D40A/G9SX-NS
Electronic Detection Mechanism for
Better Stability in Non-contact Door
Switch Operation
Features
● Small Actuator
● Save Labor with Connector and Reduce Inventory
An actuator that is smaller than the switch
saves space, even inside the door. Wiring time can be reduced with the connector.
Cable lengths can be selected, and only cables of
Even when mounted with an L-bracket, the
required lengths can be purchased.
actuator's height will not hinder installation or
Switches can be integrated into a single Switch
operation.
with a connector when installing in a machine with
multiple doors or various types of machines,
Compact which can reduce inventory.
Switch Actuator
Up to 30 Switches
1
D40A/G9SX-NS
Issue 1 The Switch does not accurately detect the door when it is closed slowly, resulting in an error.
Conventional switch
An error can occur
Door if the door is closed
closed slowly with
slowly. conventional
switches.
Solution 1 Conventional Switches The D40A does not use reed switches and
provides stable detection with electronic switches.
Slow
Slow
If the switching timing of reed
Magnet Magnet switch contacts 1 and 2 varies Stable Detection
too much, the Controller
detects an error and turns OFF
with the D40A's
Reed switch contacts Reed switch contacts the output to maintain safety. New System
Note: The figure is intended
Error only as an illustration.
Detects slow lateral operation. Detects slow rotating operation.
All doors must be opened and closed before operation can be started.
Solution 2
Issue 3 Various cable lengths and complex wiring are required for multiple doors.
Solution 3
The model with a connector allows you to select the cable lengths that are connected and purchase the
cables of required lengths. Switches can be integrated into a single Switch with a connector.
Downtime can be reduced by replacing the cable and switch partially at maintenance time.
2
D40A/G9SX-NS
G9SX-NS G9SX-NSA
@Logical AND @Logical AND
connection input connection input
● Mechanical Safety Door Switches Can Also Be Connected with the G9SX-NSA
Inputs can be accepted
D40A
from both D40A Switches
and mechanical switches to
reduce the number of Safety Door
Switches
Controllers and costs.
● Expansion Units to Easily Increase the Number of Outputs with the G9SX-NSA
3
D40A/G9SX-NS
Issue 1 Two Controllers are required for emergency stop switches and
non-contact door switches.
Application
●One hazard.
●The system must be stopped D40B
when either a door is opened
Emergency D40A
or an emergency stop switch stop switch *
is pressed.
Solution 1
D40B-J1
Application
●Two hazards.
●The power supply must be D40B
Emergency D40A
stop switch *
turned OFF immediately when
the emergency stop switch is
pressed.
●When a door is opened, a stop Solution 2
signal is sent to only Emergency
D40B-J1
4
D40A/G9SX-NS
Function Blocks
5
D40A/G9SX-NS
Ordering Information
List of Models
Non-Contact Door Switches (Switch/Actuator)
Classification Appearance Auxiliary outputs Cable length Model
2m D40A-1C2
Standard models
5m D40A-1C5
Semiconductor
outputs *1
Expansion Units
Safety outputs Auxiliary Rated
OFF-delay time Terminal block type Model
Instantaneous OFF-delayed outputs voltage
Screw terminals G9SX-EX401-RT
4PST-NO --- ---
1 Spring-cage terminals G9SX-EX401-RC
24 VDC
(Semiconductor) *1 Screw terminals G9SX-EX041-T-RT
--- 4PST-NO *2
Spring-cage terminals G9SX-EX041-T-RC
*1. PNP transistor output
*2. The OFF-delay time is synchronized to the OFF-delay time setting in the connected Controller (G9SX-NSA222-T03-@).
6
D40A/G9SX-NS
Accessories
Terminal Block
Appearance * Specifications Applicable units Model Remarks
Two Terminal Blocks (black) with screw
Terminal Block with screw
G9SX-NSA Y9S-03T1B-02A terminals, and a set of six code marks to
terminals (3-pin)
prevent erroneous insertion.
Two Terminal Blocks (black) with screw
Terminal Block with screw G9SX-NS
Y9S-04T1B-02A terminals, and a set of six code marks to
terminals (4-pin) G9SX-EX-@
prevent erroneous insertion.
Two Terminal Blocks (black) with spring-cage
Terminal Block with spring-
G9SX-NSA Y9S-03C1B-02A terminals, and a set of six code marks to
cage terminals (3-pin)
prevent erroneous insertion.
