HEATING, VENTILATION &


AIR-CONDITIONING
Facility Management


VARINDER TAPRIAL, PRIYA KANWAR

HEATING, VENTILATION
& AIR-CONDITIONING
FACILITY MANAGEMENT

2
Heating, Ventilation & Air-Conditioning: Facility Management
1st edition
© 2018 Varinder Taprial, Priya Kanwar & bookboon.com
ISBN 978-87-403-2537-9

3
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Contents

CONTENTS
About the Authors 6

1 Introduction 8

2 Fundamentals of HVAC Systems 10


2.1 Sources of Heat Gain 10
2.2 Sources of Humidity 11
2.3 Sources of Impurities 11
2.4 The Concept of Heat Exchange 12
2.5 Types of HVAC Systems 13

3 Heating Systems 16
3.1 Furnace Based Heating Systems 16
3.2 Boiler Based Heating Systems 20
3.3 Heat Pump 24

Free eBook on
Learning & Development
By the Chief Learning Officer of McKinsey

Download Now

4
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Contents

4 Ventilation Systems 29
4.1 Air Handling Unit (AHU) 29
4.2 Fan Coil Units (FCU) 33
4.3 Variable Air Volume (VAV) Systems 35
4.4 Chilled Beams 36
4.5 Ventilation Scrubbers 38
4.6 Exhaust Fans 38
4.7 Jet Fans 39
4.8 Maintenance of Ventilation Systems 40

5 Air-Conditioning Systems 41
5.1 Types of Cooling 41
5.2 Operating Principle of AC Systems 43
5.3 Components of Air-Conditioning System 46
5.4 Types of Air-Conditioning Units 49

6 Chillers 55
6.1 Chiller 56
6.2 Chilled Water Systems (CWS) 58
6.3 Cooling Towers 60
6.4 Maintenance of Chillers 62

7 Conclusion 63

8 Common Terminology 65

5
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT About the Authors

ABOUT THE AUTHORS


Varinder Taprial is an Electrical Engineer, graduated from the Naval College of Engineering.
He served in the Indian Navy for 22 years wherein he gained vast experience in operations
and maintenance management including related functions like procurement, finance,
budgeting etc. it was during this time that he started dabbling in writing and ran his own
blog covering a variety of topics. The writing bug had bitten him and in 2009 towards the
end of his time with the Navy, he published a fiction book, “Enemy in the Ranks.” He
then went on to share his knowledge and understanding of the Internet by publishing a
book on Search Engine Optimization and another one on blogging.

After seeking voluntary discharge from the Navy, Varinder spent the next couple of years
working first with a construction company and then a wind energy company. During this
time, the opportunity for writing for Bookboon came knocking and the result was three
books published in the period 2011-12, all related to Internet and Social Media.

Varinder then joined the Facilities Management vertical with an MNC which is one of
the largest IPCs in the world. This seemed like a natural progression for him since just like
a ship which is self-sustaining a building or a campus also needs to have the capability of
sustaining by itself and provide a healthy, safe and secure environment to the occupants.
During his association with the Facilities Management function, having handled large
accounts and being the Engineering head for India, Varinder has picked up tremendous
experience and developed expertise in all aspects of the function.

Priya Kanwar graduated as a dentist from Goa University in 1991, and then worked as a
Research Fellow for 2 years at the Post Graduate Institute of Medical Education & Research
(PGIMER), Chandigarh; followed by 6 months as a Junior Resident.

After her marriage to Varinder, who was in a transferrable job, she could not pursue her
dentistry full time but kept herself occupied with jobs like a teacher in a primary school, as
a sales executive for Citi bank Credit Cards, and also in a Family Clinic in different places
across the country, gaining varied experience in multiple fields. During this time, she also
pursued a writing course through Writing Bureau, London. From then on, her life turned
to the path of a writing career.

By 2006, Google had already established itself as the best search engine and the early social
media sites were evolving. Taking advantage of the opportunity, Priya started contributing
content to the various user generated content sites as well as started her own blog, Reading
Café. By signing up with the Google Adsense program, she started generating revenue from
her contributions.

6
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT About the Authors

Having gained tremendous experience on the various platforms in the five active years of
contributing content to various platforms online, she then decided to move on to sharing
her knowledge and co-authored two books, namely “Beginner’s Guide to Blogging &
Making Money Online” & “Search Engine Optimization – Handbook of Easy Tips
Tools & Techniques” in the print format published by Pustak Mahal.

Subsequently, she co-authored three more e-books, published by Bookboon in 2012, with
her husband Varinder Taprial, namely:

1. Google Beyond Google


2. Business Blogs – The Best Social Media Tool for Businesses (Now 2nd Edition)
3. Understanding Social Media (Now 2nd Edition)

Soon after the book on social media was published by Bookboon, they received an invitation
from the Information & Broadcasting Ministry of India to contribute an article on Social
Media for their quarterly magazine “Yojana.” Her article “Social Media - a Double-edged
Sword” was selected & published in the May 2013 edition.

Over the last year and few months, she was involved in the creation of an e-learning course
in Facilities Management and created/finalized the content required for the same.

Do check out our latest e-book published on this topic by Bookboon:

1. Technical Services in Facility Management

Join us - Facebook Author Page

Write to us – Varinder@taprial.in

7
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Introduction

1 INTRODUCTION
In our earlier book, “Technical Services in Facility Management” we covered the various
aspects of management of Technical Services in facilities including the typical equipment
fit and we explained that there is a plethora of civil, electrical and mechanical elements
which need to be operated and maintained for the facility to serve its intended function.
In this book, we will cover one of the most critical equipment in a facility i.e. Heating,
Ventilation and Air-Conditioning (HVAC).

Heating, Ventilation and Air-Conditioning or HVAC is a set of equipment designed to


control and provide a consistent, conditioned indoor ambient environment viz temperature,
humidity and air quality, in a facility to ensure comfort of the occupants as also for optimal
performance of some equipment which may be sensitive to temperature.

The quest for controlling the immediate environment for specific purposes including human
comfort, which required certain conditions of temperature, humidity and contents of air,
led to the birth of modern day air-conditioning as we know it.

Varied temperatures due to geographical locations and during different seasons has been
a challenge that mankind has been living with. The impact of extreme temperatures on
human bodies is well known; frost bites, sun-strokes, dehydration, hypothermia, etc. are
conditions we have all heard of and we also know that certain environmental conditions
promote proliferation of disease causing pathogens (bacteria, fungi, mold/mildew, virus
etc.). Hence, the correlation between the survivability of the human body to the temperature
is well established. It stands to reason therefore that there are certain conditions which are
predicated for higher efficiencies, aka productivity, of the human body.

At the very essence of it, an HVAC system will comprise of a means to cool/heat a medium,
allow for heat transfer to take place between the medium and air to be conditioned, and
then throw the conditioned air into the target space. It is obvious that for the environment
to be controlled and for the HVAC system to perform optimally, the conditioned air
cannot be allowed to indiscriminately mix with the outside air and hence the space being
conditioned will need to be enclosed. However, when we do that the indoor air will soon
become cooler/warmer, contaminated and stale because of the following:

1. CO2 being released by the occupants and the odor caused by various activities
inside the space.
2. Heat generated by occupants and other equipment like lighting, computers etc.
3. Heating/cooling of building envelope by the heat/cold outside.
4. Occupants bringing in dust, dirt and grime with shoes, sweat, etc. as also some
disease carrying germs.

8
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Introduction

Now, in order to ensure that the quality of the indoor environment remains good, the
HVAC systems will need to run continuously to maintain the temperature as well as
keeping the air clean, uncontaminated and available in sufficient quantities. For this reason,
it is required that fresh air is regularly introduced into the system to maintain the oxygen
levels and remove the stale air, thereby providing proper ventilation. Additionally, the
conditioned air would also need to be distributed proportionally across the space so that
there are no hot/cold pockets, which requires what is known as “Air Balancing” to be
done on the entire distribution system.

Thus, a typical HVAC system will heat or cool the air as required, filter it, distribute it
to the conditioned space, introduce fresh air inside the building, remove odor, CO2, and
maintain temperature/humidity inside the facility.

In modern day facilities which are completely air-conditioned, HVAC systems become a
vital system since it can directly impact the quality of air that the occupants breathe and
hence can have adverse effects on their health and productivity. In other words, an ill-
maintained or incorrectly operated system can cause sickness as well as facilitate spread of
infectious diseases. Sick Building Syndrome (SBS) is a condition now widely accepted
as an illness and is symptomized by headaches, nausea, irritation of skin/eyes and other
respiratory problems. Poor ventilation, presence of chemical and biological contaminants
are the main contributing factors for this illness.

The HVAC system is spread across the entire facility and consumes a huge amount of
utility power to function. In fact, for most office buildings the HVAC consumes 35-
40% of the total power consumed in the facility. The impact on occupant satisfaction
is also evident from the recorded helpdesk data which shows that almost 50% of the total
requests/complaints received from occupants pertain to temperature. Therefore, it is of
paramount importance for the Facilities Managers to ensure that the HVAC system is
always performing optimally. This not only reduces the spend on the utility bills but also
ensures higher occupant satisfaction.

HVAC systems come in various shapes, sizes and configurations starting from a simple
window air conditioner to large centralized district heating/cooling systems. However,
irrespective of the size and the type of air-conditioning, the basic principle of operation
remains the same for all.

In the following chapters of this book, we will understand the fundamental principle
of operation of heating, cooling and ventilation systems, the types of systems and their
utilization, maintenance aspects and the impact that the HVAC systems can have on a
business.

9
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Fundamentals of HVAC Systems

2 FUNDAMENTALS OF
HVAC SYSTEMS
Heating, Ventilation and Air-Conditioning (HVAC, sometimes pronounced as ‘ech-vak’)
system comprises of all electromechanical and passive systems that are used to maintain
the thermal comfort and air quality in a building/facility. The primary objectives of the
HVAC systems are as follows:

1. Control air temperature.


2. Control humidity in air.
3. Control the quality of air.
4. Control movement and distribution of air.

It is important to understand that the temperature in a space can be controlled by either


adding heat to or removing heat from the space. The local climatic conditions and
the season will dictate whether heating, cooling or both are required. Now, as we have
seen above, temperature is not the only parameter that impacts the thermal comfort of
an individual, the humidity (moisture content) in the air also affects the perception of
temperature and therefore it is necessary to control the humidity as well i.e. add moisture
into the air (Humidification) or remove moisture from the air (De-humidification). It
should be noted however, that it cannot be a one-time activity since in addition to the heat
gain from external conditions, there are sources internally which continually add heat,
moisture to the indoor air. Therefore, the process of conditioning air needs to be continuous.
Moreover, since contaminants from external and internal sources can and do mix with the
air, it is only deemed logical that the recirculated or fresh air is filtered and cleaned. The
conditioned and cleaned air then needs to be delivered to various areas in specific volumes
and at specific speeds to ensure mixing and even distribution without creating a high
draft. This is achieved through a network of ducting with dampers and diffusers/grills.

