One and Half Breaker Bus System

In Switchyard different Bus Bar arrangements are used for evacuation of power
generated but the two most used schemes are One and Half Breaker Bus System and
Double Bus Bar arrangement. In high voltage Switchyard like in 400 kV Switchyard,
One and Half Breaker Bus System is used due to many advantages of this scheme. The
advantages of this scheme will be dealt latter in this post. D:\Karthik\Study
material\Primary\Bus configuration

Bus Bar arrangement is nothing but a combination of Bus and Circuit Breaker. Normally
in Switchyard, Bus are made of hollow tubular aluminum called IPS Tubes (here IPS
stands for Iron Pipe Size, a code for selection of tubes). Corona and electrostatic field
performance is better for tube bus, therefore Aluminum Tubes are used for Buses.

Now coming to One and Half Breaker Bus System, carefully observe the figure below.

In the figure above, CB stands for Circuit Breaker, LA for Lightening Arrestor, ES for
Earth Switch and DS for Disconnect Switch also called Isolator.

In One and Half Breaker Scheme, three breakers are connected between the two
buses. Each Breaker is provided with two Isolators and two Earth Switches. These

Unrestricted
Isolators are provided to physically isolate the Circuit Breaker for maintenance. Earth
Switch ES is provided to ensure that isolated portion is effectively earthed. Earth Switch
shall be closed after the opening of Isolator.

One bay of three breakers is called Diagonal in One and Half Breaker Scheme. In the
figure, thus two Diagonals are shown. A feeder is connected in between the two
Breakers CB-A and CB-C & CB-B and CB-C. Notice that three Breakers are used in this
scheme to protect two Feeders and therefore it is called 3/2 i.e. One and Half Breaker
scheme.

Let us consider some interesting aspects of One and Half Breaker Scheme. Let us
assume a fault in any one feeder say in Feeder-1. In this case protection shall open the
CB-A and CB-C & send Direct Trip signal to the Remote station through PLCC to isolate
the fault. Mind that even though CB-A and CB-C are open, Feeder-2 is still in service
and fed by Bus-2. Thus One and Half Breaker scheme increases the reliability of Power
System.

Let us assume that, we need to take maintenance of CB-B of Diagonal-1. So we will


open the Breaker CB-B and will isolate it by opening Isolators and closing Earth Switch
ES. Again, notice that none of the feeder will be out of service rather Feeder-2 will be
fed through CB-A and CB-C. The most important advantage of this scheme is that you
can take one Bus out for maintenance without interrupting power supply in Feeders.

Advantages of One and Half Breaker Scheme are as follows.

1) Its high security against loss of power supply to feeders which makes it particularly
suitable for Switchyard associated with generating Stations and those in which large
quantum of power is handled through individual circuits. This involves minimum outage
for maintenance.

2) Area requirement is less in this arrangement compared to Two Main and Transfer
Scheme.

3) Cost is also less compared to Two Main and Transfer Bus Scheme.

4) Either bus may be taken out any time without loss of service to the feeders.
Maintenance of more than one breaker is possible without any loss of service. In this
system no isolator operation is required for changing over from one bus to other, as all
three breakers remain closed under normal operation.

5) In case of bus fault, power supply to the connected feeders continues from the other
bus with no power interruption required for isolation of the faulty bus. This advantage is
not available with Two Main and Transfer Bus Scheme as in case of a bus fault all
associated breakers will trip resulting in interruption of power supply to affected feeders.

Unrestricted
However, failure of center breaker only reduces the flexibility of uninterrupted
changeover of feeders from one bus to the other.