Two Terminal Blocks (black) with spring-cage
Terminal Block with spring- G9SX-NS
Y9S-04C1B-02A terminals, and a set of six code marks to
cage terminals (4-pin) G9SX-EX-@
prevent erroneous insertion.
Note: The G9SX main unit comes with a terminal block as standard equipment. The accessories shown here can be ordered as a replacement.
* The illustrations show 3-pin types
Specifications
Non-contact Door Switches
Ratings and Characteristics
Item Model D40A-1C@
Operating distance OFF→ON 5 mm min.
Operating distance ON→OFF 15 mm max.
Operating
Differential travel 20% or less of operating distance at 23°C (maximum 2.5 mm)
characteristics *1
Influence of temperature (max.) ±20% of operating distance at 23°C, within temperature range of −10 to 55°C
Repeat accuracy ±10% or less of operating distance at 23°C
Ambient operating temperature −10 to 55°C (no icing or condensation)
Ambient operating humidity 25% to 85%
Insulation resistance (between charged parts and
50 MΩ max. (at 500 VDC)
case)
Dielectric strength (between charged parts and case) 1,000 VAC for 1 min
Pollution degree 3
Electromagnetic compatibility IEC/EN 60497-5-3 compliant
10 to 55 to 10 Hz (single amplitude: 0.75 mm, double
Vibration resistance
amplitude: 1.5 mm)
Shock resistance 300 m/s2 min.
Degree of protection IP67
Material PBT resin
Mounting method M4 screws
Terminal screw tightening torque 1 N·m
Power supply voltage 24 VDC +10%/−15%
Power consumption 0.6 W max.
Auxiliary outputs *2 24 VDC, 10 mA (PNP open-collector outputs)
LED indicators Actuator not detected (red); actuator detected (yellow)
Connection cables 2 m, 5 m, 0.15m (Connector type)
Number of connectable switches 30 max. (wiring length: 100 m max.) *3
Weight Switch: approx. 145 g, actuator: approx. 20 g (D40A-1C2)
*1. This is the distance where the switch operates from OFF to ON when approaching and the distance where the switch operates from ON to
OFF when separating when the switch and actuator target marks are on the same axis, and the sensing surfaces coincide.
*2. Turns ON when the actuator is approaching. The G3R series of the SSR can be driven at an auxiliary output of 10 mA. Contact your OMRON
representative for details.
*3. For details, refer to item 5 on page 29.
7
D40A/G9SX-NS
Inputs
Item Model G9SX-NS202-@/G9SX-NSA222-T03-@
Safety input *1
Operating voltage: 20.4 VDC to 26.4 VDC, internal impedance: approx. 2.8 kΩ *2
Feedback/reset input
*1. Only applies to the G9SX-NSA222-T03-@. Refers to input other than that from the Non-contact Door Switch.
*2. Provide a current equal to or higher than that of the minimum applicable load of the connected input control device.
Outputs
Item Model G9SX-NS202-@/G9SX-NSA222-T03-@
Instantaneous safety output *1 P channel MOS FET transistor output
OFF-delayed safety output *1 Load current: 0.8 A DC max. *2
PNP transistor output
Auxiliary output
Load current: 100 mA max.
*1. While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis.
When using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below.
Approx.100 ms
ON
OFF
360 µs max.
*2. The following derating is required when Units are mounted side-by-side.
G9SX-NS202-@/G9SX-NSA222-T03-@: 0.4 A max. load current
Expansion Unit
Item Model G9SX-EX-@
Rated load 250 VAC, 3 A/30 VDC, 3 A (resistive load)
Rated carry current 3A
Maximum switching voltage 250 VAC, 125 VDC
8
D40A/G9SX-NS
Characteristics
Item Model G9SX-NS202-@ G9SX-NSA222-T03-@ G9SX-EX-@
Over-voltage category II (Relay outputs 13 to 43 and 14
II
(IEC/EN 60664-1) to 44: III)
50 ms max. (Safety input: ON) *2
100 ms max. (Logical AND
100 ms max. (Logical AND
connection input ON and
Operating time (OFF to ON state) *1 connection input ON and 30 ms max. *4
Non-contact Door Switch input
Non-contact Door Switch input ON)
ON)
*3
15 ms max. (Logical AND 15 ms max. (Safety input OFF and
connection input: OFF) logical AND connection input OFF)
Response time (ON to OFF state) *1 10 ms max. *4
20 ms max. (Non-contact Door 20 ms max. (Non-contact Door
Switch input OFF) *6 Switch input: OFF) *6
ON-state residual voltage 3.0 V max. (safety output, auxiliary output)
OFF-state leakage current 0.1 mA max. (safety output, auxiliary output)
Maximum wiring length of safety
input, logical AND connection
100 m max. (External connection impedance: 100 Ω max. and 10 nF max.)
