Beruflich Dokumente
Kultur Dokumente
REVISION NO : P0
DATE OF ISSUE (MONTH/YEAR) : 24.09.2018
TOTAL NO OF PAGES (Including Cover
: 33
Sheet)
DESIGN BASIS REPORT FOR CABLING SYSTEM FOR 400kV & 230kV SWITCHYARDS
AND BoP ELECTRICALAREAS OF KKNPP 3&4 - EPC PACKAGE
M/s BGR ESL
Name Signature & Date
PREPARED &
CHECKED BY
Vijayakumar K 24.09.2018
NPCIL
Name Signature & Date
CHECKED BY
REVIEWED BY
DOCUMENT TYPE: BS
& CONCURRED BY
APPROVED BY
APPROVED BY
REVIEWED BY
REV DESCRIPTI
CHECKED BY
CHECKED BY
REVISED BY
No. ON OF
REVIEWED
DATE REVISION
TABLE OF CONTENTS
1. SCOPE
This design basis report is intended to cover the design of cabling including supply,
storage,laying / installation, testing and commissioning of MV & LV powercables, control
cablesincluding termination kits, glands, lugs, cable termination kits, hardwareaccessories,
fire barriers/stops, fire belts, fire resistant coating for cables, etc.required for completion of
cabling system works for KKNPP-3&4 Switchyard packages.
Also, this design includes supply, installation, testing and commissioning of cable carrier
system with all accessories, hardware, etc., required for safe installation.
It’s also includes selection of fire barriers/stops, fire belts, fire resistance coating on cables.
2. PURPOSE
This design basis is created to define the minimum requirements for the design, selection,
laying and termination of cables (MV & LV Power cables and Control cables) along with
cable carriers and its accessories and are read in conjunction with all other Project
specifications and the requirements of applicable codes, standards and regulations. The main
objectives are:
Proper sizing and selection of cables, cable tray supports & cable trays
Explain the philosophy adopted for selection of supports and trays
Explain the philosophy adopted for selection of cables
Explain the philosophy adopted for fire barrier and fire resistant coating
3. SYSTEM DESCRIPTION
The system consists of sizing and design for selection of MV & LV power cables, control
cables and all special cables like OFC cables, LAN cables, cable supports etc.The cables
shall be laid in above-ground cable trays as well as on supports in the underground trenches /
tunnels or on overhead trestles as per the requirement. Cables shall not be directly buried in
the ground. Wherever small lengths of cables exist which cannot be run on trestles, tunnels,
etc. the same shall be routed in RCC trenches.
The main cable routes between buildings (with large number of cables) in KKNPP-3&4shall
be provided through underground cable tunnels and cable routes with smaller number of
cables can be routed through covered trenches.
MV & LV Power cables shall be laid on top tier and control cables shall be laid below
power cable tray and instrumentation, OFC cables shall be laid on bottom most cables trays.
However for 230kV tie feeder from Unit – 1 & 2 to Unit - 3 & 4, 245kV EHV cable from
existing Unit – 1 & 2 shall be buried in ground initially to cross 400kV Substation of Unit –
1 & 2 till the 1st Transmission Line tower.
The following design parameters of the systems are considered for arriving at appropriate
type and size of cables,
Design criteria MV LV
Loads located beyond 1 kM Single core cable -
Loads located 200 – 1000 Single core / 3 Core
1 Core / 4 Core cable
M cable
Single core / 3 Core
Load located up to 200M 1 Core / 4 Core cable
cable
No. of cores for power
supply panel incomer - 5 (3Ph+1N+1PE)
cables
No. of cores for motor
- 4 (3Ph+1N)
cables
Loads beyond 1000A rating
and located near the Bus duct Bus duct
transformer
Recommended limiting size 300 (for 4/5 core cable)
630
of multi-core cable (mm2) 630 (for 1 core cable)
Recommended limiting size
300 (for 3 core cable) 300 (for 4/5 core cable)
of multi-core cable (mm2)
- Incomerfrom
transformer: 1
- Incomer from other
switchboard: 0.6
Short circuit withstand time
- Plant feeder: 0.6 Not Applicable
(seconds)
- Motor/Transformer
feeder: 0.2/higher
as decided during
detailing
Insulation voltage grade Unearthed Unearthed
Type of cable insulation XLPE PVC
Conductor materials Cu Cu
Vd = IRCos Ѳ + IXsin Ѳ
Where
The maximum voltage drops in various section of the electrical system under steady state
conditions at full load shall be within the limits and typical requirements are as per the
following table:
Maximum
Sl No System Description permissible
voltage drop
a) Cables between transformer secondary and 0.5 %
switchboards
b) LV Cables between PCC/PMCC and MCC or
Auxiliary switchboard
MCC/ASB located near PCC/PMC 0.5 %
MCC/ASB located remote from PCC/PMCC 2 to 2.5 %
c) MV Cable between MV switchboard and MV 3%
motor
d) LV Cables between PCC/PMCC and motor 5%
e) LV cables between MCC (situated near 5%
File Name: GID/379/EL/YYY/BS/3006 SEPTEMBER2018
NOT FOR UNAUTHORISED PUBLICATION / PRESENTATION OUTSIDE NPCIL
NUCLEAR POWER CORPORATION OF INDIA LTD.
PAGE NO. : Page 7 of 35
KUDANKULAM NUCLEAR POWER PROJECT-3&4
REV. NO : P0
DESIGN BASIS REPORT FOR CABLING SYSTEM
REV. DATE : 24.09.2018
The current carrying capacity of a cable corresponds to the maximum current that it can
carry under specified conditions without the conductors exceeding the permissible limit of
steady state temperature for the type of insulation concerned.
