Beruflich Dokumente
Kultur Dokumente
Globe Valve
8900 420-1900 21/ 2" Two Pass
Angle Valve
Dominator 300-2100 21/ 2" Two Pass
Ball Valve
Motorized Valve
Solenoid
Operated Valve
1
Self-Operated
Valve
Pressure
Reducing Valve
Check Valve
Pressure
Relief Valve
Flow Switch
NOTES:
Thermometer Adjustment Procedure To Maintain Inlet Temperature
1. Boiler circuit piping must be sized large enough to handle
Above Dew Point
maximum flow through unit.
T1-Temp-Min=110° For Atmospheric
2. Boiler pump sized to boiler design flow requirements.
T1-Temp-Min=125° Sealed Combustion
Aquastat Union
3. All boilers furnished with factory mounted outlet water
temperature gauge. 1. Turn heater on and open valves A & B.
4. Boiler pump purging required. Use terminals supplied. 2. After steady-state operation, if T1 is less than Temp-Min
slowly close valve B until T1 climbs to desired operating
Pressure Switch temperature above Temp-Min.
Notice: These drawings show suggested piping configuration and valving.
Check with local codes and ordinances for specific requirements. 3. If T1 is greater than desired operating temperature, slowly
close valve A to adjust to lower desired temperature above
Temp-Min.
Gas Pressure
Regulator 4. Check after system operating temperature has
stabilized. Make final adjustments.
5. Follow same adjustment procedure for sealed combustion.
Automatic Backflow-Prevention
Air Vent Device
3
MULTIPLE BOILERS
PRIMARY/SECONDARY
LOW TEMPERATURE
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613 HEAT PUMP Hydronic Piping H-4
Rev. 3
Globe Valve
8900 420-1900 21/ 2 " Two Pass
Angle Valve
Dominator 300-2100 21/ 2" Two Pass
Ball Valve
Motorized Valve
SYSTEM SYSTEM
Solenoid RETURN SUPPLY
Operated Valve
Self-Operated
Valve B B
A A
Pressure
Reducing Valve
T1 T1
Check Valve
Pressure
Relief Valve
Flow Switch
Thermometer NOTES:
Adjustment Procedure To Maintain Inlet Temperature
Above Dew Point
1. Boiler circuit piping must be sized large enough to handle
T1-Temp-Min=110° For Atmospheric
maximum flow through unit.
T1-Temp-Min=125° Sealed Combustion
Aquastat Union
2. Boiler pump sized to boiler design flow requirements.
3. All boilers furnished with factory mounted outlet water 1. Turn heater on and open valves A & B.
temperature gauge. 2. After steady-state operation, if T1 is less than Temp-Min
4. Boiler pump purging required. Use terminals supplied. slowly close valve B until T1 climbs to desired operating
Pressure Switch temperature above Temp-Min.
Notice: These drawings show suggested piping configuration and valving. 3. If T1 is greater than desired operating temperature, slowly
Check with local codes and ordinances for specific requirements. close valve A to adjust to lower desired temperature above
Temp-Min.
Gas Pressure
Regulator 4. Check after system operating temperature has
stabilized. Make final adjustments.
5. Follow same adjustment procedure for sealed combustion.
Automatic Backflow-Prevention
Air Vent Device
4
5
6
7
8
9
MULTIPLE BOILERS
PRIMARY/SECONDARY
CONSTANT TEMPERATURE
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613 REVERSE RETURN Hydronic Piping H-15
Rev. 3
Pump
Valve
Globe Valve
Angle Valve
5
Bufferfly Valve
Balance Valve
Ball Valve
1
Motorized Valve
Solenoid
Operated Valve
Self-Operated
Valve
Pressure
Reducing Valve
Check Valve
Pressure
Relief Valve
Flow Switch
Boiler Connection Pipe Sizing
NOTES:
and Heat Exchanger Configuration
1. Boiler circuit piping must be sized large enough to handle
Thermometer Heater Model Pipe size NPS Configurations
maximum flow through unit.
2. Boiler pump sized to boiler design flow requirements. Spectrum 100-400 11 / 2 " Two Pass
3. All boilers furnished with factory mounted outlet water
temperature gauge.