input, and Non-contact Door Switch
input
Reset input time
100 ms min.
(Reset button pressing time)
Accuracy of OFF-delay time *5 --- Within ±5% of the set value Within ±5% of the set value
Between logical AND
connection terminals,
and power supply input
terminals and other ---
Insulation input and output
20 MΩ min. (at 100 VDC)
resistance terminals connected
together
Between all terminals
100 MΩ min.
connected together and
(at 500 VDC)
DIN rail
Between logical AND
connection terminals,
and power supply input
terminals and other ---
input and output
terminals connected 500 VAC for 1 min.
together
Dielectric Between all terminals
strength connected together and
DIN rail 1,200 VAC for 1 min
Between different poles
of outputs
Between relay outputs ---
connected together and
2,200 VAC for 1 min
other terminals
connected together
Vibration resistance 10 to 55 to 10 Hz, 0.375 mm single amplitude (0.75 mm double amplitude)
Shock Destruction 300 m/s2
resistance Malfunction 100 m/s2
100,000 cycles min. rated load,
Electrical --- switching frequency: 1,800
Durability cycles/hour)
5,000,000 cycles min. (switching
Mechanical ---
frequency: 7,200 cycles/hour)
Ambient operating temperature −10 to 55°C (no icing or condensation)
Ambient operating humidity 25% to 85%
Terminal tightening torque 0.5 N·m (For the G9SX-NS@-RT (with screw terminals) only)
Weight Approx. 125 g Approx. 200 g Approx. 165 g
*1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and
response times, respectively, of all the Units connected by logical AND.
*2. Represents the operating time when the safety input turns ON with all other conditions set.
*3. Represents the operating time when the logical AND input and the Non-contact Door Switch input turn ON with all other conditions set.
*4. This does not include the operating time or response time of G9SX-NS@ that are connected.
*5. This does not include the operating time or response time of internal relays in the G9SX-EX-@.
*6. The failure detection time for 24 V short-circuit failure on the input to Non-contact Door Switches is 35 ms max.
If using the Switch for an application other than as a Door Switch, calculate the safe distance using a failure detection time of 35 ms.
For product information of G9SP,refer to the website at:http://www.ia.omron.com/
9
D40A/G9SX-NS
10
D40A/G9SX-NS
G9SX-@
G9SX-NS@ G9SX-NS@ G9SX-NS@ G9SX-NS@
2. Any G9SX-NS@ Controller that receives a logical AND connection G9SX-AD@ G9SX-AD@ G9SX-AD@ G9SX-AD@
input can be logically connected to other Controllers on up to five or
G9SX-NS@
or
G9SX-NS@
or
G9SX-NS@
or
G9SX-NS@
layers.
G9SX-NS@
G9SX-AD@ G9SX-AD@ G9SX-AD@ G9SX-AD@
or or or or
G9SX-NS@ G9SX-NS@ G9SX-NS@ G9SX-NS@
Note: The G9SX-NS@ in the above diagram can be replaced by the Number of Units connected
in series by logical AND: 5
G9SX-AD@ Advanced Unit. Units max. Total number of Units
connected by logical AND:
For details on G9SX-AD@ Advanced Units, refer to the 20 Units max.
G9SX-series Flexible Safety Unit catalog. (Cat. No. J150).
11
D40A/G9SX-NS
2. G9SX-NSA@
Non-contact Door D4NS Max. response time Max. operating time
Switch input Safety input
(excluding Expansion (excluding Expansion
Units) *1 Units) *2
Logical AND input
Non-contact Door Switch input 20 ms 100 ms
Safety input 15 ms 50 ms
Logical AND input 15 ms 100 ms
*1. The maximum response time is the time it takes the output to switch from ON to OFF after
the input switches from ON to OFF.