The current carrying capacity of the above Ground Installation and in RCC Trench / Tunnel
can be calculated as below:
C = Ca X Cg X Cd
Where
C = De-rating factor
Ca = Rating factor for variation in Ambient air temperature
Cg = Rating factor for Grouping of cables
Cd = Rating factor for variation in depth of cables
De-rating factor as obtained above multiplied by the cable current gives the effectivecurrent
carrying capacity of a cable.
Appropriate de-rating factors shall be used in sizing of the power cables depending on
thetype of laying of cables, either in ladder tray or cable ducts in concrete trenches, etc. If
theroute consists of different methods of laying the worst de-rating factor shall be used
forconsidering the design ambient temperature. Typical data given below for choice of de-
ratingfactors.
c) For cables in ladder type trays in concrete trenches without covers with 1 diameter spacing
0.800
d) For cables in ladder type trays in concrete trenches with covers with 1 diameter spacing
0.62
The above values are for reference only. For the sizing calculations however the data from
prospective vendor catalogue will be considered.
The cross sectional area calculated shall not be less than the value determined by the
following formula
𝐼 √𝑡
𝑆=
K
Where
S = Nominal cross sectional area of the conductor in mm2.
I = Value of fault current for a fault of negligible impedance in Amperes.
t = Operating time of the disconnecting device in seconds for fault current
– I as given below:
- (1.0 sec.) Incomer from Transformer
- (0.6 sec.) Interconnecting cables between two MV Switchboards
- (0.2 sec.) Motor/transformer breaker feeder
K = Protective factor for conductor taking account of the resistivity, temperature
Co-efficient, heatcapacity of the conductor material, initial and
finalTemperature.
- 115 and 143 for PVC and XLPE insulated Copper Cables
respectively.
Where the application of the formula results in a non-standard size, a conductor of the next
higher standard cross-section area shall be used.
𝑆 = 50000 x √1 / 143
𝑆 = 350 Sqmm
Next higher standard cross section of conductor is 400 mm2.
Minimum cable size used for 6kV incomer is 9 Runs of 1C x 400 mm2, XLPE, Cu. Cable.
Minimum cable size used for 6kV tie feeders is 9 Runs of 1C x 400 mm2, XLPE, Cu. Cable
runs between two MV Switchboards.
Proposed minimum cable size for 6kV Motors and Transformers is 3C x 185 mm2, XLPE,
Cu. Cable.
The cables shall be sized based on the type of usage, type of load, maximum
continuous load current, voltage drop, system voltage, system earthing and short
circuit withstand criteria as applicable. The de-rating, due to ambient air temperature
(40 degree centigrade as standard), ground temperature, grouping and proximity of
cables with each other, thermal resistivity of soil (if applicable), depth of laying, etc.
will be taken into account while sizing of the cable.
All power and control cables shall be in continuous lengths without any splices or
intermediate joints along the entire length.
All cables shall be flame retardant low smoke with low hydrogen chloride emission
(Maximum halogen content by weight will be referred from respective technical
specification).
Formatted: Indent: Left: 0.5", No bullets or
Fire resistant cables with three hour rating are used for the selected critical
systems/equipments.
LAN and Optical fibre cables shall be used as per requirements. Formatted: Font: Underline
Formatted: Indent: Left: 0.5", No bullets or
Fire proof coating over a bunch of cables installed on trays where volume of
combustible material in tray exceeds 7 liters per running meter of tray as per
IEC60332.
Formatted: Underline
Formatted: Indent: Left: 0.75", Bulleted + Level: 3 +
Aligned at: 1.5" + Indent at: 1.75"
Screened cables shall be used for the following systems / circuits: Formatted: Normal, Indent: Left: 0"
o Overall screening for VT Circuit
o Overall screening for electrical protection circuit
o Overall screening for communication system
o Overall screening for control cables when the system voltage is less than
220V.
o Additionally, individual core / pair shielding shall be provided for control
cable circuits with millivolt / mill ampere signals.
o In addition to the above requirements, shielding will be provided to suit the
selected equipment as per the system developer’s recommendations, to
ensure minimum permissible voltage drop or signal loss, as applicable / as
the case may be.
All control cables shall have at least 10% spare cores.
The conductor shall be solid for nominal area up to and including 6mm2 and
stranded beyond 6mm2. Conductors of nominal area less than 16mm2 shall be
circular. Conductors of nominal area 16mm2 and above may be circular or shaped.
Conductors in fire resistance (fire survival) cables shall also be circular.
MV Power Cables shall be steam cured / gas cured / electron beam cured cross-linked
polyethylene (XLPE) insulated, extruded of polyvinyl-chloride thermoplastic compound
(ST2 type) (inner and outer) sheathed with low hydrogen chloride emission, unarmored type
with copper. MV Power cable voltage rating U0/U (Um) 6/6 (7.2) kV, frequency 50 Hz and
above shall be provided with both conductor screening and insulation screening.
The inner and outer sheaths will have properties as mentioned below:
- Minimum critical oxygen index value at room temperature : 35
When tested as per ASTM-D-2863-77
- Minimum temperature index : 3000C
- Maximum halogen content (by weight) in sheaths material : 14 %
When tested as per IEC-60754-1
- Minimum light transmittance during smoke density test as per : 60 %
IEC-61034-2
Finished cables shall pass the flammability test as per IEC: 60332 Part-1 and Part-
III
Suitable for all climatic for macroclimatic regions on land and sea, except
macroclimatic regions with a very cold climate for indoor operation (inside enclosed
spaces) with elevated humidity
Cable voltage rating (U0/U) 6/6 kV frequency 50 Hz. Peak AC voltage of the power
cable is intended for – 7.2 kV.