Aquastat Union 8900 420-1900 21/ 2 " Two Pass
4. Boiler pump purging required. Use terminals supplied.
5. Secondary loop pipe diameter must be sized large enough to 8800 2000-4000 3" Two Pass
handle maximum flow through all units.
Pressure Switch
Notice: These drawings show suggested piping configuration and valving. Dominator 300-2100 21/ 2 " Two Pass
Check with local codes and ordinances for specific requirements.
LCD 225-400 11 / 2" Two Pass
Gas Pressure
Regulator LCD 600-2300 21/ 2" Two Pass
10
SINGLE FUTERA FUSION BOILER
PRIMARY/SECONDARY
LOW TEMPERATURE
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613 HEAT PUMP/SWIMMING POOL Hydronic Piping H-16
Pump
Valve
Balance Valve
Pressure
Reducing Valve
1
Check Valve
Pressure
Relief Valve
Flow Switch
2
Thermometer
2
Aquastat Union
Automatic
Air Vent
Temperature &
Pressure
Relief Valve
NOTES:
Vacuum
Relief Valve
1. Boiler circuit piping must be sized large enough to handle
maximum flow through unit.
2. Boiler and pump purging required. Air must be purged from
3-way valve after the boiler is filled. Use purge valves provided.
Purge valve may be located on pump flange. On multiple boiler
Drain Valve
installations the flow switch may fail due to trapped air. Heater Connection Pipe Sizing
(Typ.)
See manual for procedure.
3. All boilers furnished with factory mounted outlet water
temperature gauge. Heater Model Pipe size NPS
Notice: These drawings show suggested piping configuration and valving. Futera Fusion 500-1000 2"
3-Way Check with local codes and ordinances for specific requirements.
Mixing Valve Futera Fusion 1250-2000 21/ 2"
11
MULTIPLE FUTERA FUSION BOILERS
PRIMARY/SECONDARY
REVERSE RETURN
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613 LOW TEMPERATURE Hydronic Piping H-17
2
Pump
Valve
Balance Valve
Pressure 1
Reducing Valve
Check Valve
Pressure
Relief Valve
Flow Switch
3
Thermometer
Aquastat Union 3
Automatic
Air Vent
Temperature &
Pressure
Relief Valve Factory Piped
NOTES:
12
BOILER PROTECTION OPTION
FOR VARIABLE LOW
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613 TEMPERATURE
THERMOSTATIC MIXING VALVE
Hydronic Piping H-18
NOTES:
13
BOILER PROTECTION OPTION
FOR MULTIPLE BOILERS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613 LOW VARIABLE TEMPERATURE
THERMOSTATIC MIXING VALVE
Hydronic Piping H-19
NOTES:
14
SINGLE BOILER
PRIMARY/SECONDARY
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
SWIMMING POOL
THERMOSTATIC MIXING VALVE
Hydronic Piping H-20
NOTES:
15
SINGLE BOILER
PRIMARY/SECONDARY
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
SWIMMING POOL
BALANCING VALVE
Hydronic Piping H-21
NOTES:
Balance Valve
16
ONE HEATER
TWO PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
ONE VERTICAL TANK Domestic Piping D-1
Rev. 6
Pump
Valve
Globe Valve
Angle Valve
Bufferfly Valve
Balance Valve
3
1
Ball Valve
8
4
Motorized Valve
Solenoid
Operated Valve 2
Self-Operated
Valve
Pressure
Reducing Valve
Temperature & Vacuum Drain Valve Futera 500-1000 2" Four Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve Futera 1250-2000 21/ 2" Four Pass
17
ONE HEATER
TWO PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
TWO VERTICAL TANKS Domestic Piping D-2
Rev. 6
Valve
Globe Valve
Angle Valve
Bufferfly Valve
3
Balance Valve
8
6
Ball Valve
4
1
Motorized Valve 7
2
Solenoid
Operated Valve
7
Self-Operated 2
Valve
Pressure
Reducing Valve
Check Valve
NOTES: Attention:
Not all RBI stock storage tanks
1. Optional cold water make up and recirculation line location. incorporate this tapping: See Note 1.
Pressure 2. When using intermittent pump and pump delay, locate remote aquastat well
Relief Valve in lower 1/3 of tank. Install aquastat with heat sensing compound.
