Beruflich Dokumente
Kultur Dokumente
Generator Differential
Protection
ABCD
blank page
MX3DPG3A MDE/B133 2501 001
CONTENTS
1. TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2. GENERAL CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Selection of rated values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3. OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Stabilized differential protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Breaker failure protection (BF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 Main and spare settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4. ADDITIONAL FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Output circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.3 LED signalling circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.4 Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.5 Additional timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.6 Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.7 Event logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.8 Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.9 Breaker pole wear index Σ(I2t) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.10 Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.11 Alphanumeric plant identifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.12 Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.13 LCD settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.14 Inhibiting operation - Deconfiguring the unit via network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.15 Serial communication via LONWORKS (TM) field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.16 RS485 serial communication and MODBUS protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.17 Fault recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.18 Testing the trip circuits for continuity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5. LOCAL INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
pag. 3
MX3DPG3A MDE/B133 2501 001
8. INSTALLATION - SHIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.1 ESD Electrostatic Charges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.2 Acceptance - storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.3 Assembling and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
pag. 4
MX3DPG3A MDE/B133 2501 001
1. TECHNICAL DATA possibility of setting all output relays as "all normally ener-
gized" or "all normally de-energized"
The device belongs to the Modulex 3 line and digitally proc-
possibility of selecting, for each output relay and LED, the
esses six phase currents to provide a percent differential
monostable or bistable (hand-reset) operating mode
protection for generators, synchronous and asynchronous
possibility of assigning, to each output relay, a minimum
motors with accessible star point.
pulse width
The protection can communicate with a control and supervi-
opto-insulated digital inputs programmable for locks, con-
sory system through a LONWORKS (TM) bus, thus providing
trol and reset functions by normal energizing or de-energiz-
a local user interface.
ing. Possibility of use to control trip continuity
It is furthermore capable of communicating with a Personal
Partial and total counters per each trip threshold
Computer through a connector located on the relay front and
an interface programme. This feature makes it easier and
safer to programme the setting parameters and configure and THREE-POLE DIFFERENTIAL PROTECTION
read the set values, measurements and logged events; the settable rated phase current In: 1 A or 5 A
measurement range: 0 ÷ 20 In
programming can also be taken from previously created files. continuous thermal withstand : 4 In
short-time thermal withstand: 100 In
burden at 5 A: ≤ 0.15 VA per phase
Protective functions:
first tripping threshold Id> with adjustable percent hold
Settings
operating characteristic
rated current In
second quick trip threshold Id>> without hold first threshold Id>: 0.04÷1 In / OFF
breaker failure by steps of 0.01 In
possibility of two groups of settings, main and spare slope of first segment of percent characteristic P1: 20÷ 50%
by steps of 1%
slope of second segment of percent characteristic P2
Measuring functions: with intersection with hold current axis at 2.5InTR: 40 ÷100%
by steps of 1%
effective values of the six phase currents expressed in second threshold Id>>: 1÷20 In / OFF
multiples of In by steps of 0.1 In
effective values of the six phase currents expressed in operating time Id> < 40 ms
Amperes operating time Id>> < 30 ms
effective values of differential phase currents expressed in
multiples of In ADDITIONAL SETTINGS
primary rated current of CT net side: 10 ÷ 10000 A
maximum effective values of the six phase currents ex-
primary rated current of CT star point side: 10 ÷ 10000 A
pressed in multiples of In by steps of: 1 A
breaker pole wear index CT's polarity on net side NORM or INV
recording of the latest 8 events with storage of tripped CT's polarity on star point side NORM or INV
threshold, date, time and values of phase and differential rated frequency fn: 50 or 60 Hz
minimum pulse width of end relays timp: 0.02 ÷ 1 s
currents at the time of the fault. breaker arching time on net side t52: 0.01 ÷ 0.1 s
fault recorder: recording, for a total time of 2.5 s, of the instant additional timer tX1: 0.02 ÷ 600 s
values (12 samples per period) of the input quantities and additional timer tX2: 0.02 ÷ 600 s
the 19 logical states among which are digital inputs and additional timer tX3: 0.02 ÷ 600 s
breaker failure delay tBF: 0.02 ÷ 1 s / OFF
additional timers settings step: 0.01
RCE: recording of the latest 32 changes in state (with
related date and time); exclusively available through PC or Auxiliary power supply
via network. MX3DPG3A.11, .61 and .71 versions
Uaux: 19 ÷ 100 Vcc
Uaux: 19 ÷ 72 Vca
Other functions: MX3DPG3A.12, .62 and .72 versions
selection of the rated current between 1A or 5A through Uaux: 64 ÷ 300 Vcc
internal jumpers. Uaux: 64 ÷ 275 Vca
frequency for Uaux in a.c.: 47 ÷ 63 Hz
selection of the rated frequency between 50Hz or 60Hz
burden (minimum/maximum) in d.c.: 5 W / 10 W
selection of the dialogue language (Italian, English, French burden (minimum/maximum) in a.c.: 10VA / 20VA
and Spanish)
self-monitoring with detailed indication of fault and alarm Contacts characteristics
through LED's indications and "normally energized" output rated current: 5 A
relay (X6). breaking capacity (110 Vcc; L/R= 40 ms; 105 operations): 0.3 A
optional serial communication with both a local PC and a make and carry for 0.5 s: 30 A
mechanical durability: 106 operations
LONWORKS (TM) field-bus.
Three additional timers available for allocation to digital
inputs IN DIG1, IN DIG2, IN DIG3
possibility of assigning one or more functions (for instance,
trips, timer starts) to each output relay and LED
pag. 5
MX3DPG3A MDE/B133 2501 001
Other characteristics
reset ratio: > 0.80
overshoot time: ≤ 50 ms
Operating ranges
service temperature: -10 °C ÷ +60 °C
storage and transport temperature: -25 °C ÷ +80 °C
relative humidity: < 95% with no formation of condensate
vibration: IEC255-21-1; class 2; 0.075mm 10-60Hz; 1g 60-500Hz
Weight
total: 2.5 Kg
Protection class
device: IP52
on request, front protection when flush-mounted in a panel: IP66
terminals with mounted cover: IP20
Insulation
To ground and between two independent circuits whatsoever:
2 kV, 50 Hz per minute
Impulse test: 5 kV 1.2/50 µs
pag. 6
MX3DPG3A MDE/B133 2501 001
I CAUTION
Hazardous voltages can remain in the device even when
the latter has been de-energized or pulled out of its casing
(condenser memory).
