 Type 310A Pilot-Operated

 
Regulator
Type VL1000 FIELDVUE
Valve Link

Fisher Controls July 1994 Bulletin 71.2:310A

The Type 310A pilot-operated high-pressure regulator (fig-  Tight Shutoff—Throttling-sleeve design with TFE
ure 1) is used where high capacity and accurate control are seat in body (figure 2) ensures positive shutoff.
essential. This regulator includes one Type 32A pilot as-
sembly mounted on the main valve for pressure-reducing  Accurate Control—Molded pilot diaphragms pro-
or wide-open monitoring applications, or two Type 32A pi- vide a narrow proportional band, and registration of outlet
lots mounted on the main valve for working monitor ap- pressure on the main diaphragm allows excellent control
plications. sensitivity.

 Minimum Installation Space Required—Since


main valve design incorporates actuator spring, less instal-
lation space is needed for Type 310A regulators than for
other regulators of comparable capacity.

Features  Reduced Relief Requirements—An optional re-


stricted trim helps reduce relief valve size requirements;
 High Capacity—Straight-through flow passage al- the regulator is easily converted to full capacity by chang-
lows exceptionally high capacities and stable operation. ing the trim, if flow conditions increase.

W6278

Figure 1. Typical Construction


D102066X012

Fisher Controls International, Inc 1994; All Rights Reserved


Bulletin

71.2.310A
page 2

Specifications
Available Configurations psi (49.6 bar) for Class 300 body

Regulator with  one Type 32A pilot for standard Outlet Control Pressure Ranges(2)
pressure-reducing and wide-open monitoring applica-
tions or with  two Type 32A pilots for working moni- Spring Range Pilot Spring
Sp g Spring
Sp g
tor applications Psig Bar Part Number Color Code
10 to 20 0.69 to 1.4 1D8096 27022 Cadmium
10 to 100 0.69 to 6.9 1E3925 27022 Yellow
Body Sizes 100 to 250 6.9 to 17.2 1D3872 27022 Blue
250 to 600 17.2 to 41.4 1D4651 27142 Red
 1,  2,  3,  4, &  4 x 6 in. (inlet x outlet)
Maximum Outlet Pressures(2)
End Connection Styles(1) Operating: 600 psig (41.4 bar)
To Avoid Internal Part Damage: 600 psig (41.4 bar).
 NPT screwed (1 in. body) or ANSI Class  300 or Exceeding this pressure may result in gas venting
 600 raised-face flanged (1, 2, 3, 4, and 4 x 6 in. from pilot spring case
bodies) Emergency (Casing): 1480 psig (102.0 bar) or maxi-
mum inlet pressure whichever is lower. Exceeding
this pressure may result in rupture of metal pressure-
Available Trim Sizes retaining parts

Percent Of Flow Capacity Flow Capacities


Body Size, Inch
Standard Restricted See tables 2 through 6
1 100 50, 30
2, 3, 4, 4 x 6 100 70, 50, 30 Flow Coefficients
See tables 7 through 9

Proportional Bands
Maximum Inlet Pressures and Temperatures (1,2)
Proportional Band Pilot Sp
Spring
g Part
As listed below up to maximum material temperature Psig Bar Number
capabilities 0.5 0.03 1D8096 27022
Screwed End Connections: Consistent with Class 2 0.14 1E3925 27022
600 pressure-temperature ratings per ANSI 5 0.34 1D3872 27022
B16.34-1988 12 0.83 1E4651 27142
Flanged End Connections: Consistent with applica-
ble Class  300 or  600 pressure-temperature rat-
ings per ANSI B16.34-1988 Maximum Travel
See table 7 or 8

Maximum Allowable Pilot Supply Pressure(2) Flow Characteristic


Same as inlet pressure Linear

Flow Direction
Minimum Allowable Difference Between Pilot Supply Straight-through flow as shown in figure 2
and Control Pressure
Noise Information
15 psi (1.0 bar)
See Catalog 10 for sound pressure level prediction

Construction Materials
Maximum Pressure Drop(2)
Main Valve
 1425 psi (98.3 bar) for Class 600 body or  720 Body: WCB steel
- Continued -
Bulletin
71.2.310A
page 3

Specifications (Continued)
Construction Material (continued) 0 to 200F (–18 to 93C)
Fluoroelastomer Parts with Standard Wiper Ring
Throttling Sleeve: Stainless steel Removed(3): 0 to 300F (–18 to 149C)
Seat: TFE
Diaphragm Plates: Steel
Diaphragm:  Nitrile (std) or  Fluoroelastomer Downstream Pressure Registration
O-Rings:  Nitrile (std) or  Fluoroelastomer Externally through control line
Mainspring: Steel
Valve Plug: Stainless steel Pressure Connections
Travel Indicator Rod: Stainless steel
Wiper Ring: Polyurethane See figures 6 and 7