*2. The maximum operating time is the time it takes the output to switch from OFF to ON after
the input switches from OFF to ON.
20 ms + 15 ms = 35 ms
(D40A (1)) (Logical AND
connection (1))
Case 2
Response Time from When D4NS Turns from ON to OFF until Safety Output (3) Turns from ON
Safety output to OFF
(1) 15 ms + 15 ms + 15 ms = 45 ms
D40A (2)
Logical AND (D4NS) (Logical AND (Logical AND
(1) connection (1)) connection (2))
D40A (3)
Logical AND
(2)
12
D40A/G9SX-NS
Engineering Data
Guaranteed value and typical data of operating characteristics
15mm * 5mm * 0mm
ON
OFF
* When the switch and actuator target
Unstable range
marks are on the same axis, and the
sensing surfaces coincide.
18 18
Sensing
10 Engineering 10 Z
Data Y Engineering
Y
(OFF to ON) Data
8 8 (OFF to ON)
Minimum
6 operating distance 6 Minimum Target marks
Target marks
(OFF to ON) operating distance
(OFF to ON)
4 4
2 ON range 2 ON range
0 0
−6 −4 −2 0 2 4 6 −15 −10 −5 0 5 10 15
Distance from the target mark on the switch X (mm) Distance from the target mark on the switch Z (mm)
Note: 1. The operating distance is the distance between the switch and actuator sensing surfaces.
2. Data in the diagram is typical data at an ambient temperature of 23°C. Actual operating values may vary.
The operating distance may be affected by ambient metal, magnet catches, and temperature.
Connections
Internal Connection
G9SX-NS202-@ (Non-contact Door Switch Controller) G9SX-NSA222-T03-@
(Non-contact Door Switch Controller)
A1 D1 D2 D3 D4 T31 T32 T33 T41 T42
A1 T11 T12 T21 T22 T31 T32 T33 Y1 D1 D2 D3 D4 T41 T42
*2
Power Non-contact Door Reset/Feedback Logical AND *2
supply Switch control Input input
circuit
Power Safety Safety Reset/Feedback Cross fault Non-contact Door
detection
Logical
supply AND input
*1 Safety output control
Auxiliary input 1 input 2 Input input Switch control
output control circuit
*1 Auxiliary Expansion Unit
Safety output control output control output control
A2 S14 S24 L1 X1 X2
A2 S14 S24 S44 S54 L1 X1 X2
*3
*3
*1. Internal power supply circuit is not isolated.
*2. Logical AND input is isolated.
*3. Outputs S14 to S24 are internally redundant. *1. Internal power supply circuit is not isolated.
*2. Logical AND input is isolated.
G9SX-EX401-@/G9SX-EX041-T-@ *3. Outputs S14 to S54 are internally redundant.
(Expansion Unit/Expansion Unit OFF-delayed Model)
*1
A1 13 23 33 43 Internal Circuit Diagram
Safety *2
D40A-1C@
output
Power control
supply
Exp. circuit Auxiliary K1 Exp.
Brown
sig.
output
control sig.
IN
K2 OUT Blue
Internal circuit
White
A2 X2 14 24 34 44
Black
13
D40A/G9SX-NS
Dimensions and Terminal Arrangement (Unit: mm)
38 48 48 38
(Actuator) (Switch)
G9SX-NS202
24VDC
PWR FB
PWR FB
AND NS
100 max. AND NS
EI ERR
EI ERR
No.
T41 T42 X2 A2
S14 S24 L1 D4
T41 T42 X2 A2
S14 S24 L1 D4
23 max.
115 max. (6) (See note 2.)
(22.5) *
Note: 1. Above outline drawing is for models with spring-cage terminals (-RC).
2. For models with spring-cage terminals (-RC) only.
* Typical dimension
T1 T2
G9SX-NSA222-T03
24VDC
PWR FB
AND NS
T1 T2
EI ED
AND NS
100 max.
0.7
EI
0.8 0.91.0
1.2
ED
ERR
0.6 1.4
0.5 1.8
0.4 2.0 ERR
0.3 2.5
0.2 0 3.0
OFF-DELAY No.
35.5 max.
(10) 115 max. (6) (See note 2.)
