SIMATIC
Preface, Contents
PCS 7 V7.0 Architectures Introduction 1
Standard Architecture
Selection Guide 2
Starter System 3
Single Station System 4
Multiple Single Stations
Systems 5
Client-Server System 6
Multi-Server 7
SIMATIC Batch 8
Route Control 9
SIMATIC PDM 10
Archiving 11
Asset Management 12
Field Bus 13
Network Architecture 14
Safety System 15
Connectivity 16
AS-OS PO Count 17
Edition 06/2007
A5E01172031-01
Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to
prevent damage to property. The notices referring to your personal safety are highlighted in the manual
by a safety alert symbol, notices referring to property damage only have no safety alert symbol. The
notices shown below are graded according to the degree of danger.
Danger
! indicates that death or severe personal injury will result if proper precautions are not taken.
Warning
! indicates that death or severe personal injury may result if proper precautions are not taken.
Caution
! with a safety alert symbol indicates that minor personal injury can result if proper precautions are not
taken.
Caution
without a safety alert symbol indicates that property damage can result if proper precautions are not
taken.
Notice
indicates that an unintended result or situation can occur if the corresponding notice is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of
danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a
warning relating to property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning
and operation of a device/system may only be performed by qualified personnel. Within the context of
the safety notices in this documentation qualified persons are defined as persons who are authorized to
commission, ground and label devices, systems and circuits in accordance with established safety
practices and standards.
Prescribed Usage
Note the following:
Warning
! This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers
which have been approved or recommended by Siemens.
Correct, reliable operation of the product requires proper transport, storage, positioning and assembly
as well as careful operation and maintenance.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG.
The remaining trademarks in this publication may be trademarks whose use by third parties for their
own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and
software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency.
However, the information in this publication is reviewed regularly and any necessary corrections are
included in subsequent editions.
Training Centers
Siemens Technical Training Center provides extensive training for all levels of
plant personnel to ensure optimal performance from PCS 7 control systems.
Classes include extensive hands-on activities using appropriate equipment, making
the training directly and immediately applicable.
On-line information is available: http://www.sea.siemens.com/sitrain
Siemens also offers a number of training courses to familiarize you with the
SIMATIC S7 automation system. Please contact your regional training center or
our central training center in D 90327 Nuremberg, Germany for details:
Telephone: +49 (911) 895-3200.
Internet: http://www.sitrain.com
Nürnberg
7 Multi-Server 7-1
7.1 Multi-Server Single Bus System Architecture................................................... 7-2
7.1.1 Multi-Server Single Bus System Bill of Materials ............................................. 7-3
7.2 Multi-Server Redundant Bus System Architecture ........................................... 7-5
7.2.1 Multi-Server Redundant Bus System Bill of Materials...................................... 7-6
8 SIMATIC Batch 8-1
8.1 SIMATIC BATCH Starter System Architecture................................................. 8-3
8.1.1 SIMATIC BATCH Starter System Bill of Materials ........................................... 8-4
8.2 SIMATIC BATCH Single Station Architecture .................................................. 8-5
8.2.1 SIMATIC BATCH Single Station Architecture Bill of Materials......................... 8-6
8.3 SIMATIC BATCH Client-Server Architecture ................................................... 8-7
8.3.1 SIMATIC BATCH Client-Server Bill of Materials .............................................. 8-8
8.4 SIMATIC BATCH Client-Server Redundant Architecture............................... 8-10
8.4.1 SIMATIC BATCH Client-Server Redundant Bill of Materials.......................... 8-11
8.5 SIMATIC BATCH Multi-Server Architecture ................................................... 8-14
8.5.1 SIMATIC BATCH Multi-Server Bill of Materials.............................................. 8-15
9 Route Control 9-1
9.1 Route Control Single Station System Architecture........................................... 9-2
9.1.1 Route Control Single Station System Bill of Materials...................................... 9-3
9.2 Route Control Client-Server System Architecture ............................................ 9-5
9.2.1 Route Control Client-Server System Bill of Materials....................................... 9-6
9.3 Route Control Client-Server Redundant Architecture ...................................... 9-8
9.3.1 Route Control Client-Server Redundant Bill of Materials ................................. 9-9
9.4 Route Control Multi-Server Architecture......................................................... 9-11
9.4.1 Route Control Multi-Server Bill of Materials.................................................... 9-12
10 SIMATIC PDM 10-1
10.1 SIMATIC PDM Stand-Alone System Architecture.......................................... 10-3
10.1.1 SIMATIC PDM Stand-Alone System Bill of Materials..................................... 10-4
10.2 SIMATIC PDM Workshop Set-up Architecture ............................................... 10-5
10.2.1 SIMATIC PDM Workshop Set-up Bill of Materials.......................................... 10-6
10.3 SIMATIC PDM and PCS 7 Starter System Architecture ................................ 10-7
10.3.1 SIMATIC PDM and PCS 7 Starter System Bill of Materials ........................... 10-8
10.3.2 SIMATIC PDM and PCS 7 Single Station System ......................................... 10-9
10.4 SIMATIC PDM and PCS 7 Client-Server System Architecture .................... 10-10
10.4.1 SIMATIC PDM and PCS 7 Client-Server System Bill of Materials ............... 10-11
10.5 SIMATIC PDM and non-SIMATIC S7 Master Architecture .......................... 10-13
10.5.1 SIMATIC PDM and non-SIMATIC S7 Master Bill of Materials ..................... 10-14
11 Archiving 11-1
11.1 Client – Server System Architecture............................................................... 11-2
11.1.1 Client – Server System Bill of Materials ......................................................... 11-3
11.2 Redundant OS Server, Single Central Archive Server Architecture .............. 11-5
11.2.1 Redundant OS Server, Single Central Archive Server Bill of Materials ......... 11-6
11.3 Redundant OS Server, Redundant Central Archive Server Architecture....... 11-8
11.3.1 Redundant OS Server, Redundant Central Archive Server Bill of Materials.. 11-9
11.4 Client – Server System StoragePlus Architecture........................................ 11-11
11.4.1 Client – Server System StoragePlus Bill of Materials................................... 11-12
Number of users:
one to two
Number of users:
one to two
Number of users:
two to five
Dell Dell
Number of users: XP XP
three to sixteen
Number of users:
twelve to thirty-two
Starter System
When one or two users and less than 300 IO needs to be supported, the SIMATIC
PCS 7 BOX 416 system is a powerful yet cost effective solution.
In the system the Automation System (AS) and Operator System (OS) are
integrated in an Industrial PC allowing for minimal cabinet space requirements. The
AS is based on a PCI Slot form factor S7-416-2 CPU that can run autonomously in
case of failure of the PC. The basic architecture integrates the Engineering System
(ES) functionality on the same platform.
Dual Monitor
The Starter System can be equipped with a Multi-VGA graphics card “2 Screens”
allowing for two monitors to be attached to the system.
Notes
The second OS relies on the Ethernet interface of the SIMATIC PCS 7 BOX 416
Industrial PC for it’s communication with the AS. Failure of the industrial PC will
stop the communication between the second OS and the AS.