pag. 7
MX3DPG3A MDE/B133 2501 001
3. OPERATION
3.1 General
The differential protection is aimed at operating in the event of
all type of faults occurring within a given area that is signalled
ID>> D E
out by the installation points of the CT's current reducers that
pag. 8
MX3DPG3A MDE/B133 2501 001
4.1 Diagnostics The signalling circuits are made of twelve LED's (see fig. 5).
Four LED's are rigorously assigned to previously established
Diagnostic activities are envisaged which are automatically
indicating functions:
carried out upon powering on the device as well as from time
- (Uaux) green LED ON in the presence of input voltage and
to time during the running, and which provide the following
with correct feeder output voltage values
actions:
- (RUN) green LED ON with fixed light in normal conditions
- signalling fault or failure conditions. This signal de-
and blinking during setting changing and testing functions
energizes the diagnostic relay, turns off the green LED
- (RUN) red LED ON with fixed light when the diagnostic
(indicating running system) and lights up the red LED
detects a fault or a condition of inhibition.
(indicating system failure).
- (Rx Tx) green LED ON with fixed light when the device is
- system lockout in the event of faults that might entail ill-timed
correctly connected, blinking with the communication
operation (VITAL FAULTS).
board not enabled or not properly set; OFF when the
- failure code display.
communication board is not present on the device.
The following failures are classed as NON-VITAL FAULTS:
Each of the eight LED's left, if duly programmed from the
- output relay(s) (X1 - X5) failure
keyboard, a Personal Computer or the network, can be:
- communication failure
- set to perform one or more functions
- internal clock failure
- preset for:
The following failures are classed as VITAL FAULTS:
- monostable operation; it immediately goes off when the
- feeder failure
cause that made it go on is removed
- EEPROM failure
- bistable (MEMOR) operation; the LED remains ON until a
- internal or external RAM failure
reset signal is sent from the front push-button, the digital
- Analogue/Digital converter failure
input or the serial connection. Any failure of auxiliary voltage
In the presence of vital faults, the device will automatically
only entails a momentary loss of the luminous signals,
displays the fault code; this condition can only be reset, if the
which come back again as soon as voltage is restored.
equipment allows this condition to be reset, by enabling the
A pocket is provided close to the LED's, where LED describing
"settings change' command.
labels can be placed.
In the event of , upon starting up the equipment, an EEPROM
failure making it impossible to retrieve the information on the
selected dialogue language, the device will continue working 4.4 Digital Inputs
using Italian as the default dialogue language. Each of the three opto-insulated inputs can be associated with
The device includes the 'Watch Dog' function. one or more protection functions by properly programming
The diagnostic activity is also aimed at signalling any condition them from the keyboard, through a Personal Computer or via
of "inhibited equipment"; this condition is displayed with a network. The input voltage may happen not to match the
dedicated code, the diagnostic relay is de-energized and the auxiliary voltage of the device.
red LED (faulty device) lights up. This condition can only be The digital inputs can be programmed to be enabled by normal
reset by enabling the 'change settings' command. energizing or normal de-energizing.
The diagnostic menu also indicates the date when last changes
were made to the equipment. 4.5 Additional timers
All of the optoinsulated inputs (IN DIG 1,IN DIG 2,IN DIG 3) can
4.2 Output circuits be programmed to be associated with additional timers (t_X1,
The output circuits are composed of six relays, each of them t_X2, t_X3).
equipped with two contacts (see block diagram). When the programmed input is energized, the associated
The X6 relay, normally energized, is strictly assigned to the additional timer is started, and if the timer reaches the overtime
diagnostic function. status, the tripping signal is sent and maintained until the input
Each of the five relays left, if duly programmed from the is reset.
keyboard, a Personal Computer or a network, can be:
- set to perform one or more functions 4.6 Counters
- preset for:
Each tripping threshold is associated with a partial and a total
- monostable operation: immediate return to the quiescent
counter.
position when the cause that operated it is removed.
The counters work within the 0-9999 range; if number 9999 is
- bistable operation (MEMOR): the tripping position is main-
exceeded, the counter is automatically reset and the count
tained until a reset signal comes from the front push-button,
restarts from the beginning.
the digital input or the serial connection.
All of the partial counters may be reset by acting through the
- a minimum duration of the signal or command (t_IMP).
keyboard, through a Personal Computer or via network.
The output relays, except for the diagnostic relay, can all be
simultaneously set to "normally energized" (NORMAL.ON=ON)
or "normally de-energized" (NORMAL.ON=OFF): this selection
is made by acting on the S1 jumper, which can only be reached
when the relay is pulled out (see fig. 1, 4e, 4f).
pag. 9
MX3DPG3A MDE/B133 2501 001
4.7 Event logging - the relay test allows the output relays X1 to X5 to be
sequentially selected and checked for correct operation. In
When a trip event occurs, the following information is stored
this way, any external signalling or control circuit can be
in the circulating memory:
tested, too.
- first operated threshold
The tested relay remains energized for 150 to 200 ms.
- day, month, year, time, minute, second and millisecond
If starting or tripping commands are already present, the
identifying the tripping moment.
test is not carried out and a dedicated message appears on
- phase current values as measured on the net-side winding
the display unit.
and on the star-point side winding when the trip occurred.
The test on auxiliary relays does not affect counters, event
logs and LED's.
All information identifying one trip is called event.
The circulating memory allows the last 8 events to be stored,
and when this number is exceeded, a new record replaces the 4.11 Alphanumeric plant identifier
older: the latest event is stored as EVENT 1. The device can be identified in the plant by an alphanumeric
The stored events can be read from the front display unit or from code, which can be set by the user directly on the equipment
a PC that is serially connected to the device. or from a PC. With a network-linked device, the alphanumeric
The device can also record the latest 32 changes of state (with code can only be modified by acting via network.
related date and time) and make them available exclusively
through PC or via network. 4.12 Language
The device can display information in four languages: Italian,
4.8 Measurements English, French and Spanish. The language can be selected
The device is in a position to display the present current values through the keyboard.
as measured on the net-side winding 1 and on the star-point
side winding 2, stated in multiples of the rated currents In and 4.13 LCD settings
as an absolute value in Primary Amperes.