3. Thermal expansion tank may be required, check local codes.
4. When using optional factory mounted pump, max pipe length 30' total, 6-90° Heater Connection Pipe Sizing
Flow Switch elbows, full pipe size. and Heat Exchanger Configuration
5. CAUTION: TEST WATER HARDNESS AND pH AT JOB SITE.
The pH and water hardness must be measured before selecting heat Heater Model Pipe size NPS Configurations
exchanger and pump. Consult the Heat Exchanger Graph and
Thermometer Pumping Performance Table before making selection. Spectrum 100-250 11 / 2 " Four Pass
6. Common piping must be sized for maximum combined heater flow.
7. Hot water tanks should be equipped with a combination Spectrum 300-400 11 / 2 " Two Pass
temperature & pressure relief valve.
Aquastat Union 8. MA Code requires an 1/8" hole in check valve to compensate for thermal 8900 420-1900 21/ 2 " Two Pass
expansion.
8800 2000-4000 3" Two Pass
Notice: These drawings show suggested piping configuration and valving.
Pressure Switch Check with local codes and ordinances for specific requirements. Dominator 300-2100 21/ 2" Two Pass
Tempera ture & Vacuum Drain Valve Futera 500-1000 2" Four Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve Futera 1250-2000 21/ 2 " Four Pass
18
TWO HEATERS
TWO PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
ONE VERTICAL TANK Domestic Piping D-3
Rev.6
Valve
Globe Valve
Angle Valve
Bufferfly Valve
1
Balance Valve
4
Ball Valve
6 3
8
Motorized Valve
4
Solenoid
Operated Valve
7
Self-Operated
Valve
2
Pressure
Reducing Valve
Check Valve
NOTES: Attention:
Not all RBI stock storage tanks
1. Optional cold water make up and recirculation line location.
2. When using intermittent pump and pump delay, locate remote aquastat well in incorporate this tapping: See Note 1.
Pressure
Relief Valve lower 1/3 of tank. Install aquastat with heat sensing compound.
3. Thermal expansion tank may be required, check local codes.
4. When using optional factory mounted pump, max pipe length 30' total, 6-90° Heater Connection Pipe Sizing
Flow Switch
elbows, full pipe size.
5. CAUTION: TEST WATER HARDNESS AND pH AT JOB SITE. and Heat Exchanger Configuration
The pH and water hardness must be measured before selecting heat Heater Model Pipe size NPS Configurations
exchanger and pump. Consult the Heat Exchanger Graph and
Thermometer Pumping Performance Table before making selection. Spectrum 100-250 11/ Four Pass
2"
6. Common piping must be sized for maximum combined heater flow.
7. Hot water tanks should be equipped with a combination Spectrum 300-400 11/ 2 " Two Pass
temperature & pressure relief valve.
8. MA Code requires an 1/8" hole in check valve to compensate for thermal 8900 420-1900 21/ 2 " Two Pass
Aquastat Union
expansion.
8800 2000-4000 3" Two Pass
Pressure Switch Notice: These drawings show suggested piping configuration and valving.
Check with local codes and ordinances for specific requirements. Dominator 300-2100 21/ 2 " Two Pass
Te mperature & Vacuum Drain Valve Futera 500-1000 2" Four Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve Futera 1250-2000 21/ 2" Four Pass
19
TWO HEATERS
TWO PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
TWO VERTICAL TANKS Domestic Piping D-4
Rev. 6
Valve
Globe Valve
Angle Valve
4
Bufferfly Valve
3
Balance Valve 8
6
4
Ball Valve
1
7
Motorized Valve
2
Solenoid
Operated Valve 7
2
Self-Operated
Valve
Pressure
Reducing Valve
Temperature & Vacuum Drain Valve Futera 500-1000 2" Four Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve Futera 1250-2000 21/ 2" Four Pass
20
45 ' #
,#!6 / 5578
9:47:8; , < 9:47:849
$:
%
" #$
# " #$ 9
1 ## " #$
#!
! " #$
#,
!