Notes
Field Bus components, racks, modules and Field devices are not listed
1. PCS 7 BOX 416 requires 24 VDC Power Supply
Operator System
COMPUTER PCS 7 ES/OS IL43 BCE WXP
1 6ES7 650-0LF07-0YX0
3.4GHZ
1 LCD MONITOR, 19"
1 6ES7 648-0CB00-0YA0 KEYBOARD SIMATIC PC INTNAL, USB (G)
1 6ES7 900-0BA00-0XA0 POWER CABLE US, 3 M
1 6ES7 658-2AA07-0YA0 SOFTWARE PCS 7 SS V7.O PO 250 (2
1 6ES7 652-0XD07-2YB5 SOFTWARE PCS 7 SFC VISUALIZATION
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Field Bus components, racks, modules and Field devices are not listed
1. PCS 7 BOX 416 requires 24 VDC Power Supply
2. Initial number of POs may be selected higher, optional Power packs available
Engineering System
1 6ES7 650-0LF07-0YX0 COMPUTER PCS 7 ES/OS IL43 BCE WXP 3.4 GHZ
1 LCD MONITOR, 19"
1 6ES7 648-0CB00-0YA0 KEYBOARD SIMATIC PC INTNAL, USB (G)
1 6ES7 900-0BA00-0XA0 POWER CABLE US, 3 M
(2
1 6ES7 658-5AA07-0YA5 SOFTWARE PCS 7 ENG V7.0 AS/OS 250PO OS RT
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Field Bus components, racks, modules and Field devices are not listed
1. PCS 7 BOX 416 requires 24 VDC Power Supply
2. Initial number of POs may be selected higher, optional Power packs available
Notes
Field Bus components, racks, modules and Field devices are not listed
1. PCS 7 BOX 416 requires 24 VDC Power Supply
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Field Bus components, racks, modules and Field devices are not listed
Minimal Client-Server Architecture has been listed, refer to Section describing
Client-Server Architecture for full architecture
1. PCS 7 BOX 416 requires 24 VDC Power Supply
2. Initial number of POs may be selected higher, optional Power packs available
3. PCS 7 BOX 416 may contain Engineering System, requires PCS 7 BOX 416
Complete System
Dual Monitor
A Single Station Operator or Engineering System can be equipped with a Multi-
VGA graphics card “2 Screens” or “4 Screens” allowing for up to four monitors
attached to a system.
System Bus
1 6GK5 2080BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
1 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (3
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
System Bus
1 6GK5 2080BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
1 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (4
Notes
Field Bus components, racks, modules and Field devices are not listed
Laptops with Web Client functionality have not been listed
Wireless connection to laptops is not listed
1. Quad Multi-VGA is available, number of monitors must be increased
accordingly
2. Initial number of POs may be selected higher, optional Power packs available
3. Scalance switch requires 24VDC power supply (not listed)
4. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
Redundancy
Optionally the OS Single Stations may be equipped with redundancy software and
hardware to create a redundant Operator System. In this case there will be an
archive synchronization between the two redundant single stations. The Terminal
Bus, System Bus, Automation System(s) (AS) and Field Bus can be made
redundant as well.
Dual Monitor
Each Operator or Engineering System can be equipped with a Multi-VGA graphics
card “2 Screens” or “4 Screens” allowing up to four monitors to be attached to a
system.
Web Server
One of the Operator Systems can be used to install the PCS 7 Web Server option.
In this case, the system hardware has to have a server class Operating System
installed (Windows 2003). The selected Web Server order number allows
connection of up to 3 Web Clients, Web Clients may connect via a Wireless LAN
connection. If more than 3 Web Clients should be connected, Web Server licenses
for up 10, 25 and 50 web clients are available.
For a topology where one Web Client accesses multiple Web Servers or where
fewer than 3 Web Clients are required, SIMATIC PCS 7 Web Server offers “Diag”
Web Server and Web Client licensing providing a more cost effective solution.
Notes
The number of Operator System Single Stations can be increased; however,
archive synchronization and redundancy for alarms and process tags is not
available for the Operator Systems beyond two of the Operator Systems that act as
a redundant pair.
If the number of Operator Systems exceeds two, the client server architecture is
more economical.
The Multiple Single Station architecture has constraints in the deployment of
SIMATIC BATCH, typically only one system can be used as Batch Server and
Client.
Operator System
2 6ES7 650-0LF07-0YX0 COMPUTER PCS 7 ES/OS IL43 BCE WXP 3.4GHZ
2 LCD MONITOR, 19"
2 6ES7 900-0BA00-0XA0 POWER CABLE US, 3 M
2 6ES7 648-0CB00-0YA0 KEYBOARD SIMATIC PC INTNAL, USB (G)
2 6ES7 658-2AB07-0YA0 SOFTWARE PCS 7 SS V7.0 PO 1000 (1
2 6ES7 652-0XD07-2YB5 SOFTWARE PCS 7 SFC VISUALIZATION
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
3 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
1 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (3
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
Operator System
2 6ES7 650-0LF07-0YX1 COMPUTER PCS 7 ES/OS IL43 IE WXP 3.4GHZ
2 LCD MONITOR, 19"
2 6ES7 9000BA00-0XA0 POWER CABLE US, 3 M
2 6ES7 648-0CB00-0YA0 KEYBOARD SIMATIC PC INTNAL, USB (G)
1 6GK1 161-3AA01 SIMATIC NET, CP1613 A2 (1
1 6ES7 652-0XX01-1XF0 COMPUTER 2 NETWORK CRDSRED TERMINALBUS (2
1 6ES7 652-3AB07-2YA0 SOFTWARE PCS 7 SS RED V7.0 PO 1000 (3
2 6GK1 716-0HB64-3AC0 SIMATIC NET, REDCONNECT UPGRADE (4
2 6ES7 652-0XD07-2YB5 SOFTWARE PCS 7 SFC VISUALIZATION
Terminal Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
6 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
8 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
1 6ES7 654-2PE67-0XC0 AS417-2H; AC10A W/RED. PS OPT; 2x9 SLOT RACK; (6
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required if a redundant System Bus network is selected
2. Required if a redundant Terminal Bus is selected
3. Initial number of POs may be selected higher, optional Power packs available
4. Required if redundant System Bus or redundant Automation System is
selected
5. Scalance switch requires 24VDC power supply (not listed)
6. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
Operator System
2 6ES7 650-0LF07-0YX0 COMPUTER PCS 7 ES/OS IL43 BCE WXP 3.4GHZ
4 LCD MONITOR, 19"
2 6ES7 900-0BA00-0XA0 POWER CABLE US, 3 M
2 6ES7 648-0CB00-0YA0 KEYBOARD SIMATIC PC INTNAL, USB (G)
2 6ES7 652-0XX03-1XE0 COMPUTER MULTI VGA 2-SCREEN CARD 360MHZ (1
2 6ES7 658-2AB07-0YA0 SOFTWARE PCS 7 SS V7.0 PO 1000 (2
2 6ES7 652-0XD07-2YB5 SOFTWARE PCS 7 SFC VISUALIZATION
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
3 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
1 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Quad Multi-VGA is available, number of monitors must be increased
accordingly
2. Initial number of POs may be selected higher, optional Power packs available
3. Scalance switch requires 24VDC power supply (not listed)
4. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
Operator System
1 6ES7 650-0LF07-0YX0 COMPUTER PCS 7 ES/OS IL43 BCE WXP 3.4GHZ
1 LCD MONITOR, 19"
1 6ES7 900-0BA00-0XA0 POWER CABLE US, 3 M
1 6ES7 648-0CB00-0YA0 KEYBOARD SIMATIC PC INTNAL, USB (G)
1 6ES7 658-2AB07-0YA0 SOFTWARE PCS 7 SS V7.0 PO 1000 (1
1 6ES7 652-0XD07-2YB5 SOFTWARE PCS 7 SFC VISUALIZATION
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
3 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
1 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (4
Notes
Field Bus components, racks, modules and Field devices are not listed
Laptops used as Web Clients have not been listed
Wireless LAN used to connect laptops has not been listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Web Server Diagnose Clients allow Client Side licensing, one Client accessing
multiple servers
3. Scalance switch requires 24VDC power supply (not listed)
4. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
Operation on Server
Operator System Servers can be used for monitoring and control on an attached
monitor(s) if the total number of monitors (attached to the OS Clients and the OS
Server) do not exceed four.