Pilot Approvals
Spring Case, Diaphragm Spacer, Pilot Body, and
Spring Case Cap: Cast steel DVGW
Adjusting Screw: Zink plated steel
Diaphragm Plates: Zink plate steel Approximate Weights
Diaphragm:  Nitrile (std) or  Fluoroelastomer
Orifice Assembly: Stainless steel Weight
Body Size, Inches
Yoke: Stainless steel Lb Kg
Valve Disc Assembly:  Stainless steel and nitrile 1 45 20
(std) or  stainless steel and fluoroelastomer 2 90 41
Bleed Valve and Orifice: Stainless steel 3 145 66
Piston and Piston Seat Assembly: Stainless steel and 4 190 86
nylon 4x6 235 107
Pilot Main Spring: Cadmium plated steel

Additional Options
Material Temperature Capabilities(2)
 Main valve body without pilot for on-off service,
Nitrile Elastomer Parts with Standard Wiper Ring:  remote-mounted pilot,or  electrically controlled
–20 to 150F (–29 to 66C) pilot using Type 662 remote drive  unit travel indica-
Fluoroelastomer Parts with Standard Wiper Ring: tor KixcelTM
1. DIN (or other) rating and end connections, or end connections threaded to various nation- should not be exceeded.
al or international thread standards, can usually be supplied. Contact your Fisher sales of- 3. Polyurethane wiper ring limits construction to 200F (93C) maximum temperature. Wip-
fice or sales representative. er ring is removed to obtain 300F (149C) maximum temperature.
2.The pressure/temperature limits in this bulletin, and any applicable standard limitation,

Principle of Operation When gas demand in the downstream system has been
satisfied, the outlet pressure acting on the bottom dia-
Figure 3 schematically illustrates the operation of a single- phragm of the diaphragm plate and yoke assembly results
pilot Type 310A regulator with external pilot supply. in a force that overcomes the pilot spring setting and moves
the assembly toward the relay seat, closing it. The loading
Regulator inlet pressure enters the pilot and is used as sup- pressure acting on the main valve diaphragm bleeds to the
ply pressure for the pilot. The setting of the pilot control downstream system through the small hole in the dia-
spring determines the reduced outlet (downstream) pres- phragm plate and yoke assembly. When rapid main valve
sure. closure is required by unusual control conditions, the bleed
valve opens for increased bleed rate. The force of in-
In operation, assume the outlet pressure is less than the creased outlet pressure acting on the main valve dia-
setting of the pilot control spring. Pilot control spring force phragm plus the main valve spring force overcomes the
then overcomes the force resulting from outlet pressure force of decreased loading pressure acting on the main
acting on the bottom diaphragm. The spring pushes the di- valve diaphragm and moves the throttling sleeve toward
aphragm plate and yoke assembly away from the relay the stationary valve plug to decrease the gas flow to the
seat, opening it and supplying additional loading pressure downstream system.
to the main valve diaphragm. When this additional loading
pressure exceeds the force resulting from outlet pressure
acting on the main valve diaphragm plus the force of the The top diaphragm in the pilot acts as a sealing member for
main valve spring, the diaphragm is pushed away from the the loading chamber and as a balancing member to the bot-
stationary valve plug. The throttling sleeve opens wider, tom diaphragm. The two diaphragms are connected by a
and the required gas is supplied to the downstream sys- machined yoke. Pressure change in the center chamber
tem. has little effect on the positioning of the valve disc.
Bulletin