The display can be set for fixed (OFF) or timed (ON) back-
It also displays the differential current, stated in multiples of the
lighting; in the last case, the display lights up for 300s any time
rated current. The unit also displays the maximum current
a key is pressed .
values, stated in multiples of the rated currents In, as meas-
ured since the last 'Reset maximum values' ever entered, or
since the latest power supply failure ever affecting the relay. 4.14 Inhibiting operation - Deconfiguring the unit via network
Inhibiting the device is required in operating plants, to avoid
4.9 Breaker pole wear index Σ (I t) 2 inefficiency on feeding a protection whose settings are un-
known or need to be changed.
Every time the protection operates, along with the measured
The inhibition is performed by holding the settings change
fault current values, the parameter Σ(I2t) proportional to the
button pressed for about 2 s,while injecting the auxiliary
power interrupted by each breaker pole is calculated, as a
voltage until the following message is displayed:
'wear index' of the same. [ BLOC ]
It is defined, namely, by Σ(I)2 t_52. [ ]
where:
t_52 is the breaker opening time. On releasing the push-button, the condition of inhibited device
I, phase current expressed in primary Amperes is signalled by a diagnostic message of P fault.
The wear indexes are available in the measurements menu, The normal operating conditions can only be restored by
and may only be reset by acting through a PC or via network. moving to the settings change function, which is enabled at all
events; a temporary loss of the auxiliary voltage supply does
not affect the inhibited state of the device.
4.10 Test
If the device is also equipped with a field-bus board, by holding
Besides the normal diagnostic already dealt with, the device the settings change push-button further pressed for about 2
also offers, in the TEST mode, the possibility of testing the s, in the BLOC state, the device will display:
LED's, the display unit and the output relays. [ NET RESET ? ]
- The LED test turns on all the LED's, from L1 to L8, and the [_ NO YES _]
display unit (LCD) for two seconds.
Once the test is over, the LED's that were supposed to be if a confirmation is provided, the device can also be made lose
ON before the test remain ON and the display unit goes back its network configuration.
to the previous information displayed. The test can also be The full procedure for inhibiting and de-configuring the device
performed in any operating condition, without affecting the via network must be enacted any time you need to replace the
operation in progress. unit.
pag. 10
MX3DPG3A MDE/B133 2501 001
By resetting an inhibited and deconfigured unit, a K fault 4.16 RS485 serial communication and MODBUS protocol
message will be displayed and remain on until the unit
Concerning the communication of devices provided with
undergoes a new configuration process.
software version 2.00 and subsequent, three different versions
Operation can only be reset by moving to the settings change
are possible:
function, a function that always remains enabled .
- whitout any communication card (version
MX3DPG3A .11 e .12);
4.15 Serial communication via LONWORKS (TM) field bus - provided with LonWorks(TM) communication card (version
The device, in the version including the special bus board, can MX3DPG3A .61 e .62);
communicate with a central monitoring and control system at - provided with Modbus communication card (version
a speed equalling 1.2 5 Mbaud. The connection to the field bus MX3DPG3A .71 e .72);
is made through terminals 43 and 45. The identification of the installed communication card is
The communication board, which may also be added later, is automatic.
only enabled if the related jumper is correctly in place in S6, When using an unit provided with LonWorks(TM) communication
whereas it is not enabled in the event of the jumper standing card, it's required first to effect the relay wiring according to its
vertical between S5 and S6 (see fig. 2). wiring diagram and later proceed with the configuration of all
If the jumper is placed in S6 but the communication board is connected devices; the automatic configuration of connected
not provided, the diagnostic function will display a failure devices is possible by connecting a PC provided with PCLTA10
message, as if the board were present but failed to operate. or SLTA10 card, in which CORMOX2 software has been
Appendix A lists the parameters that are available for use with installed.
the network (field bus). When using a device provided with Modbus communication
the configuration of each relay may be realized by the front
interface, or by the IRMA2 program installed on a PC connected
to the relay via front plug. The configuration may be realized
also on relays not jet connected together and may be eventually
TOP SIDE organized in files together with all other settings.
Parity NONE
EVEN
BOARD BOARD ODD
NOT ENABLE
ENABLE
Data Bit 7
8
A-A VIEW A-A VIEW
Stop Bit 1
2
fig. 2
Address 1 - 255 (0 broadcast)
I CAUTION
Hazardous voltages can remain in the device even when
the latter has been de-energized or pulled out of its casing
(capacitor's memory).
pag. 11
MX3DPG3A MDE/B133 2501 001
pag. 12
MX3DPG3A MDE/B133 2501 001
Key It scrolls the menu to the left or selects - Twelve LED's, four of which are rigorously dedicated to
the digit to be changed, if the settings general running functions.
change function is enabled. [ï] - A four-pin connector in compliance with FCC 68.
By means of a special optoelectrical adapter, an optical
fibre cable and a RS232 optical converter, it allows the
Key It resets the stored LED signals if the
device to be locally linked with a personal computer.
cause has been removed, or the par-
The P.C., through a special interface programme, makes
tial counters, if you are in the "display it possible to read and change the settings, read measured
counters" menu. values, counters, logged events, diagnostic- and fault re-
It takes the end relays to quiescent corder-related information.
state when they are set to bistable
operation.
Keys If simultaneously
pressed for at least 2s, these keys
enable the protection to be tested.
When the testing activity is enabled,
the green LED (RUN) lights up blink-
ing.
If simultaneously pressed for at least
2s during the TEST routine, these
keys enable you to leave the protec-
tion testing mode.
pag. 13
MX3DPG3A MDE/B133 2501 001
6. LCD MENU STRUCTURE c) By pressing ò or ñ you scroll the stored languages menu.
For the purpose of our example, we must stop when the
6.1 MAIN VIEWING MENU following message is displayed:
[MENU: ENGLISH ]
The device features a main menu that leads to several sub- [ ]
menus (tree-style structure). All displays can be made perma-
nent . d) By pressing ï you confirm the selected dialogue language
and go back to the main menu. The following message appears
[IA_1 In ] Present value of phase A current on the display:
[IB_1 In ] Present value of phase B current [MENU: ENGLISH ]
ñ ò [ ]
[MENU: ENGLISH] Dialogue language
[ ] ð change dialogue language
ñ ò 6.1.2 Change date and time
[DATE ] present date and time Access to "change date/time" is denied when the protection is
[TIME ] ð change date and time network-connected. If the network connection is made after
ñ ò entering the change function, the local changes are not ena-
[SETTINGS: ] display settings in use
[ MAIN] bled.
ñ ò Let us assume we wish to change the starting date 10/06/93
[SETTINGS READING] ð display main settings into 24/05/95.