Let us now look at the sources of heat gain, humidity and impurities in a facility.

2.1 SOURCES OF HEAT GAIN


While for heated buildings the internal heat loads actually do not have much impact on
the temperature as they are actually helping heat the building, on the other hand, for the
building that requires cooling, both the external and the internal heat sources put a
higher load on the cooling requirements. The sources of heat can be:

10
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Fundamentals of HVAC Systems

• External – Heat transfer from Sun’s radiant heat or outdoors through the building
structure, doors, roof etc. and glass windows/façade and infiltration of outdoor hot
air to indoor space.
• Internal – Heat generated by occupants, lighting loads, equipment and appliances
like kitchen equipment, computers, printers, etc.

The need for adding fresh air to maintain the air quality also brings in air at a higher
ambient which needs to be cooled more than the recirculated internal air.

2.2 SOURCES OF HUMIDITY


Air usually carries water vapor, the amount being dependent on the temperature of the
air. The warmer the air, the more its capacity to hold water vapor. Too high or too low
humidity can cause adverse effects on human comfort. Damp air, i.e. high humidity can
cause conditions conducive to growth of fungi, bacteria and dust mites as also result in
condensation which can potentially damage materials, equipment and promote bad odor.
Very dry air also causes discomfort by causing dryness and itchiness in nose /skin and may
cause static in the equipment/surfaces in addition to having potentially harmful impact on
electronic/IT equipment.

While the moisture in the outdoor air will depend on the outdoor atmosphere, the humidity
in the indoor space is impacted by internal sources as well. These could be:

1. Water vapor exhaled by human occupants


2. Cooking and washing activities
3. Water seepages through building envelope
4. Plumbing leaks
5. Poor ventilation

2.3 SOURCES OF IMPURITIES


1. External - The quality of indoor air can get affected by the contaminants that can
enter from outside the building in the form of:
-- Industrial Pollutants (Emissions from nearby sources/buildings/industries)
-- Vehicle exhaust
-- Pollen, dust, fungal spores, pesticides used for pest control
-- Contaminants from previous uses of the site or nearby locales (e.g. landfills)

11
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Fundamentals of HVAC Systems

2. Internal - Apart from the external factors that contribute to poor quality of air,
there are several factors inside the building itself, that can contribute towards poor
quality, which are as follows:
-- Housekeeping chemicals and pesticides used inside the facility,
-- Dust, grime from outside brought inside by occupant movements
-- Dust or dirt in ductwork or other components left over from project stage,
ineffective filtration, poor filter maintenance
-- Smoking, cooking, improper venting of combustion products
-- Body odor, cosmetic odor
-- Microbiological growth in drip pans, humidifiers, ductwork, coils, soiled
furnishings, carpets etc.
-- CO2 exhaled by occupants

SOURCES OF INDOOR POLLUTANTS

Outdoor Air Pollutants


Chemicals Released from
Modern Building & Molds & Bacteria
Furnishing Materials

Chemicals from
Cleaning Products
Cumbustion Gases
from Fireplaces & Cigarette Smoke contains
Woodburning Stoves some 4,000 Chemicals

Chemical Fumes from Animal Hair & Dander


Paints & Solvents

Carbon Monoxide Fumes


Gases including Radon from attached garage
seeping through foundation

Figure 2.1: Sources of Pollutants in a Building

2.4 THE CONCEPT OF HEAT EXCHANGE


As we have learnt earlier, the maintenance of temperature in a space will require either
removal or addition of heat from the space being conditioned. The same is achieved by
what is known as heat transfer and the equipment used for such heat transfer is called a
Heat Exchanger. When an object comes in contact with another object or surroundings
which are at a different temperature, heat will flow so that the objects or their surroundings
achieve the same temperature (thermal equilibrium). The heat always flows from the
warmer object to the cooler object.

12
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Fundamentals of HVAC Systems

It is therefore clear, that if we were to pass air over a set of pipes containing hot fluid, the
air will gain heat i.e. become hot and likewise if the pipes contained a cold fluid, the air
would lose heat, i.e. become cold. In both case heat transfer is taking place. At the heart
of the HVAC systems, it is this concept which is used to condition the air in both Heating
and Air-Conditioning. For heating, the common medium used in the pipes is Water or
Steam and for Air-Conditioning (Cooling), it could be water, glycol or a refrigerant (Refer
Chapter 5 – What is a Refrigerant?).

Air Flow Hot Air

Concept of Heat Transfer Heat Gain

Pipes Containing Hot Fluid


Warm Cool
Object Object
Pipes Containing Cold Fluid
Heat always Flows from Hot to Cold
Heat Loss

Air Flow Cold Air

Figure 2.2: Concept of Heat Transfer

Systems in which the refrigerant picks up heat directly from the air to be cooled are known
as Direct Expansion (DX) systems. However, if the refrigerant is used to cool another fluid,
which is then used to gain heat from the air in the space to be cooled, then the cooling
systems are called Chillers.

2.5 TYPES OF HVAC SYSTEMS


Now that we have understood the basic concept of HVAC systems, it becomes easier to
appreciate that the types of systems required in a particular facility will depend upon
various factors like area to be conditioned (small/big, single room/floor, multiple floors/
rooms), end purpose (heating/cooling/ventilation), placement of different components etc.

The type of units or systems used in smaller spaces would be Local Systems requiring maybe
individual units which could be placed inside or close to the space being conditioned,
whereas a larger space spread across multiple floors/rooms would require a Large Central
System with elaborate network of piping and ducting system to distribute the conditioned
air in all areas as per requirement.

13
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Fundamentals of HVAC Systems

HVAC systems can also be classified as per the construction or configuration, namely
Package Systems and Split Systems. As the names suggest, Split units will have the
components spilt into two units (indoor and outdoor) whereas a package unit will have
all the components housed in a single unit. In the split units, the indoor unit and outdoor
unit are connected through tubing through which the hot water or refrigerant flows. There
is, however a restriction on the length of the tubing that can be used for the unit to be
efficient. In a split unit, since the air handling components are in the indoor unit normally
no ducting will be required. A package unit can be placed outside and since the air handler
is also in the same unit ducts are required to distribute air within the spaces to be cooled.

2.5.1 LOCAL SYSTEMS

A local HVAC system is deployed to serve a single space and will usually be placed within
the space itself or at the boundary between the space and external environment. These systems
are standalone i.e. independent of each other and will usually be relatively smaller in size
and ratings. The local systems mostly house the cooling/heating mechanism, filtration
and distribution within the same unit. A window air-conditioner or a room electric heater
are examples of local systems.

www.sylvania.com

We do not reinvent
the wheel we reinvent
light.
Fascinating lighting offers an infinite spectrum of
possibilities: Innovative technologies and new
markets provide both opportunities and challenges.
An environment in which your expertise is in high
demand. Enjoy the supportive working atmosphere
within our global group and benefit from international
career paths. Implement sustainable ideas in close
cooperation with other specialists and contribute to
influencing our future. Come and join us in reinventing
light every day.

Light is OSRAM

14
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Fundamentals of HVAC Systems

There are certain advantages of local systems because of which they might be preferred for
certain applications. They are easier to control since only one space is being managed and
hence there is only one point of control. There is a reduced risk to operations since failure
of one unit impacts only a single location while others can continue to work normally. For
the same reason, scheduling the maintenance is easier since the systems can be shut off
when the spaces are not occupied. Because of their smaller size, common housing and less
complexity local systems are easy to maintain and replace.

However, there are associated disadvantages as well. For a larger building and the same
cooling load requirement, the combined initial cost of local systems will be higher compared
to a central system. Local systems cannot take over additional load (of adjacent space), if
required. Smaller units are less efficient and have a lower Coefficient of Performance (COP).

At times the architecture of the building (like glass façade) may not allow installation of
the local unit. This can be overcome by use of split systems wherein, part of the equipment
is placed as an outdoor unit installed on a ledge, ground or rooftop and the other part
being the indoor unit placed inside the space to be conditioned. Another aspect is that
due to the installation of local units, the aesthetics of the building may get affected (think
AC units jutting out of windows or outdoor units placed on ledges)

2.5.2 CENTRAL SYSTEMS

Central systems are designed to condition multiple spaces/zones with each zone having its
own controls. These systems are larger in size and rating. Most of the electromechanical
components are placed in a central isolated location like a machine room and the distribution
systems are placed across the conditioned spaces.

The central systems can take advantage of economies of scale, reduce noise and the impact
on aesthetics, are more efficient and provide the option of moving the conditioned cooling/
heating medium between spaces as required. Hence return on initial costs and savings in
energy costs can be derived from effective use of the systems.

However, they do have the disadvantage of a single equipment failure impacting the
complete building. Redundancies need to be built to overcome such issues. Moreover, the
systems are generally more complex and will have more maintenance requirements and
that too from Original Equipment Manufacturers (OEMs) or specialist contractors.

15
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

3 HEATING SYSTEMS
The H in HVAC stands for Heating Systems which are used extensively in places with
cold temperatures and climate. The heating systems are also of two types, as mentioned
in the last chapter, Local systems and the Central Heating Systems.

The local heating systems are the smaller individual units in various forms that are used to
provide heat in smaller areas for e.g. portable electric heaters, wood stove and fire places
etc. that are used commonly in most homes or even small offices/shops. However, as pointed
out, all these systems are only suitable for smaller spaces like individual rooms.

Larger spaces or commercial facilities like office spaces, hospitals, educational buildings,
malls etc. require a larger heating system, which is provided by the central heating plant.
At some places, the local systems may also be used to complement a central heating system.

As explained earlier, the heating process comprises of generation of heat, heat exchange
with the air to be conditioned and distribution of the conditioned air in the facility. Thus,
a typical central heating system will have three basic parts: the heating plant itself where
fuel is converted into useful heat, a distribution system comprising of network of pipes/
ducts to deliver heat to various spaces and controls to regulate the system.

In a central heating system, heat source used may be a Furnace, a Boiler or a Heat Pump.
Let’s look at each of these in detail.

3.1 FURNACE BASED HEATING SYSTEMS


A Furnace is a device to generate heat and comprises of an enclosed structure in which
fuel is burned to generate very high temperatures. The fuel that is used can be in the form
of natural gas, propane and fuel oil or even electricity can be used to produce heat. The
heat that is produced thus is transferred to air in a heat exchanger. The air is pushed through
the heat exchanger using a fan and then circulated/distributed via ducts to provide warm
air to the spaces served through registers/grills. The cooler air from the space is sucked in
back to the furnace system via the return air ducts for reheating. It should be noted here
that in the earlier days gravity systems were in vogue wherein the warm air used to rise up
the building naturally due to convection and replace the heavier cold air. However, forced
air systems are used with most furnaces these days. The by-products of combustion are
taken out to the outdoors via a flue pipe.