" #$
%
!% " #$
21
45 &- ) &
/)(6 # 57589
7:;<8;9<=7 /'> 7:;<8;97:
*;
+
! " #
" $ " %
!')*
)3 !')*
) !')*
:
+//&/)2 !')*
7
8
')' !')*
')) !')*
= 4
#&1( !')*
)(
&'( !')*
= 4
)/
&'(
!')*
&+&
(+ !')*
-0 !')*
A
&+& 7;
') )( ,'& '0 +
'( &&+)' ) )';
)/ !')* 4; - + &
+
'(
+
()'26 )' & '.+'' ,))
),& 7?: / '0; ')) '.+'' ,- -'
+(;
:; -&') >
' '0 '2 3 &.+&(6 -0 )') (; '&
1
), ,- ; - +
') /'&2 +(
+
6 '>
)- :5B ')6
95C '( ' >-'& /+&'
)3,6 /+))
1;
<; "A #"
D ; '& #()
1 /+&'
-
'( ,'& -'&( + 3 '+&( 3/& ) -'
-&& >-'& '(
+
; +) - ' >-'& &'
- '(
&+ 755
4<5 77? 4 @ +& '
+
&/&' '3) 3/& '0 );
;
+ 3 1( /& '>+ 3( -'& /),;
&+ :55
55 77? 4 @ , '
=; ,'& '0 -+)( 3 .+
22
6 '. * '
0*)& 2 6678
9:;7:8; 0(< 9:;7:89
+:
,
!"# $ %& ""%
$(*+
#*5 $(*+
* $(*+ 9
!,00'0*4 $(*+
7
!(*( $(*+
!(** $(*+
2'3) $(*+
*)
'() $(*+
*0
'()
$(*+
','
), $(*+
".1 $(*+
?
:
(* *) -(' (1 ,
() '',*( * *(:
',' : . , '
,
()
,
)*(4& *( ' (/,(( -**
*0 $(*+ *-' =9 0 (1: (** (/,(( -. .(
,):
9: .'(* <
( (1 (4 5 '/,')& .1 *(* ):
: . ,
(* 0('4 ,)
,
& (<
*. 96@ (*&
86A (' "
3
*- -. *5-& 0,**
3: () ( <.(' "0,'(
;: "%? 2%
B! :
.
() -(' .(') , 5 (,') 50' * .( (' 2)*
3 "0,'(
<.(' ()
,
: ",* . ( <.(' #'(
. ()
.'' ,
'0'( (5* 50' (1 *:
', 66
;6 = > ,' (
: "
, 5 3) 0' (<, 5) .(' 0*-:
: -(' (1 .,*) 5 /,
23
TWO HEATERS
TWO PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
TWO HORIZONTAL TANKS Domestic Piping D-8
Rev.4
Globe Valve
Angle Valve
1
3 6
Bufferfly Valve
4
Balance Valve 8
Ball Valve 4
Motorized Valve
7 2
Solenoid
Operated Valve
7 2
Self-Operated
Valve
6
Pressure
Reducing Valve
Check Valve
NOTES:
1. Optional cold water make up and recirculation line location.
Pressure 2. When using intermittent pump and pump delay, locate remote aquastat well in
Relief Valve lower 1/3 of tank. Install aquastat with heat sensing compound.
3. Thermal expansion tank may be required, check local codes.
4. When using optional factory mounted pump, max pipe length 30' total, 6-90¡ Heater Connection Pipe Sizing
Flow Switch elbows, full pipe size. and Heat Exchanger Configuration
5. CAUTION: MEASURE WATER HARDNESS AND pH AT JOB SITE.
The pH and water hardness must be measured before selecting heat Heater Model Pipe size NPS Configurations
exchanger and pump. Consult the Heat Exchanger Graph and
Thermometer Pumping Performance Table before making selection. Spectrum 100-250 11 / 2 " Four Pass
6. Common piping must be sized for maximum combined heater flow.
7. Hot water tanks should be equipped with a combination Spectrum 300-400 11 / 2 " Two Pass
temperature & pressure relief valve.
Aquastat Union 8. MA Code requires an 1/8" hole in check valve to compensate for thermal 8900 420-1900 21/ 2 " Two Pass
expansion.