(35) *
Note: 1. Above outline drawing is for models with spring-cage terminals (-RC).
2. For models with spring-cage terminals (-RC) only.
* Typical dimension
14
D40A/G9SX-NS
Expansion Unit
G9SX-EX401-@
Expansion Unit (OFF-delayed Model)
G9SX-EX041-T-@
Terminal arrangement
G9SX-EX401-@ G9SX-EX041-T-@
(Expansion Unit) (Expansion Unit
with OFF Delay)
13 23 33 43 13 23 33 43
(6) (See note 2.)
PWR PWR
EI ED
ERR ERR
100 max.
A1 X2 A2 A1 X2 A2
14 24 34 44 14 24 34 44
23 max.
115 max. (6) (See note 2.)
(22.5) *
Note: 1. Above outline drawing is for models with spring-cage terminals (-RC).
2. For models with spring-cage terminals (-RC) only.
* Typical dimension
XS2W-D521-JG1-A (L=10m)
XS2W-D521-KG1-A (L=15m) 40.7 44.7
L
XS2W-D521-LG1-A (L=20m)
Wiring Diagram for 5 Cores
Contact No. Cable lead
colors
1 1 Brown
2 2 White
3 3 Blue
4 4 Black
5 5 Gray
15
D40A/G9SX-NS
Non-contact Door Switch D40A and Non-contact Door Switch Controller G9SX-NS@ Wiring
Example: Wiring a Single Switch Example: Wiring Multiple Switches
Connect Up to 30 Non-contact Door Switches
D40A-1C@
Brown
Brown
Brown
White
White
White
Black
Black
Black
Brown
Blue
Blue
Blue
Yellow
White
Black
Blue
D1 D2 D3 D4 A2
G9SX-NS202-@
G9SX-NSA222-T03-@
D1 D2 D3 D4
G9SX-NS202-@
G9SX-NSA222-T03-@
4 3
1 2
16
D40A/G9SX-NS
Feedback loop
To set the safety outputs in the ON state, the ON state
KM
signal must be input to T33. Otherwise the safety Auto reset +24 V
input to T32 must change from the OFF state to the Reset
KM +24 V
Manual reset Switch
ON state, and then to the OFF state. Otherwise the
safety outputs cannot be in the ON state. T31 T32 T33
Input a
A logical AND connection means that one unit (Unit Unit A
A) outputs a safety signal “a” to a subsequent unit G9SX-NS/NSA
(Unit B) and Unit B calculates the logical AND (i.e., Output (a) L1 A2 Logical AND connection sig.
Next unit (4 unit max.)
outputs the AND) of the signal “a” and safety signal (1st layer)
Input b
“b”, which is input to Unit B. Unit B T41 T42 T41 T42
Logical AND
T41, T42 Thereby the logic of the safety output of Unit B is G9SX-NS/NSA G9SX-NS/NSA
connection input
(AND). (An AND of inputs “a” and “b” is output.) Output (a&b) L1 A2 Logical AND connection sig.
Next unit (4 unit max.)
To set the safety outputs of the subsequent Unit in the (2nd layer)
17
D40A/G9SX-NS
G9SX-NSA222-T03-@
Terminal
Signal name Description of operation Wiring
name
Power supply Connect the power source to the A1 and A2 Connect the power supply plus (24 VDC) to the A1 terminal.
A1, A2
input terminals. Connect the power supply minus (GND) to the A2 terminal.
+24 V
+24 V +24 V
To set the safety outputs in the ON state, the high Using safety input 2 system
state signals must be input to both safety input 1 (without short-circuit +24 V
and safety input 2. Otherwise the safety outputs monitoring between
cannot be in the ON state. systems) T11 T12 T21 T22 Y1
state. D1 D2 D3 D4
input T33 To set the safety outputs in the ON state, the signal Feedback loop
input to T32 must change from the OFF state to the Reset
KM +24 V
Manual reset Switch
ON state, and then to the OFF state. Otherwise the
safety outputs cannot be in the ON state. T31 T32 T33
Input a
Unit A
A logical AND connection means that one unit (Unit G9SX-NS/NSA
A) outputs a safety signal “a” to a subsequent unit Output (a) L1 A2 Logical AND connection sig.
Next unit (4 unit max.)