16
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

Figure 3.1: Heating Systems

A furnace is ideally suitable for residential use and small office spaces and typically not
used for larger spaces. However, the system is simple and does a sufficiently effective job
of heating the spaces. The operation is controlled through thermostats, relays and valves.

When the temperature of the conditioned space falls below a set level, the thermostat
sends a signal to a relay which operates the valve to allow fuel into the furnace to start the
heat generation process. Similarly, once the temperature is achieved the fuel supply to the
furnace is shut down.

17
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

Modern high-efficiency furnaces can be 98% efficient and operate without a chimney. The
small amount of waste gas and heat produced are mechanically ventilated using PVC/Metal
pipes through the side wall or roof of the building. The Fuel Efficiency in a gas furnace
is measured in AFUE (Annual Fuel Utilization Efficiency). AFUE is the ratio of annual
heat output of the furnace compared to the total annual fossil fuel energy consumed by
a furnace or boiler. An AFUE of 90% means that 90% of the energy in the fuel becomes
heat and the rest 10% escapes up the chimney and elsewhere. AFUE doesn’t include the
heat losses of the duct system or piping, which can be as much as 35%.

3.1.1 COMPONENTS OF A FURNACE

For ease of convenience, we will discuss a Gas based furnace since it is most prevalent one
in use. A furnace will typically comprise of the following major components:

Figure 3.2: Components of Gas Furnace

18
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

• Thermostat: A thermostat is a device or component which can detect temperature


in a room and send signals to control other devices. In air-conditioned spaces, a
thermostat recognizes when a particular temperature set point has been reached
and will send a signal for the furnace to shut off or start.
• Heat Exchanger: A heat exchanger consists of a set of coils or tubes that are looped
inside the furnace. The heat exchanger in a furnace serves two purposes; this is
where the gas or fuel combusts thereby creating the heat and the air which passes
around it gets heated up. A blower motor is used to push the air over the heat
exchanger and the into the ductwork for transportation to the conditioned spaces.
• Igniter: A furnace requires fire/heat to ignite the gases when it is switched on.
The older furnaces used a pilot light, which was a small fire continuously burning
inside the burner that would ignite the gas as soon as it entered the chamber.
Nowadays, a hot surface igniter is used that is heated up by electricity making it
red hot to light up the gas.
• Burners: The fuel comes out of the burner and mixes with the air to burn and
produce the flame.
• Gas Valve: The gas valve is electrically operated to control the gas going into a
furnace and also to shut off the gas, when a safety switch fails.
• Blower Fan: The blower fan is used to suck in the air returning from the conditioned
space, as well as fresh air and blow it over the hot heat exchanger. The conditioned
air is then circulated throughout space to be conditioned via ductwork. The ductwork
has grilles and registers on the other end, viz the rooms to be conditioned, through
which the hot air enters the rooms. A fan limit switch ensures that the fan operates
only when a set temperature is reached, thus preventing cold air from being circulated
and also shuts off the furnace, if the temperature becomes too high. Some furnace
models offer a blower fan that can run at variable speeds to improve efficiency.
• Flue: A flue or chimney acts as an exhaust for gaseous by-products of combustion
used to create heat.
• Return Air Filter: A filter is fitted at the entry point of return air to the furnace
to prevent any material, debris, dust etc from going inside the furnace.
• Draft Inducer Fan: The draft induced creates a vacuum in the exhaust pipe to
ensure a safe path for the exhaust gases to go out. It also helps in drawing air into
the burner assembly.
• Flame Sensor: A Flame sensor is used to detect presence of heat and to shut off
the gas in case the there is no flame.
• Furnace Limit Switch: When the furnace becomes too hot, a limit switch will turn
the furnace (gas supply) off to prevent any damage to the furnace
• Safeties: There are additional safety features installed on a furnace like blower door
open limit switch, electric motor overload trip, flue gas spill switch etc.

19
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

Furnaces are available in various sizes that can be used to heat an area quickly, i.e. faster
than a boiler-based system. It also costs lesser to install a furnace system compared to a
boiler-based system. Condensing furnaces are now available which recover heat from the
exhaust gases using a secondary heat exchanger, which is used for pre-heating the return
air thus enabling higher efficiencies. Since furnaces use a ductwork to circulate hot air,
the same ductwork can be used with an integrated cooling system as well, where required.

3.1.2 MAINTENANCE OF FURNACE BASED HEATING SYSTEMS

Routine maintenance on the furnace will involve the following:

1. The furnace and the area around it should be kept clean since the air movement
may get obstructed if it is not clean.
2. The filters get choked/caked while in operation and need to be changed regularly
since a poorly working filter can reduce efficiencies, cause unnecessary load on the
system and also result in higher utility bills. Blowers, blower motor, pulleys etc should
also be inspected and cleaned, belts should be inspected and replaced as required.
3. Inspection of the complete system is required to be undertaken to check for leaks in
the ducting system, gas line and flue system. While a leak in the gas line can be a
fire hazard, a leak in the combustion chamber or flue system can expose occupants
to waste gases like carbon monoxide. Heat exchangers need to be checked for cracks.
Electrical connections should be checked and tightened if required.
4. Calibration of thermostats and any measuring instruments/gauges need to be done,
replace batteries where required.
5. Annual inspections by a specialist vendor needs to be conducted and the same
will include a thorough inspection of the complete system; including burners,
flame properties, gas line pressures, ignition systems, safety systems and checking
performance of individual components.

3.2 BOILER BASED HEATING SYSTEMS


The second type of heating systems are called Boilers that uses hot water or steam for
providing heat to the spaces inside a facility. The hot water or steam is circulated via a
piping network to delivery devices placed in the spaces to be conditioned. Theses delivery
devices are essentially heat exchangers and could be in the form of radiators, air handlers
or convectors. The hot water/steam transfers its heat to the air blowing over the delivery
device and becomes cooler. In a steam system, the steam condenses into water. The cooler
water returns to the boiler for reheating. Besides the specific purpose of conditioning air,

20
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

boilers and furnaces may be used for other industrial applications requiring hot water, steam
and manufacturing as well.

Just like furnaces, boilers can be operated on natural gas, LPG, solid fuels, electricity and
fuel oil. Again, gas-based boilers are more prevalent and therefore we shall discuss only
those for understanding the complete system.

3.2.1 OPERATION OF GAS BASED BOILER

A gas-based boiler, as the name suggests, uses natural gas or LPG as fuel to heat the water.
There are essentially two types as mentioned above, the steam boiler and the hot-water boiler.
It is important to note that while a steam boiler actually boils water to produce steam, the
hot-water boiler does not necessarily boil water, and only heats it to 50-800 C. A continuous
supply of natural gas stream is made available to the boiler through a pipe that is supplied
from the gas mains. The burner sprays the gas into the combustion chamber and ignites it.
The flames are directed onto pipes containing water which gets heated up. The water pipes
run through the space to be heated and is connected to delivery devices (radiators) fitted
in the space to be heated. A pump is used to push the hot water through the distribution
network of pipes. As the hot water passes through the radiators it loses heat to the room air
thus warming it in the process. The cooler water is then returned to the boiler to be heated
again. In this manner, the process continues to maintain the temperature in the conditioned
space. A thermostat in the conditioned space will switch on/off the boiler when the set
temperatures are reached. Waste gases from the boiler are exhausted through a flue system.

Figure 3.3: Boiler System

21
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

3.2.2 COMPONENTS OF GAS BASED BOILER

Apart from the boiler, the heating system will also have following components:

• Heat Emitters/Delivery Devices: These are essentially heat exchangers where the
heat from hot water is transmitted to the medium for heating air. These can be
in form of radiators which heat the air in the room as it passes over the radiator
surface or they can be radiant heating system i.e. a network of pipes distributing
the hot water, that run through the floor slab/walls to heat it up which in turn
heats the air in contact. The warm air then moves up pushing the cooler air to
come down and get heated or there could be fan heaters, which use a fan to blow
the cool air over the radiator pipes to heat it.
• Piping Network: A continuous piping network is created to deliver the hot water
to the emitters and then return it to the boiler.
• Pump: An electric pump is used to pump the water through the pipe network.
• Expansion Tank: The volume of water changes with temperature and the change
in volume needs to be catered for, else the pressure may become too high. The
expansion tank provides the space for the extra water to move when hot and move
back into the network as it cools.
• The Feed Tank or the Makeup Tank: This tank stores feed water for the boiler to
make up for losses of water and tops up the quantity when required as per the design

Vent (chimney)
Pressure Reducing
Valve
Pressure Relief
Water Feed Air Vent Valve
Valve
Aquastat
Flow Control
Valve RETURN
SUPPLY

Pressure/
Expansion Temp Gauge
Tank

Burners Circulator(s)
(pump)
Drain Valve
Gas Valve

GAS FIRED HOT WATER BOILER

Figure 3.4: Components of Boiler

22
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

• Thermostats: There are two types, one is the boiler thermostat which controls
the temperature of the water in the boiler and the other is the room thermostat
which controls switching ON/OFF of boiler basis the room temperature.
• Thermostatic Radiator Valves: These valves facilitate setting of different temperatures
in different spaces by regulating the flow of hot water through the radiator.
• Pressure Relief Valve: If the system pressure becomes too high the relief valve comes
into action and releases the pressure to prevent bursting of pipes.
• Motorised valves: If the boiler system is also being used to provide hot water
for domestic purposes a motorised valve is used to direct the flow of water to the
respective system.
• Boiler Controls: The hot water or steam needs to be produced in a regulated,
efficient, and safe manner. Combustion and operating controls regulate the rate
of fuel use to meet the demand. The main operating control monitors hot water
temperature or steam pressure and sends a signal to control the firing rate, i.e. the
rate at which fuel and air enters the burner. Multiple sensors may be available and
include, flue gas CO2 levels, flue gas temperature, stack smoke density, steam/
water flow, oil/gas consumption, etc. The boiler controls are very finely tuned and
any disturbance can result in efficiencies going down, and improper combustion.
• Safeties: A boiler is a pressurised vessel and hence there is always a risk of pressure
becoming too high. It is therefore necessary to have adequate safety systems built
in. The safety systems include cut-outs for high pressure and temperature, high and
low gas/oil pressure, high and low water level and flame safeguard. These controls
break the electrical circuit to prevent firing of the boiler if any of the parameter goes
beyond the set limits. Flame detectors monitor the flame condition and deactivate
the burner in the event of a non-ignition or other unsafe condition.
• Condensing Boilers: Just like a condensing furnace, the exhaust gases from the
boiler are at a high temperature and carry a lot of heat which is wasted. In a
condensing boiler the exhaust gases are used to pre-heat the cooler water that is
returned from the radiators/heat emitters thereby reducing the work that boiler
has to do to get the water heated to the desired temperature. This improves the
efficiency of the entire system.