71.2.310A
page 4

DIAPHRAGMS AND
DIAPHRAGM PLATES
SPRING CASE

BLEED VALVE

PISTON
SEAT ASSEMBLY

ADJUSTING
SCREW

PILOT CONTROL
SPRING

YOKE

ORFICE ASSEMBLY

O-RINGS

WIPER RING

THROTTLING
SLEEVE STATIONARY
VALVE PLUG
MAIN VALVE
SPRING

MAIN VALVE
BODY

TFE SEAT

BACKUP
RINGS
BACKUP DIAPHRAGM PLATES
W6281–1*
RINGS

Figure 2. Sectional of Type 310A Regulator with One Type 32A Pilot

Monitoring Systems be able to withstand full inlet pressure or be protected from


it in case the working monitor fails wide open.
Monitoring regulators serve as overpressure protection de-
vices to limit system pressure in the event of open failure Table 1 gives the spread between normal distribution pres-
of a working regulator feeding the system. Two uses for the sure and the minimum pressure at which the working moni-
Type 310A regulator in monitoring systems follow: tor regulator can be set to take over if the working regulator
fails open.
 Working Monitor—On a working monitor installation
(figure 4), the working monitor regulator is always up-  Wide-Open Monitor—Either the upstream or down-
stream and acts as a first-stage regulator through the work- stream regulator can be the monitoring regulator as shown
ing pilot during normal operation. This arrangement allows in figure 5. During normal operation, the monitoring regula-
the working monitor’s performance to be observed at all tor is standing wide open with the reduction to distribution
times. Then, should the second-stage regulator fail open, pressure being taken across the working regulator. Only in
the working monitor regulator assumes the entire pressure case of open failure of the working regulator does the wide-
reduction function of the system through the monitoring pi- open monitoring regulator take control at its slightly higher
lot. Note that the working monitor regulator actuator must setting.
Bulletin
71.2.310A
page 5

Figure 3. Principle of Operation Schematic


Bulletin

71.2.310A
page 6

34B4133A
C0786

Figure 4. Working Monitor System Schematic


Bulletin
71.2.310A
page 7

Table 1. Working Monitor Performance


TYPE 32A MONITORING PILOT SPRING RANGE
MINIMUM PRESSURE AT WHICH MONITORING PILOT CAN BE SET
Psig Bar
10 to 20 0.69 to 1.4 3.0 psi (0.21 bar) over normal distribution pressure
10 to 100 0.69 to 6.9 5.0 psi (0.34 bar) over normal distribution pressure
100 to 250 6.9 to 17.2 10 psi (0.69 bar) over normal distribution pressure
250 to 600 17.2 to 41.4 15 psi (1.0 bar) over normal distribution pressure

Table 2. Capacities for 1-Inch Body with 100 Percent Trim and Body Size Piping (Thousands of Scfh of 0.6 Specific Gravity Gas(1))
INLET
PRES- OUTLET PRESSURE
SURE
Psig 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600
Bar 1.7 3.4 5.2 6.9 8.6 10.3 12.0 13.8 15.5 17.2 19.0 20.7 22.4 24.1 25.9 27.6 29.3 31.0 32.8 34.5 36.2 38.0 39.6 41.4
50 3.4 48
75 5.2 69 61
100 6.9 88 87 73
150 10.3 127 127 125 115 92
200 13.8 165 165 165 163 156 139 107
250 17.2 204 204 204 204 202 195 182 160 121
300 20.7 243 243 243 243 242 240 234 223 206 178 134
350 24.1 281 281 281 281 281 281 278 273 263 248 227 195 145
400 27.6 320 320 320 320 320 320 319 317 312 303 290 272 246 211 156
450 31.0 358 358 358 358 358 358 358 358 355 350 342 331 315 294 265 225 165
500 34.5 397 397 397 397 397 397 397 397 396 393 389 381 371 357 338 314 282 239 175
550 38.0 435 435 435 435 435 435 435 435 435 434 432 427 420 411 398 381 360 333 298 252 184
600 41.4 474 474 474 474 474 474 474 474 474 474 473 470 466 459 450 438 423 404 381 351 314 264 192
650 44.8 512 512 512 512 512 512 512 512 512 512 512 511 508 504 498 489 478 465 448 427 401 369 328 276
700 48.3 551 551 551 551 551 551 551 551 551 551 551 551 549 547 542 536 528 518 505 490 471 448 420 385
750 51.7 589 589 589 589 589 589 589 589 589 589 589 589 589 588 585 581 575 567 558 546 531 514 493 468
800 55.2 628 628 628 628 628 628 628 628 628 628 628 628 628 628 626 623 619 614 606 597 586 572 556 537
850 58.6 666 666 666 666 666 666 666 666 666 666 666 666 666 666 666 664 662 658 652 645 636 626 613 598
900 62.1 705 705 705 705 705 705 705 705 705 705 705 705 705 705 705 704 703 700 696 691 684 676 665 653
950 65.5 744 744 744 744 744 744 744 744 744 744 744 744 744 744 744 743 743 741 738 734 729 723 715 705
1000 69.0 782 782 782 782 782 782 782 782 782 782 782 782 782 782 782 782 782 781 779 777 773 768 761 754
1100 75.8 859 859 859 859 859 859 859 859 859 859 859 859 859 859 859 859 859 859 859 858 856 853 850 845
1200 82.7 936 936 936 936 936 936 936 936 936 936 936 936 936 936 936 936 936 936 936 936 936 935 933 930
1300 89.6 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1013 1011
1400 96.5 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 1090
Shaded areas show where no flow occurs because outlet pressure is equal to or greater than inlet pressure.
1. See Capacity Information section for conversion to equivalent capacities of other gases and/or m3/hr.

