43

Requirements table
The following table shows how to select the motor insulation system and when an optional ABB du/dt
filter, insulated N-end (non-driven end) motor bearings and ABB common mode filters are required. The
motor manufacturer should be consulted regarding the construction of the motor insulation and
additional requirements for explosion-safe (Ex) motors. Failure of the motor to fulfil the following
requirements or improper installation may shorten motor life or damage the motor bearings and voids
the warranty.

Motor type Nominal mains Requirement for


voltage (AC line Motor ABB du/dt filter, insulated N-end bearing and ABB common
voltage) insulation mode filter
Manufacturer

system PN < 100 kW 100 kW < PN < PN > 350 kW


and 350 kW or or
frame size < IEC frame size > IEC frame size > IEC
315 315 400
PN < 134 HP 134 HP < PN < PN > 469 HP
and frame size < 469 HP or frame size >
NEMA 500 or frame size > NEMA 580
NEMA 500
A Random- UN < 500 V Standard - +N + N + CMF
B wound M2_ 500 V < UN < 600 V Standard + du/dt + du/dt + N + du/dt + N + CMF
B and M3_
or
Reinforced - +N + N + CMF
600 V < UN < 690 V Reinforced + du/dt + du/dt + N + du/dt + N + CMF
Form-wound 380 V < UN < 690 V Standard n.a. + N + CMF PN < 500 kW: + N
HX_ and + CMF
AM_ PN > 500 kW: + N
+ CMF + du/dt
Old* form- 380 V < UN < 690 V Check with the + du/dt with voltages over 500 V + N + CMF
wound HX_ motor
and modular manufacturer.
Random- 0 V < UN < 500 V Enamelled wire + N + CMF
wound HX_ 500 V < UN < 690 V with fibre glass + du/dt + N + CMF
and AM_ ** taping

Planning the electrical installation