3.2.3 MAINTENANCE OF GAS BASED BOILERS

A boiler, like any other equipment, also needs regular maintenance for it to continue
functioning in a safe and efficient manner.

23
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

Conducting Regular Maintenance helps to reduce the boiler operating and energy costs,
improves safety, and extends the life of the boiler. Maintenance tasks will typically involve
following:

1. Ensure that the area around the boiler is clean and no combustible materials are
available. Check the floor under and around the boiler for leaking water. Check
for any unusual noise/vibration.
2. Check pressure and/or temperature readings and the display panel for any service
codes or errors.
3. Check the combustion air opening for any obstructions.
4. Ensure the vent termination is not blocked with snow, ice, or debris. Visually
check the flue gas vent piping and combustion air piping for any signs of blockage,
leakage or deterioration.
5. Check for sweating/leakage on the boiler relief valve and the relief valve discharge
pipe.
6. Check the water pipe network completely for leaks.
7. Inspection of burners and state of ignition system components.
8. Check filters and replace, if required.

Annual Maintenance includes:

1. Thorough inspection and cleaning of heating system, burner assemblies and heat
exchangers.
2. Check all wiring and connections.
3. Checking of water PH levels.
4. Inspect condensate system and clean and flush as necessary.
5. Inspect venting system, air inlet and vent terminations for blockage, corrosion or
deterioration and ensure all joint and pipe connections are tight.
6. Check systems operating settings and test safety controls.
7. Check for proper operation after it has been cleaned and inspected.

3.3 HEAT PUMP


The third type of heating system is called a Heat Pump, which is a device that moves heat
energy from one place to the other. It is very much like an air conditioner (discussed in a
later chapter) with the advantage that it can reverse direction of flow thus enabling it to
condition air on both cold and warm days. In cooler days it removes heat from outside
and transfers it inside and vice versa on warmer days. It is also feasible to use heat pumps
simultaneously for heating and cooling operation. A heat pump can draw/give away heat
from/to multiple sources, i.e. environment air, water and even ground.

24
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

heat exchanger

soil soil

aquifer aquifer

heat storage heat storage


Summer cooling Winter heating

360°
Figure 3.5: Heat and Cold Storage with Heat Pump

thinking
For climates with moderate heating and cooling needs, heat pumps offer an energy-efficient
alternative to furnaces and air conditioners.
.

360°
thinking . 360°
thinking .
Discover the truth at www.deloitte.ca/careers Dis

© Deloitte & Touche LLP and affiliated entities.

Discover the truth at www.deloitte.ca/careers © Deloitte & Touche LLP and affiliated entities.

Deloitte & Touche LLP and affiliated entities.

Discover the truth at www.deloitte.ca/careers


25
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

Figure 3.6: Heat Pump

Heat pumps can be classified based on the medium used as the source/sink for heat. There
are three types of heat pumps:

1. Air-Source Heat Pumps use the outside air as the heat source in winter and heat
sink in summer.
2. Water-Source Heat Pumps use water bodies as the heat source/sink. This is not
very popular due to its dependence on availability of water body nearby.
3. Ground-Source (also called geothermal, GeoExchange, or GX) Heat Pumps
which get their heat from the ground.

Both Water and Ground-Source heat pumps take advantage of the fact that temperatures
beyond a certain depth in water and ground respectively are nearly constant all through
the year i.e. it will be warmer than outdoor air temperatures in winters and cooler than
outdoor air temperatures in summers.

Air-Source heat pumps are cheaper and easier to install and hence more common. Ground-
Source heat pumps, though higher in cost, are more efficient.

While an air-source heat pump is installed much like a central air conditioner, ground-
source heat pumps require that a “loop” of piping be buried in the ground, usually in long,

26
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

shallow (3–6’ deep) trenches or in one or more vertical boreholes. Similarly, water source
heat pumps will need to have a loop in touch with a water body like a lake, ocean etc.
The method used will depend on the location, the size of the facility and the subsoil. In a
direct exchange system, the ground loop contains the refrigerant that traverses through the
length of pipe to exchange heat with the soil. In indirect exchange systems water is used
to transfer the heat from the refrigerant to the ground. The refrigerant gains/loses heat to
water in the water heat exchanger section and the water runs through the ground loop
to exchange the heat with the soil. The image (Figure 3.7) below shows the layout of the
ground loop and the heat exchange process.

Figure 3.7: Ground-Source Heat Pump

Since heat pump only moves heat rather than generate it, Heat pumps are more efficient
than other heating systems using furnaces and boilers and are also much more safer and
easier to maintain. The Coefficient of Performance (COP) of heat pumps can have values
ranging from 1.75 to 6.

27
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Heating Systems

We will understand more on the Air-Conditioning cycle in Chapter 5 (Air-Conditioning


Systems) and the concept or the operation of heat pump will become clearer. Since the
components of a heat pump are similar to the Air-Conditioning system, the maintenance
needs of a heat pump will also be similar to an Air-Conditioning system besides the reversing
valve and the refrigerant / water loop.

28
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

4 VENTILATION SYSTEMS
Ventilation (V of HVAC) is an important aspect of the HVAC systems. It is the process of
exchanging, replacing or recirculating air in any space with the objective of maintaining
the Indoor Air Quality (IAQ) and thus contribute towards the health and comfort of the
occupants. Ventilation introduces outside air into the building thus replenishing oxygen
and recirculating indoor air to prevent stagnation. This results in removal of unpleasant
smells, excessive moisture, heat, dust, bacteria and gases like carbon monoxide and
carbon dioxide from the atmosphere inside a facility.

Though natural ventilation is a component of the larger scheme, we will cover forced or
mechanical ventilation in this chapter. All the equipment in a facility which handle/process
air can be deemed to be part of the ventilation system. These, as explained earlier, could be
standalone units or work in conjunction with other equipment. Heat exchangers, filtration
units, supply and exhaust fans, humidifiers/dehumidifiers, the ductwork for carrying the air
for distribution and delivery devices are all part of the building ventilation systems.

4.1 AIR HANDLING UNIT (AHU)


As the name suggests, an Air Handling Unit (AHU) handles air. The basic function of
the AHU is to circulate indoor air, add fresh air to it and condition it to the right
temperature and humidity before delivering it back to the conditioned spaces through
ductwork. To serve this function, the AHU has filters for cleaning the air, humidifiers
and dehumidifiers for humidity control, a heat exchanger which cools/heats the air and
a fixed/variable speed fan to move the air to/from the conditioned space. Ducting is used
to carry the air to the conditioned spaces and the same is insulated to suppress the sound
of the running AHU motor and that of movement of air. Please note that while a central
system usually uses a separate AHU, package systems have the air handler installed in the
same unit, however the function remains the same.

29
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

Figure 4.1: Air Handling Unit with Labeled Parts


1 - Supply duct; 2 - Fan compartment; 3 - Flexible connection; 4 - Heating and/or
cooling coil;5 - Filter compartment; 6 - Return and fresh air duct

4.1.1 OPERATING PRINCIPLE OF AHU

The AHU is an enclosed equipment with a fan, filter, heat exchanger, humidifier/dehumidifier
connected to ductwork. There are two sets of ducts, the supply air ducts which take the
air from the AHU to the conditioned space and the return side ducts which carry air from
the conditioned space to the AHU. When the fan runs, it pushes the air out through the
supply side ducts which creates a vacuum in the plenum (empty space provided for mixing)
and pulls the used air from the conditioned space through the return air ducts. The fan
also pulls in some fresh air from outside environment. The air is mixed in the plenum
and passed through a filter for cleaning and then over a heat exchanger which either heats
or cools the air. Thereafter, the air is passed through the humidifiers or dehumidifiers and
into the ductwork. This cycle continues. The flow through the supply duct and the return
duct should be almost same in order to maintain the pressure in the conditioned space.

30
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

Figure 4.2: Working of AHU (Image sourced from MDPI; Shah, A.; Huang, D.; Chen, Y.; Kang, X.;
Qin, N. Robust Sliding Mode Control of Air Handling Unit for Energy Efficiency Enhancement.
Energies 2017, 10, 1815. Creative commons attribution license)

The entry of fresh air serves the purpose of maintaining the quality of air and also to
replace air lost through openings and exhausts in the floor (exfiltration), thus maintaining the
pressure inside the building to prevent untreated air to come into the building (infiltration).
If the exfiltration is not sufficient to remove excess air dedicated fans, or exhaust fans in
toilets and kitchens can be used to remove the excess air.

4.1.2 COMPONENTS OF AN AHU

An AHU will typically have the following common components:

• Housing: The housing that contains all the other components of an AHU, comprising
of a metal base frame held together by an extruded aluminium framework. The
panels are made of galvanised steel sheets injected with environment friendly PUF
(Polyurethane foam, an insulator) of uniform density. The insulated panels are fixed
to the frame work using self-drilling & tapping screws. A drain pan is also provided
to drain the water in the event of condensation of water.
• Air Mixing Section: Fresh air & return air are mixed at the desired rate with
dampers that are specially designed for maximum air efficiency.
• Blower Section: The blower (motor-fan) helps to recycle the air present in the
buildings. Large AHUs can have multiple blowers and fans. When the blower
runs it pushes the air over the heating/cooling coils and in the process a vacuum
is created behind the blower which pulls in the air from the conditioned space
through the return air ducts in the building. The fan & motor is normally mounted
on a common channel fitted with anti-vibration isolators to avoid the vibration
transfer to main casing.