Redundancy
SIMATIC PCS 7 supports redundancy at all levels by introducing a second OS
Server and the OS redundancy software. The access of OS clients to real-time
and historical data and the storage of historical data is redundant and provides
higher availability. Optionally the system supports redundancy at the terminal bus,
system bus, Automation System and field levels.
Dual Monitor
Operator System Clients can be equipped with a Multi-VGA graphics card “2
Screens” or “4 Screens” allowing for up to four monitors to be attached to an
Operator System Client. You can decide if a Multi-VGA card is used for each
Operator System Client.
Web Server
A dedicated Operator System Client can be equipped with SIMATIC PCS 7 Web
Server software, allowing up to 50 Web Clients to perform monitoring and control
tasks simultaneously. The concurrent server based licensing of the Web Server
allows many more than 50 users to access the Web Server over time.
Notes
An Operator System Server supports up to 32 Operator System Clients. If Multi-
VGA graphics cards are implemented on an Operator System Client then each
monitor counts as one in the calculation of the maximum load of clients.
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
2 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (3
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Monitor for engineering and maintenance only
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
2 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (4
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (5
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (5
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Maximum number of OS Clients with operation on OS Server is 3, an OS
Client with Dual Monitor counts as 2 OS Clients. In total a maximum of 4
monitors can be controlled by an OS Server with operation.
3. Scalance switch requires 24VDC power supply (not listed)
4. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
5. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
2 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (4
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (5
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (5
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Maximum number of OS Clients with operation on redundant OS Server is 2,
an OS Client with Dual Monitor counts as 2 OS Clients
3. Scalance switch requires 24VDC power supply (not listed)
4. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
5. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
Terminal Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required if a redundant System Bus network is selected
2. Required if a redundant Terminal Bus is selected
3. Initial number of POs may be selected higher, optional Power packs available
4. Required if redundant System Bus or redundant Automation System is
selected
5. Scalance switch requires 24VDC power supply (not listed)
6. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
7. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
8. Monitor for engineering and maintenance only
Web Server
1 6ES7 650-0LH07-0YX0 COMPUTER PCS 7 OS SERVER IL43 BCE SRV/03 P4
1 LCD MONITOR, 19"
1 6ES7 648-0CB00-0YA0 KEYBOARD SIMATIC PC INTNAL, USB (G)
1 6ES7 900-0BA00-0XA0 POWER CABLE US, 3 M
1 6ES7 658-2CX07-0YA5 SOFTWARE PCS 7 OS CLIENT V7.0
SOFTWARE PCS 7 WEB SVR V7.0
1 6ES7 658-2GA07-2YB0 (2
3 CLIENTS
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
6 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
2 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (4
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (5
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (5
Notes
Field Bus components, racks, modules and Field devices are not listed
Laptops used as Web Clients have not been listed
Wireless LAN used to connect laptops has not been listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Initial number of Web Clients may be selected higher, optional Power Packs
available
3. Scalance switch requires 24VDC power supply (not listed)
4. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
5. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
6. Monitor for engineering and maintenance only
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (3
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
2 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (4
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (5
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (5
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Quad Multi-VGA is available, number of monitors must be increased
accordingly
2. Initial number of POs may be selected higher, optional Power packs available
3. Scalance switch requires 24VDC power supply (not listed)
4. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
5. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
6. Monitor for engineering and maintenance only
Multi-Server System
For large systems the multi-server architecture of SIMATIC PCS 7 allows the
implementation of large distributed systems. In this case multiple Operator System
(OS) Servers, single or redundant, are used to connect a large number of Operator
System (OS) Clients to real-time and historical data. One or more Engineering
Systems (ES) connect to both terminal bus and system bus to allow the download
of changes to both OS and Automation Systems (AS). If desired, the engineering
system can be used as an OS client when no engineering tasks are performed.
Redundant Bus
The availability of the connection between the OS Servers and the AS’s, as well as
between the OS Servers and the OS Clients, can be increased by means of
redundant interfaces and network components.
Notes
An OS Server supports up to 32 OS Clients. If Multi-VGA graphics cards are
implemented on an Operator System Client then each monitor counts as one in the
calculation of maximum load of Operator System Clients.
The number of OS Clients in the system can exceed 32, however, each OS Server
supports up to 32 OS Clients.
The maximum number of OS Servers that an OS Client can connect to is 12.
Terminal Bus
2 6GK5 414-3FC00-2AA2 SWITCH MODULAR 1EX414-3E 10/100/1000MB (3
MM491 MEDIA MODULE, MULTI-MODE FO
2 6GK5 491-2AB00-8AA2
CABLE UP TO 3 KM
2 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
2 6GK5 414-3FC00-2AA2 SWITCH MODULAR 1EX414-3E 10/100/1000MB (3
MM491 MEDIA MODULE, MULTI-MODE FO
2 6GK5 491-2AB00-8AA2
CABLE UP TO 3 KM
2 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
9 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
AS417-2H; AC10A W/RED. PS OPT; 2x9 SLOT
2 6ES7 654-2PE67-0XC0 (4
RACK
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (5
2 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (5
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required for redundant Automation System
2. Initial number of POs may be selected higher or lower, optional Power packs
available
3. Scalance switch requires 24VDC power supply (not listed)
4. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
5. AS PO RT License expanded to total 3000 PO based on, 600 PO included in
ES, 100 PO included in each AS
6. Monitor for engineering and maintenance only
Terminal Bus
2 6GK5 414-3FC00-2AA2 SWITCH MODULAR 1EX414-3E 10/100/1000MB (2
MM491 MEDIA MODULE, MULTI-MODE FO
2 6GK5 491-2AB00-8AA2
CABLE UP TO 3 KM
2 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
20 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
2 6GK5 414-3FC00-2AA2 SWITCH MODULAR 1EX414-3E 10/100/1000MB (2
MM491 MEDIA MODULE, MULTI-MODE FO
2 6GK5 491-2AB00-8AA2
CABLE UP TO 3 KM
2 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
18 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
AS417-2H; AC10A W/RED. PS OPT; 2x9 SLOT
2 6ES7 654-2PE67-0XC0 (3
RACK
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
2 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher or lower, optional Power packs
available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
4. AS PO RT License expanded to total 3000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Monitor for engineering and maintenance only
SIMATIC BATCH
SIMATIC PCS 7 standard software for ISA-88 Recipe Management and Batch
processing tasks is SIMATIC BATCH. SIMATIC BATCH is based on scalable and
modular software that can be deployed across all SIMATIC PCS 7 architectures.