Cable shall be single conductor or three conductor depending upon the application.
cable design is in compliance with the requirements of IEC 60502-2 Maximum
outside diameter, maximum permissible specific combustion heat, combustion mass
of polymer materials and design mass of PvVng(A)-LS type cables shall be as per
below table
1. Electric conductor
2. Semiconducting cross-linked compound screen
3. Insulation
4. Semiconducting cross-linked compound screen
5. Semiconducting tape
6. Copper wire screen
7. Copper binding tape
8. Inner sheath
File Name: GID/379/EL/YYY/BS/3006 SEPTEMBER2018
NOT FOR UNAUTHORISED PUBLICATION / PRESENTATION OUTSIDE NPCIL
NUCLEAR POWER CORPORATION OF INDIA LTD.
PAGE NO. : Page 13 of 35
KUDANKULAM NUCLEAR POWER PROJECT-3&4
REV. NO : P0
DESIGN BASIS REPORT FOR CABLING SYSTEM
REV. DATE : 24.09.2018
9. Thermal barrier
10. Outer sheath.
The cables shall be manufactured with copper conductors. Conductor shall be round,
compacted and comply with class2 as per IEC 60228
Cable insulation shall be made of cross-linked polyethylene (XLPE) as per IEC
60502-2
The “ng – LS” cable inner and outer sheaths shall be extruded of polyvinyl-chloride
thermoplastic compound (ST2 Type) as per IEC 60502-2 with low release of
hydrogen chloride. Maximum hydrogen chloride release shall not be more than 14%
The conductor screen, XLPE insulation and insulation screen shall be extruded in
one operation by “Triple Extrusion” process to ensure perfect bonding between the
layers. Curing shall be through continuous vulcanization (CV). Core identification
shall be by colored strips or printed numerals.
Heat Deformation
- Relative elongation after ageing for 175 -
15 min at (200+3) 0C and tensile
load of 0.2 N/mm2, %, Not more
than 15 -
- Relative elongation after the load
removal and cooling, %, not more
than
All electrical parameters of the cable shall be as per IEC 60502-2and fungi fouling
level shall not be more than two points during the test as per IEC 60068-2-10.
Inner and outer sheath – Oxygen index shall be 35% minimum and temperature
index 300 0C minimum
Cable service life shall be not less than 40 years
The allowable current load of cables shall correspond to the value provided in below
table
Correctional factor for current loads of PvVng (A)-LS Cables shall be as per below
table
The 6kV (UE) MV Power cables shall meet the Special requirements mentioned in
NPCIL Technical specification for MV Power cables (Cable type – PvVng(A)-LS),
Clause no. 6.2
6. LV POWER CABLES
LV Power Cablesshall be extruded of PVC compound (PVС/А type) with low hydrogen
chlorideemission, extruded of polyvinyl-chloride thermoplastic compound (ST1 type) (inner
andouter) sheathed with low hydrogen chloride emission, unarmored type with
copperconductors. LV power cable voltage rating U0/U (Um) 0.6/1 (1.2) kV frequency 50
Hzand above.
Finished cables shall pass the flammability test as per IEC: 60332 Part-1 and Part-III
and fire-resistant (fire survival) test as per IEC 60331-23
Suitable for all climatic for macroclimatic regions on land and sea, except macroclimatic
regions with a very cold climate for indoor operation (inside enclosed spaces) with
elevated humidity
Cables are to be manufactured for rated AC voltage (U0/U) 0.6/1 kV, 50 Hz frequency
or 2.4 kV DC voltage.
The design of screened and non-screened cables shall meet the requirements of IEC
60502-1, 2004.
The cables shall be manufactured with copper conductors. Conductors shall comply with
Class 1 or 2 as per IEC 60228.
The fire resistant (fire survival) cables ("ng - FRLS") shall be with circular conductor.
The fire resistant (fire survival) cables ("ng - FRLS") shall be provided with minimum
two layers of Glass Mica tapes, over conductors, with a minimum 30% overlapping of
individual tapes.
Cable insulation shall be of extruded PVC compound (PVС-А type) as per IEC 60502-1
with low hydrogen chloride emission.
Maximum hydrogen chloride emission during cable testing as per IEC 60754-1 shall not
exceed 15 %.
Nominal cable insulation thickness shall comply with the requirements of IEC 60502-1.
For all twisted insulated conductors of multi-conductor screened cables and insulated
conductor of single-conductor screened cable it is necessary to provide an inner extruded
sheath of polyvinylchloride polymer compound with low hydrogen chloride emission,
which shall fill the space between conductors of multi-conductor cable. Maximum
hydrogen chloride emission during PVC compound testing as per IEC 60754-1 shall not
exceed 14 %.
The inner sheath shall not weld with conductor insulation and during cable termination
shall freely separate from the conductor insulation without insulation damage.
The inner sheath thickness shall be not less than 1.0 mm.
A screen in the form of wrapped copper foil or copper strip with a rated thickness of not
less than 0.1 mm, with overlapping of at least 30 % shall be provided on top of the inner
sheath of the screened cable, which ensures the continuity of the screen at permissible
cable bending radius.
A bare copper wire of 0.4 mm diameter shall be provided longitudinally under the
screen as drain wire.
The elongation of Copper foil/ tape for screened cables shall not be less than 15%.
The cable outer sheath shall be extruded from PVC compound (ST1 type) as per IEC
60502-1 with low hydrogen chloride emission.
Maximum hydrogen chloride emission during PVC compound testing as per IEC 60754-
1 shall not exceed 14 %.
Nominal cable outer sheath thickness shall comply with the requirements of IEC 60502-
1.
Outside diameters, maximum permissible specific combustion heat and combustible
mass of cable polymer materials shall comply with the values provided in NPCIL
Technical specification for LV Power Cables, table 6.1.14.1& 6.1.14.2 ##
The physical-mechanical and chemical characteristics of LV Power cables as per below
table
Correctional factor for current loads of LV Power Cables shall be as per below table
Ambient temperature, оС
Design Standardized
6.4. S
ambient conductor
ptemperature, temperature, 5 10 15 20 25 30 35 40 45 50
e о
С о
С
c Correctional factor
i
25 70 1.2 1.15 1.11 1.05 1 0.94 0.88 0.81 0.74 0.67
a
l
Requirements
LV Power cables for a voltage below 0.6/1kV shall meet the Special requirements
mentioned in NPCIL Technical specification for LV Power cables (Cable type -
VVGng-FRLS &VVGEng-FRLS) and (Cable type – VVGng-LS &VVGEng-LS),
Clause no. 6.2 .