31
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

• Filter Section: A Filter section is fitted in all the air handling units which help to
filter the impure air i.e. remove dust and other foreign particles. Filters are rated
by their MERV (Minimum Efficiency Reporting Value) and the selection will
depend on the level of cleaning required. In some AHUs, UV filtration may also
be implemented for getting rid of bacteria. Filters may be of different types like
Plate Filters, Bag Filters, Compact Filters, EPA Filters, HEPA Filters, ULPA Filters,
Carbon Filters etc.
• Heat Exchanger Section - Cooling/Heating Coils: The Heat exchanger section
comprises of the cooling or heating coil to cool/heat air. The coils are arranged in
rows with different fin spacing. Aluminium fins and copper tubes are used in the
design of the coils. The coils could carry the refrigerant or water/glycol as per the
system.
• Heat Recovery Systems: Heat recovery systems may be used in AHUs to reduce
energy costs by extracting heat from the facility’s exhaust air stream before it is
vented outside.
• Humidifiers (Adiabatic/Evaporative Pad, Non-Pressurized Steam, Pressurized
Steam): The humidifiers are used to increase the humidity of the air, when required.
The same is achieved by adding moisture, water vapour into the air.
• Dehumidifiers: Normally, the cooling of air takes away some of the moisture but
in places with high humidity some additional measures may be required. Excess
moisture is removed by condensation or absorption.
• Dampers: Dampers are devices which regulate the air flow by modifying the
resistance to the air flow including shutting it off completely. The dampers are at
times also connected to the Fire Alarm panel to automatically shut off in case of
fire and thus stop the flow of air into the conditioned space.
• Ductwork: Ducts are used to carry air to/ from the source (AHU) to the conditioned
space. Two duct paths are made one for supply and the other for return. The return
is required to recirculate as much indoor air as possible since it is already treated to
some level and hence is more economical to re-treat. Ducts are made of galvanized
sheets and the supply ducts are insulated while return ducts are not.
• Ducting Accessories: The delivery components in a ducting network are components
placed in the conditioned space to deliver/retrieve the air. These could be registers,
diffusers or grilles and are available in different shapes and sizes.

4.1.3 CLASSIFICATION AND TYPES OF AHUS

AHUs can be broadly classified based on how they are mounted, i.e. Horizontal Floor
Mounted, Vertical Floor Mounted or Ceiling Suspended. Another way to classify them
is based on where the fan is located with respect to the cooling coils and filter as:

32
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

1. Draw-Through Type: Here the fan is located towards the discharge side and pulls
the air through the filters and cooling coil before discharging it from the fan outlet
to the ducting network.
2. Blow-Through  Type: Here the fan blows the air through the filters and cooling
coil before discharging them to the ducting system.

Discharge
Filter Coil plenum
Fan

Return Air Supply Air

(a) Draw-Through Type

Discharge
Filter Coil plenum
Fan

Return Air Supply Air

(b) Blow-Through Type

Figures 4.3 (a) & (b): Diagrammatic representation of Draw-Through & Blow-Through type of
AHUs

4.2 FAN COIL UNITS (FCU)


A fan coil unit is a terminal unit for air-conditioning system and works more or less in
the same way as an AHU. It facilitates a versatile way of providing conditioned air into
a space. It is small in size and capacity, has greater controllability and can be mated
with a whole variety of grilles and diffusers to match the vision of the architect or interior
designer. If required, it also allows the conditioned air to be spread around the served room
via discharge ducts, to allow a single unit to distribute conditioned air to a large area.

A fan coil unit (FCU) is a very simple device consisting of a heating or cooling/heating
coils and fan. The coils could carry refrigerant (in case of DX units) or water (in case of
use in conjunction with a chilled water system). Fan coil units can be wall-mounted,
freestanding or ceiling-mounted and may be concealed in ceiling voids. A fan coil unit

33
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

(FCU) receives chilled water from a chiller line or hot water from a boiler and circulates
that through the heat exchanger. The fan draws the room air blows it over the cooling or
heating coil in the heat exchanger. The air comes out of the FCU either cooler or hotter
than before. Temperature control can be achieved either by controlling the flow of water/
refrigerant to the unit or by controlling the flow of air through the FCU, thus achieving
a wide range of temperatures. A thermostat integrated with the unit can be used to signal
the demand to FCU.

Figure 4.4: Fan Coil Unit

Fan coil units can be either 2 pipe units or 4 pipe units, the difference being that 2 pipe
systems can either cool or heat at one time (either chilled water or hot water is flowing
through one set of pipes), whereas 4 pipe systems has two independent sets of pipes; one
each for hot water and chilled water and can heat and cool at the same time. This means
the 4 pipe units are not system dependent i.e. they are not dependent on the mode of
temperature control of the building

34
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

4.3 VARIABLE AIR VOLUME (VAV) SYSTEMS


An AHU will usually consider the entire conditioned space as one zone and supply air at a
constant air flow at a particular temperature to all the outlets in the network i.e. temperature
can be controlled by changing the set point at AHU only. These systems are called Constant
Volume Systems. While some amount of uniformity in temperature can be achieved by air
balancing, individual control at the outlet is not feasible. Variable Air Volume systems (VAV’s)
can be used to control temperature in a space (cabin or meeting room) by modulation of the
amount of air at a constant temperature that serves the particular space. However, it should
be kept in mind that since the VAV’s control the flow of volume of air, it is important that
the AHU motor is also of variable speed in order to maintain the pressures in different zones.

A simple VAV system can be considered to be a box that controls air from a single supply
duct and varies the airflow to each space based upon the temperature in that space. From
a control perspective, such a system would consist of a temperature sensor, an air flow
sensor, a controller, an actuator and a damper.

We will turn your CV into


an opportunity of a lifetime

Do you like cars? Would you like to be a part of a successful brand? Send us your CV on
We will appreciate and reward both your enthusiasm and talent. www.employerforlife.com
Send us your CV. You will be surprised where it can take you.

35
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

The volume of the air flowing into the space is controlled by a motorized damper which
is actuated by a thermostat positioned within the condition space. The damper opens and
closes depending on the temperature in the room thus varying the amount of cool air going
into the conditioned space.

VAVs are supplied air by an AHU and hence in the presence of multiple VAVs operating
independently the AHU must be capable of handling the fluctuating load. Variable speed
motors in the AHU facilitate this need, wherein the speed of the AHU blower goes up or
down depending on the demand.

4.4 CHILLED BEAMS


A chilled beam is a terminal unit that uses convection for heating or cooling large spaces.
Technically, they are heat exchangers in a casing, mounted on or suspended from the ceiling,
using chilled water for cooling air by convection. The beams are distributed across the
ceiling. Chilled beams may be Passive or Active.

• A Passive Chilled Beam completely relies on the air being drawn into the heat
exchanger by convection. Chilled water is passed through pipes in a heat exchanger
(Beam) either suspended from the ceiling or integrated into the false ceiling systems.
The air around the heat exchanger gets cooled and the cooler, denser air falls to
the ground causing a pressure drop in the beam that draws in warmer air into the
beam. This causes a continuous convective flow to be established thus cooling the
entire space.

A passive chilled beam does not have any ducts or fans and hence recirculates only
the indoor air. Additional arrangements will have to be made for fresh air entry and
humidification. It is obvious that the concept will not work efficiently for heating
systems since warmer air will continue to be higher up near the ceiling.

• Active Chilled Beams have a primary air system i.e. air is supplied to the beam
in certain quantity, through ductwork. The primary air pressurises the plenum and
then the air is discharged through nozzles which induce air from the conditioned
space to pass through the cooling coils. The primary air mixes with the cooled air
before being introduced into the conditioned space through nozzles or slots in the
beam. The main air handling unit supplies primary air to the chilled beam.

36
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

Figure 4.5: Active Chilled Beam

Active beams are recommended for spaces like classrooms, private and public office buildings,
meeting facilities, health care facilities, where the sensible cooling and ventilation air are
required.

Active chilled beam for Active chilled beam for


exposed installation suspended installation

Mixed Air

Induction Air

Primary air supply, typically


through a piece of duct
approximately 5" in diameter

Figure 4.6: Active Chilled Beams: Source Gibson, Thomas, and Mindy Espinosa. “Chilled
Beams: What They Are, Why You Should Use Them.” The NEWS Magazine, 20 May 2013.
Web. 16 Jan. 2017. (Creative Commons license)

37
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

Figure 4.7: Active and Passive Chilled Beams

4.5 VENTILATION SCRUBBERS


A scrubber is used to remove particulates/contaminates from the air. The ventilation scrubbers
for HVAC application clean the fresh outside air before it is fed into the indoor HVAC
system. A pre-filter removes dirt and dust contaminants and a special activated media
captures the gaseous contaminants using adsorption.

Air scrubbers are commonly used in facilities where the outdoor air quality is not good.
In such areas, it becomes necessary to clean the fresh air before being introduced into the
building.

4.6 EXHAUST FANS


Exhaust fans are used to remove the adulterated/stale air from places like wash rooms and
live kitchens. These are regular fans but placed in a manner so as to suck air from the inside
and throw it outside. For obvious reasons, the exhaust fans would be installed on the wall
with a boundary to the outside environment. Under normal conditions the action of the
exhaust fans would create a partial vacuum in the room and hence it is desirable that a
grille or louver is built into the door of the room to facilitate replacement of air inside the
room. In such a case not only will the fan have to work harder to move the air but the
higher pressure will create a draft of air whenever the door is opened.

38
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

4.7 JET FANS


Jet Fans are used to ventilate enclosed / underground car parks and basements. Since there is no
natural ventilation and due to the large area, the air may become stagnant in certain pockets.
The parking spaces, unless properly ventilated, may accumulate Carbon Monoxide and Carbon
Dioxide emitted along with the vehicle exhausts. In order to prevent higher concentrations
of these gases and avoid a fire risk, jet fans are used to systematically remove these gases out of
the spaces by directing the same at high speeds. Multiple jet fans positioned appropriately and
directing the air out can take out the contaminating gases efficiently out of the parking lots. Jet
Fans do not need any ducts resulting in tremendous cost savings, power savings and increased
installation efficiency. Jet Fans can be used for normal ventilation and also for smoke extract
in case of a fire. CO/CO2 sensors may be installed and integrated with jet fans to automatically
start the fans whenever the concentration of the gas goes beyond the set level.

Figure 4.8: Jet Fans

39
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Ventilation Systems

4.8 MAINTENANCE OF VENTILATION SYSTEMS


All components of the ventilation systems require maintenance for better efficiency,
effectiveness and longevity of the equipment. Before maintaining any equipment, it is
important that the supply should be switched off. AHUs may at times be considered as
confined space (depending on where they are fitted) and due care (Work Permit) needs to
be taken while working on these.

The heating/cooling coils in the AHU need to be cleaned regularly to maintain heat transfer
efficiency. The motors of blower/ fans need to be checked for proper functioning, tightness
of connection, currents drawn. Belts if available need to be checked for tension and replaced
when required. Filters need to be cleaned and replaced as required. Condensation is a
frequent issue in AHUs and needs correction since it adds to humidity and also can promote
biological growth, mold etc. Areas need to be kept clean at all times. Variable speed drives
will also need maintenance removing dust, dirt, moisture, tightening connections, checking
capacitors etc. Sensors and thermostats should be checked for proper operation.

The ducting needs to be inspected regularly for leakages. Accumulation of dirt inside the
ducting is not good for health and also increases friction for the air. Duct cleaning may
be needed when the ducts become overly dirty. Dampers need to be checked for proper
operation.

