FOAM CONCENTRATE CONTROL VALVE

TECHNICAL DATA

MODEL CV
SIZE 40NB, 50NB, & 65NB
RATED PRESSURE 14 Kg./sq.cm. (200 PSI)
END CONNECTION Flanged end to ANSI B 16.5
Class 150#
PRESSURE SENSING Teflon tube with Stainless
HOSE Steel braided cover
TRIM CONNECTION Brass / Stainless Steel
FACTORY 25 Kg./sq.cm. (365 PSI)
HYDROTESTED
FINISH Epoxy red painted
ORDERING Specify Model, Size
INFORMATION of valve
FOAM CON.
INLET
APPLICATION
3
Foam concentrate control valve is designed for use 5
in bladder tank foam system or inline balance 4
pressure proportioning system. The valve opens 2
automatically when water supply is established
through the inlet pipe of ratio controller of bladder
ED
OS

tank or in the inline balance pressure proportioning


CL

system. The valve opens at minimum of 3 Kg. ( 42.8


OPEN

1
psi ) water pressure. No electric power is required 5
to operate the valve.

SPECIFICATION
FOAM CON.
OUTLET
The foam concentrate control valve utilizes water
as the medium to open the valve. A manual override WATER PRESSURE
SENSER SUPPLY FROM
facility is provided to open the valve. In normal INLET SIDE OF
RATIO CONTROLLER
condition the valve remain in closed position. When,
a minimum water pressure of 3 Kg./sq.cm. ( 42.8
psi ) is established the valve opens and closing of
SR NO. DESCRIPTION MATERIAL SPECIFICATION
the valve is manual.
1 Valve Stainless Steel
INSPECTION AND MAINTENANCE 2 Pipe Stainless Steel
A qualified and trained person must commission the 3 Cylinder Stainless Steel
system. After few initial successful tests, an 4 Hose Stainless Steel
authorised person must be trained to perform the 5 Flange Stainless Steel
inspection and testing of the system at lest once
in a week. The inspection should verify that all the
control valves are in their proper position as per SELECTION OF FOAM CONCENTRATE
the system requirement and no damage has taken CONTROL VALVE
place to any component. The foam concentrate
FG Proportioner Foam Concentrate Control
control valve / system must be operated at least
Size Valve Size
once in six weeks. The total system should be fully
tested at lest once in a year as per NFPA / TAC 80 NB 40NB
manual or in accordance to the guidelines of the 100 NB 40NB
organisation having local jurisdiction. 150 NB 50NB
200 NB 65NB

Company Registration No. 5717368 • V.A.T No. 883908672 www.fireguard-uk.com


Tel: 00-44-8450751042 Fax: 00-44-8450751043 Email: info@fireguard-uk.com
2nd FLOOR | 145-157 ST.JOHNS STREET | LONDON | EC1V 4P Y | UNITED KINGDOM

TYPICAL INSTALLATION OF FOAM CONCENTRATE CONTROL VALVE

FOAM CONCENTRATE SWING FOAM CONCENTRATE


CONTROL VALVE CHECK VALVE CONTROL VALVE

FOAM CONCENTRATE
TO SPRINKLER

FOAM CONCENTRATE
NETWORK

CONTROLLER
WATER

RATIO
WATER
BLADDER TANK
DELUGE FOAM
VALVE SOLUTION BLADDER TANK
OUTLET SPRINKLER
RATIO ALARM
ALARM VALVE
CONTROLLER

WATER
WATER INLET CONTROL
VALVE

WATER INLET