Capacity Information for critical pressure drops (absolute outlet pressure is


equal to or less than one-half the absolute inlet pressure):
Tables 2 through 6 give typical natural gas regulating capa-
Q = (P1abs) (Cg ) (1.29)
cities. To determine equivalent capacities for air, propane,
butane, or nitrogen, multiply the table value by the ap-
where,
propriate conversion factor: 0.775 for air, 0.628 for pro-
pane, 0.548 for butane, or 0.789 for nitrogen. For gases of
other specific gravities, multiply the given capacity by
Q = flow capacity in scfh
0.775, and divide by the square root of the appropriate spe-
P1abs = absolute inlet pressure in psig (P1gauge +
cific gravity. Then, if capacity is desired in normal cubic me-
14.7)
ters per hour at 0C and 1.01325 bar, multiply scfh by
Cg = regulating or wide-open gas sizing coefficient
0.0268.
from table 7, 8, or 9

If pressure drops will be lower than critical (absolute outlet


To determine regulating capacities at pressure settings not pressure greater than one-half the absolute inlet pressure),
given in the tables or to determine wide-open capacities for use the sizing slide rule or the sizing nomographs in Cata-
relief sizing at any inlet pressure, use the following formula log 10.
Bulletin

71.2.310A
page 8

Table 3. Capacities for 2-Inch Body with 100 Percent Trim and Body Size Piping (Thousands of Scfh of 0.6 Specific Gravity Gas(1))
INLET
PRES- OUTLET PRESSURE
SURE
Psig 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 600
Bar 1.7 3.4 5.2 6.9 8.6 10.3 12.0 13.8 15.5 17.2 19.0 20.7 22.4 24.1 25.9 27.6 29.3 31.0 32.8 34.5 36.2 38.0 41.4
50 3.4 205
75 5.2 292 265
100 6.9 373 369 315
150 10.3 536 536 532 497 399
200 13.8 698 698 698 695 668 602 468
250 17.2 861 861 861 861 858 835 785 693 529
300 20.7 1024 1024 1024 1024 1024 1020 1000 959 889 775 584
350 24.1 1186 1186 1186 1186 1186 1186 1183 1165 1130 1072 983 849 634
400 27.6 1349 1349 1349 1349 1349 1349 1349 1345 1329 1298 1248 1175 1070 917 680
450 31.0 1512 1512 1512 1512 1512 1512 1512 1512 1508 1493 1465 1421 1359 1271 1151 981 724
500 34.5 1674 1674 1674 1674 1674 1674 1674 1674 1674 1670 1656 1631 1592 1537 1462 1361 1226 1041 765
550 38.0 1837 1837 1837 1837 1837 1837 1837 1837 1837 1837 1833 1820 1796 1761 1711 1645 1559 1446 1298 1098 804
600 41.4 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 1995 1983 1961 1928 1884 1824 1748 1651 1526 1366 1152
650 44.8 2162 2162 2162 2162 2162 2162 2162 2162 2162 2162 2162 2162 2158 2146 2125 2095 2054 2000 1932 1846 1738 1603 1204
700 48.3 2325 2325 2325 2325 2325 2325 2325 2325 2325 2325 2325 2325 2325 2320 2309 2289 2261 2223 2174 2112 2034 1939 1677
750 51.7 2488 2488 2488 2488 2488 2488 2488 2488 2488 2488 2488 2488 2488 2488 2483 2472 2453 2427 2391 2346 2289 2218 2029
800 55.2 2650 2650 2650 2650 2650 2650 2650 2650 2650 2650 2650 2650 2650 2650 2650 2645 2634 2617 2592 2558 2516 2463 2321
850 58.6 2813 2813 2813 2813 2813 2813 2813 2813 2813 2813 2813 2813 2813 2813 2813 2813 2808 2797 2780 2756 2725 2685 2576
900 62.1 2976 2976 2976 2976 2976 2976 2976 2976 2976 2976 2976 2976 2976 2976 2976 2976 2975 2970 2960 2944 2921 2891 2808
950 65.5 3138 3138 3138 3138 3138 3138 3138 3138 3138 3138 3138 3138 3138 3138 3138 3138 3138 3138 3133 3123 3107 3085 3021
1000 69.0 3301 3301 3301 3301 3301 3301 3301 3301 3301 3301 3301 3301 3301 3301 3301 3301 3301 3301 3300 3295 3285 3270 3222
1100 75.8 3626 3626 3626 3626 3626 3626 3626 3626 3626 3626 3626 3626 3626 3626 3626 3626 3626 3626 3626 3626 3625 3620 3596
1200 82.7 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3952 3945
1300 89.6 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277 4277
1400 96.5 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602 4602
Shaded areas show where no flow occurs because outlet pressure is equal to or greater than inlet pressure.
1. See Capacity Information section for conversion to equivalent capacities of other gases and/or m3/hr.