SIMATIC BATCH deploys a client-server architecture as standard with clients for
recipe editing and batch control. SIMATIC BATCH clients can run on SIMATIC
PCS 7 Single Station, Server and Client systems as well as PC’s with no other
SIMATIC PCS 7 software installed.
Starter System
Even small processes can leverage the benefits of SIMATIC BATCH structured
recipe and batch execution capabilities. The smallest system that supports
SIMATIC BATCH is the PCS 7 BOX 416 which economically can control as few as
100 Inputs and Outputs.
Single Station
The next level is the Single Station architecture; all functions, engineering,
operation and batch control are comprised on a single computer. Batch phases
and operations execute in the Automation System.
Client-Server
Medium size systems that support multiple users and do not require redundancy
are implemented with Client-Server systems. SIMATIC BATCH follows the
Operator System architecture seamlessly by distribution of Batch Server and Client
applications on the equivalent Operator System Computers.
Client-Server Redundant
If redundancy is required and the number of servers must be kept at a minimum,
SIMATIC BATCH allows deployment of a redundant Batch Server on the pair of
redundant Operator System Server Computers.
Client-Multi-Server Redundant
For large and high-performance applications the SIMATIC PCS 7 Client-Server
architecture allows for distribution of applications on multiple computer platforms.
In this case the Batch Server and OS Server run on two independent computers.
Each of them can be made redundant providing maximum availability. The OS
clients computers can run the Batch Client application and look at both OS Server
and Batch Server seamlessly. If necessary the OS Client and Batch Client
application can also run on separate computers.
Notes
Field Bus components, racks, modules and Field devices are not listed
1. PCS 7 BOX 416 requires 24 VDC Power Supply (not listed)
System Bus
1 6GK5 2080BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
1 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (3
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. Initial number of units may be selected higher, optional Power packs available
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
5 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
2 6ES7 654-1TE58-0XX0 CONTROLLER AS416-3IE, AC120/230V10A, 4MB (3
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Initial number of units may be selected higher, optional Power packs available
6. Monitor for engineering and maintenance only
Terminal Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required if a redundant System Bus network is selected
2. Required if a redundant Terminal Bus is selected
3. Initial number of POs may be selected higher, optional Power packs available
4. Required if redundant System Bus or redundant Automation System is
selected
5. Scalance switch requires 24VDC power supply (not listed)
6. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
7. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
8. Initial number of units may be selected higher, optional Power packs available
9. Additional network cards required for redundancy switch-over
10. Monitor for engineering and maintenance only
Batch Server
2 6ES7 650-0LH07-0YX0 COMPUTER PCS 7 OS SERVER IL43 BCE SRV/03 P4 (7
2 LCD MONITOR, 19” (8
2 6ES7 648-0CB00-0YA0 KEYBOARD SIMATIC PC INTNAL, USB (G)
2 6ES7 900-0BA00-0XA0 POWER CABLE US, 3 M
SOFTWARE SIMATIC BATCH
2 6ES7 657-0SA07-0YB0 (6
BASIC PACKAGE 10 UNITS
2 6ES7 657-0FX07-2YB0 SOFTWARE SIMATIC BATCH HIERARCHICAL RECIPE
SOFTWARE SIMATIC BATCH
2 6ES7 657-0GX07-2YB0
ROP LIBRARY
SOFTWARE SIMATIC BATCH
2 6ES7 657-0HX07-2YB0
SEPARATION PROCEDURE FORMULA
Terminal Bus
1 6GK5 414-3FC00-2AA2 SWITCH MODULAR 1EX414-3E 10/100/1000MB (3
2 6GK5 204-2BB00-2AA3 SCALANCE X204-2, MANAGED IE (3
3 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 414-3FC00-2AA2 SWITCH MODULAR 1EX414-3E 10/100/1000MB (3
1 6GK5 204-2BB00-2AA3 SCALANCE X204-2, MANAGED IE (3
2 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
9 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
2 6ES7 654-2PE67-0XC0 AS417-2H; AC10A W/RED. PS OPT; 2x9 SLOT RACK (4
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (5
2 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (5
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required for redundant Automation System
2. Initial number of POs may be selected higher or lower, optional Power packs
available
3. Scalance switch requires 24VDC power supply (not listed)
4. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
5. AS PO RT License expanded to total 3000 PO based on, 600 PO included in
ES, 100 PO included in each AS
6. Initial number of units may be selected higher, optional Power packs available
7. Second Network card used for redundancy switch-over
8. Monitor for engineering and maintenance only
Single Station
The smallest system that supports all Route Control functions is the Single Station
System. Route Control Engineering, Server and Client functionality are
concentrated in one computer and run in parallel with the Operator System.
Client-Server
Medium size systems that support multiple users and do not require redundancy
are implemented with Client-Server systems. SIMATIC Route Control follows the
Operator System architecture seamlessly by distribution of Route Control Server
and Client applications on the equivalent Operator System Computers.
Client-Server Redundant
If redundancy is required and the number of servers must be kept at a minimum,
SIMATIC Route Control allows deployment of a redundant Route Control Server on
the both of the redundant Operator System Server computers.
Client-Multi-Server Redundant
For large and high-performance applications the SIMATIC PCS 7 Client-Server
architecture allows for distribution of applications on multiple computer platforms.
In this case the Route Control Server and OS Server run on two independent
computers. Each of them can be made redundant providing maximum availability.
The OS clients computers can run the Route Control Client application and look at
both OS Server and Route Control Server seamlessly. If necessary the OS Client
and Route Control Client application can also run on separate computers.
System Bus
1 6GK5 2080BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
1 6ES7 654-1KF58-0XX0 CONTROLLER AS416-3, AC120/230V10A, 8MB (3
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3 Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
4. Initial number of active Routes may be selected higher, optional Power packs
available
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
5 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
2 6ES7 654-1KF58-0XX0 CONTROLLER AS416-3, AC120/230V10A, 8MB (3
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Initial number of active Routes may be selected higher, optional Power packs
available
6. Monitor for engineering and maintenance only
Terminal Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System Redundant
AS417-2H; AC10A W/RED. PS OPT; 2x9
1 6ES7 654-2PE67-0XC0 (7
SLOT RACK;
3 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (6
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (6
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required if a redundant System Bus network is selected
2. Required if a redundant Terminal Bus is selected
3. Initial number of POs may be selected higher, optional Power packs available
4. Required if redundant System Bus or redundant Automation System is
selected
5. Scalance switch requires 24VDC power supply (not listed)
6. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
7. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
8. Initial number of active Routes may be selected higher, optional Power packs
available
9. Monitor for engineering and maintenance only
Terminal Bus
1 6GK5 414-3FC00-2AA2 SWITCH MODULAR 1EX414-3E 10/100/1000MB (3
2 6GK5 204-2BB00-2AA3 SCALANCE X204-2, MANAGED IE (3
3 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 414-3FC00-2AA2 SWITCH MODULAR 1EX414-3E 10/100/1000MB (3
1 6GK5 204-2BB00-2AA3 SCALANCE X204-2, MANAGED IE (3
2 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
9 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
2 6ES7 654-2PE67-0XC0 AS417-2H; AC10A W/RED. PS OPT; 2x9 SLOT RACK (4
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (5
2 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (5
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required for redundant Automation System
2. Initial number of POs may be selected higher or lower, optional Power packs
available
3. Scalance switch requires 24VDC power supply (not listed)
4. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
5. AS PO RT License expanded to total 3000 PO based on, 600 PO included in
ES, 100 PO included in each AS
6. Initial number of units may be selected higher, optional Power packs available
7. Monitor for engineering and maintenance only
SIMATIC PDM
Configuration of HART, Profibus PA and Profibus DP devices, based on the open
EDDL (Electronic Device Description Language) is easy by means of the Process
Device Manager or SIMATIC PDM. SIMATIC PDM also is the basis for diagnostics
and asset management functionality and is fully integrated in the SIMATIC PCS 7
Engineering and Operator System.