(Unit B) and Unit B calculates the logical AND (i.e., (1st layer)
Input b
outputs the AND) of the signal “a” and safety signal Unit B T41 T42 T41 T42
Logical AND “b”, which is input to Unit B. G9SX-NS/NSA G9SX-NS/NSA
T41, T42
connection input Thereby the logic of the safety output “b” is output.) Output (a&b) L1 A2 Logical AND connection sig.
Next unit (4 unit max.)
To set the safety outputs of the subsequent Unit in (2nd layer)
18
D40A/G9SX-NS
Operation
Functions
Logical AND Connection Connecting Expansion Units
A logical AND connection means that the G9SX outputs a safety • The G9SX-EX and G9SX-EX-T Expansion Units can be connected
signal “a” to another G9SX, and that G9SX creates the logical AND of to a G9SX-NSA222-T3-@ Non-contact Door Switch Controller to
safety signal “a” and safety signal “b.” The safety output of the increase the number of safety outputs. (They cannot be connected
G9SX-NSA222-T03-@ with the logical AND connection shown in the to a G9SX-NS202-@.)
following diagram is “a” AND “b.” • A maximum of five Expansion Units can be connected to one
G9SX-NSA222-T03-@. This may be a combination of G9SX-EX
instantaneous models and G9SX-EX-T OFF-delayed models.
• Remove the terminating connector from the receptacle on
a b
G9SX-NSA222-T03-@ and insert the Expansion Unit cable
G9SX-NS202-@ G9SX-NSA222-T03-@
connector into the receptacle. Insert the terminating connector into
the receptacle on the Expansion Unit at the very end (rightmost).
• When Expansion Units are connected to a Controller, make sure
that power is supplied to every Expansion Unit. (Refer to the
following diagram for actual Expansion Unit connection.)
a a (AND) b
Robot 2
Robot 1
Emergency
stop switch * D40A D40A
G9SX- G9SX-
NSA222-T03-@ NS202-@
Robot 1 Robot 2
19
D40A/G9SX-NS
Setting Procedure
1. Cross Fault Detection (G9SX-NSA222-T03-@) 3. Setting Logical AND Connection (G9SX-NS202-@/
Set the cross fault detection mode for safety inputs by shorting Y1 NSA222-T03-@)
to 24 V or leaving it open. When connecting two or more Non-contact Door Switch
When cross fault detection is set to ON, short-circuit failures are Controllers by logical AND connection, set the logical AND
detected between safety inputs T11-T12 and T21-22. When a connection preset switch on the Controller that is on the input side
cross fault is detected, the following will occur. (Unit B in the following diagram) to AND. The default setting of the
(1) The safety outputs and logical AND outputs lock out. logical AND connection preset switch is set to OFF.
(2) The LED error indicator is lit.
Unit A
(3) The error output (auxiliary output) turns ON.
AND
Cross fault L1 A2
Wiring OFF
detection
+24 V
T41 T42 AND
OFF
Using safety input 1 Unit B
+24 V
system
T11 T12 T21 T22 Y1
Note: A setting error will occur and Unit B will lock out if the logical
OFF AND setting switch on the Unit B is set to OFF.
+24 V +24 V
4. Setting the OFF-delay Time (G9SX-NSA222-T03-@)
The OFF-delay preset time on G9SX-NSA222-T03-@ is set from
+24 V the OFF-delay time preset switch (1 each on the front and back of
T11 T12 T21 T22 Y1
the Unit).
Using safety input 2 Normal operation will only occur if both switches are identically set.
system An error will occur if the switches are not identically set. The default
setting of the OFF-delay time preset switch is set to 0 s.
Front Back
ON
T11 T12 T21 T22 Y1
Switch
2. Reset Mode (G9SX-NS202-@/NSA222-T03-@)
Set the reset mode using feedback/reset input terminals T31, T32, Switch
and T33.
Auto reset mode is selected when terminal T32 is shorted to 24 V
and manual reset mode is selected when terminal T33 is shorted
to 24 V.
Refer to the following illustration for details on setting switch positions.
Auto reset mode Manual reset mode
G9SX-NSA222-T03-@
KM1 KM1
20
D40A/G9SX-NS
LED Indicators
G9SX-
Marking Color Name G9SX-NS202 G9SX-EX G9SX-EX-T Function Reference
NSA222
Power supply
PWR Green ❍ ❍ ❍ ❍ Lights while power is supplied. ---
indicator
Lights while a high signal is input to T12.