Table 4. Capacities for 3-Inch Body with 100 Percent Trim and Body Size Piping (Thousands of Scfh of 0.6 Specific Gravity Gas(1))
INLET
PRES- OUTLET PRESSURE
SURE
Psig 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 500 550 600
Bar 1.7 3.4 5.2 6.9 8.6 10.3 12.0 13.8 15.5 17.2 19.0 20.7 22.4 24.1 25.9 27.6 29.3 31.0 34.5 38.0 41.4
50 3.4 434
75 5.2 617 561
100 6.9 739 781 668
150 10.3 1133 1133 1126 1052 845
200 13.8 1477 1477 1477 1471 1414 1276 993
250 17.2 1821 1821 1821 1821 1815 1768 1663 1470 1123
300 20.7 2165 2165 2165 2165 2165 2159 2118 2032 1884 1643 1239
350 24.1 2510 2510 2510 2510 2510 2510 2503 2467 2393 2271 2084 1800 1345
400 27.6 2854 2854 2854 2854 2854 2854 2854 2847 2814 2749 2645 2491 2268 1946 1444
450 31.0 3198 3198 3198 3198 3198 3198 3198 3198 3190 3160 3102 3011 2879 2695 2440 2081 1536
500 34.5 3542 3542 3542 3542 3542 3542 3542 3542 3542 3534 3506 3453 3372 3256 3098 2886 2601 2209
550 38.0 3886 3886 3886 3886 3886 3886 3886 3886 3886 3886 3878 3851 3803 3729 3626 3487 3304 3066 2330
600 41.4 4230 4230 4230 4230 4230 4230 4230 4230 4230 4230 4230 4222 4196 4151 4084 3990 3866 3705 3237 2445
650 44.8 4574 4574 4574 4574 4574 4574 4574 4574 4574 4574 4574 4574 4566 4541 4499 4437 4351 4238 3913 3400 2555
700 48.3 4918 4918 4918 4918 4918 4918 4918 4918 4918 4918 4918 4918 4918 4909 4886 4846 4788 4709 4475 4111 3556
750 51.7 5262 5262 5262 5262 5262 5262 5262 5262 5262 5262 5262 5262 5262 5262 5253 5231 5193 5138 4969 4701 4301
800 55.2 5606 5606 5606 5606 5606 5606 5606 5606 5606 5606 5606 5606 5606 5606 5606 5597 5575 5539 5418 5219 4919
850 58.6 5950 5950 5950 5950 5950 5950 5950 5950 5950 5950 5950 5950 5950 5950 5950 5950 5941 5920 5836 5688 5459
900 62.1 6294 6294 6294 6294 6294 6294 6294 6294 6294 6294 6294 6294 6294 6294 6294 6294 6293 6284 6231 6122 5948
950 65.5 6638 6638 6638 6638 6638 6638 6638 6638 6638 6638 6638 6638 6638 6638 6638 6638 6638 6637 6608 6532 6399
1000 69.0 6982 6982 6982 6982 6982 6982 6982 6982 6982 6982 6982 6982 6982 6982 6982 6982 6982 6982 6972 6922 6823
1100 75.8 7670 7670 7670 7670 7670 7670 7670 7670 7670 7670 7670 7670 7670 7670 7670 7670 7670 7670 7670 7659 7612
1200 82.7 8358 8358 8358 8358 8358 8358 8358 8358 8358 8358 8358 8358 8358 8358 8358 8358 8358 8358 8358 8358 8347
1300 89.6 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046 9046
1400 96.5 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735 9735
Shaded areas show where no flow occurs because outlet pressure is equal to or greater than inlet pressure.
1. See Capacity Information section for conversion to equivalent capacities of other gases and/or m3/hr.
Bulletin
71.2.310A
page 9