Implementation and operation condition requirements shall meet the NPCIL
Technical specification for LV Power cables (Cable type - VVGng-FRLS
&VVGEng-FRLS) and (Cable type – VVGng-LS &VVGEng-LS), Clause no. 6.4 .
7. CONTROL CABLES
Control Cable shall be extruded of PVC compound (PVС/А type) with low hydrogen
chloride emission, extruded of polyvinyl-chloride thermoplastic compound (ST1 type) (inner
and outer) sheathed sheath with low hydrogen chloride emission, unarmoured type with
copper conductors. Nominal alternating voltage of the control cables is not higher than 660
V of frequency not higher than 100 Hz or direct voltage is not higher than 1000 V.
alternative.
Outer sheath Extruded PVC
Suitable for all climatic for macroclimatic regions on land and sea, except
macroclimatic regions with a very cold climate for indoor operation (inside enclosed
spaces) with elevated humidity.
Nominal alternating voltage of the cables is not higher than 660 V of frequency not
higher than 100 Hz or direct voltage is not higher than 1000 V.
The design of screened and non-screened cables shall meet the requirements of IEC
60502-1, 2004.
The cables shall be manufactured with copper conductors. Conductors shall comply
with Class 1 or 2 as per IEC 60228.
The fire resistant (fire survival) cables ("ng - FRLS") shall be with circular
conductor.
The fire resistant (fire survival) cables ("ng - FRLS") shall be provided with
minimum two layers of Glass Mica tapes, over conductors, with a minimum 30%
overlapping of individual tapes.
Cable insulation shall be of extruded PVC compound (PVС-А type) as per IEC
60502-1 with low hydrogen chloride emission.
Maximum hydrogen chloride emission during cable testing as per IEC 60754-1 shall
not exceed 15 %.
Nominal cable insulation thickness must correspond to the table given below
10.0 0.9
The control cables, fire resistant at alternating voltage up to 660 V by frequency not Formatted: Bulleted + Level: 1 + Aligned at: 0.75" +
higher than 100 Hz or at direct voltage up to 1000 V shall meet the Special Indent at: 1"
requirements mentioned in NPCIL Technical specification for Control cables (Cable
type - KVVGng-FRLS &KVVGEng-FRLS) and (Cable type – KVVGng-LS
&KVVGEng-LS), Clause no. 6.2 .
Implementation and operation condition requirements shall meet the NPCIL
Technical specification for control cables ((Cable type - KVVGng-FRLS
File Name: GID/379/EL/YYY/BS/3006 SEPTEMBER2018
NOT FOR UNAUTHORISED PUBLICATION / PRESENTATION OUTSIDE NPCIL
NUCLEAR POWER CORPORATION OF INDIA LTD.
PAGE NO. : Page 21 of 35
KUDANKULAM NUCLEAR POWER PROJECT-3&4
REV. NO : P0
DESIGN BASIS REPORT FOR CABLING SYSTEM
REV. DATE : 24.09.2018
2454kV EHV cable have been proposed for the tie line connectivity between
KKNPP-1&2 and KKNPP-3&4, which are crossing the 400kV outdoor switchyard.
On one side of the cable, the respective phases of the cable shall be connected to
lattice columns (one for every phase) and on the other side the cable shall be
connected to a tower (for overhead line).
Cable will be directly buried below the ground at a level of 800mm from ground.
Trench will be made at a depth of 1000mm and width of 600mm. Fine sand to be
filled, after laying the cable in trefoil formation and top layer of trench will be made
by red colored reinforced concrete slab at a size of 400x300x100mm. (Reference
NPCIL Drawing No. I05.KK34.0.0.ET.OKS.WD006 – Appendix-10 for Details of
230kV Cable and FOP cable laying arrangement).
EHV cables size as per tender specification has been followed.
The XLPE cable and the associated accessories shall conform to the followingIndian
and International standards as amended /revised till date, as applicable:
IEC 62067 Power cables with extruded insulation and their accessories forrated
voltages above 150 kV (Um = 170 kV) up to 500 kV (Um = 550 kV)– Test methods
and requirements
IEC 60228 Conductor for insulated cables.
IEC 60229 Tests on cable over sheaths.
IEC 60230 Impulse tests on cables and their accessories.
IEC 60270 Partial discharge measurements.
IEC 60287 Calculation of continuous current carrying capacity and losses.
IEC 60502 All cables with extruded insulation and their accessories.
IEC 60840 Test for power cables with extruded insulation.
IEEE 48 Test procedure and requirement for high voltage cabletermination.
IEEE 404 Joint for use with solid dielectric cables.
IEEE 635 Guide for selection and design of aluminum sheaths.
IS 7098 (Part 3) Cross linked polyethylene insulated thermoplastic sheathed cables –
specification for working voltage from 66 kV up to and including220kV
IS 5216 Guide for safety procedure and practices in electrical works
IS 1893 Criteria for earthquake resistant design of structure
Indian Electricity Rules.
Indian Electricity Act
The continuous vulcanizing, dry cured cross linked polyethylene insulated (XLPE)
cable shall be manufactured in accordance with the internationally accepted standard
and also conform to the requirements of IEC 62067 / IS 7098. The cable shall be
suitable for laying in an area likely to be flooded by water and shall be designed to
be protected against rodent and termite attack. The conductor screen, insulation and
insulation screen shall all be extruded through common head triple extrusion in a
single onetime process to ensure homogeneity and absence of voids
245 kV cable shall be supplied in single length without any joint.