[MAIN ]
ñ ò a) Press the key ò or ñ until the display shows:
[SETTINGS READING] ð display spare settings [DATE 10/06/93]
[SPARE ] [TIME 9:38:43]
ñ ò
[ MEASUREMENTS ] ð display/reset present and b) By pressing the key ð the change function is enabled and
[ ] stored measured values
the following message appears on the display:
ñ ò [DATE 10/06/93]
[ COUNTERS ] ð display counters and reset [TIME 9:38:43]
[ P=RESETTABLE ] partial counters
ñ ò
[ EVENTS ] ð display stored events c) By pressing ð select the value to be changed. To select the
[EVENT 1 = LAST] last digit that makes up the date, pressð six times, the displays
ñ ò will show:
[OUTPUT RELAYS] ð display output relays [DATE 10/06/93]
[ ] settings [TIME 9:38:43]
ñ ò
[ DIGITAL ] ð display digital d) By pressing ñ, increase the selected value. Hold the key
[ INPUTS ] inputs settings pressed until the display shows:
ñ ò [DATE 10/06/95]
[ LED ] ð display LED's settings [TIME 9:38:43]
[ ]
ñ ò e) By pressing ï , select the fourth digit that makes up the date,
[ RELAY DATA ] ð display model- software rel. the display will show:
[ ] and plant identifier [DATE 10/06/95]
ñ ò [TIME 9:38:43]
[ DIAGNOSTICS ] ð display faults
[ ] date of last change f) By pressing ò, decrease the selected value until the display
shows:
All the following examples take their start from the main menu. [DATE 10/05/95]
[TIME 9:38:43]
6.1.1 Change dialogue language g) By pressing ï twice further, select the second digit that
The default language is ITALIAN. makes up the date, and the display will show:
Here follows an example showing how to change the dialogue [DATE 10/06/95]
language. Suppose we wish to set ENGLISH as the desired [TIME 9:38:43]
language.
h) By pressing ñ, change the selected value (upon reaching
number 9, the tens will go up by one unit) until the display
a) Press the key ò or ñ until the following message appears shows:
on the display: [DATE 24/05/95]
[MENU: ITALIAN ] [TIME 9:38:43]
[ ]
i) Press ï until you move to the beginning of the line. The
b) By pressing the key ð the language change function is display will show:
enabled, and the following message appears on the display: [DATE 24/05/95]
[MENU: ITALIAN ] [TIME 9:38:43]
[ ]
pag. 14
MX3DPG3A MDE/B133 2501 001
j) By pressing ò the "change time" function is enabled. The c) By pressing ï anywhere in the sub-menu,you will go back
steps are the same as those described in c) to i). to the main viewing menu:
The device does not accept time or date settings that do not
exist. [SETTINGS READING]
[MAIN ]
The time counting starts upon moving from the digits that make
up the time to the wording TIME at the beginning of the line.
6.1.5 Display spare settings
k) By pressing ï the changes made are confirmed and the a) Press ò or ñ until the display shows:
system moves back to the main menu. The display will show: [SETTINGS READING]
[DATE 24/05/95] [SPARE ]
[TIME 9:38:43]
b) Press ð to enter the spare settings viewing menu, and press
ò or ñ to scroll across the whole sub-menu, which will lists :
6.1.3 Display settings in use
a) Press ò or ñ until the display shows, for instance: first differential threshold Id>
[SETTINGS IN USE:] first percent characteristic slope P1
[ MAIN] second percent characteristic slope P2
second differential threshold Id>>
The second line will display the group of settings the device
currently uses. Those parameters that are not present in the SPARE menu will
Any <!> possibly displayed, notwithstanding the contents of the take the same values as the MAIN settings.
second line, indicates the device is working with the SPARE
settings. c) By pressing the key ï anywhere in the sub-menu, you will go
back to the main reading menu:
[SETTINGS IN USE:]
[ <!> MAIN] [SETTINGS READING]
[ SPARE ]
The device will continue working with the SPARE settings as
long as the "change settings" command sent by the IN DIG1 6.1.6 Display current and stored measured values
digital input remains enabled. When the <!> characters disap-
pear, the device restarts working with the group of settings
a) Press the key ò or ñ until the display shows:
displayed.
[ MEASUREMENTS ]
[ ]
6.1.4 Display main settings
b) By pressing the key ð you will enter the measurement
a) Press ò or ñ until the display shows:
viewing menu, and by pressing the key ò or ñ the following
[SETTINGS READING]
[ MAIN ] sub-menu will be scrolled across:
b) By pressing ð, the main settings display sub-menu is present value of phase A net-side curr.in multiples of In IA-1
entered, by pressing ò or ñ the following sub-menu is scrolled: present value of phase B net-side curr. in multiples of In IB-1
present value of phase C net-side curr.in multiples of In IC-1
rated frequency fn present value of ph. A star-p. side curr.in multiples of In IA-2
CT's rated current on net side In-1 present value of ph. B star-p.side curr.in multiples of In IB-2
CT's rated current on star point side In-2 present value of ph. C star-p. side curr.in multiples of In IC-2
CT's primary rated current on net side In TA-1 present value of phase A differential current IA-D
position of CT's polarities on net side POLARITIES0) present value of phase B differential current IB-D
CT's primary rated current on star point side InTA-2 present value of phase A differential current IC-D
position of CT's polarities on star point side POLARITIES0) present value of phase A net-side current in Amperes IA'-1
first differential threshold Id> present value of phase B net-side current in Amperes IB'-1
first percent characteristic slope P1 present value of phase C net-side current in Amperes IC'-1
second percent characteristic slope P2 present value of phase A star-p. side current in Amp. IA'-2
second differential threshold Id>> present value of phase B star-p. side current in Amp IB'-2
breaker failure delay t_BF present value of phase C star-p. side current in Amp IC'-2
minimum pulse width of end relays t_IMP max. value of phase A net-side curr. in multiples of In IA-1- MAX
additional delay t_X1 max. value of phase B net-side curr. in multiples of In IB -1-MAX
additional delay t_X2 max. value of phase C net-side curr. in multiples of In IC -1-MAX
additional delay t_X3 max. value of phase A star-p. side current in In IA-2- MAX
breaker arching time t_52 max. value of phase B star-p. side current in In IB -2-MAX
max. value of phase C star-p. side current in In IC -2-MAX
0
) NORM or INV (see fig.7 ) breaker pole wear index phase A A
breaker pole wear index phase B B
breaker pole wear index phase C C
pag. 15
MX3DPG3A MDE/B133 2501 001
c) Press RESET to cancel the maximum values in store on phase A star-point side current value in multiples of In when the
display. The wear indexes may only be reset by means of a PC trip occurred IA_2_G
or via network. phase B star-point side current value in multiples of In when the
trip occurred IB_2_G
phase C star-point side current value in multiples of In when the
d) Press the key ï anywhere in the sub-menu to go back to
trip occurred IC_2_G
the main viewing menu:
phase A differential current value when the trip occurred in
multiples of In IA_D_G
[ MEASUREMENTS ]
[ ] phase B differential current value when the trip occurred in
multiples of In IB_D_G
phase C differential current value when the trip occurred in
6.1.7 Viewing counters multiples of In IC_D_G
a) Press the key ò or ñ until the following message is
displayed: d) By pressing ï anywhere in the sub-menu, you will go back
to the event viewing sub-menu; to view other events go through
[ COUNTERS ] step c) again. By pressing ï anywhere in the sub-menu you
[ P=RESETTABLE ]
will go back to the main viewing menu:
b) Press ð to enter the counters viewing sub-menu, and press [ EVENTS ]
ò or ñ to scroll across the whole sub-menu, which will list the [EVENT 1=LAST]
following parameters:
total trips of first differential threshold Id> T 6.1.9 Viewing output relays
partial trips of first differential threshold Id> P a) Press ò or ñ until the display shows:
total trips of second differential threshold Id>> T
partial trips of second differential threshold Id>> P [OUTPUT RELAYS]
total trips of breaker failure threshold BF T [ ]
partial trips of breaker failure threshold BF P
b) By pressing ð you will enter the sub-menu that displays the
c) Press the RESET key to reset the count of the partial counter allocations of the auxiliary output relays. The display will shows:
[Id> START]
being displayed.