Table 5. Capacities for 4-Inch Body with 100 Percent Trim and Body Size Piping (Thousands of Scfh of 0.6 Specific Gravity Gas(1))
INLET
PRES- OUTLET PRESSURE
SURE
Psig 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 500 550 600
Bar 1.7 3.4 5.2 6.9 8.6 10.3 12.0 13.8 15.5 17.2 19.0 20.7 22.4 24.1 25.9 27.6 29.3 31.0 34.5 38.0 41.4
50 3.4 709
75 5.2 1004 919
100 6.9 1284 1274 1096
150 10.3 1843 1843 1836 1724 1390
200 13.8 2403 2403 2403 2396 2313 2094 1635
250 17.2 2963 2963 2963 2963 2957 2889 2725 2415 1849
300 20.7 3522 3522 3522 3522 3522 3517 3460 3327 3090 2701 2041
350 24.1 4082 4082 4082 4082 4082 4082 4077 4027 3915 3723 3422 2962 2217
400 27.6 4642 4642 4642 4642 4642 4642 4642 4636 4592 4495 4333 4087 3728 3202 2380
450 31.0 5201 5201 5201 5201 5201 5201 5201 5201 5196 5156 5070 4929 4720 4424 4012 3427 2533
500 34.5 5761 5761 5761 5761 5761 5761 5761 5761 5761 5756 5719 5641 5517 5335 5082 4741 4278 3638
550 38.0 6321 6321 6321 6321 6321 6321 6321 6321 6321 6321 6315 6281 6211 6098 5937 5717 5424 5039 3837
600 41.4 6880 6880 6880 6880 6880 6880 6880 6880 6880 6880 6880 6875 6843 6778 6676 6531 6335 6078 5322 4027
650 44.8 7440 7440 7440 7440 7440 7440 7440 7440 7440 7440 7440 7440 7435 7404 7344 7251 7118 6942 6422 5592 4209
700 48.3 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 7994 7966 7909 7823 7701 7334 6751 5850
750 51.7 8559 8559 8559 8559 8559 8559 8559 8559 8559 8559 8559 8559 8559 8559 8554 8527 8474 8393 8132 7709 7066
800 55.2 9119 9119 9119 9119 9119 9119 9119 9119 9119 9119 9119 9119 9119 9119 9119 9113 9087 9038 8857 8546 8070
850 58.6 9679 9679 9679 9679 9679 9679 9679 9679 9679 9679 9679 9679 9679 9679 9679 9679 9673 9648 9529 9303 8945
900 62.1 10238 10238 10238 10238 10238 10238 10238 10238 10238 10238 10238 10238 10238 10238 10238 10238 10238 10233 10163 10003 9734
950 65.5 10798 10798 10798 10798 10798 10798 10798 10798 10798 10798 10798 10798 10798 10798 10798 10798 10798 10798 10769 10662 10462
1000 69.0 11357 11357 11357 11357 11357 11357 11357 11357 11357 11357 11357 11357 11357 11357 11357 11357 11357 11357 11352 11288 11144
1100 75.8 12477 12477 12477 12477 12477 12477 12477 12477 12477 12477 12477 12477 12477 12477 12477 12477 12477 12477 12477 12471 12411
1200 82.7 13596 13596 13596 13596 13596 13596 13596 13596 13596 13596 13596 13596 13596 13596 13596 13596 13596 13596 13596 13596 13590
1300 89.6 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715 14715
1400 96.5 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835 15835
Shaded areas show where no flow occurs because outlet pressure is equal to or greater than inlet pressure.
1. See Capacity Information section for conversion to equivalent capacities of other gases and/or m3/hr.
Bulletin