The conductor shall consist of Aluminium stranded wires of nominal cross section
of minimum 1200 sq. mm. The shape of the conductor shall be compact circular
stranded.
The conductor screen shall consist of extruded semi conducting compound. Semi
conducting separator tapes shall be applied between conductor and the extruded
insulation
The extruded XLPE insulation shall be of very high degree of purity and dry cured.
The insulation shield shall consist of extruded semi-conducting XLPE. Suitable
bedding tapes shall be applied over the extruded semi-conducting XLPE. Water
swellable absorbent shall be applied over the insulation screen.
The metallic sheaths shall consist of corrugated Aluminum. It shall be able to
withstand earth fault current of 40 kA for 3 second. Bidder shall furnish
prequalification tests on complete cable system and meet other qualifying
requirements of specification. The minimum thickness at any point shall not fall
below the nominal value by more than 10%. Anti-corrosive compound shall be
applied over the aluminum sheath.
The outer jacket shall consist of extruded PVC type ST-2 with fire resistance (FR)
properties. The minimum thickness at any point shall not fall below 90% of the
The cable end termination and other accessories shall include out-door end cable
termination, cable fixing clamps, surge voltage limiter, link boxes, bonding cable of
required length and also any special tools and tackles required for making these
terminations. All accessories shall be suitable for tropical climatic conditions
specified in the specification and are likely to be subjected to submergence in water.
The cable end termination shall be of outdoor anti-fog type complete with porcelain
insulators. The outdoor terminal should be suitable for heavily polluted atmosphere
conditions with creepage distance of 44mm/kV for highest phase to earth system
voltage.
The housing shall be made of homogeneous, vitreous porcelain of highmechanical
and dielectric strength. Glazing of porcelain shall be of uniformbrown or dark brown
colour with a smooth surface arranged to shed awayrain water or condensed water
parties.
The internal electric stress of the cable termination shall be controlled by
premoulded silicon cone arrangement
The largest load out of the following combination of loads shall be taken as the
maximum working load of insulator and to be considered for the Mechanical design
of the cable end termination insulator.
- Electromagnetic force due to short circuit current + wind load +Normal
operating load.
- Electromagnetic force due to short circuit current + Earthquake force+ Normal
operating load.
Outdoor type sealing end: The cable sealing end with Composite/Porcelain type
insulator, link box with sheath voltage limiter conforming to IEC- 62067 of
termination for maximum continuous voltage of 245 kV cables. The silicone rubber
/composite bushing termination of rated capacity, suitable for outdoor installation in
moderately polluted atmosphere shall be used. It should resistant to UV exposure.
The termination stress control shall be means of stress cone. The stress cone made of
silicone rubber shall inhibit possible mechanical stress and deformation of the cable
insulation surface during operation and also shall be capable of accommodating
minor radial and longitudinal movement without determent to the dielectric stress in
the insulation shield.
Fibre Optic Cable shall be provided on Transmission Tower end. The other end of 245 kV
cable will be connected to LA with suitable outdoor termination kit.
File Name: GID/379/EL/YYY/BS/3006 SEPTEMBER2018
NOT FOR UNAUTHORISED PUBLICATION / PRESENTATION OUTSIDE NPCIL
NUCLEAR POWER CORPORATION OF INDIA LTD.
PAGE NO. : Page 24 of 35
KUDANKULAM NUCLEAR POWER PROJECT-3&4
REV. NO : P0
DESIGN BASIS REPORT FOR CABLING SYSTEM
REV. DATE : 24.09.2018
The Armoured underground fibre optic cable required to connect Overhead Fibre
Optic Cable (OPGW) between the two overhead transmission wherever 220kV line
is crossing 400kV outdoor switchyard.
Fiber optic cable will be laid through protective duct (HDPE Pipe) on the same
trench, where EHV cables are laid to cross the 400kV Outdoor switchyard of
KKNPP-1 & 2. FO cable will be laid above the EHV cable by maintaining
minimum clearance of 200mm throughout the trench. (Reference NPCIL Drawing
No. I05.KK34.0.0.ET.OKS.WD006 – Appendix-10 for Details of 230kV Cable and
FOP cable laying arrangement)
Approach cable shall contain fibres with identical optical/ physical characteristics
asthose in the OPGW cables.
Cable and fibre service loops are provided for facilitating the installation,
maintenance andrepair of the optical fibre cable plant.
Indoor Cable Service Loops: FODPs shall provide at least three (3) meters of cable
service loop. Service loops shall be neatly secured and stored, coiled such that the
minimum recommended bend radius' are maintained.
Fibre Units Service Loops: For all fibre optic cable splicing, the cable shall be
stripped back a sufficient length such that the fan-out of fibre units shall provide for
at least one (1) meter of fibre unit service loop between the stripped cable and the
bare fibre fan-out.
Pigtail Service Loops: Connectorised pigtails spliced to bare fibres shall provide at
least 1 meter of service loop installed in the FODP fibre organizer and at least one
(1) meter of service loop to the couplings neatly stored behind the FODP coupling
panels.
Fibre Service Loops: At least 0.5 meter of bare fibre service loop shall be provided
on each side of all fibre splices
Cable carrier system elementsshall be hot dip galvanized and fabricated from carbon
steel with a thickness of zinc coating not less than 80 microns.
The quality category shall be commensurate with safety class 2S. For BOP areas the
safety class shall be 3N or 4 as applicable.
The elements/components of cable metal structures shall include:
- Racks (ceiling, wall, floor, spacer-types);
- Cantilevers;
- Trays for laying power and control cables;
- Flat Cable ducts for laying power and control cables;
- Modular Cable ducts for laying power and control cables;
- Separating partitions for installation in ducts;
- Duct - bend sections.
- Accessories for the elements/components
- Fasteners for the assembly
- Cable fastening clamps – of all types
10.2. Racks
The lengths of racks shall be in standard sizes ranging from 300 to 3000 mm with a
50-mm pitch for the (circular) slotted holes on all the faces.