[REL X..3.5]
d) By pressing ï anywhere in the sub-menu, you will go back the first line will display the function that is associated with the
to the main viewing menu: relay/s that is/are listed in the second line.
By pressing the keys ò or ñ the whole sub-menu will be
[ COUNTERS ] scrolled across. The functions that can be associated with the
[ P=RESETTABLE ] output relays are:
c) By pressing the key ò or ñ, select the event to be displayed. c) By pressing the key ï anywhere in the sub-menu, you will
Once the selection is made, press ð ; thus, you enter the event go back to the main viewing menu:
display sub-menu, and by pressing ò or ñ the following sub-
[OUTPUT RELAYS]
menu is scrolled: [ ]
pag. 16
MX3DPG3A MDE/B133 2501 001
b) By pressing the key ð you will enter the sub-menu that lists 6.1.12 Viewing relay data
the allocation of digital inputs. The following message appears
on the display: a) Press the key ò or ñ until the following message is
[BLOC. 87 ] displayed:
[IN DIG .2.] [ RELAY DATA ]
[ ]
the first line will display the function associated with the digital
inputs that are listed in the second line. b) By pressing the key ð you will enter a sub-menu where the
By pressing the keys ò or ñ the sub-menu is scrolled. protection model and the software release are displayed:
[MX3DPG3A ]
The functions that may be associated with the inputs are:
[Soft Rel. 1.00]
protection trip lock BLOC. 87
timer tX1 start t_X1 c) By pressing the key ò once again, the second line will display
timer tX2 start t_X2 the alphanumeric plant identification code fixed by the user, for
timer tX3 start t_X3 instance:
[PLANT IDENTIFIER]
switching to spare settings
[CELL No. 17bis ]
SETTINGS SWITCH
reset LED's and output relays RESET d) By pressing the key ï anywhere in the sub-menu, you will
go back to the main viewing menu:
The unit may also display the digital inputs that are set to be [ RELAY DATA ]
enabled by normal energizing or de-energizing). [ ]
pag. 17
MX3DPG3A MDE/B133 2501 001
The following table provides the fault codes and the corre- If the settings change menu is already acceded through a PC
sponding fault description: or a network, any local change is inhibited, and the following
message will be displayed:
Code fault description [SETTINGS CHANGE]
A X1 relay coil interrupted or related driver [NOT AVAILABLE ]
B X2 relay coil interrupted or related driver
C X3 relay coil interrupted or related driver The access priority to the changing function among PC, net-
D X4 relay coil interrupted or related driver work and keyboard is time-dependent.
E X5 relay coil interrupted or related driver During the settings change operations, the device continues
F internal feeder failure working with the old settings.
G EEPROM failure All displayed messages may show up at any time.
H Internal RAM failure
[SETTINGS: ] settings in use
I External RAM failure
[MAIN ] ð selection of current settings
J Analogue to Digital converter
ñ ò
K communication board failure or board [SETTINGS CHANGE] ð change main settings
enabled but not configured [MAIN ]
L internal clock failure ñ ò
[SETTINGS CHANGE] ð change spare settings
If jumper S6 (see fig.2) that enables the communication board [SPARE ]
is connected when the board is not present, the K code shows ñ ò
up, as if a failure were detected in the board. [ OUTPUT RELAYS ] ð output relays settings
[ ]
d) As far as the NON-VITAL FAULTS are concerned, by pressing ñ ò
the key ï anywhere in the sub-menu you go back to the main [DIGITAL INPUTS ] ð digital inputs settings
display menu: [ ]
[ DIAGNOSTIC ] ñ ò
[ ] [ LED ] ð LED's settings
[ ]
whereas, as regards the VITAL FAULTS, you can only leave the ñ ò
diagnostic sub-menu, if the device allows you to do that, by [ RELAY DATA ] ð plant identifier setting
entering the “settings change” menu. [ ]
ñ ò
2) Inhibited device [ LCD ] ð permanent display back-lighting
The condition of “inhibited device” is displayed as follows: [AUTOMATIC RETURN] (LCD) enabled
[FAULT <!>]
[..............P ]
By pressing the key anywhere in the changing menu
This condition can only be reset by entering the "settings for at least 2 seconds, you will go back to the main viewing
change“ menu (it is however necessary to confirm when you menu, but you will first be prompted to confirm or discard the
are prompted to SAVE CHANGES, although no setting has changes made:
been changed). [NEW SET.CONFIRM?]
[< NO YES >]
Warning: even simply view the set parameters from the
“settings change” menu, since upon leaving this condition, the By pressing ï all the changes made will be discarded, whereas
device will not be inhibited any longer. by pressing ð the changes made will be confirmed.
