Beruflich Dokumente
Kultur Dokumente
TECHNICAL PRESENTATION
COURSE OUTLINE
Kato Alternator
MGS Standard Rating Available
MGS Standard Rating Available
MGS Basic Installation Requirement
Foundation Pad
1. Fuel pipes should be B.I pipe and must have separate and individual line for supply and
return pipe line especially when having multiple generator set.
2. Fuel Day Tank maximum height should not be exceed 1.5M from center line of generator
set as shown in the drawing section detail.
3. Prior to fuel filling, it should be flash out and clean from welding flux or foreign material.
4. Fuel supply line should be with wye strainer and ball valve for maintenance purpose.
5. Fuel-water should be installed inside fuel day tank containment area.
Exhaust System
1. Exhaust pipe system restriction including muffler must not exceed
600mmH2O.
2. Flexible joint should be free and not carrying the weight of exhaust
muffler and exhaust pipe.
3. Internal temperature of exhaust pipe may reach up to 500-600 degree
Celsius. Nearby material should be fire retardant.
4. Exhaust muffler and exhaust pipe should have minimum of two (2) inch
thick Rockwool insulation with wire mesh prior to aluminum cladding.
5. Provide drain pipe at lowest portion of exhaust piping system.
6. Exhaust tail end should have flapper for vertical end and tapered cut for
horizontal end.
7. MHIESP will conduct final inspection on exhaust flexible flange for
foreign debris prior to genset start up.
Electrical System
1. Make sure that power cables with the same phase must not be laid out
together and per phase power cable ampacity must not be less than rated
current of generator set.
2. Generator output should have CB prior to Automatic Transfer Switch or
Manual Transfer Switch to load side. CB over current relay should be set
as per rated current of generator set.
3. Provide power cable at generator set neutral bus bar going to generator set
ground, if required.
4. Provide grounding connection from generator body frame to building
grounding system.
5. Provide 220V AC power supply for every generator set battery charger
with dedicated CB on the distribution panel.
6. Other device may need separate power supply depend on option
accessories included.
Engine and AC Alternator Specification
Engine Specification
SAE 40
Alternator Specification
Alternator Specification
MGS SYSTEM CONTROL & DEVICES
Outgoing
Terminal
AVR Diesel Engine
Radiator
Gov. Act. L.O press C/W
Sensor Sensor
Exciter Stator
PMG
Battery
Governor
Controller
I/F
MGS 7310 Controller
Frequency Adj.
Engine Protection Measurement Circuit
Voltage Adj.
Generator Measurement Circuit
Other Circuit
Communication Port
(USB port for programming, RS485, RS232
7310 Panel
Generator Control Panel (Local)
Generator Local Panel
Note: Once 560 module is damage, replacement should be 7310 panel assembly
Operation Comparison
Key switch
Start button
Manual Button
Key switch
Auto Button
N N
G1 G2
W W
U V U V
CB CB
“ON” “OFF”
DG1 DG2
Synch Panel Full Manual Operation
Synch Panel Full Manual Operation
DIESEL GENERATOR
MAINTENANCE
Safety it’s up to you
Safety it’s up to you
PERFORM PERIODIC MAINTENANCE PER
RUNNING HOUR INTERVALS OR WHICH
EVER COME FIRST
ADJUST
WALK AROUND INSPECTION
BEFORE OPERATION
WALK AROUND INSPECTION
DURING OPERATION
WEEKLY INSPECTION
ANALYZE
ENGINE OIL
PROPERTIES
ANALYZE
COOLANT
PROPERTIES
Every 2 years or 250 running hours
MAINTENANCE FOR AC
GENERATOR AND SWITCHGEAR
Every 3 Months:
GENERATOR AND SWITCHGEAR
Every Year:
GENERATOR AND SWITCHGEAR
Every Year:
Scope of Rank Maintenance
Rank A
Rank B, C & D
Rank E ( For SU Genset)
Rank F1
BASIC TROUBLESHOOTING
Basic Troubleshooting
Basic Troubleshooting
Basic Troubleshooting
Basic Troubleshooting
Basic Troubleshooting
Basic Troubleshooting
Basic Troubleshooting
Thank You!