Notice: These drawings show suggested piping configuration and valving. 8800 2000-4000 3" Two Pass
Pressure Switch Check with local codes and ordinances for specific requirements. Dominator 300-2100 21/ 2 " Two Pass
LCD 225-400 11 / 2 " Two Pass
Gas Pressure
Regulator LCD 600-2300 21/ 2 " Two Pass
Temperature & Vacuum Drain Valve Futera 500-1000 2" Four Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve Futera 1250-2000 21/ 2 " Four Pass
24
ONE HEATER
SINGLE PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
ONE VERTICAL TANK Domestic Piping D-9
Rev. 6
Pump
Valve
Globe Valve
Angle Valve
Bufferfly Valve
Balance Valve 3
1
4
Ball Valve 8
Motorized Valve
7
Solenoid
Operated Valve 2
Self-Operated
Valve
Pressure
Reducing Valve Attention:
Not all RBI stock storage tanks
Check Valve NOTES: incorporate this tapping: See Note 1.
Te mperature & Vacuum Drain Valve 8800 2000-4000 4" Single Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve 8900 420-1900 21/ 2" Single Pass
25
TWO HEATERS
SINGLE PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
ONE VERTICAL TANK Domestic Piping D-10
Rev. 6
Valve
Globe Valve
Angle Valve
Bufferfly Valve
Balance Valve
6 4
3
Ball Valve
8 4
Motorized Valve
Solenoid
Operated Valve
2
Self-Operated
Valve
Pressure 1
Reducing Valve
Check Valve
Attention:
NOTES: Not all RBI stock storage tanks
incorporate this tapping: See Note 1.
1. Optional cold water make up and recirculation line location.
Pressure 2. When using intermittent pump and pump delay, locate remote aquastat well in
Relief Valve
lower 1/3 of tank. Install aquastat with heat sensing compound.
3. Thermal expansion tank may be required, check local codes.
4. When using optional factory mounted pump, max pipe length 30' total, 6-90°
Flow Switch elbows, full pipe size.
5. CAUTION: TEST WATER HARDNESS AND pH AT JOB SITE.
The pH and water hardness must be measured before selecting heat
exchanger and pump. Consult the Heat Exchanger Graph and
Thermometer Pumping Performance Table before making selection.
6. Common piping must be sized for maximum combined heater flow.
7. Hot water tanks should be equipped with a combination
temperature & pressure relief valve.
Aquastat Union 8. MA Code requires an 1/8" hole in check valve to compensate for thermal
expansion.
Notice: These drawings show suggested piping configuration and valving.
Pressure Switch
Check with local codes and ordinances for specific requirements.
Heater Connection Pipe Sizing
and Heat Exchanger Configuration
Gas Pressure
Regulator Heater Model Pipe size NPS Configurations
Te mperature & Vacuum Drain Valve 8800 2000-4000 4" Single Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve 8900 420-1900 21/ 2" Single Pass
26
ONE HEATER
SINGLE PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
TWO VERTICAL TANKS Domestic Piping D-11
Rev.6
Valve
Globe Valve
Angle Valve
Bufferfly Valve
Balance Valve 3
8 4
6
Ball Valve
Motorized Valve
1
7
Solenoid
Operated Valve 2
7
Self-Operated
Valve
2
Pressure
Reducing Valve
Check Valve
NOTES:
Attention:
1. Optional cold water make up and recirculation line location.
Pressure 2. When using intermittent pump and pump delay, locate remote aquastat well in
Not all RBI stock storage tanks
Relief Valve lower 1/3 of tank. Install aquastat with heat sensing compound. incorporate this tapping: See Note 1.
3. Thermal expansion tank may be required, check local codes.
4. When using optional factory mounted pump, max pipe length 30' total, 6-90°
Flow Switch elbows, full pipe size.
5. CAUTION: TEST WATER HARDNESS AND pH AT JOB SITE.
The pH and water hardness must be measured before selecting heat
exchanger and pump. Consult the Heat Exchanger Graph and
Thermometer Pumping Performance Table before making selection.
6. Common piping must be sized for maximum combined heater flow.
7. Hot water tanks should be equipped with a combination
temperature & pressure relief valve.
Aquastat Union 8. MA Code requires an 1/8" hole in check valve to compensate for thermal
expansion.
Pressure Switch Notice: These drawings show suggested piping configuration and valving.
Check with local codes and ordinances for specific requirements.