If, beside inhibiting the device, you have also deconfigured it, The green LED (RUN) will stop blinking and will become
the return to operation causes a fault K message to be permanent.
displayed until the unit is configured anew (see paragraph If upon confirming the changes, a fault is detected, the settings
4.14). will not be accepted for as long as the fault event persists. This
state will be signalled for 3s by the following message:
pag. 18
MX3DPG3A MDE/B133 2501 001
Note: the “change settings” function can even be implemented Press ò or ñ until the threshold to be changed is displayed as
when the device is “forced” to use the SPARE SETTINGS. In selected on the display unit:
such a case, the system only interrupts the selection of [Id> OFF]
[Id> 0.80 In]
SETTINGS: MAIN until the external forcing signal disappears.
If a setting is changed when the system is “forced” from the
Press ð to be able to edit the selected setting I>>>, the display
outside, the following message will be displayed:
will show:
[SPARE SETTINGS]
[Id> OFF]
[FROM EXT.CONTROL]
[Id> 0.80 In]
All of the following examples start from the main settings Press ò or ñ and choose ON, the display will show:
change menu. [Id> ON ]
[Id> 0.80 In]
6.2.1 Select current settings group
Press ï to move back to the beginning of the line. Then press
a) Press the key ò or ñ until the following message is dis-
ò to enter the second line.
played:
[SETTINGS: ] Press ð to select the digit to be changed.
[ MAIN] In our example, press 5 times the key ð, the display will show:
[Id> ON ]
b) After pressing the key ð, the current settings may start being [Id> 0.80 In]
changed. The following message will be displayed:
[SETTINGS: ] Press ñ to increase the selected number until the desired value
[ MAIN] is reached, in our example:
[Id> ON ]
c) By pressing ò or ñ, the following message will be displayed: [Id> 0.85 In]
[SETTINGS: ]
[ SPARE] Now press ï to select the third digit, the display will show:
[Id> ON ]
d) By pressing the key ï the new selection will be confirmed, [Id> 0.85 In]
and the system will be go back to the main settings change
menu. The following message will be displayed: Press ñ to edit the number (on reaching number 9 the units
[SETTINGS: ] will increase by 1) until the display shows:
[ SPARE] [Id> ON ]
[Id> 1.15 In]
6.2.2 Change main settings By pressing the key ï, the cursor will move back to the
beginning of the line and the main settings change menu will
a) Press the key ò or ñ until the following message is be displayed:
displayed: [SETTINGS CHANGE]
[SETTINGS CHANGE] [MAIN ]
[MAIN ]
b) By pressing the key ð, you will enter the main settings 6.2.3 Change spare settings
change sub-menu, which will list all of the parameters already a) Press the key ò or ñ until the following message is
listed in § 7.1.3, except for In and Ion, which may only be changed displayed:
in the hardware mode, as described in § 2.1.
[SETTINGS CHANGE]
[SPARE ]
c) By pressing the keys ò or ñ , you may scroll across the whole
sub-menu, and by pressing the key ð you may start changing b) By pressing the key ð , you will enter the spare settings
the displayed parameter. The change can be entered by change sub-menu, which will list all of the parameters already
pressing the keys ò or ñ . listed in § 7.1.6.
d) By repeatedly pressing the key ï anywhere in the sub- c) By pressing the keys ò or ñ ,you may scroll across the sub-
menu, you will go back to the main changing menu: menu, and by pressing the key ð you can start changing the
[SETTINGS CHANGE] displayed parameter. The change may be entered by pressing
[MAIN ] the keys ò or ñ .
The settings change procedure mirrors that described in the
Example of setting example already given in the paragraph related to the main
Let us assume we need to enable and set threshold Id> to 1.15 settings.
stating from an initial setting of 0.80, OFF.
Go through steps a) and b).
pag. 19
MX3DPG3A MDE/B133 2501 001
d) By pressing the key ï anywhere in the sub-menu, you will 6.2.5 Setting digital inputs
go back to the main settings change menu:
a) Press the key ò or ñ until the display shows:
[SETTINGS CHANGE]
[SPARE ] [ DIGITAL ]
[ INPUTS ]
6.2.4 Setting output relays b) By pressing the key ð , you enter the digital input setting sub-
a) Press the key ò or ñ until the display shows: menu, which contains all the parameters already listed in §
[OUTPUT RELAYS] 7.1.11.
[ ]
c) By pressing the key ò or ñ the sub-menu is vertically
b) By pressing the key ð, you will enter the output relay setting scrolled, and by pressing the key ð, you can start changing
sub-menu, which contains all the parameters already listed in the selected parameter. The change can be made by pressing
§ 7.1.10, except for NORMAL ON (which can only be set as the key ò or ñ
indicated in § 5.2). The setting procedure mirrors that described in the example
of output relay configuration.
c) By pressing the keys ò or ñ ,you can vertically scroll the sub-
menu, and by pressing the key ð you can start changing the To switch from the main settings to the spare settings, the
displayed parameter. The change can be made by pressing digital input number 1 (IN DIG 1) must be used
the keys ò or ñ. SETTINGS SWITCH
To reset the LED's and the auxiliary relays, the digital input
d) By pressing the key ï anywhere in the sub-menu, you go number 3 (IN DIG 3) must be used.
back to the main settings change menu: RESET(LED+Xmem)
[OUTPUT RELAYS]
[ ] d) By pressing the key ï anywhere in the sub-menu, you go
back to the main changing menu:
Example of allocation [ DIGITAL ]
[ INPUTS ]
Let us assume we need to allocate the trip of threshold Id>
to relay X5 starting from the initial setting of Id> allocated to X2.
Go through steps a) and b). 6.2.6 Setting LED's
Press the key ò or ñ until the display unit shows: a) Press the key ò or ñ until the display shows:
[ LED ]
[Id> TRIP] [ ]
[REL X.2...]
b) By pressing the key ð , the LED setting sub-menu, which
Each position after the letter X corresponds to an output relay. contains the parameters already listed in § 7.1.12., is entered.
More relays can be associated with one function.
c) By pressing the key ò or ñ the sub-menu is vertically
By pressing the key ð, you may move close to the relay that you
scrolled, and by pressing the key ð, you can start changing
wish to associate with the function..
the displayed parameter. The change can be made by press-
In our example, press the key ð five times. The display will
ing the keyò or ñ .The setting procedure mirrors that described
show:
in the example of output relays setting.