Stand-alone
If full integration of SIMATIC PDM is not required then the stand-alone version can
be installed on a standard computer and connected to the Profibus DP Field Bus.
With this setup engineering and maintenance tasks on any HART, Profibus PA and
Profibus DP device can be performed.
Workshop Setup
If the usage of PDM is limited to parameterization of instruments in a workshop
then connection to a DP/PA coupler provides easy access to individual Field
Devices.
Starter System
The fully integrated version of SIMATIC PDM can be deployed in the system that is
an economical solution for as few as 100 Inputs and Outputs. All engineering and
maintenance functionality is available through seamless connectivity to HART,
Profibus PA and Profibus DP devices that are connected to the SIMATIC PCS 7
BOX 416 system.
Single Station
When deployed in a Single Station Engineering and Operator System, PDM is
connected to Field Devices via the Ethernet System Bus and the routing
functionality of the Automation System.
Client-Server
For medium and large size systems, with or without redundant Servers, PDM is
installed on the Engineering System and connects to Field Devices via the
Ethernet System Bus and the routing functionality of the Automation System.
Notes
SIMATIC PCS 7 Single Station System is not listed
Field Bus components, racks, modules and Field devices are not listed
1. For Desktop PC system use CP5611 A2 (listed as optional)
Notes
Field Bus components (except DP/PA Coupler), racks, modules and Field devices
are not listed
1. For Desktop PC system use CP5611 A2 (listed as optional)
2. FDC 157-0 DP/PA Coupler requires 24 VDC Power Supply (not listed)
Notes
Field Bus components, racks, modules and Field devices are not listed
1. PCS 7 BOX 416 requires 24 VDC Power Supply
2. Number of Tags can be increased, optional Power packs available
System Bus
1 6GK5 2080BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE, AC120/230V10A,
1 6ES7 654-1TE58-0XX0 (3
4MB
COMMUNICATION PROCESSOR
1 6GK7 443-5DX04-0XE0
PROFIBUS CP443-5 EXTENDED
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. Initial number of units may be selected higher, optional Power packs available
5. Number of Tags can be increased, optional Power packs available
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
5 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE, AC120/230V10A,
2 6ES7 654-1TE58-0XX0 (3
4MB
COMMUNICATION PROCESSOR
2 6GK7 443-5DX04-0XE0
PROFIBUS CP443-5 EXTENDED
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Initial number of units may be selected higher, optional Power packs available
6. Number of Tags can be increased, optional Power packs available
7. Monitor for engineering and maintenance only
System Bus
SWITCH MANAGED IE X208
1 6GK5 208-0BA00-2AA3 (1
10/100MBIT/S
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
1 6GK1 411-5AB00 IE/PB LINK MODULE (3
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Scalance switch requires 24VDC power supply (not listed)
2. Number of Tags can be increased, optional Power packs available
3. IE/PB Module requires 24VDC power supply (not listed)
Client-Server System
The Central Archive Server always runs on a separate computer and the PCS 7
hardware used is the same as for the OS Server. All OS Clients can gather data
from the Central Archive Server seamlessly, e.g. there is no difference in looking at
data from the OS Server or from the Central Archive Server.
Terminal Bus
SWITCH MANAGED IE X208
1 6GK5 208-0BA00-2AA3 (2
10/100MBIT/S
5 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
SWITCH MANAGED IE X208
(2
1 6GK5 208-0BA00-2AA3 10/100MBIT/S
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE,
2 6ES7 654-1TE58-0XX0 (3
AC120/230V10A, 4MB
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Number of Variables can be increased, optional Power packs available
6. Monitor for engineering and maintenance only
Terminal Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
AS417-2H; AC10A W/RED. PS OPT; 2x9
1 6ES7 654-2PE67-0XC0 (7
SLOT RACK;
3 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (6
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (6
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required if a redundant System Bus network is selected
2. Required if a redundant Terminal Bus is selected
3. Initial number of POs may be selected higher, optional Power packs available
4. Required if redundant System Bus or redundant Automation System is
selected
5. Scalance switch requires 24VDC power supply (not listed)
6. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
7. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
8. Number of Variables can be increased, optional Power packs available
9. Monitor for engineering and maintenance only
Engineering System
Required Optional Product Number Product Description Notes
COMPUTER PCS 7 ES/OS IL43 IE WXP
1 6ES7 650-0LF07-0YX1
3.4GHZ
1 LCD MONITOR, 19"
1 6ES7 648-0CB00-0YA0 KEYBOARD SIMATIC PC INTNAL, USB (G)
1 6ES7 900-0BA00-0XA0 POWER CABLE US, 3 M
SOFTWARE PCS 7 ENG V7. AS/OS UNL
1 6ES7 658-5AF07-0YA5
600 AS RT
1 6GK1 161-3AA01 SIMATIC NET, CP1613 A2 (1
1 6GK1 716-0HB64-3AC0 SIMATIC NET, REDCONNECT UPGRADE (4
COMPUTER 2 NETWORK CRDSRED
1 6ES7 652-0XX01-1XF0 (2
TERMINALBUS
1 6ES7 652-0XD07-2YB5 SOFTWARE PCS 7 SFC VISUALIZATION
1 6ES7 658-1CX07-2YA5 SIMATIC VERSION CROSS MANAGER
1 6ES7 658-1FX07-2YA5 SIMATIC VERSION TRAIL
1 6ES7 658-1DX07-2YB5 IMPORT/EXPORT ASSISTANT
Terminal Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
AS417-2H; AC10A W/RED. PS OPT; 2x9
1 6ES7 654-2PE67-0XC0 (7
SLOT RACK;
3 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (6
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (6
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required if a redundant System Bus network is selected
2. Required if a redundant Terminal Bus is selected
3. Initial number of POs may be selected higher, optional Power packs available
4. Required if redundant System Bus or redundant Automation System is
selected
5. Scalance switch requires 24VDC power supply (not listed)
6. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
7. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
8. Number of Variables can be increased, optional Power packs available
9. Monitor for engineering and maintenance only
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
5 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE, AC120/230V10A,
2 6ES7 654-1TE58-0XX0 (3
4MB
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Monitor for engineering and maintenance only
Starter System
The SIMATIC PCS 7 BOX 416 system supports Engineering, Operator System and
full Asset Management functionality for all its connected Field Devices, integrated
Automation System and computer.
Single Station
Connected via an Ethernet System Bus, Engineering, Operator System and Asset
Management functionality are concentrated on a SIMATIC PCS 7 Single Station
System. Asset Management delivers diagnostics and maintenance of all connected
Field Devices, Automation System components, Active Networking components
and computers.