40
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

5 AIR-CONDITIONING SYSTEMS
So far, we covered the Heating & Ventilation components of the HVAC system in the
previous two chapters, and that brings us to the last component of the acronym, AC i.e.
Air-Conditioning systems. The Air-Conditioning traditionally referred to the cooling
component of the HVAC systems, but now that we have seen that a heat pump can serve
both the purposes of cooling and heating, Air-Conditioning inadvertently becomes the
right term to use.

In this chapter, we will focus on Air-Conditioning systems that help in cooling the air.
Once the concept of cooling is clear, the working of heat pump, discussed earlier (Chapter
3), will also become clearer since it only involves reversal of the flow of gas.

Unlike the furnace and the boiler, which actually generate heat, the air-conditioning systems
do not generate heat but just move the heat between inside the building and outside using
the principles of thermodynamics. We know that heat energy will spontaneously flow
from a warmer body/medium to a cooler body/medium. However, in order to make the
heat move from a cooler body to a warmer body requires work to be done. This work is
performed by the air-conditioning or refrigeration equipment.

5.1 TYPES OF COOLING


There are different mechanisms by which cooling can be achieved by the Air-Conditioning
systems, of which the following are predominantly used for cooling a facility:

1. Free Cooling: In relatively cooler climates or at night times in certain places,


outdoor temperature can be lower than that required inside the facility. The lower
external temperatures can be used to chill a coolant which in turn can be used to
cool air inside. A pump is used to circulate the coolant, which may be Water or
Glycol, to the heat exchangers (AHUs) in the space to be cooled thus removing
heat from the air in the area. At times, the chilled coolant may also be stored
for later use i.e. to provide cooling on warmer days. The modern day mechanical
cooling systems also make use of free cooling in the economizer mode, by allowing
a larger amount of the cooler outside air to come in to the facility thus obviating
the need to run the cooling system and saving energy.
2. Evaporative Cooling: If hot air is passed through water or a wet pad some of the
water will evaporate and provide a cooling effect to the air. This principle is used
for cooling in very dry hot climates. A fan located inside an enclosure with wet

41
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

pads on the sides will suck in air from outside through the wet pads. As the air
passes through the pads it becomes cooler and moister before being discharged
into the room. This helps to maintain the temperature and humidity in the room.
It should be noted that these systems will be ineffective where the humidity in
outside air is already at high levels.
3. Mechanical Cooling: Mechanical cooling is the lowering of temperature within a
space using refrigerant compressors, absorbers or other systems that require energy
use and mechanical work to be done in order to condition the space.

5.1.1 WHAT IS A REFRIGERANT?

We know that when ice, a solid, is heated it changes into a liquid form (water) and similarly
when water is heated, it changes form into gas (vapour). Similarly, when the vapour is
cooled it condenses into liquid and on being cooled further it gets converted to ice. In
fact, this is true for all substances. When a substance changes its state of matter, it either
gains heat or loses heat. The transition from solid to liquid to gas absorbs heat and the
transition from gas to liquid to solid gives up heat. This property of substances is used in
Air-Conditioning to absorb heat from the indoor and then give up heat to the outdoor.
Certain substances are more amenable to use for this purpose than others depending on
their characteristics like vapor density, thermal conductivity, toxicity, cost etc.

A refrigerant is a substance, often a fluid, used in a refrigeration cycle to transfer heat


from one place to another using the laws of thermodynamics. The refrigerant changes its
phase from liquid to gas and back to liquid during each cycle thus enabling the heat
transfer which is so important for the refrigeration/ Air-Conditioning purposes.

Many refrigerants have been used in the past, the more common ones being Chlorofluorocarbons
(CFC) and Hydrochlorofluorocarbons (HCFC) (R-12 & R-22). However, both these
types have an ozone depleting potential and hence are being phased out.

R-290 (Propane) and R-600A (Iso-Butane) are environment-friendly refrigerants that


are completely halogen free, have no ozone depletion potential and are lowest in terms of
global warming potential. These are essentially hydrocarbons and have high-energy efficiency
but are also highly flammable.

42
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

5.2 OPERATING PRINCIPLE OF AC SYSTEMS


So far, we have learnt that Air-Conditioning uses a cyclic process wherein the refrigerant
changes its state to absorb and reject heat alternately. There are two basic cycles which
are employed in the Air-Conditioning systems, which are:

• Vapor Compression Cycle


• Vapor Absorption Cycle

5.2.1 VAPOR COMPRESSION CYCLE

In the Vapor Compression Cycle, as shown in Figure 5.1 below, the refrigerant is in a
vapor form when it enters the compressor where it is compressed. The high pressure and
high temperature vapor from the compressor is let out to a condenser (heat exchanger)
where it loses some of its heat to the outside environment and condenses i.e. turns into
the liquid state. The low temperature liquid which is still at a high pressure is then sent to
an expansion valve, where the pressure decreases abruptly causing evaporation of part of
the liquid and in the process cooling it. The expansion valve, also called a metering unit
or throttling unit, also regulates the flow of liquid into the evaporator. The mixture of cool
liquid and vapor is then sent to the evaporator where the remaining liquid also evaporates
absorbing the heat from the warm air around it and thus cooling it in the process. The
moisture from the air is also removed as the moisture condenses on the evaporator coil.
The water will drip down into the condensate pan located underneath the coil. The water
is then discharged to the drain by connecting a hose or piping to the pan. Thereafter, the
cycle repeats itself.

Figure 5.1: Refrigeration cycle

43
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

In order for this cycle to be deployed in air-conditioning, the refrigerant in the evaporator
interacts with the indoor air and removes heat and the heated refrigerant in the condenser
interacts with the outdoors to give away heat. Most Air-Conditioning systems in facilities
use the vapor compression cycle for cooling. If the direction of the flow of refrigerant is
changed then the condenser and evaporator roles are interchanged (Indoor coil becomes
the condenser and outdoor coils become the evaporator) and the same process can be used
for heating as well.

�e Graduate Programme
I joined MITAS because for Engineers and Geoscientists
I wanted real responsibili� www.discovermitas.com
Maersk.com/Mitas �e G
I joined MITAS because for Engine
I wanted real responsibili� Ma

Month 16
I was a construction Mo
supervisor ina const
I was
the North Sea super
advising and the No
Real work he
helping foremen advis
International
al opportunities
Internationa
�ree wo
work
or placements ssolve problems
Real work he
helping fo
International
Internationaal opportunities
�ree wo
work
or placements ssolve pr

44
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

Hot Air Discharge


High Pressure Vapor High Pressure Liquid

Condenser

Outside Ambient Air

Metering
Compressor
Device

Indoor Ambient Air

Air
Handler

Low Pressure Vapor Evaporator Low Pressure Liquid/Vapor


Coil

Figure 5.2: Vapor Compression Cycle

5.2.2 VAPOR ABSORPTION CYCLE

Vapor Absorption Machines (VAMs) use the vapor absorption cycle which is similar to the
vapor compression cycle, except that instead of the compressor a combination of absorber,
pump and a generator is used to achieve the high-pressure gas required for the condenser.

The refrigerant (Ammonia or Water) in vapor form, at a relatively higher pressure in the
evaporator, moves into the absorber and is absorbed (dissolved) in a suitable liquid (Water
for Ammonia and Lithium Bromide for Water). The absorption process reduces the volume
of the mixed solution thereby allowing more vapor to move in from the evaporator. A pump
is used to raise the pressure of the saturated solution heating it in the process and drives
the solution into the generator. The saturated solution is further heated in the generator
causing the refrigerant to evaporate and separate from the liquid. The hot refrigerant
in vapor form passes through the condenser where it loses its heat and condenses. The
refrigerant is then taken through an expansion valve thereby cooling further and then finally
into the evaporator where it gains heat and turns back completely into the vapor form.

The absorption cycle systems have a very low Coefficient of Performance and are predominantly
used only where waste heat is readily available than electricity. Below is a comparison between
the two systems. We will discuss only vapor compression systems in this book.

45
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

S.no Aspect Vapor Absorption System Vapor Compression System

Vapor absorption system uses waste Vapor compression system uses electrical
1 Energy Input heat from furnace, exhaust team or or mechanical energy for operation of
solar heat. compressor.

Only a small pump is the moving An electrically driven compressor is


2 Moving parts
part. used.

Can handle partial loads without The performance is impacted at partial


3 Load variation
much impact on performance load.

No risk of equipment being damaged Liquid in the compressor can damage the
4 Risk of damage
by liquid entry. compressor

Coefficient of
5 The COP of the system is poor. The COP is higher.
Performance

Figure 5.3: Comparison between Vapor Absorption & Vapor Compression Systems

5.3 COMPONENTS OF AIR-CONDITIONING SYSTEM


Let us now look at the different components of the Air-Conditioning systems. Since vapor
compression systems are more prevalent, only those will be discussed here. The Figure 5.4
below shows the components of a simple Window AC.

Figure 5.4: Components of a Simple Window AC

• Compressor: A compressor is a device that compresses a gas thus increasing its


pressure by reducing its volume. In an Air-Conditioning system, the compressor
draws the low-pressure gas from the evaporator and compresses it to a high
temperature - high pressure gas before supplying it to the condenser. Compressors

46
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

used in Air-Conditioning may be classified into reciprocating, centrifugal, rotary,


screw and scroll compressors. However, in Window and Split ACs we would
normally find only reciprocating or rotary types of compressors.
• Condensers: A condenser is a device used to convert a substance from its gaseous
state to its liquid state. In the process, heat is transferred from the substance to its
surrounding medium or a condenser coolant, which may be air or water.

Figure 5.5: Condenser

Air-Cooled Condensers may use natural convection or forced air convection. In both the
systems the refrigerant flows inside the condenser tubes and the outside air flows over the
condenser tubes cools the refrigerant.

In a Water-Cooled Condenser, instead of using air, cold water is used to take away the
heat from the refrigerant. The condensers may be of double tube type or shell & tube
type. The water-cooled condensers require a cooling tower (described in chapter 6) to take
away the heat from the water and then resupply it for condenser cooling. Water-cooled
condensers normally require lesser space but are more difficult to maintain. They are used
for large conditioning plants serving large cooling loads. There are evaporative condensers
also available but not in vogue due to lesser efficiencies.

• Expansion Valve: Expansion valves are also called metering devices, allow expansion
of the refrigerant from a liquid to a vapor state. While the condenser allows the
refrigerant to cool, the pressure remains unchanged. The expansion valves are flow
restricting devices which reduce the pressure of the fluid passing through it and
allows it to expand. It does so by means of a combination of a movable pin and
spring. The temperature at the outlet of evaporator and pressure of the evaporator
are used as the controlling factor. Higher temperatures cause more fluid to flow
into the evaporator. A constant supply of the refrigerant is also ensured to the
evaporator by the expansion valve.