[Id> TRIP]
[REL X.2...] d) By pressing the key ï anywhere in the sub-menu , you go
back to the main changing menu:
Press the key ò or ñ to associate the selected relay X5, the [ LED ]
display unit will show: [ ]
[Id> TRIP]
[REL X.2..5] 6.2.7 Setting the plant identifier
a) Press the key ò or ñ until the display shows:
Press the key ï to select the second relay, the display unit will
[ RELAY DATA ]
show: [ ]
[Id> TRIP]
[REL X.2..5]
b) By pressing the key ð, you can change/set an alphanumeric
Press the keyò or ñ to dissociate the selected relay, the display code that identifies the device. The display will show, for
unit will show: instance:
[Id> TRIP] [PLANT IDENTIFIER]
[REL X....5] [CELL N. 17bis ]
Press ï to move back to the beginning of the line and move back
to the main changing menu:
[OUTPUT RELAYS]
[ ]
pag. 20
MX3DPG3A MDE/B133 2501 001
c) Further press the key ð to select the character(s) to be The test to be carried out on any auxiliary relay X..will make the
changed, and press ò or ñ to scroll across all of the capital and latter trip, so that the associated command and/or signal are
small letters of the alphabet, numbers and some special allowed to be sent. That is why, before running it, the systems
characters, among which the blank space is found. prompts you to further confirm its execution:
d) By pressing the key ï, the cursor will move back to the [ ARE YOU SURE? ]
beginning of the line (no character selected), and by further [< NO YES >]
pressing the key ï, you will go back to the main changing menu:
[ RELAY DATA ] If, upon confirming the execution, some starting or tripping
[ ] commands are already present or a digital input associated
with a timer happens to be enabled, the test will not be
6.2.8 LCD back-lighting performed, and this condition will be signalled by the following
a) Press the key ò or ñ until the display shows: message:
[ LCD ] [TEST ]
[AUTOMATIC RETURN] [NOT AVAILABLE ]
b) By pressing the key ð, you may set the LCD back-lighting The LED and display test makes them light up for two seconds.
to permanent (OFF) or timed (ON). Let us assume the display Therefore, it can be run at any time during operation
shows:
[ ON ] By pressing the two keys for two seconds
[ ]
anywhere in the test menu, the TEST function is disabled. The
c) By pressing the keys ò or ñ, the current setting may be
green LED (RUN) stops blinking, and the system will go back
changed: to the main viewing menu.
[ OFF]
[ ]
[TEST LED]
[ YES >] ð TEST LED’s L1-L8 and display
ñ ò
[TEST RELAY X1]
[ YES >] ð TEST relay X1
ñ ò
[TEST RELAY X2]
[ YES >] ð TEST relay X2
ñ ò
[TEST RELAY X3]
[ YES >] ð TEST relay X3
ñ ò
[TEST RELAY X4]
[ YES >] ð TEST relay X4
ñ ò
[TEST RELAY X5]
[ YES >] ð TEST relay X5
pag. 21
MX3DPG3A MDE/B133 2501 001
pag. 22
MX3DPG3A MDE/B133 2501 001
9. SETTING THE UNIT AT WORK Figure 7 shows the way to set the item POLARITY as a function
of the protection insertion type
The relay is supplied with factory settings and configurations
Load the settings and configure the relays, the LED’s and the
as indicated in tables A, B and C (factory settings), which are
digital inputs as per the design plans.
related to the insertion as shown in figure 5.
Since the unit is equipped with a self-monitoring system, all
These settings may happen not to match the specific system
hardware and software failures possibly occurring are auto-
where the unit is to be placed. Therefore, the relay settings
matically detected, which this makes it useless to test the
must be changed in compliance with the tables D, E and F for
thresholds for accuracy, which can however be tested by
provided for customer’s use, which must be used as a support
making reference to the tolerance values as specified by the
to develop a customized setting scheme.
manufacturer.
9.3 Final inspection If the relay has not worked correctly or shows VITAL failures,
Inject auxiliary voltage into the device. it must be put out of order and sent back to the factory for repair
On switching on, after a long time of power failure, the device or re-gauging.
can indicate an 'L' type fault (internal clock), a NON-VITAL The presence of a NON-VITAL fault does not cause an ill-timed
FAULT which does not affect the remaining functions: by operation, but demands an analysis of the fault type to assess
updating DATE and TIME, the normal service conditions are its importance (for instance, a failing end relay should be
restored. replaced with another end relay that is not currently being used
If the system is running and the relay settings are unknown, the or, else, whose function is not strictly required).
unit must be inhibited from operating before feeding it with The possibility of exchanging the relays makes it possible to
voltage by pressing the “settings change” key (see § 5.14 and maintain the protection scheme working during repairs, so
7.1.14 clause 2) to avoid troubles. that any faulty relay can be replaced with a new one of the same
Select the rated frequency of the system on the device, set the type.
rated values of the CT's primary current on the net side and on
the star-point side along with the related polarities.