Client-Server (Redundant)
In a Client-Server architecture the Asset Management system follows SIMATIC
PCS 7 distributed Client-Server structure. The Asset Management System uses
standard PCS 7 OS display and alarming. The Maintenance Server functionality is
integrated in the OS Server and no additional computer is needed. The OS Clients
can access the Maintenance Screens like standard PCS 7 process pictures. For
detailed diagnostics and trouble shooting of intelligent field devices the Asset
Management System provides additional information on the Maintenance System.
Notes
Field Bus components, racks, modules and Field devices are not listed
1. PCS 7 BOX 416 requires 24 VDC Power Supply
2. Number of PDM Tags can be increased, optional Power packs available
3. Number of Asset Tags can be increased, optional Power packs available
System Bus
SWITCH MANAGED IE X208
1 6GK5 2080BA00-2AA3 (2
10/100MBIT/S
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE,
1 6ES7 654-1TE58-0XX0 (3
AC120/230V10A, 4MB
6GK7 443-5DX04- COMMUNICATION PROCESSOR
1
0XE0 PROFIBUS CP443-5 EXTENDED
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. Initial number of units may be selected higher, optional Power packs available
5. Number of Tags can be increased, optional Power packs available
6. Number of Asset Tags can be increased, optional Power packs available
System Bus
1 6GK5 2080BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE,
1 6ES7 654-1TE58-0XX0
AC120/230V10A, 4MB
COMMUNICATION PROCESSOR
1 6GK7 443-5DX04-0XE0
PROFIBUS CP443-5 EXTENDED
Terminal Bus
SWITCH MANAGED IE X208
1 6GK5 208-0BA00-2AA3 (2
10/100MBIT/S
5 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
SWITCH MANAGED IE X208
(2
1 6GK5 208-0BA00-2AA3 10/100MBIT/S
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE,
2 6ES7 654-1TE58-0XX0 (3
AC120/230V10A, 4MB
COMMUNICATION PROCESSOR
2 6GK7 443-5DX04-0XE0
PROFIBUS CP443-5 EXTENDED
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. AS PO RT License expanded to total 1000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Initial number of units may be selected higher, optional Power packs available
6. Number of Tags can be increased, optional Power packs available
7. Monitor for engineering and maintenance only
8. Number of Asset Tags can be increased, optional Power packs available
Terminal Bus
SWITCH MANAGED IE X208
1 6GK5 208-0BA00-2AA3
10/100MBIT/S
5 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
SWITCH MANAGED IE X208
1 6GK5 208-0BA00-2AA3 10/100MBIT/S
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE,
2 6ES7 654-1TE58-0XX0
AC120/230V10A, 4MB
COMMUNICATION PROCESSOR
2 6GK7 443-5DX04-0XE0
PROFIBUS CP443-5 EXTENDED
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
5 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE, AC120/230V10A,
2 6ES7 654-1TE58-0XX0 (3
4MB
COMMUNICATION PROCESSOR
2 6GK7 443-5DX04-0XE0
PROFIBUS CP443-5 EXTENDED
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. AS PO RT License expanded to total 1000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Initial number of units may be selected higher, optional Power packs available
6. Number of Tags can be increased, optional Power packs available
7. Monitor for engineering and maintenance only
8. Asset Runtime Notes:
- Number of Asset Tags can be increased, optional Power packs available
- Increase in Asset Tags requires increase in AS and OS RT Process
objects for the Maintenance Server
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S
5 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE, AC120/230V10A,
2 6ES7 654-1TE58-0XX0
4MB
COMMUNICATION PROCESSOR
2 6GK7 443-5DX04-0XE0
PROFIBUS CP443-5 EXTENDED
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100
ET200M
ET200M WITH HOT SWAPPING
1 6ES7 654-0XX07-1XA0 (3
CAPABILITY
DIAGNOSTICS REPEATER
1 6ES7 972-0AB01-1XA0 RS485 DIAGNOSTICS REPEATER (3
DP/PA LINK
1 6ES7 157-0AC83-0XA0 DP/PA COUPLER FDC 157-0 (5
IM153-2 MODULE FOR DP/PA LINK
1 6ES7 153-2BA81-0XB0 AND Y-LINK, EXTENDED (4
TEMPERATURE RANGE
PROFILE RAIL FOR HOT SWAPPING
1 6ES7 195-1GA00-0XA0 (6
LENGTH 19 INCHES
BUS MODULE FOR PS AND ONE
1 6ES7 195-7HA00-0XA0
IM153-2 HIGH FEATURE MODULE
BUS MODULE FOR ONE DP/PA
1 6ES7 195-7HF80-0XA0
COUPLER FDC 157-0
DP/FF LINK
DP/FF LINK BUNDLE, SUPPORTS 4
1 6DL4 400-1AA FOUNDATION FIELD BUS H1 (7
SEGMENTS
Notes
IO Modules, Bus Modules for IO Modules, Network Cable and Connectors have
not been listed
1. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
2. CP443-5 Extended Notes:
3. Max. number of Profibus Slaves per Master 125 (Typical 30-80)
4. Max. number of slaves per segment 32, segments are separated by
(Diagnostics) Repeaters
5. ET200M, IM 153-2, Diagnostics Repeater require 24VDC Power Supply (not
listed)
6. Max. 48 Field Devices per DP/PA Link, IM 153-2 requires 24VDC Power
Supply (not listed)
7. FDC 157-0 Notes:
8. Max. 5 FDC 157-0 DP/PA Couplers in one DP/PA Link
9. Max. 31 Field Devices per FDC 157-0. (Typical 20-25)
10. Max. Current provided by FDC 157-0 is 1000 mA
11. Max. PA Segment length is 1900 m (Typically 500-1000 m)
12. Longer lengths are available
13. Max. 64 Field Devices per DP/FF Link (Typical 20-30)
ET200M
ET200M WITH HOT SWAPPING
1 6ES7 654-0XX07-1XA0 (3
CAPABILITY
DP/PA LINK
1 6ES7 157-0AC83-0XA0 DP/PA COUPLER FDC 157-0 (5
IM153-2 MODULE FOR DP/PA LINK AND Y-
1 6ES7 153-2BA81-0XB0 (4
LINK, EXTENDED TEMPERATURE RANGE
PROFILE RAIL FOR HOT SWAPPING
1 6ES7 195-1GA00-0XA0 (6
LENGTH 19 INCHES
BUS MODULE FOR PS AND ONE IM153-2
1 6ES7 195-7HA00-0XA0
HIGH FEATURE MODULE
BUS MODULE FOR ONE DP/PA COUPLER
1 6ES7 195-7HF80-0XA0
FDC 157-0
DP/FF LINK
DP/FF LINK BUNDLE, SUPPORTS 4
1 6DL4 400-1AA (7
FOUNDATION FIELD BUS H1 SEGMENTS
Notes
IO Modules, Bus Modules for IO Modules, Optical and Electrical Network Cable
and Connectors have not been listed
1. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
2. CP443-5 Extended Notes:
- Max. number of Profibus Slaves per Master 125 (Typical 30-80)
- Max. number of slaves per segment 32, segments are separated by
(Diagnostics) Repeaters
3. ET200M, IM 153-2, Diagnostics Repeater require 24VDC Power Supply (not
listed)
4. Max. 48 Field Devices per DP/PA Link, IM 153-2 requires 24VDC Power
Supply (not listed)
5. FDC 157-0 Notes:
- Max. 5 FDC 157-0 DP/PA Couplers in one DP/PA Link