47
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

Figure 5.6: Expansion Valve

• Evaporator: The final component in the refrigeration cycle is the evaporator,


where the cold refrigerant absorbs heat from the air passing over it, thereby
cooling the air and in the process changes state from liquid to gaseous form.
The air flows directly over the surface and is cooled by the refrigerant passing
through the tubes. Plates and fins are added to increase the area of contact. The
evaporators in larger systems like those used with chillers are of the shell and
tube construction and can be classified as dry expansion (Refrigerant flows on
tube side and while the water flows on the shell side) or flooded type (refrigerant
level is maintained in the shell and water flows through the tubes).

48
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

Figure 5.7: Evaporator Coil

• Thermostat: A thermostat is used in all the air conditioners for feedback and
maintaining the desired temperature in the area to be conditioned. Thermostat
senses the temperature and switches on/off the cooling/heating system at previously
decided set points. Thermostats may be mechanical (bi-metal), electrical or electronic
(thermistors).

5.4 TYPES OF AIR-CONDITIONING UNITS


Now that we have learnt the principle of operation of an Air-Conditioning system and the
major components, let us look at the various types of systems available.

5.4.1 WINDOW AIR CONDITIONERS

A classic package unit, these are small units that can fit into an opening in the wall/window
of a facility. These are limited by capacity and are used for smaller spaces/rooms. All the
components are installed within a compact unit and a fan is used to blow air over the
evaporator coils and then directly into the room. Filters are added on the return side to
prevent dust from entering into the system.

49
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

5.4.2 SPLIT TYPE UNITS

The basic air conditioner is split into two parts, an outdoor unit and an indoor unit. All
components except the evaporator are installed in the outdoor unit and the evaporator is
placed inside the room to be cooled. The two units are interconnected by copper tubing
for the refrigerant flow. The outdoor unit houses the compressor and hence noise and
vibration inside the cooled space is reduced to a large extent. These units are suitable for
use in smaller rooms and two or more units can be deployed to offer rotation as well as
redundancy. In facilities with central cooling, the split ACs can be used as an alternate for
off-peak hours when only few critical spaces may need cooling thus conserving energy and
reducing utility bills.

It should be noted that the distance between the indoor and outdoor units is constrained
by the limitation of length of copper tubing (150 feet max) due to pressure drop in the
refrigerant over the distance.

Figure 5.8: Types of Air Conditioners

5.4.3 PACKAGED DUCTABLE SYSTEMS

Just like the window air conditioner, in construction a packaged system houses all the
components in a single unit. However, these are typically larger and installed outdoors
and instead of throwing air directly into the room they use a blower to push the air into
the conditioned spaces through ducting installed for the purpose. In cooler environments,
a heating system may also be integrated into the package unit, thus obviating the need to

50
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

have a separate heating system in cold weathers. The condenser cooling could be by air or
water.

These units are used commonly in places that may be large enough to preclude use of
split ACs or located away from central areas to justify the extensive ductwork and piping
required for a central AC.

The window and split air conditioners are usually used for the small Air-Conditioning
capacities up to 5 tons. The central Air-Conditioning systems are used for where the
cooling loads extend beyond 20 tons. For intermediate cooling capacities the packaged air
conditioners may be used. The packaged air conditioners are available in the fixed rated
capacities of 3, 5, 7, 10 and 15 tons.

5.4.4 VARIABLE REFRIGERANT FLOW/VOLUME (VRF/VRV)

VRVs are systems used to control the temperature in a conditioned space by varying the flow
of refrigerant to the indoor units as per the demand. They are similar to split ACs with the
difference that they can serve multiple indoor units of varying capacities in different zones
and vary the flow of refrigerant to each as per the demand of the specific indoor unit. The
technology offers many advantages like simultaneous cooling, heating in different zones,
a tighter control on temperature, higher efficiencies and finally the scalability to add more
indoor units if capacity exists in the outdoor unit.

The indoor units used could be of any type like FCUs, ceiling mounted cassette, floor
standing units, hi-wall units etc.

Daikin, a Japanese company, developed the technology calling it VRV (Variable Air Volume).
Daikin registered VRV as a trademark and hence other manufacturers using the similar
technology use the term VRF.

Like the systems discussed earlier, VRF systems also operate on the direct expansion (DX)
principle meaning the refrigerant is circulated in the heat exchangers in indoor units
(evaporators) and directly cools the air.

The outdoor unit is connected through piping to multiple indoor units. The refrigerant
travels through these pipes to the expansion valves in each branch. Dedicated electronic
expansion valves are used to accurately control the flow of refrigerant to each evaporator
depending on the feedback received from temperature sensors and hence the flow in each

51
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

evaporator is different basis the requirement. The overall demand or the change in the same
is managed by varying the speed of the inverter driven compressor in the outdoor unit. A
capacity control ranging from 6% to 100% can be achieved by these compressors. Due to
this tighter control the VRF system have higher efficiencies and energy consumption is
also substantially reduced. A schematic VRF arrangement is indicated below (Figure 5.9):

Figure 5.9: Typical VRF Layout

The refrigerant pipe-work uses a number of separation tubes and/or headers (refer schematic
Figure 5.9). A separation tube has 2 branches whereas a header may have more than 2
branches. Either can be used however, the separation tube is not provided after a header
because of air balancing issues.

5.4.5 PRECISION AIR-CONDITIONING UNIT (PAC)

Some mission critical facilities or spaces like data centers, server rooms, laboratories etc.
require a very strict control of temperature and humidity as well as have a low level of
tolerance to dust. The comfort Air-Conditioning systems are not capable of meeting these
needs.

The precision air conditioners, also known as a CCU (Close Control Units) or CRAC
(Computer Room Air Conditioner) are refrigerating equipment specifically designed to
provide precise control of temperature and humidity in all applications which require a
very high degree of precision.

Precision Air Conditioners (PAC) are designed specifically to meet the following objectives
to be achieved with a very high degree of reliability:

52
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

• Air temperature control (± 1.0°C).


• Air humidity control (± 7/8%).
• High airflow rate.
• Year-round operation (24 hours a day, 365 days a year), without any interruption.

The working principle of PACs is the same as any other AC with the difference being in
the components and control systems used for maintaining the air quality to a high degree
of precision. The PAC deploys higher capacity components with higher efficiencies like a
scroll compressor, electronically commutated fans, electronic expansion valves and solid-state
microprocessor-based controls. Redundancy may be built in by having multiple gas circuits
in a single unit and also by providing multiple units to cater for the load.

PACs may be classified: (a) as per the condenser cooling mechanism i.e. Water Cooled
or Air Cooled or (b) according to the manner in which the air is distributed i.e. Under
Floor System (air supplied through the openings in raised flooring) as shown in the Figure
5.10 or Overhead System in which the flow is reversed (air is delivered through openings
in the ceiling).

Warm Air Warm Air

PAC
Server Server

Raised Floor
Cool Air
Hard Floor

Figure 5.10: Under Floor System

5.4.6 CENTRAL PLANTS

All the systems we discussed so far, are direct expansion systems, which means that the
refrigerant cools the air directly without any intermediary medium. While a central plant
can be a direct expansion, it is not suitable for the modern-day facilities where the cooling
load is very high, and such a plant if used would require large amounts of refrigerant to
be circulated through a maze of tubes/pipes to cool all the areas/floors of a facility. Such a

53
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Air-Conditioning Systems

plant, in addition to facing technical complexities, will also bring forth a safety concern of
large amounts of refrigerant leaking into the occupied spaces.

To overcome this issue, central plants are used to cool water or a water solution which is
in turn circulated through pipes and heat exchangers (typically, AHUs/FCUs) on the floors
to cool the air. Since the plants chill the water or other solution, these types of central
systems are also called Chillers (Refer Chapter 6). The systems require additional equipment
on the liquid side, for pumping and recirculating the liquid. Primary and secondary pumps
are installed for pumping the liquid in the system and an expansion tank may be added to
prevent hammering in the pipes.

54
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Chillers

6 CHILLERS
For deployment of DX systems in larger facilities, like a complete floor of a large building
having multiple zones to be cooled or a full hospital building, higher capacity units or more
number of units will need to be used to meet the cooling load thereby increasing the capital
costs. DX units are constrained by the length of piping that can be used for carrying the
refrigerant from condenser to evaporator due to pressure drop and thermal losses over the
length of the pipe making it impractical and uneconomical to have a common unit serving
multiple indoor units at a large distance. This will also require use of a large quantity of
refrigerant, which is not inexpensive by any means. In addition, there is always the risk of
a leak in the pipe which may release a large amount of gas in the occupied space.

Chilled Water Systems or Chillers provide a solution to cool larger buildings efficiently
without suffering from the issues with DX systems as indicated above. The principle of
operation of various components remains the same; however, indirect cooling is used for
cooling the air in conditioned spaces. The chiller’s refrigerant gas is used to cool water
instead of air in the evaporator. This chilled water, which now acts like a secondary
refrigerant, is then transported to the heat exchanger of the various air handling units of
the facility and cools the air, just like the refrigerant does in the DX system. There are no

55
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Chillers

issues of pressure loss with water and it can be pumped to any height or distance using
pumps. Any water loss in the system can be made up by simply adding more. There is of
course an addition of piping and pumps to distribute the cold water through the building
and back to the chiller for cooling. However, the total capital and operating cost is much
lower than it would be for a DX plant serving a similar area.

A typical chilled water central Air-Conditioning system comprises of three major sub-systems:
The Chiller, Chilled Water System and Air Distribution System. In case of a water-cooled
chiller, another component of condenser cooling system comes into play i.e. the Cooling
Tower. We will cover only the water related systems here as the Air Handling Systems
was covered in Ventilation Systems (Chapter 4).

6.1 CHILLER
A Chiller is a machine that removes heat from a liquid via a vapor-compression or absorption
refrigeration cycle to produce chilled liquid (secondary refrigerant). This chilled liquid flows
through pipes in a building and passes through heat exchanger coils in air handlers, fan-coil
units, or other systems, thereby cooling and also dehumidifying the air in the building. The
liquid used for cooling may be Water, or a Brine with a Salt or Glycol base, or a mix
of Glycol & Water. The basic requirement of a secondary refrigerant is that it should be
non-corrosive, inexpensive, have high specific heat, have good heat transfer characteristics,
should be chemically stable and have a low viscosity. Examples of secondary refrigerants are
water, sodium chloride, calcium chloride, ethylene glycol, ethyl alcohol, trichloroethylene
etc. For general Air-Conditioning requirements water is preferred due to less cost but some
industrial processes may require use of other liquids.