Heater Connection Pipe Sizing
and Heat Exchanger Configuration
Gas Pressure
Regulator Heater Model Pipe size NPS Configurations
Temperature & Vacuum Drain Valve 8800 2000-4000 4" Single Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve 8900 420-1900 21/ 2" Single Pass
27
TWO HEATERS
SINGLE PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
TWO VERTICAL TANKS Domestic Piping D-12
Rev. 6
Valve
Globe Valve
Angle Valve
Bufferfly Valve
3 4
Balance Valve 8
6
Ball Valve 4
1
7
Motorized Valve
2
Solenoid
Operated Valve 7
2
Self-Operated
Valve
Pressure
Reducing Valve
Check Valve
NOTES:
Attention:
1. Optional cold water make up and recirculation line location. Not all RBI stock storage tanks
2. When using intermittent pump and pump delay, locate remote aquastat well in
lower 1/3 of tank. Install aquastat with heat sensing compound.
incorporate this tapping: See Note 1.
Pressure
Relief Valve 3. Thermal expansion tank may be required, check local codes.
4. When using optional factory mounted pump, max pipe length 30' total, 6-90°
elbows, full pipe size.
5. CAUTION: TEST WATER HARDNESS AND pH AT JOB SITE.
Flow Switch
The pH and water hardness must be measured before selecting heat
exchanger
and pump. Consult the Heat Exchanger Graph and
Thermometer
Pumping Performance Tabl e before making selection.
6. Common piping must be sized for maximum combined heater flow.
7. Hot water tanks should be equipped with a combination
temperature & pressure relief valve.
8. MA Code requires an 1/8" hole in check valve to compensate for thermal
Aquastat Union
expansion.
Notice: These drawings show suggested piping configuration and valving.
Pressure Switch Check with local codes and ordinances for specific requirements.
Heater Connection Pipe Sizing
and Heat Exchanger Configuration
Gas Pressure
Regulator Heater Model Pipe size NPS Configurations
Temperatur e & Vacuum Drain Valve 8800 2000-4000 4" Single Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve 8900 420-1900 21/ 2 " Single Pass
28
34 ' #
5+#!6 . 4478
9:3798:; + < 9:37983
$9
%
" #$
# " #$
0 # " #$
;
0 ## " #$
#!
! " #$
#+
!
" #$
%
!% " #$
29
456 &- ) &
/)(7 # 6689
:;<58;9<= /'> :;<58;95:
*;
+
! " #
" $ " %
!')*
)3 !')*
) !')*
:
+//&/)2 !')*
')' !')* 8
')) !')*
#&1( !')*
= 4
)(
&'( !')*
= 4
)/
&'(
!')*
5
&+&
(+ !')*
-0 !')*
C
;
') )( ,'& '0 +
'( &&+)' ) )';
&+& 4; - + &
+
'(
+
()'27 )' & '.+'' ,))
)/ !')* ),& @: / '0; ')) '.+'' ,- -'
+(;
:; -&') >
' '0 '2 3 &.+&(7 -0 )') (;
; - +
') /'&2 +(
+
7 '>
)- :6D ')7 5
96E
), ,- )3,7 /+))
1;
<; "C #"
F ;
-
'( ,'& -'&( + 3 '+&( 3/& ) -'
>-'& '(
+
; +) - ' >-'& &'
- '(
-&& +
&/&' '3) 3/& '0 );
5;
+ 3 1( /& '>+ 3( -'& /),;
=; ,'& '0 -+)( 3 .+
30
5 &- ) &
/)(% 1 5567
89:6:7; /'< 89:6:79
*: 8
+
!" # $% ""$
#')*
)4 #')*
) #')*
!+//&/)3 #')* 9
!')' #')* 8
6
!')) #')*
8
1&2( #')*
;
)(
&'( #')*
)/
&'(
#')*
&+&
(+ #')*
31
TWO HEATERS
SINGLE PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
TWO HORIZONTAL TANKS Domestic Piping D-16
Rev. 4
Globe Valve
Angle Valve
6
Bufferfly Valve 3
1
Balance Valve
8 4
Ball Valve
Motorized Valve 4
7 2
Solenoid
Operated Valve
7 2
Self-Operated
Valve
6
Pressure
Reducing Valve
Check Valve
NOTES:
1. Optional cold water make up and recirculation line location.
Pressure 2. When using intermittent pump and pump delay, locate remote aquastat well in
Relief Valve lower 1/3 of tank. Install aquastat with heat sensing compound.