The thickness of the racks (sheet steel) shall be 3-4mm approximately and.actual Formatted: Left, Right: 0", Don't adjust space between
dimensions shall be as in the drawings to be provided by NPCIL to the successful Latin and Asian text, Don't adjust space between Asian
bidder text and numbers
In cases where the requirement at site is in between two standard lengths, it is Formatted: Font: (Default) Times, 12 pt
permitted tocut and weld standard elements to suit actual site conditions. Care needs
to be taken toproperly coat the affected surfaces with cold galvanizing paint.
Rack fastening elements shall permit attachment to the previously installed
embedded parts by welding. The designs of racks shall have provisions (through
appropriate fittings/accessories) for attachment to the building floor, wall and ceiling
by anchor bolts wherever EPs are not available.
The design/fabrication/assembly/installation elements shall be permit easy dis- Formatted: Font: (Default) Times, 12 pt
assembly when called for Formatted: Left, Right: 0", Don't adjust space between
It shall be possible to secure horizontal supports to vertical supports anywhere along Latin and Asian text, Don't adjust space between Asian
thelength of the rack, at multiples of not more than 50 mm. text and numbers
Typical sections of the racks are shown below. Formatted: Font: (Default) Times, 12 pt
Typical sketch of the racks (S, S1, S2) Typical sketch of the racks (SS3)
10.3. Brackets
The trays are intended for installation of cables and wires. Cable trays shall be in
standard widths of – 100, 200, 300, 400, 500, 600mm. The thickness of the sheet
steel for forming of cable trays shall be about 2mm.
The cable tray rungs shall be welded to the collar through a full weld on the meshing
area.
The various types of cable tray element include the following:
- Straight trays;
- Tray corner section with a 90º turn in a horizontal plane;
- Tray branching section for 3 directions with a 90º turn;
- Tray branching section for 4 directions with a 90º turn;
- Separating partition;
- Section with an upward turn (rotary connection elements can be used);
- Section with a downward turn (rotary connection elements can be used).
Typical sections of cable trays are shown in NPCIL Technical specification for
Cable carrier systems, Clause no.5.3.7
Wire mesh cable trays are to be used in Indoor for running the cables for lighting
and receptacles, fire alarm and protection, welding/multipurpose receptacles and
maintenance lighting.
Wire mesh cable tray installed in indoor common access area shall be made of hot
dip galvanized carbon steel with the thickness of zinc coating no less than 85 m.
For outdoor applications and a corrosive atmosphere, the material shall be SS 316.
The duct fabrication/design shall have brackets attached to the duct through
fasteners. Thedesign/fabrication also have provision to connect trays with a turn in a
horizontal planethrough 135° and 90º.
Width of the duct shall be of 100, 200, 300, 400, and 500 mm. and Height of the
duct shall be 100 and 150 mm. The thickness of the sheet steel of the ducts shall be
about 2mm. There are no sharp edges at connections attachments of ducts.
The duct covers shall be fastened to ducts both in horizontal and vertical sections so
as toexclude possible damage to cables during an earthquake.
If required, the ducts shall permit installation of a separating partition inside them
with apitch of 50 mm.
The distance between supports, for cable ducts, in general shall be 2m.
Typical sections of cable duct are shown in NPCIL Technical specification for
Cable carrier systems, Clause no.5.4.15
Control and power cables shall be taken out from the duct through an outlet wall,
installed in place of the duct rear wall.
The interval of support shall not be more than 6 m in a straight cable route. The
support interval is based on the self-bearing capacity of a 6-m block assembled out
of three numbers of 2-m-long sections.
MCD sections shall be connected to each other using bolted or welded joints.
Elements for fastening of modular cable duct to the civil structures of buildings
The typical details/ sketch of MCDs are shown in NPCIL Technical specification for
Cable carrier systems, Clause no.5.5.8, Figures 5.5.1 - 5.5.6.
Group 1
Cables above 1000 V; they are located on separate brackets apart from allother
Cable Groups in bundles, consisting of three separate cores / phases and spaced
atintervals / distance at least the diameter of one phase between them.
Group 2
Cables up to 1000 V with conductor cross section greater than 16 mm2
insection.They shall be installed in one layer on separate trays.
Group 3
Cables up to 1000 V with conductors 16 mm2 in section and lower. They maybe
installed in one/ multiple layer(s) on separate tray with due de-rating factors.
Group 4
Cables greater than 42V, free of any specific requirements for their locations,cables
feeding valves and controllers and cables towards end switches of valves. Theyshall
be installed on separate trays apart from all other Cable Groups in
one/multiplelayers within cable trays/ducts or in bundles over supporting structures
File Name: GID/379/EL/YYY/BS/3006 SEPTEMBER2018
NOT FOR UNAUTHORISED PUBLICATION / PRESENTATION OUTSIDE NPCIL
NUCLEAR POWER CORPORATION OF INDIA LTD.
PAGE NO. : Page 30 of 35
KUDANKULAM NUCLEAR POWER PROJECT-3&4
REV. NO : P0
DESIGN BASIS REPORT FOR CABLING SYSTEM
REV. DATE : 24.09.2018
and in trays; CableGroups 3 and 4 can be located together, if they belong to same
process unit.
Group 5
Cables of 42V and lower, with no specific system requirement andcommunication
cables. They shall be installed in one/ multiple layers within cabletrays/ducts or in
bundles over supporting structures and in trays or separate brackets apartfrom all
other Cable Groups.
