10 Press RIGHT key to edit Editable

support@elmeasure.com value digit blinks.


Ph: +91 80 32904489
11 Press DOWN key to Changed Select the required value.
change digit blinks.

12 Press RIGHT key to Blinking digit Follow the same procedure


ALPHA+ 3A accept stabilizes. to set 4 digits.

AMPS 13 Press DOWN key Decimal Set Kilo while setting


point blinks decimal point. Eg : To set
11.00kV. Set 4 digits (1100)
K as explained above. Press
DOWN key to place Decimal
RYB ON - AVG
R µA+ 3V
point while Kilo LED comes ON.
R Y B AVG Y VOLTS 14 Press Down key to go to Displays Pt.SE (In case of Voltmeter)
B
next parameter. Pt.SE / Ct.SE Ct.SE (In case of Ammeter)

PRG
PRG Hz
KILO

MICRO ALPHA
ALPHA+ 15 Press the RIGHT Key to 415.0 / 5.000 PT secondary or CT
edit Follow the secondary
procedure as per
Sl. No. 9 to 13.

PROGRAMMING GUIDE 16 Press DOWN key to


go to next parameter.
To save the setting mode.
Option : Y(YES) / n(NO)
Display returns can be selected by using
Alpha+/ µAlpha+Series 17 Press RIGHT key to
memorize the changes done. to Home page RIGHT & DOWN keys
Once the required parameter is programmed, to reach SAVE page directly, press the down key
continuously up to it reaches SAVE page.
www.elmeasure.com

4. LED INDICATION
LED Status Alpha+3A / µAlpha+ 3A LED Status Alpha+3V / µAlpha+ 3V
1. UNIQUE FEATURES - Meaning - Meaning
True RMS R - ON R Phase Amps R - ON R Phase Voltage(VLN)
STAR (Wye)/ Delta Programmable / Single Phase Y - ON Y Phase Amps Y - ON Y Phase Voltage (VLN)
PT ratio / CT ratio programmable including CT B - ON B Phase Amps B - ON B Phase Voltage (VLN)
secondary K - ON Kilo Hz Frequency
Universal Auxiliary (80-300 V AC) supply. RYB-ON Amps Average Value RY - ON R-Y Voltage (VLN)
Universal Voltage Input (80 - 550 VAC) and LED Status µ Alpha+A/V/Hz/ YB - ON Y-B Voltage (VLN)
Current Secondary (0.5A to 6A). Alpha+ A/V/Hz BR - ON B-R Voltage (VLN)
- Meaning K - ON Kilo
Clearance & creepage distance meets UL61010 standard.
Compact size and light Weight. RYB - ON VLL Average Value
K - ON Kilo
RYB - OFF VLN Average Value

5. Mechanical Specification:
2. KEY FUNCTIONS Dimension Bezel: 96 x 96 mm (Depth 50mm behind Bezel) Panel Cutout:
96 × 48 mm (Depth 45mm behind Bezel) 90-0+2 x 90-0+2 mm
Key In SET (Programming) mode In RUN (Measurement) mode 90-0+2 x 42-0+2 mm
Right/UP To select the value and to accept To scroll the pages to look at
the value different parameters Panel
90 mm

DOWN To edit the value/system type down- To scroll down the pages to

90 mm
ward in edit mode and scroll through look at different parameters
the parameters. 90 mm
42 mm

Clamp

3. ENTERING CONFIGURATION (SETUP) MODE


Follow the following steps to configure the setup parameters through front panel keys.
Step Actions Display Reads Range/Options/Comments
1 Press RIGHT & (Password)
DOWN keys together to with first digit
enter SETUP “0” blinking.
2 Press Down key till the with first digit Default is 1000
first digit read “1”. “1” blinking.
3 Press the DOWN key. displays now. ELE Element (Wiring)
(Applicable only in 3A ,3V)
4 Press the RIGHT key StAr means STAR system.
Meter would display the
last set up value/ system.
5 Press the RIGHT key blinking. Now other options
can be chosen by using
RIGHT & DOWN keys.
6 Press the DOWN key Options : StAr (Star/ Wye),
dELt (Delta), Single phase
[Selected option is displayed]
7 Press RIGHT key to set Blinking stops. Displays
the system type required. steady system type.
8 Press DOWN key to Displays Pt.Pr Pt.Pr (PT Primary - In case
go to next page. / Ct.Pr of Voltmeter).
Ct.Pr (CT Primary - In case
of Ammeter)
9 Press the RIGHT key 415.0 /5.000 Indicates the last set value.
to set the PT primary/CT Programmable range:100V -
Primary 999kV (For Voltmeters) 0.5A
to 99kA (For Ammeters) PG/AL/V3/0415