71.2.310A
page 10

Table 6. Capacities for 4 x 6-Inch Body with 100 Percent Trim and 2:1 Swaged Piping
(Thousands of Scfh of 0.6 Specific Gravity Gas (1))
INLET
PRES- OUTLET PRESSURE
SURE
Psig 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 500 550 600
Bar 1.7 3.4 5.2 6.9 8.6 10.3 12.0 13.8 15.5 17.2 19.0 20.7 22.4 24.1 25.9 27.6 29.3 31.0 34.5 38.0 41.4
50 3.4 968
75 5.2 1342 1198
100 6.9 1716 1716 1348
150 10.3 2464 2464 2464 2200 1618
200 13.8 3213 3213 3213 3213 2795 2525 1858
250 17.2 3961 3961 3961 3961 3961 3832 3374 2820 2075
300 20.7 4709 4709 4709 4709 4709 4709 4639 4203 3700 3093 2276
350 24.1 5457 5457 5457 5457 5457 5457 5457 5443 5021 4549 4005 3347 2463
400 27.6 6206 6206 6206 6206 6206 6206 6206 6206 6206 5835 5383 4877 4294 3589 2641
450 31.0 6954 6954 6954 6954 6954 6954 6954 6954 6954 6954 6644 6206 5725 5187 4567 3817 2809
500 34.5 7702 7702 7702 7702 7702 7702 7702 7702 7702 7702 7702 7451 7024 6561 6052 5483 4828 4035
550 38.0 8450 8450 8450 8450 8450 8450 8450 8450 8450 8450 8450 8450 8257 7838 7388 6900 6366 5767 4244
600 41.4 9198 9198 9198 9198 9198 9198 9198 9198 9198 9198 9198 9198 9198 9061 8648 8209 7738 7228 6041 4445
650 44.8 9946 9946 9946 9946 9946 9946 9946 9946 9946 9946 9946 9946 9946 9946 9864 9457 9026 8568 7544 6305 4639
700 48.3 10695 10695 10695 10695 10695 10695 10695 10695 10695 10695 10695 10695 10695 10695 10695 10668 10264 9841 8916 7850 6561
750 51.7 11443 11443 11443 11443 11443 11443 11443 11443 11443 11443 11443 11443 11443 11443 11443 11443 11443 11071 10213 9252 8146
800 55.2 12191 12191 12191 12191 12191 12191 12191 12191 12191 12191 12191 12191 12191 12191 12191 12191 12191 12191 11462 10574 9580
850 58.6 12939 12939 12939 12939 12939 12939 12939 12939 12939 12939 12939 12939 12939 12939 12939 12939 12939 12939 12680 11844 10926
900 62.1 13688 13688 13688 13688 13688 13688 13688 13688 13688 13688 13688 13688 13688 13688 13688 13688 13688 13688 13688 13079 12216
950 65.5 14436 14436 14436 14436 14436 14436 14436 14436 14436 14436 14436 14436 14436 14436 14436 14436 14436 14436 14436 14237 13467
1000 69.0 15184 15184 15184 15184 15184 15184 15184 15184 15184 15184 15184 15184 15184 15184 15184 15184 15184 15184 15184 15184 14690
1050 72.4 15932 15932 15932 15932 15932 15932 15932 15932 15932 15932 15932 15932 15932 15932 15932 15932 15932 15932 15932 15932 15892
1100 75.8 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680 16680
1150 79.3 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428 17428
1200 82.7 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177 18177
1300 89.6 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673 19673
1400 96.5 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170 21170
Shaded areas show where no flow occurs because outlet pressure is equal to or greater than inlet pressure.
1. See Capacity Information section for conversion to equivalent capacities of other gases and/or m3/hr.

Table 7. Regulating Flow Coefficients for Body Size Piping


TRIM
MAXIMUM SIZE C1
BODY Cg AT PERCENT OF MAXIMUM TRAVEL
TRAVEL (PERCENT AT
SIZE,
OF MAXIMUM
INCH
Inch mm FLOW 10 20 30 40 50 60 70 80 90 100 TRAVEL
CAPACITY)
100% 65 115 210 343 427 485 523 549 573 597 28.8
1 1/2 13 50% 60 93 124 151 178 204 226 250 272 289 29.5
30% 56 83 107 126 140 150 159 168 177 184 28.0
100% 210 460 810 1120 1440 1750 2040 2260 2430 2520 27.7
70% 200 396 583 758 925 1090 1240 1400 1550 1700 26.6
2 7/8 22
50% 190 311 430 540 646 744 841 946 1040 1130 27.6
30% 185 260 325 385 444 502 561 624 690 761 26.4
100% 346 810 1520 2380 3270 3890 4410 4820 5080 5330 27.6
70% 340 735 1120 1480 1840 2190 2540 2900 3210 3530 29.2
3 1 25
50% 325 615 875 1130 1380 1630 1880 2130 2380 2640 28.7
30% 305 460 606 755 902 1060 1210 1360 1510 1670 28.3
100% 805 1800 3100 4350 5480 6310 7040 7640 8140 8670 27.2
70% 725 1310 1990 2650 3280 3950 4550 5110 5700 6390 30.2
4 1-1/8 29
50% 615 1040 1480 1900 2300 2730 3140 3540 3950 4390 27.2
30% 510 705 917 1130 1340 1540 1740 1950 2200 2680 26.5
100% 895 2235 3800 5510 7300 9010 10,580 12,100 13,600 14,900 21.5
70% 800 1680 2550 3300 4150 5010 5870 6720 7570 8450 25.0
4x6 1-1/2 38
50% 780 1420 2050 2650 3250 3840 4430 5030 5650 6320 23.5
30% 760 1160 1550 1940 2330 2720 3110 3500 3870 4210 24.2
Bulletin
71.2.310A
page 11