3. Thermal expansion tank may be required, check local codes.
4. When using optional factory mounted pump, max pipe length 30' total, 6-90¡
Flow Switch elbows, full pipe size.
5. CAUTION: MEASURE WATER HARDNESS AND pH AT JOB SITE.
The pH and water hardness must be measured before selecting heat
exchanger and pump. Consult the Heat Exchanger Graph and Pumping
Thermometer Performance Table before making selection.
6. Common piping must be sized for maximum combined heater flow.
7. Hot water tanks should be equipped with a combination
temperature & pressure relief valve.
Aquastat Union 8. MA Code requires an 1/8" hole in check valve to compensate for thermal
expansion.
Notice: These drawings show suggested piping configuration and valving.
Pressure Switch Check with local codes and ordinances for specific requirements.
Heater Connection Pipe Sizing
and Heat Exchanger Configuration
Gas Pressure
Regulator Heater Model Pipe size NPS Configurations
Temperature & Vacuum Drain Valve 8800 2000-4000 4" Single Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve 8900 420-1900 21/ 2 " Single Pass
32
FUTERA FUSION
WITH BYPASS PIPING
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
ONE VERTICAL TANK Hydronic Piping D-17
Pump
7
Valve 8
Balance Valve
8
Pressure
Reducing Valve
Check Valve 5
Pressure
Relief Valve
1
D-17
Flow Switch
2
Thermometer
6
Aquastat Union
Automatic
Air Vent
NOTES:
1. When using intermittent pump and pump delay, locate remote aquastat well in
Temperature &
Pressure lower 1/3 of tank. Install aquastat with heat sensing compound.
Relief Valve 2. Thermal expansion tank may be required, check local codes..
3. CAUTION: MEASURE WATER HARDNESS AND pH AT JOB SITE.
Be sure to specify when ordering the pH and water hardness. This must be
measured before selecting heat exchanger and pump. Consult the Heat
Exchanger Graph before making selection.
Vacuum
4. Common piping must be sized for maximum combined heater flow.
Relief Valve
5. Hot water tanks should be equipped with a combination temperature &
pressure relief valve.
6. MA Code requires an 1/8" hole in check valve to compensate for thermal
expansion.
7. Use balance valve to set the temperature rise through the boiler. (Delta T)
Drain Valve 8. Boiler and pump purging required. Air must be purged from 3-way valve after
(Typ.) Heater Connection Pipe Sizing the boiler is filled. Use purge valves provided. Purge valve may be located on
pump flange. On multiple boiler installations the flow switch may fail
Heater Model Pipe size NPS due to trapped air. See manual for procedure.
Futera Fusion 500-1000 2" Notice: These drawings show suggested piping configuration and valving.
3-Way Check with local codes and ordinances for specific requirements.
Mixing Valve Futera Fusion 1250-2000 21/ 2"
33
TWO FUTERA FUSION
WITH BYPASS PIPING
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
TWO VERTICAL TANK Hydronic Piping D-18 Rev. 1
Pump 7
8
Valve
Balance Valve 7
8
4
2
Pressure 8
Reducing Valve 6
1
5
Check Valve
2
Pressure 5
Relief Valve
1
Flow Switch
Thermometer
Aquastat Union
Automatic
Air Vent
NOTES:
1. When using intermittent pump and pump delay, locate remote aquastat well in
lower 1/3 of tank. Install aquastat with heat sensing compound.
Temperature &
Pressure
2. Thermal expansion tank may be required, check local codes..
Relief Valve 3. CAUTION: TEST WATER HARDNESS AND pH AT JOB SITE.
Be sure to specify when ordering the pH and water hardness. This must be
measured before selecting heat exchanger and pump. Consult the Heat
Exchanger Graph before making selection.
4. Common piping must be sized for maximum combined heater flow.
Vacuum 5. Hot water tanks should be equipped with a combination temperature &
Relief Valve
pressure relief valve.