pag. 23
MX3DPG3A MDE/B133 2501 001
pag. 24
MX3DPG3A MDE/B133 2501 001
RELAY RELAY
FRONT FRONT
fig. 4a fig. 4b
RELAY RELAY
FRONT FRONT
fig. 4c fig. 4d
RELAY RELAY
FRONT FRONT
fig. 5
pag. 26
MX3DPG3A MDE/B133 2501 001
OVERALL DIMENSIONS
fig. 6
pag. 27
MX3DPG3A MDE/B133 2501 001
TA-1
TA-2
TA-1 TA-2
A B polarity C D polarity
P1 S1 NORM P1 S1 NORM
P1 S2 INV P1 S2 INV
P2 S1 INV P2 S1 INV
P2 S2 NORM P2 S2 NORM
fig. 7
pag. 28
MX3DPG3A MDE/B133 2501 001
WARNING:
The factory settings may happen not to suit the system. In such a case, the device needs to be configured anew upon installation
pag. 29
MX3DPG3A MDE/B133 2501 001
WARNING:
The factory settings may happen not to suit the system. In such a case, the device needs to be configured anew upon installation
TABLE OF SETTINGS
DESCRIPTION FUNCTION MAIN SPARE
ON OFF VALUE ON OFF VALUE
rated frequency fn 50 Hz / / /
rated phase current on relay side In-1 5A / / /
CT's primary rated current on relay side In TA-1 200 A / / /
CT's polarity on net side polarity NORM / / /
rated phase current on star-point side In-2 5A / / /
CT's primary rated current on star-point side In TA-2 200 A / / /
CT's polarity on star-point side polarity NORM / / /
pag. 30
MX3DPG3A MDE/B133 2501 001
tab. D
tab. E
/ not to be allocated
pag. 31
MX3DPG3A MDE/B133 2501 001
tab. F
TABLE OF SETTINGS
DESCRIPTION FUNCTION MAIN SPARE
ON OFF VALUE ON OFF VALUE
rated frequency fn / / /
rated phase current on net side In-1 / / /
CT's primary rated current on net side In TA-1 / / /
CT's polarity on net side polarity / / /
rated phase current on star-point side In-2 / / /
CT's primary rated on star-point side In TA-2 / / /
CT's polarity on star-point side polarity / / /
pag. 32
MX3DPG3A MDE/B133 2501 001
Identification
commercial name relay--> centre AR
plant identifier relay--> centre AR
rated phase current on primary side relay--> centre AR
rated phase current on secondary side relay--> centre AR
Present measurements
phase A current on primary side relay--> centre T and AR
phase B current on primary side relay--> centre T and AR
phase C current on primary side relay--> centre T and AR
phase A current on secondary side relay--> centre T and AR
phase B current on secondary side relay--> centre T and AR
phase C current on secondary side relay--> centre T and AR
phase A differential current relay--> centre T and AR
phase B differential current relay--> centre T and AR
phase C differential current relay--> centre T and AR
CT's primary rated current on primary side relay--> centre T and AR
CT's primary rated current on secondary side relay--> centre T and AR
Maximum measurements
phase A overcurrent on primary side on primary side relay--> centre AR
phase B overcurrent on primary side relay--> centre AR
phase C overcurrent on primary side relay--> centre AR
phase A overcurrent on secondary side relay--> centre AR
phase B overcurrent on secondary side relay--> centre AR
phase C overcurrent on secondary side relay--> centre AR
CT's primary rated current on primary side relay--> centre AR
CT's primary rated current on secondary side relay--> centre AR
pag. 33
MX3DPG3A MDE/B133 2501 001
wear index
phase A wear index on primary side relay--> centre AR
phase B wear index on primary side relay--> centre AR
phase C wear index on primary side relay--> centre AR
phase A wear index on secondary side relay--> centre AR
phase B wear index on secondary side relay--> centre AR
phase C wear index on secondary side relay--> centre AR
Event logging
event date / time relay--> centre VP and AR
first differential threshold trip relay--> centre VP and AR
second differential threshold trip relay--> centre VP and AR
breaker failure start relay--> centre VP and AR
breaker failure trip relay--> centre VP and AR
state of digital input 1 relay--> centre VP and AR
state of digital input 2 relay--> centre VP and AR
state of digital input 3 relay--> centre VP and AR
state of timer tX_1 relay--> centre VP and AR
state of timer tX_2 relay--> centre VP and AR
state of timer tX_3 relay--> centre VP and AR
States
first differential threshold trip relay--> centre AV (a.p.)
second differential threshold trip relay--> centre AV (a.p.)
breaker failure trip relay--> centre AV (a.p.)
state of digital input 1 relay--> centre AV (a.p.)
state of digital input 2 relay--> centre AV (a.p.)
state of digital input 3 relay--> centre AV (a.p.)
state of timer tX_1 relay--> centre AV (a.p.)
state of timer tX_2 relay--> centre AV (a.p.)
state of timer tX_3 relay--> centre AV (a.p.)
Locks
protection lock centre--> relay AV
Counters
total trips of first threshold relay--> centre AR
partial trips of first threshold relay--> centre AR
total trips of second threshold relay--> centre AR
partial trips of second threshold relay--> centre AR
total trips of breaker failure threshold relay--> centre AR
partial trips of breaker failure threshold relay--> centre AR
Events
date relay--> centre AR
time relay--> centre AR
tripped threshold relay--> centre AR
phase A fault current value on primary side relay--> centre AR
phase B fault current value on primary side relay--> centre AR
phase C fault current value on primary side relay--> centre AR
phase A fault current value on secondary side relay--> centre AR
phase B fault current value on secondary side relay--> centre AR
phase C fault current value on secondary side relay--> centre AR
phase A differential fault current value relay--> centre AR
phase B differential fault current value relay--> centre AR
phase C differential fault current value relay--> centre AR
pag. 34
MX3DPG3A MDE/B133 2501 001
Output relays
X1 setting relay--> centre--> relay AR
X2 setting relay--> centre--> relay AR
X3 setting relay--> centre--> relay AR
X4 setting relay--> centre--> relay AR
X5 setting relay--> centre--> relay AR
LED's
L1 setting relay--> centre--> relay AR
L2 setting relay--> centre--> relay AR
L3 setting relay--> centre--> relay AR
L4 setting relay--> centre--> relay AR
L5 setting relay--> centre--> relay AR
L6 setting relay--> centre--> relay AR
L7 setting relay--> centre--> relay AR
L8 setting relay--> centre--> relay AR
Digital inputs
input 1 setting relay--> centre--> relay AR
input 1 setting as enabled HIGH/LOW relay--> centre--> relay AR
input 2 setting relay--> centre--> relay AR
Input 2 setting as enabled HIGH/LOW relay--> centre--> relay AR
input 3 setting relay--> centre--> relay AR
input 3 setting as enabled HIGH/LOW relay--> centre--> relay AR
Reset
LED's centre--> relay AR
relays centre--> relay AR
resettable counters centre--> relay AR
maximum measurements centre--> relay AR
wear index centre--> relay AR
Commands
output relays enabling centre--> relay AV and AR
settings switch centre--> relay AV
settings switch survival delay centre--> relay AR
Fault recorder
fault recorder starting parameters relay--> centre--> relay AR
fault recorder pre-triggering time relay--> centre--> relay AR
fault recorder triggering command centre--> relay AR
fault recorder reset command centre--> relay AR
fault recorder data relay--> centre AR
Clock
date centre--> relay S
time centre--> relay S
date relay--> centre AR
time relay--> centre AR
KEY
AR aperiodic message
AV (a.p.) aperiodic variable sent upon high-priority variation
AV aperiodic variable sent upon variation
VP variable on request
T periodic variable with periods to be set between 1 and 5 s
S synchronization
pag. 35
MX3DPG3A MDE/B133 2501 001
pag. 36
ALSTOM T&D Protection & Côntrole is bound by the foregoing specifications, dimensions and diagrams only after confirmation.
ABCD
ALSTOM FIR S.p.a. - via Viscardi, 5 - 24016 SAN PELLEGRINO T. - BG - ITALIA
Tel. ++39 0345 28111 - Fax ++39 0345 22590 - Telex 301152 FIR I - E-mail: alstom.fir@tde.alstom.com