- Max. 31 Field Devices per FDC 157-0. (Typical 20-25)
- Max. Current provided by FDC 157-0 is 1000 mA
- Max. PA Segment length is 1900 m (Typically 500-1000 m)
6. Longer lengths are available
7. Max. 64 Field Devices per DP/FF Link (Typical 20-30)
8. OLM/G12 implements a fault tolerant Optical Profibus DP Ring. OLM/G12
requires 24 VDC Power Supply (not listed)
ET200M
IM 153-2 REDUNDANCY BUNDLE, ET200M
1 6ES7 153-2AR02-0XA0 (3
WITH HOT SWAPPING CAPABILITY
Y-LINK
Y-LINK, NETWORK TRANSITION FROM
1 6ES7 197-1LA10-0XA0 (3
REDUNDANT TO SINGLE PROFIBUS DP
DIAGNOSTICS REPEATER
2 6ES7 972-0AB01-0XA0 RS485 DIAGNOSTICS REPEATER (3
DP/PA LINK
2 6ES7 157-0AC83-0XA0 DP/PA COUPLER FDC 157-0 (5
IM153-2 MODULE FOR DP/PA LINK AND Y-
2 6ES7 153-2BA81-0XB0 (4
LINK, EXTENDED TEMPERATURE RANGE
PROFILE RAIL FOR HOT SWAPPING
1 6ES7 195-1GA00-0XA0 (6
LENGTH 19 INCHES
BUS MODULE FOR REDUNDANT IM153-2
1 6ES7 195-7HD80-0XA0
HIGH FEATURE MODULE
BUS MODULE FOR TWO DP/PA
1 6ES7 195-7HG80-0XA0
COUPLERS FDC 157-0
2 6ES7 157-0AF81-0XA0 ACTIVE FIELD DISTRIBUTOR
Notes
IO Modules, Bus Modules for IO Modules, Network Cable and Connectors have
not been listed
1. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
2. CP443-5 Extended Notes:
- Max. number of Profibus Slaves per Master 125 (Typical 30-80)
- Max. number of slaves per segment 32, segments are separated by
(Diagnostics) Repeaters
3. ET200M, IM 153-2, Y-LINK and Diagnostics Repeater require 24VDC Power
Supply (not listed)
4. Max. 48 Field Devices per DP/PA Link, IM 153-2 requires 24VDC Power
Supply (not listed)
5. FDC 157-0 Notes:
- Max. One pair of redundant FDC 157-0 per DP/PA Link and 3 single FDC
157-0
- Max. 31 Field Devices per redundant pair of FDC 157-0. (Typical 20-25)
- Max. Current provided by FDC 157-0 is 1000 mA
- Max. PA Segment length is 1900 m (Typically 500-1000 m)
6. Longer lengths are available
7. Max. 64 Field Devices per DP/FF Link (Typical 20-30)
ET200M
IM 153-2 REDUNDANCY BUNDLE, ET200M
1 6ES7 153-2AR02-0XA0 (3
WITH HOT SWAPPING CAPABILITY
Y-LINK
Y-LINK, NETWORK TRANSITION FROM
1 6ES7 197-1LA10-0XA0 (3
REDUNDANT TO SINGLE PROFIBUS DP
DP/PA LINK
2 6ES7 157-0AC83-0XA0 DP/PA COUPLER FDC 157-0 (5
IM153-2 MODULE FOR DP/PA LINK AND Y-
2 6ES7 153-2BA81-0XB0 (4
LINK, EXTENDED TEMPERATURE RANGE
PROFILE RAIL FOR HOT SWAPPING
1 6ES7 195-1GA00-0XA0 (6
LENGTH 19 INCHES
BUS MODULE FOR REDUNDANT IM153-2
1 6ES7 195-7HD80-0XA0
HIGH FEATURE MODULE
BUS MODULE FOR TWO DP/PA
1 6ES7 195-7HG80-0XA0
COUPLERS FDC 157-0
2 6ES7 157-0AF81-0XA0 ACTIVE FIELD DISTRIBUTOR
Notes
IO Modules, Bus Modules for IO Modules, Optical and Electrical Network Cable
and Connectors have not been listed
1. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
2. CP443-5 Extended Notes:
- Max. number of Profibus Slaves per Master 125 (Typical 30-80)
- Max. number of slaves per segment 32, segments are separated by
(Diagnostics) Repeaters
3. ET200M, IM 153-2, Diagnostics Repeater require 24VDC Power Supply (not
listed)
4. Max. 48 Field Devices per DP/PA Link, IM 153-2 requires 24VDC Power
Supply (not listed)
5. FDC 157-0 Notes:
- Max. 5 FDC 157-0 DP/PA Couplers in one DP/PA Link
- Max. 31 Field Devices per FDC 157-0. (Typical 20-25)
- Max. Current provided by FDC 157-0 is 1000 mA
- Max. PA Segment length is 1900 m (Typically 500-1000 m)
6. Longer lengths are available
7. Max. 64 Field Devices per DP/FF Link (Typical 20-30)
8. OLM/G12 implements a fault tolerant Optical Profibus DP Ring. OLM/G12
requires 24 VDC Power Supply (not listed)
Star Topologies
The robust SCALANCE network components, active and managed switches, can
be used to create cost-effective network topologies providing connectivity to large
numbers of nodes.
Electrical X200
Required Optional Product Number Product Description Notes
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (1
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Optical X200
2 6GK5 204-2BB00-2AA3 SCALANCE X204-2, MANAGED IE (1
1 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Electrical X400
SWITCH MODULAR 1EX414-3E
1 6GK5 414-3FC00-2AA2 (1
10/100/1000MB
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Optical X400
SWITCH MODULAR 1EX414-3E
1 6GK5 414-3FC00-2AA2 (1
10/100/1000MB
MM491 MEDIA MODULE, MULTI-MODE FO
1 6GK5 491-2AB00-8AA2
CABLE UP TO 3KM
1 6GK5 204-2BB00-2AA3 SCALANCE X204-2, MANAGED IE (1
1 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Automation System and Operator System components are not listed
1. Scalance switch requires 24VDC power supply (not listed)
System Bus
SWITCH MODULAR 1EX414-3E
1 6GK5 414-3FC00-2AA2 (1
10/100/1000MB
MM491 MEDIA MODULE, MULTI-MODE FO
1 6GK5 491-2AB00-8AA02
CABLE UP TO 3KM
1 6GK5 204-2BB00-2AA3 SCALANCE X204-2, MANAGED IE (1
3 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
6 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Automation System and Operator System components are not listed
1. Scalance switch requires 24VDC power supply (not listed)
System Bus
SWITCH MODULAR 1EX414-3E
1 6GK5 414-3FC00-2AA2 (1
10/100/1000MB
2 6GK5 204-2BB00-2AA3 SCALANCE X204-2, MANAGED IE (1
8 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Automation System and Operator System components are not listed
1. Scalance switch requires 24VDC power supply (not listed)
System Bus
SWITCH MODULAR 1EX414-3E
2 6GK5 414-3FC00-2AA2 (1
10/100/1000MB
MM491 MEDIA MODULE, MULTI-MODE FO
2 6GK5 491-2AB00-8AA2
CABLE UP TO 3KM
2 6GK5 204-2BB00-2AA3 SCALANCE X204-2, MANAGED IE (1
4 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
8 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Automation System and Operator System components are not listed
1. Scalance switch requires 24VDC power supply (not listed)
System Bus
SWITCH MODULAR 1EX408-2
3 6GK5 408-2FD00-2AA2 (1
10/100/1000MB
3 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
6 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Automation System and Operator System components are not listed
1. Scalance switch requires 24VDC power supply (not listed)
Client-Server
Medium to large systems are implemented by combining standard and Safety
Automation Systems connected to an Operator System Server. The Engineering
and Operation and Monitoring functions are distributed across the Engineering and
Operator System Computers.