Figure 6.1: Chiller

56
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Chillers

The Chiller also comprises of a compressor, condenser, evaporator and expansion valve,
there being two main differences; (1) the size of the components is much larger and (2)
instead of the refrigerant cooling the air in the evaporator, it is now cooling water. Another
component which can be seen in the Figure 6.2 below is that there is a connection going
to the cooling tower which means that this diagram represents a water-cooled chiller.

Cooling Tower

Water Line

Refrigerant Loop
CHILLER Condenser Compressor
TEV
UNIT
Evaporator

Chilled Water to
Water Line
Living Space

Figure 6.2: Chilled Water System

Chillers can be broadly classified into two by the manner in which the condenser is cooled:
Air-Cooled or Water-Cooled.

57
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Chillers

Figure 6.3: Air-Cooled Water Chiller Plant

6.2 CHILLED WATER SYSTEMS (CWS)


After the water has been cooled by the chiller, there is a need to transport it to the various
end users i.e. the air handling units where the chilled water will cool the air being supplied
to the conditioned spaces.

The water also needs to be transported back to the chiller for cooling again. The movement
of water is achieved through pumps, piping and valves. Technically speaking, at this stage
the chilled water can be classified as a secondary refrigerant.

The pressure and volume of water changes with temperature and there may be water
losses as well. An expansion tank used in the chilled water system facilitates maintenance
of pressure and caters for the change in overall volume of the system.

There can be multiple configurations of the pumping system deployed in the chilled water
system. Two are discussed below for a basic understanding.

58
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Chillers

6.2.1 DIRECT PRIMARY (CONSTANT FLOW)

In a Primary only system, there is only one set of pumps which is used for distribution of
the chilled water to the entire network and bring it back. The distribution is at constant
flow irrespective of the load. Valves at the building air handling systems will allow the
chilled water to be bypassed under low load conditions so that the total flow through the
chiller remains constant. This system is inefficient because of the wastage of energy. The
mixing of chilled bypass water with the return water reduces the efficiency of the chillers.

Direct Primary

Loads

Chiller Chiller Chiller


1 2 3

3-Way valves

Primary Pumps
Balancing Valves

Return

Figure 6.4: Direct Primary Distribution System

6.2.2 PRIMARY – SECONDARY SYSTEM

In this scheme, the chilled water system is divided into two distinct loops, primary and
secondary. This arrangement can supply variable flow through the system while maintaining
a constant flow through the chillers.

3-way valves in the secondary loop control the flow of water through the air handlers
depending on load, however the overall quantity of water through the system will remain
the same.

59
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Chillers

Primary Loop Secondary Loop

Secondary Pumps

Loads

Chiller Chiller Chiller


1 2 3

Supply

3-Way valves

Primary Pumps
Balancing Valves

Return

Figure 6.5: Primary Secondary Distribution System

6.3 COOLING TOWERS


As discussed earlier, for water cooled condensers the cooling water needs to lose the heat
gained to the environment. This is done using a Cooling Tower. The tower blows air
through a stream of water causing some of it to evaporate, and the evaporation cools the
water stream. Some water is lost due to evaporation and also by falling outside the sump,
therefore water has to be added regularly to make up for the lost water. Make up water
also helps in removing the high concentration of minerals from the water which collect
due to evaporation of water.

Cooling water in a cooling tower may require chemical treatment or dozing to maintain
the quality of water. Warmer temperatures and the deposits like sludge, scale, rust etc in
the cooling towers encourage the growth of the bacteria legionella and need to be guarded
against. Legionnaire’s disease can be a fatal condition and it is recommended that the cooling
tower water be tested for Legionella regularly.

Though there may be slight differences in how water and air react inside a cooling tower,
the basic principle remains the same. A diagrammatic representation of cooling tower is
shown in Figure 6.6 below.

60
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Chillers

Figure 6.6: Cooling Tower

Figure 6.7: Cooling Tower of Large Office Building

61
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Chillers

6.4 MAINTENANCE OF CHILLERS


• Clean and inspect outdoor coils: Dirty condenser coils reduce the efficiency of
the condenser thereby reducing the efficiency of the entire system. Clean condenser
fan, coils, comb bent fins, lubricate bearings, inspect belts and drives if available
and check all connections,
• Inspect the compressor(s). It must be working properly for your system to operate
efficiently. Check for leakage and vibration, refrigerant level, oil levels, crankcase
heater and check operating temperatures
• In the control panel check wiring, switches, and other components. These may
have a direct impact on the performance and also includes safeties which prevent
damage to the equipment
• Inspect the water system for water leaks and repair as required. Check operation
of pumps, valves and actuators in the system. Depending on the quality of water
in the system, the same may require chemical treatment/dosing
• For cooling towers, water testing and treatment with corrosion inhibitors and
biocides is required to be done; fans, motors, belts and gears need to be cleaned,
adjusted and replaced if worn; electrical components such as wiring and capacitors
need to be checked and replaced if needed, inspection and cleaning of basin, louvres,
fills, spray nozzles, water and air flow need to be checked.

62
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Conclusion

7 CONCLUSION
Control of the indoor environment has become a necessity in a modern-day facility and
rightly so. Most people spend up to 80% of their time indoors. Poor quality of air and
thermal conditions in those places can impact their health and also cause illness. While
some of these conditions could be short term like itching, nausea, headaches etc., some
other long-term effects include respiratory diseases, heart problems and cancer. No one is
comfortable in a space which is too hot or too cold, is smelly or damp or where the air feels
stale. It is also obvious that since the larger buildings house a greater number of people,
the impact is that much greater.

For any business, be it a commercial office space, a mall, a hospital, an educational institute
etc., the impact of poor indoor environment is detrimental to the overall business. The
productivity of employees is affected, illnesses mean more absenteeism, then there is the
cost of medical treatment and severe conditions may even lead to employee attrition. For
public spaces, the poor indoor environment can cause a direct loss of customers.

A well designed and maintained HVAC plant can help maintain a good quality of indoor
air and obviates conditions which are contra-indicated for a productive, healthy and safe
indoor environment. Regular maintenance and optimized operations can reduce the total
cost of ownership as well as the utility bills.

We learnt about the various types of equipment used for Heating, Cooling & Ventilation
and understood how they work in unison to undertake the task of maintaining temperature
and humidity, circulation and filtration of air, addition of fresh air to replenish oxygen and
moisture and removal of stale air.

In facilities, the ownership of HVAC systems may vary from a single ownership to a
distributed ownership. A landlord or building owner will generally cater only for central
plants for human comfort, the smaller systems or PACs if required will need to be installed
by the occupiers/tenants. For a central plant also, the landlord may provide the complete
HVAC system for the building including the chilled water system and the AHUs or provide
only the chilled water connection to the floor. The AHUs and the ventilation ducting
becomes the responsibility of the tenants. On the other hand, the landlord may not provide
the HVAC system at all and will ask the tenant to install their own. The operations and
maintenance of the plant becomes the responsibility of the entity that installed the system.

There is cost involved in operating and maintaining the HVAC plants. For a single occupancy
building, the central plant HVAC costs can directly be billed to the single tenant. However,

63
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Conclusion

if there are multiple tenants, the billing is done basis the energy consumed by the tenant.
This is measured by what is called a BTU meter. BTU meters measure the energy content
of liquid flow in British Thermal Units (BTU), a basic measure of thermal energy. The
amount of chilled water flowing through the circuit and the temperature differential between
the chilled water supply and chilled water return lines are used for this purpose.

Irrespective of who maintains and operates the HVAC system, timely and effective maintenance
on HVAC systems can not only improve occupant health and safety but can also go a
long way towards enhancing the equipment useful life thus obviating or at least delaying
high repair/capital costs. Proper scheduling of the equipment and managing the temperature
set points basis the occupancy and during different times of the day can result in energy
savings of a high order.

Lastly, please remember that irrespective of how well you maintain and operate the
HVAC equipment, there will still be some occupants who will complain about the thermal
comfort. It is because there are a lot of factors which impact an individual’s perception
of the temperature including the clothes they are wearing, their metabolism, their gender,
size, age, level of activity etc. ASHRAE (American Society for Heating, Refrigerating
and Air-Conditioning Engineers) requires that at least 80% of the occupants be satisfied
with the indoor thermal conditions. What it means is that, there is no need to go around
changing the setting of the HVAC system every time there is a complaint about feeling
hot/cold. Though you must investigate the complaint for any local issues, if 80% or more
of the occupants are satisfied with the thermal conditions, you can trust the HVAC system
to be working just fine.

64
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Common Terminology

8 COMMON TERMINOLOGY
TR – Tons of Refrigerant is a unit used to define the heat extraction capacity of an air-
conditioning unit. One ton of refrigeration is the amount of cooling obtained by one ton
of ice melting in one day.

BTU – British Thermal Unit Another measure of heat, a BTU is the amount of heat
required to raise the temperature of one pound of water by one-degree Fahrenheit. Number
of BTUs per hour define the capacity of a plant. 1 TR = 12000 BTU/hr.

KW – At times KW may be used to define the capacity of the plant, 1 TR is equal to


3.517 KW.

COP – Coefficient of Performance is the ratio of outpower and input power. Since it is a
ratio it is dimensionless. Both output and input power need to be the same unit, i.e. KW.

EER – Energy Efficiency Ratio is the ratio of output in BTU and input power energy
in KWh used as a measure of energy efficiency of the plant. Therefore, the unit is BTU/
KW/h. the higher the EER, more is the efficiency.

CFM – Cubic Feet per Minute is used to define capacity of a fan/ventilation system by
the volume of air moved in a minute.

iKW/TR – Input Kilowatt per ton is the amount of power required to produce 1TR of
heating. The lower the iKW/TR the higher the efficiency.

Delta T (ΔT) – It is the difference in temperature for a fluid when it enters a system and
when it leaves the system.

Plenum – An enclosed space created to facilitate air flow and related to air distribution.

AFUE – Annual Fuel Utilization Efficiency is a measurement used to rate furnace efficiencies
by dividing the ratio of heat output by heat input.

MERV – Minimum Efficiency Reporting Value is a rating system for air filters. Ranging
from 1 -20 basis the minimum size of particulate matter that the filter can catch, the higher
the rating the more effective is the filter.

65
HEATING, VENTILATION &
AIR-CONDITIONING: FACILITY MANAGEMENT Common Terminology

Condenser Approach - is the difference in temperature of liquid refrigerant in the condenser


pipe and the leaving condenser water. Should be less than 3 0C.

Evaporator Approach - is the difference in temperature between the refrigerant in the


evaporator and the leaving chilled water. Usually between 10 - 14 0C for a single pass
evaporator and lesser for a multi-pass evaporator.

66