Sie sind auf Seite 1von 60

MITSUBISHI GENERATOR SET

TECHNICAL PRESENTATION
COURSE OUTLINE

1. Rating Definition 7. MGS Local Panel


2. Mitsubishi Alternators & Ratings 8. System Flow Diagram
3. Basic Installation Requirement 1. Cooling system
a. Foundation Pad or Slab 2. Air intake & exhaust system
b. Ventilation 3. Fuel System
4. Lubrication system
c. Fuel System
d. Exhaust System 9. Synchronization & Parallel
Operation
4. Engine and AC Alternator
Specification 10. Maintenance
6. MGS Control & Devices 11. Basic Troubleshooting
RATING DEFINITION
MITSUBISHI MGS ALTERNATORS

Stamford Alternator Leroy-Somer Alternator

Kato Alternator
MGS Standard Rating Available
MGS Standard Rating Available
MGS Basic Installation Requirement
Foundation Pad

1. Foundation Pad should be levelled smoothly


2. Dynamic/operational weight (Wet Weight + 30%) should be considered and approved
by your structural engineer including future equipment)
3. Rubber pads is not recommended due to deterioration later on.
Foundation Pad
Ventilation
Fuel System

1. Fuel pipes should be B.I pipe and must have separate and individual line for supply and
return pipe line especially when having multiple generator set.
2. Fuel Day Tank maximum height should not be exceed 1.5M from center line of generator
set as shown in the drawing section detail.
3. Prior to fuel filling, it should be flash out and clean from welding flux or foreign material.
4. Fuel supply line should be with wye strainer and ball valve for maintenance purpose.
5. Fuel-water should be installed inside fuel day tank containment area.
Exhaust System
1. Exhaust pipe system restriction including muffler must not exceed
600mmH2O.
2. Flexible joint should be free and not carrying the weight of exhaust
muffler and exhaust pipe.
3. Internal temperature of exhaust pipe may reach up to 500-600 degree
Celsius. Nearby material should be fire retardant.
4. Exhaust muffler and exhaust pipe should have minimum of two (2) inch
thick Rockwool insulation with wire mesh prior to aluminum cladding.
5. Provide drain pipe at lowest portion of exhaust piping system.
6. Exhaust tail end should have flapper for vertical end and tapered cut for
horizontal end.
7. MHIESP will conduct final inspection on exhaust flexible flange for
foreign debris prior to genset start up.
Electrical System
1. Make sure that power cables with the same phase must not be laid out
together and per phase power cable ampacity must not be less than rated
current of generator set.
2. Generator output should have CB prior to Automatic Transfer Switch or
Manual Transfer Switch to load side. CB over current relay should be set
as per rated current of generator set.
3. Provide power cable at generator set neutral bus bar going to generator set
ground, if required.
4. Provide grounding connection from generator body frame to building
grounding system.
5. Provide 220V AC power supply for every generator set battery charger
with dedicated CB on the distribution panel.
6. Other device may need separate power supply depend on option
accessories included.
Engine and AC Alternator Specification
Engine Specification

SAE 40
Alternator Specification
Alternator Specification
MGS SYSTEM CONTROL & DEVICES
Outgoing
Terminal
AVR Diesel Engine

Radiator
Gov. Act. L.O press C/W
Sensor Sensor
Exciter Stator
PMG

MP MP Stop 63Q 49W


System Coil

Starting Char. Alt.


AC Generator Motor

Battery

Governor
Controller
I/F
MGS 7310 Controller
Frequency Adj.
Engine Protection Measurement Circuit
Voltage Adj.
Generator Measurement Circuit

Other Circuit

Communication Port
(USB port for programming, RS485, RS232
7310 Panel
Generator Control Panel (Local)
Generator Local Panel

560 Panel 7310 Panel


(Old & Obsolete) New

Note: Once 560 module is damage, replacement should be 7310 panel assembly
Operation Comparison

560 Panel 7310 Panel


MGS 7310 Features
MGS 7310 Features
Manual Operation

Key switch

Stop/Reset button Emergency


Stop

Start button
Manual Button

1. Set the key switch to “ACTIVE”


2. Set the controller to manual mode.
3. To start the generator set, press the start button.
4. To stop the generator set, press the STOP BUTTON or
EMERGENCY STOP or set the key switch to OFF/RESET position.
Note: Read the Operation Manual for the detailed internal operation
of controller.
Automatic Operation

Key switch

Stop/Reset button Emergency Stop

Auto Button

1. Set the key switch to “ACTIVE”


2. Set the controller to auto mode.
3. To start the generator set, remote start signal from the ATS must be activated /
shorted.
4. To stop the generator set, remote start signal from ATS must be de-activated /
opened.
5. After remote start signal has been de-activated, engine shall automatically switch
to cool-down mode (3min) then stop.
System Flow
Cooling System Flow
Fuel System Flow
Lubrication System Flow
Air Intake & Exhaust System Flow
Air Intake & Exhaust System Flow
Synchronization & Parallel Operation of
Generator Set
Essential requirements for parallel
operation
1. All Generators must have the same voltage.
2. All Generators must have the same frequency.
3. All Generators must have the same number of phase rotation.
4. All Generators must have the same phase rotation.
5. All Generators and Prime Movers (Engines), must have similar no load,
to full load, voltage and frequency characteristics.
6. Generator installation must be provided with Synchronizing equipment.
7. Should have protection relay such as Reverse power, Over-current and
etc.
Ways to check synchronization point

N N
G1 G2
W W
U V U V

CB CB
“ON” “OFF”

1. Lamp : Synchronization point is when the Lamp is Off.


2. Tester : Synchronization point is when the tester reading is at Zero (0) Volts.
For a system with 380V: Reading of meter 380/1.732 = 220V
Maximum reading will be at 440V
Synchronizing Equipment
Synchronization Equipment is required to monitor the bus frequency and the
incoming generator frequency, to ensure that the generator are in synchronism.

DG1 DG2
Synch Panel Full Manual Operation
Synch Panel Full Manual Operation
DIESEL GENERATOR
MAINTENANCE
Safety it’s up to you
Safety it’s up to you
PERFORM PERIODIC MAINTENANCE PER
RUNNING HOUR INTERVALS OR WHICH
EVER COME FIRST

ADJUST
WALK AROUND INSPECTION
BEFORE OPERATION
WALK AROUND INSPECTION
DURING OPERATION
WEEKLY INSPECTION

CONDUCT GENSET MAINTENANCE OPERATION.


 Test run generator set with out load for 5-10 minutes.
MONTHLY INSPECTION

 CONDUCT GENSET MAINTENANCE OPERATION. Test run


generator set with load. At least 50% load for 15-30 minutes.
YEARLY INSPECTION

ANALYZE
ENGINE OIL
PROPERTIES
ANALYZE
COOLANT
PROPERTIES
Every 2 years or 250 running hours
MAINTENANCE FOR AC
GENERATOR AND SWITCHGEAR
Every 3 Months:
GENERATOR AND SWITCHGEAR
Every Year:
GENERATOR AND SWITCHGEAR
Every Year:
Scope of Rank Maintenance

Rank A
Rank B, C & D
Rank E ( For SU Genset)
Rank F1
BASIC TROUBLESHOOTING
Basic Troubleshooting
Basic Troubleshooting
Basic Troubleshooting
Basic Troubleshooting
Basic Troubleshooting
Basic Troubleshooting
Basic Troubleshooting
Thank You! 

Das könnte Ihnen auch gefallen