Client-Server Redundant
High availability of Operation, Monitoring and Automation System functionality is
provided by redundant Operator System Servers and High Availability Automation
Systems.
System Bus
SWITCH MANAGED IE X208
1 6GK5 2080BA00-2AA3 (2
10/100MBIT/S
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS414-4H,
1 6ES7 654-2MD57-0XX0 (3
AC120/230V10A,2MB
SOFTWARE ENG S7400F FAILSAFE F-
1 6ES7 833-1CC00-6YX0
RUNTIME LICENSE
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 414-4H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
Terminal Bus
SWITCH MANAGED IE X208
1 6GK5 208-0BA00-2AA3 (2
10/100MBIT/S
5 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
SWITCH MANAGED IE X208
(2
1 6GK5 208-0BA00-2AA3 10/100MBIT/S
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS417-4H,
2 6ES7 654-2RE57-0XX0 (3
AC120/230V10A,2MB
SOFTWARE ENG S7400F
2 6ES7 833-1CC00-6YX0
FAILSAFE F-RUNTIME LICENSE
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 417-4H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
4. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Monitor for engineering and maintenance only
Terminal Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (5
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required if a redundant System Bus network is selected
2. Required if a redundant Terminal Bus is selected
3. Initial number of POs may be selected higher, optional Power packs available
4. Required if redundant System Bus or redundant Automation System is
selected
5. Scalance switch requires 24VDC power supply (not listed)
6. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
7. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
8. Monitor for engineering and maintenance only
Small System
For smaller systems a cost-effective combination of OpenPCS 7 and SIMATIC
PCS 7 Operator System Client functionality is offered.
Large System
For high performance and large applications OpenPCS 7 runs on its own dedicated
computer, providing access to all data available on multiple redundant SIMATIC
PCS 7 Operator System Server and Central Archive Server systems.
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
5 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE, AC120/230V10A,
2 6ES7 654-1TE58-0XX0 (3
4MB
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
Enterprise network switch and cables are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Monitor for engineering and maintenance only
6. Enterprise Network connection
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
3 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE, AC120/230V10A,
1 6ES7 654-1TE58-0XX0 (3
4MB
3 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
Enterprise network switch and cables are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
4. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
5. Monitor for engineering and maintenance only
6. Enterprise Network connection
Terminal Bus
SWITCH MANAGED IE X208
2 6GK5 208-0BA00-2AA3 (5
10/100MBIT/S
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
SWITCH MANAGED IE X208
2 6GK5 208-0BA00-2AA3 (5
10/100MBIT/S
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required if a redundant System Bus network is selected
2. Required if a redundant Terminal Bus is selected
3. Initial number of POs may be selected higher, optional Power packs available
4. Required if redundant System Bus or redundant Automation System is
selected
5. Scalance switch requires 24VDC power supply (not listed)
6. AS PO RT License expanded to total 3000 PO based on, 600 PO included in
ES, 100 PO included in each AS
7. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
8. Number of Variables can be increased, optional Power packs available
9. Monitor for engineering and maintenance only
10. Enterprise Network connection
Client-Server 2000 PO
For Client-Server applications SIMATIC PCS 7 offers an Engineering System with
unlimited Process Objects for engineering and testing purposes. The number of
Automation System Process Objects is licensed by means of the addition of Power
packs. The number of Operator System Process Objects is licensed by the
appropriate Operator System Server license. Operator System Clients do not
require Process Object licensing and can access all Process Objects of the
connected Operator System Servers.
Multi-Server 5000 PO
Systems consisting of multiple Operator System Servers allow distribution of
Process Objects across multiple Servers. When multiple Engineering Systems are
deployed the SIMATIC PCS 7 requires the Automation System Process Objects to
be licensed only once.
Notes
Field Bus components, racks, modules and Field devices are not listed
1. PCS 7 BOX 416 requires 24 VDC Power Supply
System Bus
1 6GK5 2080BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (2
2 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE, AC120/230V10A,
1 6ES7 654-1TE58-0XX0 (3
4MB
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Initial number of POs may be selected higher, optional Power packs available
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
Terminal Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (1
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
1 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (1
4 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
CONTROLLER AS416-3IE, AC120/230V10A,
2 6ES7 654-1TE58-0XX0 (2
4MB
2 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (3
1 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (3
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Scalance switch requires 24VDC power supply (not listed)
2. AS 416-3IE Automation System listed requires 110/220 VAC Power Supply,
AS with 24VDC Power is available
3. AS PO RT License expanded to total 2000 PO based on, 600 PO included in
ES, 100 PO included in each AS
4. Monitor for engineering and maintenance only
Terminal Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (4
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
2 6GK5 208-0BA00-2AA3 SWITCH MANAGED IE X208 10/100MBIT/S (4
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required if a redundant System Bus network is selected
2. Required if a redundant Terminal Bus is selected
3. Required if redundant System Bus or redundant Automation System is
selected
4. Scalance switch requires 24VDC power supply (not listed)
5. AS PO RT License expanded to total 3000 PO based on, 600 PO included in
ES, 100 PO included in each AS
6. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
7. Monitor for engineering and maintenance only
Terminal Bus
SWITCH MODULAR 1EX414-3E
1 6GK5 414-3FC00-2AA2 (2
10/100/1000MB
1 6GK5 204-2BB00-2AA3 SCALANCE X204-2, MANAGED IE (2
3 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
9 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
System Bus
SWITCH MODULAR 1EX414-3E
1 6GK5 414-3FC00-2AA2 (2
10/100/1000MB
1 6GK5 204-2BB00-2AA3 SCALANCE X204-2, MANAGED IE (2
2 6XV1 820-5BN10 CABLE F/O W/4 BFOC 10 M
10 6XV1 870-3QH60 CABLE IE TP CORD RJ45/RJ45 6 M
Automation System
AS417-2H; AC10A W/RED. PS OPT; 2x9
2 6ES7 654-2PE67-0XC0 (3
SLOT RACK
6 6ES7 653-2BA07-0XB0 SOFTWARE PCS 7 RT PO 100 (4
3 6ES7 653-2BB07-0XB0 SOFTWARE PCS 7 RT PO 1000 (4
Notes
Field Bus components, racks, modules and Field devices are not listed
1. Required for redundant Automation System
2. Scalance switch requires 24VDC power supply (not listed)
3. AS 417-2H Automation System listed requires 110/220 VAC Power Supply, AS
with 24VDC Power is available
4. AS PO RT License expanded to total 5000 PO based on, 600 PO included in
each ES, 100 PO included in each AS
5. Monitor for engineering and maintenance only