Beruflich Dokumente
Kultur Dokumente
No. 131
Siemens is often asked to provide For simplicity, assume that main bus The heat generation of control power
estimated heat generation data for our loading in each vertical section is transformers (CPTs) is highly variable,
equipment. This issue of TechTopics equal to the total estimated load of but if considered, should be estimated
provides information that allows the switchgear lineup, and adjust the at about four percent of the VA rating
calculation of approximate heat heat generated for each vertical of the transformer, e.g., for a 15 kVA
generated by SIEBREAK metal-enclosed section by the square of the CPT, estimate 600 W heat generation
interrupter switchgear equipment percentage of total estimated load to at full load.
under assumed loading conditions. rated main bus current. While this is
Heat generation by relays and meters
seldom correct, the overstatement of
The heat generation data given in the is generally ignored and is usually not
the heat generation is not often
tables for fuses assumes class E fuses, significant in metal-enclosed
significant.
whether current-limiting or expulsion interrupter switchgear. If relays and
type (as in the relevant tables), The tables which follow show total meters are included, 50 W is a very
assuming that the continuous current heat generation for the building block conservative estimate of heat
through the fuse is 80 percent of the configurations described, and serve as generation by microprocessor relays or
E-rating of the fuse. the basis of calculations for an actual power meters.
switchgear configuration involved
For applications which differ from If heat generation is desired in BTU/
with a project.
these assumptions, convert the heat hour, the conversion factor is:
generation shown for the typical Since the heat generation value given
watts X 3.415179 = BTU/hour.
currents to that for the specific is based on rated current for
application by the ratio of the squares assemblies, the value of heat
of the currents. generation must be adjusted to reflect
the actual current in the application.
To estimate the heat generated under
actual loading conditions, determine Heat generated by current
the component heat generation for transformers is ignored as it is usually
each of the components indicated in insignificant, and varies according to
the table, with adjustments if the current transformer (CT) ratio as
necessary for differing currents. Space well as the loading.
heater load should be assumed to be
continuous.
usa.siemens.com/techtopics
Heat generation for typical section configurations
Typical Heat
Single load-interrupter switch (LIS), no main bus
current generation
Unfused, 600 A LIS 600 A 366 W
Duplex (two LIS with common load side for connection to Typical Heat
fuses), in and out (no main bus) current generation
Unfused, 600 A LIS, based on only one switch closed at a time 600 A 442 W
Typical Heat
Single LIS selector switch, in and out
current generation
Unfused, 600 A LIS without selector switch 600 A 366 W
2
Transition section (e.g., for main incoming switch to main Typical Heat
bus of feeder sections) current generation
Example one: 600 A fused switch, single unit, with 300E current-limiting fuses
Heat Heat
Component Rated current generation at Actual current generation at
rated current actual current
3
Example two: 600 A fused selector switch, single unit, with 200E expulsion fuses
Heat Heat
Component Rated current generation at Actual current generation at
rated current actual current
600 A LIS with selector
600 A 546 W 160 A 59 W
switch
Fuses, expulsion type,
160 A 45 W
200E
Total heat generation 104 W
Option:
Add space heater, single unit indoor 600 W
Heat Heat
Component Rated current generation at Actual current generation at
rated current actual current
4
This would result in 451 W – 246 W =
205 W reduction in heat generation.
This is a comparatively small reduction
(205 W is 5.8 percent of the total heat
of 3,510 W with space heaters, and
only 10.7 percent of the total heat of
1,910 W if heaters are not involved)
and explains why the reduction in
current as the units get farther from
the source is usually ignored.