10,1 - 12,5 0,8 1,1 7,98 0,0095 96,0 210 c.100
4G4 56 x 0,30 11,5 - 14,3 0,8 1,2 4,95 0,0078 153,6 299 CUT
4G6 84 x 0,30 14,7 3,30 0,0068 230,4 480 CUT

5 G 0,75 24 x 0,20 7,4 - 9,3 0,6 0,9 26,0 0,011 36,0 96 c.100
5G1 32 x 0,20 7,8 - 9,8 0,6 0,9 19,5 0,010 48,0 113 c.100
5 G 1,5 30 x 0,25 9,3 - 11,6 0,7 1,1 13,3 0,010 72,0 175 c.100
5 G 2,5 50 x 0,25 11,2 - 13,9 0,8 1,2 7,98 0,0095 120,0 260 c.100
5G4 56 x 0,30 13,0 - 16,1 0,8 1,4 4,95 0,0078 192,0 363 CUT
5G6 84 x 0,30 16,7 3,30 0,0068 288,0 583 CUT

7G1 32 x 0,20 9,0 0,6 19,5 0,010 67,2 136 c.100


7 G 1,5 30 x 0,25 10,6 0,7 13,3 0,010 100,8 195 c.100
7 G 2,5 50 x 0,25 13,0 0,8 7,98 0,0095 168,0 294 c.100

*) G = with green - yellow protective conductor, x = without green - yellow protective conductor
**) Packing: c. 100 = coin 100 m, CUT= cable in different lengths on drum or reel, possible cutting at required lengthm

32

TKgroup_01.indd 32 1/5/11 2:59 PM