Sie sind auf Seite 1von 2

GRUPO DE ISO 9001:2000

ASISTENCIA Quality Management System Certified


TÉCNICA S.R.L.

Project Information:

Case-specific: 9 vasos en paralelo con LE-440i 27 C Agua sin ablandar

System Details

Feed Flow to Stage 1 100.00 m³/h Pass 1 Permeate Flow 59.99 m³/h Osmotic Pressure:
Raw Water Flow to System 80.00 m³/h Pass 1 Recovery 74.99 % Feed 0.28 bar
Feed Pressure 6.59 bar Feed Temperature 27.0 C Concentrate 1.07 bar
Flow Factor 0.85 Feed TDS 593.61 mg/l Average 0.67 bar
Chem. Dose (100% NaOH) 22.01 mg/l Number of Elements 54 Average NDP 4.86 bar
Total Active Area 2207.30 M² Average Pass 1 Flux 27.18 lmh Power 28.16 kW
Water Classification: RO Permeate SDI < 1 Specific Energy 0.47 kWh/m³
Feed Feed Recirc Conc Conc Perm Avg Perm Boost Perm
Stage Element #PV #Ele Flow Press Flow Flow Press Flow Flux Press Press TDS
(m³/h) (bar) (m³/h) (m³/h) (bar) (m³/h) (lmh) (bar) (bar) (mg/l)
1 HRLE-440i 9 6 100.00 6.24 20.00 40.01 4.98 59.99 27.18 0.00 0.00 15.40
Pass Streams
(mg/l as Ion)
Adjusted Feed Concentrate Permeate
Name Feed
Initial After Recycles Stage 1 Stage 1 Total
NH4+ + NH3 0.00 0.00 0.00 0.00 0.00 0.00
K 29.00 29.00 45.86 113.10 1.02 1.02
Na 50.91 65.43 103.53 255.48 2.19 2.19
Mg 7.78 7.78 12.38 30.73 0.14 0.14
Ca 55.20 55.20 87.84 218.13 0.94 0.94
Sr 0.00 0.00 0.00 0.00 0.00 0.00
Ba 0.00 0.00 0.00 0.00 0.00 0.00
CO3 0.34 1.88 4.83 21.43 0.00 0.00
HCO3 334.40 369.68 582.32 1420.85 10.45 10.45
NO3 1.30 1.30 2.00 4.77 0.15 0.15
Cl 4.00 4.00 6.37 15.86 0.05 0.05
F 0.33 0.33 0.52 1.28 0.01 0.01
SO4 34.00 34.00 54.29 135.36 0.23 0.23
SiO2 25.00 25.00 39.90 99.39 0.22 0.22
Boron 0.00 0.00 0.00 0.00 0.00 0.00
CO2 34.13 7.48 7.93 12.94 9.12 9.12
TDS 542.26 593.61 939.86 2316.40 15.40 15.40
pH 7.10 7.80 7.95 8.07 6.26 6.26

orporation nor The Dow Chemical Company.

1
Grupo de Asistencia Técnica S.R.L. TeleFax: (54-11)4488-4001 / 4209 / 3144 / 3763
Av. Eva Perón 862/4 e-mail: ventas@gat.com.ar
B1704HXV - Ramos Mejía http://www.gat.com.ar
Buenos Aires - Argentina
GRUPO DE ISO 9001:2000
ASISTENCIA Quality Management System Certified
TÉCNICA S.R.L.

Design Warnings

-None-

Solubility Warnings

Langelier Saturation Index > 0


Stiff & Davis Stability Index > 0
Antiscalants may be required. Consult your antiscalant manufacturer for dosing and maximum allowable system recovery.

Stage Details

Perm Flow Perm TDS Feed Flow Feed TDS Feed Press
Stage 1 Element Recovery
(m³/h) (mg/l) (m³/h) (mg/l) (bar)
1 0.12 1.30 9.11 11.11 939.86 6.24
2 0.12 1.21 10.94 9.82 1062.17 5.92
3 0.13 1.14 13.24 8.60 1209.47 5.64
4 0.14 1.07 16.29 7.47 1390.75 5.42
5 0.16 1.01 20.36 6.40 1619.45 5.24
6 0.18 0.94 26.06 5.39 1916.77 5.09

Scaling Calculations

Raw Water Adjusted Feed Concentrate


pH 7.10 7.80 8.07
Langelier Saturation Index -0.17 0.57 1.97
Stiff & Davis Stability Index 0.51 1.22 2.12
Ionic Strength (Molal) 0.01 0.01 0.04
TDS (mg/l) 542.26 593.61 2316.40
HCO3 334.40 369.68 1420.85
CO2 34.12 7.48 12.93
CO3 0.34 1.88 21.43
CaSO4 (% Saturation) 0.48 0.48 4.84
BaSO4 (% Saturation) 0.00 0.00 0.00
SrSO4 (% Saturation) 0.00 0.00 0.00
CaF2 (% Saturation) 0.80 0.80 47.77
SiO2 (% Saturation) 19.38 19.38 67.45

2
Grupo de Asistencia Técnica S.R.L. TeleFax: (54-11)4488-4001 / 4209 / 3144 / 3763
Av. Eva Perón 862/4 e-mail: ventas@gat.com.ar
B1704HXV - Ramos Mejía http://www.gat.com.ar
Buenos Aires - Argentina