Group 6
Control cables of special systems, which require special protection, LAN andall
fibre-optic communication. They are located in multiple layers or in bundles
withinclosed metal ducts or pipes. It is allowed not to have shields where cable runs
are turning,but unshielded sections be no longer than 0.5 m. All sections of pipes
and ducts along thecable run shall have reliable electric contact between themselves
by connecting individualpipes or ducts with copper wire soldered or bolted to pipes
or ducts. Ends of pipes andducts shall be free of sharp edges, to prevent damage to
cables. Ends of pipes and ductsare to be closed with sleeves. Distance between pipes
or ducts with control cables ofspecial systems and power cables greater than 0.5 A
to be at least 0.5 m, and distance topower cables greater than 20 A to be at least 1 m.
Group 8
Power cables 24 V free of any specific requirements for their locations, whichare
jumpers between power supply cabinets and basic cabinets. They are located in
oneline in trays on separate brackets apart from other Cable Groups without gaps,
belowCable Group 2 or 3 and above Cable Groups 4 or 5.
The cable layout design pre-supposes that main cable runs are laid on cable trays
and in metal ducts. Fibre-optic cable is laid in multiple layers or in bundles in metal
ducts or pipes to prevent mechanical damage.
Cables diverted from the main cable run to individual loads shall be located in
suitable size of GI pipes orflexible conduits
RCC cable trenches shall be sealed against ingress of liquid and gases wherever the
trenches leave or enter a control room or power supply building. Pipes laid for
mechanical protection shall be sealed at both ends. All cable openings shall be
sealed with suitable sealing compound to prevent ingress of water from
outside
All cables shall carry cable tag numbers for easy identification
Signal cables shall preferably not be laid in the same trench/ tray along with
electrical cables. In case these are laid in the same trench/ tray, a clearance of
minimum 300 mm from electrical cables shall be provided
All MV &LV power cables in racks/trays/ cable ducts shall be laid in single layer
only. However LV cables below 16 sq. mm (Group-3) may be laid in multiple layers
as well, as per technical specification for cable system & cabling guidelines.
No cable joint shall be acceptable except in cases where a single length cannot be
manufactured/ transported and in case of any such constraint, the same shall be
brought to the notice of Purchaser before finalization of design & engineering. No
joints shall be permissible in hazardous areas.
Single core 6kV cables shall be laid in trefoil configuration with 1D gap. The
clamping and banding of the 6kV cables in trefoil format shall be carried out as per
the technical requirement for cable system & cabling guidelines
(I02.KK34.0.0.ET.TT.PR001)
15% spare space shall be provided in cable trays/ trenches.
All cable trays and cable ducts and its supporting structures in main routes shall be
connected to the nearest earthing grid through 40 x 4 mm galvanized steel strips, at
intervals not exceeding 25m and at both the ends. Smaller sections/field routing of
the cable tray shall be earthed with appropriate sizes of earthing conductor
Earthing continuity in cable trays shall be ensured as per IEC 61537
Grounding shall be ensured all along cable trays/cable trench. Where lined cable
trenches are available, the ground conductor shall be laid in the trenches and shall be
firmly cleated to the sidewall of concrete trenches using GI clamps at interval of 400
mm to 500 mm and near to the termination ends.
The grounding conductor shall run along one of the cable trays along a cable route.
The grounding conductor shall be suitably cleated and electrically bonded to all the
other cable trays on the same cable route at a regular interval of 25 to 30
meters.
The grounding for equipment shall be tapped from the mainground conductor
and not from cable tray support structure
Cable fire barriers are passive fire protection systems which prevent
propagation of fire from one fire compartment to the other through floor and
wall penetrations for power and control cables.
The construction consists of mineral wool board through which cables are
laid and the gaps sealed with a fire resistance sealant.
Fire resistant coating for passive fire protection are intended for coating
power and control cables in order to ensure non-propagation of fire in cables
in switchyard areas.
A fire resistant coating is applied on the surfaces of the partitions and cables
coming out of the seal.
The fire barrier and fire resistant cable coating material shall be suitable for
cables installed in above ground trays, underground tunnels- trays, direct in
underground RCC trenches, ductsFire resistant (fire survival) cables with
three hour rating shall be used for the selected criticalsystems/equipment.
The applicable standards, guide and codes of practice and reports are listed in
NPCIL Technical Specification for Fire barrier and Fire resistant coating
(I02/KK34/0/0/ET/TS/PR/015) Clause No.3.0
Fire Barriers for passive fire protection
- Fire rating required (hr.) : 3, 2& 1 Hrs.
- Details of structures through which cables /
Cabletrays /Pipe sleeves penetrate.
o Wall thickness (mm) : To be arrived at during
Detailed engineering
o Floor thickness (mm) : To be arrived at during Formatted: Font: 12 pt
Detailed engineering Formatted: Left, Right: 0", Bulleted + Level: 1 +
- Material of frame / conduits / pipes / pipe : MS / GI Aligned at: 0.75" + Indent at: 1", Don't adjust space
SleevesCable trays provided by Purchaser between Latin and Asian text, Don't adjust space
Fire resistancecoating (FRC): between Asian text and numbers
Types of cables specified by the purchaser : XLPE/LDPE/PVC/EPR/EVA Formatted: Indent: Left: 0.75", First line: 0.5"
insulated and flame retardant Formatted: Indent: Left: 4"
File Name: GID/379/EL/YYY/BS/3006 SEPTEMBER2018
NOT FOR UNAUTHORISED PUBLICATION / PRESENTATION OUTSIDE NPCIL
NUCLEAR POWER CORPORATION OF INDIA LTD.
PAGE NO. : Page 32 of 35
KUDANKULAM NUCLEAR POWER PROJECT-3&4
REV. NO : P0
DESIGN BASIS REPORT FOR CABLING SYSTEM
REV. DATE : 24.09.2018
All material shall be new, freshly manufactured and of first class quality.
The materials used in the passive fire protection systems shall not contain
flammable materials or solvents which are toxic or release toxic gases during
exposure to fire.