6. MA Code requires an 1/8" hole in check valve to compensate for thermal
expansion.
7. Use balance valve to set the temperature rise through the boiler. (Delta T)
8. Boiler and pump purging required. Air must be purged from
Drain Valve 3-way valve after the boiler is filled. Use purge valves provided.
(Typ.) Heater Connection Pipe Sizing Purge valve may be located on pump flange. On multiple boiler
installations the flow switch may fail due to trapped air.
Heater Model Pipe size NPS See manual for procedure.
Futera Fusion 500-1000 2" Notice: These drawings show suggested piping configuration and valving.
3-Way Check with local codes and ordinances for specific requirements.
Mixing Valve Futera Fusion 1250-2000 21/ 2 "
34
TWO FUTERA FUSION
WITH BYPASS PIPING
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
ONE VERTICAL TANK Hydronic Piping D-19
Pump 7
8
Valve
Balance Valve 7
8
4
2
Pressure 8
Reducing Valve 6
1
Check Valve
Pressure
Relief Valve 1
Flow Switch
Thermometer
Aquastat Union
Automatic
Air Vent
NOTES:
1. When using intermittent pump and pump delay, locate remote aquastat well in
lower 1/3 of tank. Install aquastat with heat sensing compound.
Tempera ture &
Pressure
2. Thermal expansion tank may be required, check local codes..
Relief Valve 3. CAUTION: TEST WATER HARDNESS AND pH AT JOB SITE.
Be sure to specify when ordering the pH and water hardness. This must be
measured before selecting heat exchanger and pump. Consult the Heat
Exchanger Graph before making selection.
4. Common piping must be sized for maximum combined heater flow.
Vacuum 5. Hot water tanks should be equipped with a combination temperature &
Relief Valve
pressure relief valve.
6. MA Code requires an 1/8" hole in check valve to compensate for thermal
expansion.
7. Use balance valve to set the temperature rise through the boiler. (Delta T)
8. Boiler and pump purging required. Air must be purged from
Drain Valve 3-way valve after the boiler is filled. Use purge valves provided.
(Typ.) Heater Connection Pipe Sizing Purge valve may be located on pump flange. On multiple boiler
installations the flow switch may fail due to trapped air.
Heater Model Pipe size NPS See manual for procedure.
Futera Fusion 500-1000 2" Notice: These drawings show suggested piping configuration and valving.
3-Way Check with local codes and ordinances for specific requirements.
Mixing Valve Futera Fusion 1250-2000 21/ 2 "
35
ONE HEATER
2-PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
3-VERTICAL TANKS Domestic Piping D-20
Valve
Globe Valve
Angle Valve
Bufferfly Valve
3
Balance Valve
8
6
4
Ball Valve
1
7
Motorized Valve
2
Solenoid
Operated Valve 2
Self-Operated 2
Valve
Pressure
Reducing Valve
Check Valve
NOTES:
Te mperature & Vacuum Drain Valve Futera 500-1000 2" Four Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve Futera 1250-2000 21/ 2 " Four Pass
36
ONE HEATER
2-PASS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
4-VERTICAL TANKS Domestic Piping D-21
Valve
Globe Valve
Angle Valve 3
8
6
Bufferfly Valve 4
1
Balance Valve 7
Ball Valve 7
2
Motorized Valve
7
2
Solenoid
Operated Valve 7
6
2
Self-Operated
Valve
Pressure
Reducing Valve
Check Valve
NOTES:
Temperature & Vacuum Drain Valve Futera 500-1000 2" Four Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve Futera 1250-2000 21/ 2 " Four Pass
37
THREE HEATERS
TWO VERTICAL TANKS
260 North Elm Street - Westfield, MA 01089
413.568.9571 fax 413.568.9613
Valve
Globe Valve
Angle Valve
4
Bufferfly Valve
3
Balance Valve 6 8
4
Ball Valve
1
7
4
Motorized Valve
2
Solenoid
Operated Valve 2
Self-Operated
Valve
Pressure
Reducing Valve
Temperature & Vacuum Drain Valve Futera 500-1000 2" Four Pass
Automatic Pressure Relief Valve (Typ.)
Air Vent Relief Valve Futera 1250-2000 21/ 2" Four Pass
38
39
40