Table 8. Regulating Flow Coefficients for 2:1 Swaged Piping and 100 Percent Trim
MAXIMUM C1
BODY Cg AT PERCENT OF MAXIMUM TRAVEL
TRAVEL AT
SIZE,
MAXIMUM
INCH Inch mm 10 20 30 40 50 60 70 80 90 100 TRAVEL
1 1/2 13 60 115 205 330 395 450 490 515 533 548 30.5
2 7/8 22 210 450 795 1110 1380 1610 1800 1960 2055 2140 29.7
3 1 25 340 825 1540 2350 3025 3550 3900 4200 4440 4610 29.2
4 1-1/8 29 810 1700 3050 4300 5400 6200 6900 7400 7800 8150 28.8
4x6 1-1/2 38 850 2050 3300 4650 6050 7430 8700 9860 10,800 11,600 28.5

Table 9. Wide-Open Flow Coefficients for Relief Valve Sizing with Body Size Piping
BODY TRIM SIZE
SIZE, 30% 50% 70% 100%
INCH Cg C1 Cg C1 Cg C1 Cg C1
1 238 27.7 313 30.4 --- --- 612 28.1
2 835 27.3 1240 26.8 1800 26.2 2610 27.5
3 1810 28.0 2810 28.3 3780 29.3 5510 27.5
4 3080 26.8 4620 26.8 6660 31.3 8830 27.4
4x6 4310 23.8 6520 23.4 8900 25.0 16,000 21.1

Installation 5. Range of flowing inlet pressure

The Type 310A may be installed in any position, but is nor- 6. Pressure drops
mally installed in a horizontal pipeline with the pilot or pilots
above the body. See figures 5 and 6 for typical piping instal- a. Range of flowing pressure drops
lation.
b. Maximum at shutoff
Dimensions are given in figure 7.
7. Flow rates

a. Minimum controlled flow

Ordering Information b. Normal flow

Application c. Maximum flow

When ordering, specify: 8. Maximum permissible noise level, if desired


1. Type of application: basic pressure reduction, wide- 9. Line size and schedule
open monitoring system, or working monitor system

2. Controlled gas (include chemical analysis of fluid if pos-


Regulator
sible)
Refer to the specifications on pages 2 and 3. Review the
3. Specific gravity of controlled gas description at the right of each specification, and write
down your choice whenever there is a selection to be
4. Fluid temperature made. Always specify the type number being ordered.
Bulletin

71.2.310A
page 12

Figure 5. Typical Wide-Open Monitor Installations

Figure 6. Typical Pressure-Reducing Installation


Bulletin
71.2.310A
page 13

BODY A F
SIZE
SIZE, NPT B C D E G H J K
INCH 300 RF 600 RF 300 RF 600 RF
SCRD
Inches
1 8.19 7.75 8.25 4.69 3.56 6.56 8.38 1.19 1.44 3.06 2.25 10.9 6.44
2 --- 10.50 11.25 5.69 4.56 9.00 9.75 1.69 2.06 4.44 3.12 11.9 7.44
3 --- 12.50 13.25 6.50 5.38 10.62 10.62 2.06 2.44 5.25 3.12 12.6 8.25
4 --- 14.50 15.50 8.38 7.25 14.38 12.50 3.12 3.62 7.12 3.88 14.6 10.1
4X6 --- 16.19 17.38 8.38 7.25 14.38 12.50 3.12 3.62 7.12 3.88 14.6 10.1
mm
1 208 197 210 119 90 167 213 30 37 78 57 277 164
2 --- 267 286 145 116 229 248 51 52 113 79 302 189
3 --- 318 337 165 137 270 270 52 62 133 79 320 210
4 --- 368 394 213 184 365 318 79 92 181 99 371 257
4X6 --- 411 442 213 184 365 318 79 92 181 99 371 257

NOTE:
FOR DIMENSIONS OF MAIN VALVES WITH DIN (OR OTHER)
END CONNECTIONS, CONSULT THE FISHER SALES OFFICE OR
SALES REPRESENTATIVE.
14B0914–B
44B4135–B
B2446

Figure 7. Dimensions
Bulletin

71.2.310A
page 14

While this information is presented in good faith and believed to be accurate, or any other matter with respect to the products, nor as a recommendation to
Fisher Controls does not guarantee satisfactory results from reliance upon such use any product or process in conflict with any patent. Fisher Controls reserves
information. Nothing contained herein is to be construed as a warranty or guar- the right, without notice, to alter or improve the designs or specifications of the
antee, express or implied, regarding the performance, merchantability, fitness products described herein.

For information, contact Fisher Controls:



 
 