File Name: GID/379/EL/YYY/BS/3006 SEPTEMBER2018
NOT FOR UNAUTHORISED PUBLICATION / PRESENTATION OUTSIDE NPCIL
NUCLEAR POWER CORPORATION OF INDIA LTD.
PAGE NO. : Page 33 of 35
KUDANKULAM NUCLEAR POWER PROJECT-3&4
REV. NO : P0
DESIGN BASIS REPORT FOR CABLING SYSTEM
REV. DATE : 24.09.2018
The materials used in the passive fire protection systems shall have no
shrinkage or cracking after prolonged use.
The materials used in the passive fire protection systems shall be non-
hygroscopic.
The materials used in the passive fire protection systems shall retain its
integrity andperform satisfactorily even after remaining in water for long
periods.
The materials used in the passive fire protection systems shall be anti-rodent.
The materials used in the passive fire protection systems should be non-
hazardous andshould not emit any excess smoke under fire exposure.
The materials used in the passive fire protection systems shall have
compatibility withFRLS PVC, PVC, neoprene, silicone rubber, EVA
sheathing materials of cable
The materials used in the passive fire protection systems shall be resistant to
chemicals.
The material used in the passive fire protection systems (excluding mineral
wool board)shall have oxygen index greater than 60%.
The shelf life of all materials which form a part of supply of the fire barrier
shall beindicated.
Mineral wool board shall be ROCKWOOL, of density not less than 150
kg/m3. Theboard shall be at least 50 mm thick of minimum size 1m x 0.5m.
FRC shall comply with the requirement of allowable long-term load current,
if after tests(as per IEC 60332-3-10, IEC 60332-3-22) the value of allowed
long-term load currentreduction factor for cable with FRC is no less than
0.98.
FRC shall comply with fire-non-propagation requirements, if as a result of
test (as perIEC 60332-3-10) the length of cable with FRC damaged by flame
or carbonized does notexceed 1.5 m, measured according to IEC 60332-3-22.
Material used for passive fire protection systems shall not have any corrosive
effect onmetal structures and cables.
Materials used for passive fire protection systems shall not contain organic
(withexplosive-fire-hazard vapors) solvents as their base.
Materials used for passive fire protection systems shall be non-toxic.
Materials used for passive fire protection systems shall comply with sanitary-
epidemic regulations in force at the NPP and in case of possible radiation and
heat flows shall notgenerate harmful or toxic gases.
Fire resistant coating shall be capable to be applied on cable surface, on
mineral woolboard and on the surface of cable metal structures, both painted
and non-painted.
Fire resistant coating shall be capable to be applied on cable surface both in
horizontal and vertical position.
Materials used for passive fire protection systems shall not peel from the
surface in anyNPP operation mode.
The following indicate fire safety class:
HF - Halogen-free;
FR - Fire-resistant;
LS - With low smoke and gas emissions;
FRHF - Fire-resistant, halogen-free;
For cable interface, refer Cabling Interface diagram (BGR Doc. No.
GID/379/EL/YYY/GN/3011) for scope of cables and cable carrier system in
switchyard & E-BoP package.
12. REFERENCES
Technical requirement for Cable System and Cabling Guidelines for KKNPP - 3&4
(Doc.No.I02.KK34.0.0.ET.TT.PR.001)
Technical specification for MV Power cables for KKNPP – 3&4 (Doc. No.
I02.KK34.0.0.ET.TS.PR.010)
Technical specification for LV Power cables for KKNPP – 3&4 (Doc. No.
I02.KK34.0.0.ET.TS.PR.011 and 012)
Technical specification for Control cables for KKNPP – 3&4 (Doc. No.
I02.KK34.0.0.ET.TS.PR.013 and 014)
Technical specification for 245kV Cables for KKNPP – 3&4 (Doc. No.
I05.KK34.0.0.ET.TS.PR002)
Technical specification for Optical Ground Wire(OPGW)/Fiber Optic Cable(FOC) (Doc.
No.I05.KK34.0.0.ET.TS.PR003)
Technical Specification for Cable Carrier System Elements for KKNPP – 3&4 (Doc. No.
I02.KK34.0.0.ET.TS.PR.009)
Concept note on electrical power supply system (GID/379/EL/YYY/BS/3002)
Key single line diagram (GID/379/EL/ADA/XJ/3035)
DBR for General Electrical Systems and Equipment (GID/379/EL/YYY/BS/3004)
DBR for SCADA and Protection System (GID/379/EL/YYY/BS/3083)
DBR for Fire Fighting System (GID/379/ME/SGA/BS/1002)
DBR for Ventilation System (GID/379/ME/SA/BS/1125)
400kV switchyard layout plan (I02.KK34.0.UAB.ET.0KS.WD001)
230kV switchyard layout plan (I02.KK34.0.UAD.ET.0KS.WD002)
Refer “Annexure-1” for the proposed tentative sketch of 230kV tie line interconnection
between KKNPP-1&2 and KKNPP-3&4.
Refer “Overall Electrical Bus duct& Cable layout – Balance of plant for KKNPP-3&4
(EIL Drg. No.A209-000-16-50-0015
Refer “Annexure-2” for the proposed tentative sketch of 400kV layout plan-option 1
File Name: GID/379/EL/YYY/BS/3006 SEPTEMBER2018
NOT FOR UNAUTHORISED PUBLICATION / PRESENTATION OUTSIDE NPCIL
NUCLEAR POWER CORPORATION OF INDIA LTD.
PAGE NO. : Page 35 of 35
KUDANKULAM NUCLEAR POWER PROJECT-3&4
REV. NO : P0
DESIGN BASIS REPORT FOR CABLING SYSTEM
REV. DATE : 24.09.2018
Refer “Annexure-3” for the proposed tentative sketch of 400kV layout plan-option 2
Refer “Annexure-4” for the proposed tentative sketch of 230kV layout plan-option 1
Refer “Annexure-5” for the proposed tentative sketch of 230kV layout plan-option 2