Safety input #1
T1 Orange --- ❍ --- --- Flashes when an error relating to safety
indicator
input #1 occurs.
Lights while a high signal is input to T22.
Safety input #2
T2 Orange --- ❍ --- --- Flashes when an error relating to safety
indicator
input #2 occurs.
Lights when the Non-contact Door Switch
Non-contact Door
input turns ON. Flashes when an error
NS Orange Switch input ❍ ❍ --- ---
relating to the Non-contact Door Switch
indicator
input occurs.
Lights in the following cases:
With automatic reset while a high signal is
input to T33.
Feedback/reset
FB Orange ❍ ❍ --- --- With manual reset while a high signal is
input indicator
input to T32. *
Flashes when an error relating to feedback/
reset input occurs.
Lights while a high signal is input to T41.
Logical AND input
AND Orange ❍ ❍ --- --- Flashes when an error relating to logical
indicator
AND connection input occurs.
Lights while the Instantaneous safety
Instantaneous
outputs (S14, S24, S34) are in the ON state.
EI Orange safety output ❍ ❍ ❍ ---
Flashes when an error relating to the
indicator
instantaneous safety output occurs.
Lights while OFF-delayed safety outputs
OFF-delayed
(S44, S54) are in the ON-state.
ED Orange safety output --- ❍ --- ❍
Flashes when an error relating to
indicator
OFF-delayed safety output occurs.
ERR Red Error indicator ❍ ❍ ❍ ❍ Lights or flashes when an error occurs.
21
D40A/G9SX-NS
Fault Detection
When the Non-contact Door Switch Controller detects a fault, the ERR indicator and/or other indicators light up or flash to inform the user about
the fault.
Check and take necessary measures referring to the following table, and then re-supply power to the Non-contact Door Switch Controller.
(G9SX-NS202-@/NSA222-T03-@)
ERR Other
Fault Expected causes of the fault Check points and measures to take
indicator indicator
Fault due to
1. Excessive electromagnetic 1. Check the disturbance level around the G9SX
electromagnetic
--- disturbance and the related system.
disturbance or of internal
Flashes 2. Failure of the internal circuit 2. Replace with a new product.
circuits.
1. Error in the wiring of safety input 1 1. Check the wiring to T11 and T12.
Fault involved with safety 2. Incorrect setting of cross fault 2. Check the wiring to Y1.
input 1 detection input
T1 flashes
3. Failure of the circuit of safety input 1 3. Replace with a new product.
1. Error in the wiring of safety input 2 1. Check the wiring to T21 and T22.
Fault involved with safety 2. Incorrect setting of cross fault 2. Check the wiring to Y1.
input 2 detection input
T2 flashes
3. Failure of the circuit of safety input 2 3. Replace with a new product.
1. Error in the wiring of Non-contact 1. Check the wiring to D1 and D2.
Door Switch input
2. Error in the wiring of Non-contact 2. Check the wiring to the D40A.
Fault involved with Door Switch inputs in series
Non-contact Door Switch connections.
NS
input 3. Failure of the internal circuits of 3. Replace with a new product.
flashes
Non-contact Door Switch inputs
4. Failure of the Non-contact Door 4. Replace with a new D40A.
Switch
1. Error in the wiring of feedback/reset 1. Check the wiring to T31, T32 and T33.
Fault involved with input.
feedback/reset inputs 2. Failure of the circuit of feedback/ 2. Replace with a new product.
reset input
1. Improper feedback signals from 1. Check the connecting cable of Expansion Unit
Expansion Unit and the connection of the termination socket.
FB
2. Abnormal supply voltage to 2. Check the supply voltage to Expansion Unit.
flashes
Lights Fault in Expansion Unit Expansion Unit Note: Make sure that all Expansion Units' PWR
indicators are lit.
3. Failure of the circuit of safety relay 3. Replace with a new product.
contact outputs
1. Error in the wiring of instantaneous 1. Check the wiring to S14 and S24.
safety outputs
2. Failure of the circuit of instantaneous 2. Replace with a new product.
safety outputs
Fault involved with
3. Error in the wiring of the logical AND 3. Check the wiring to L1.
instantaneous safety
connection output
outputs, logical AND
4. Failure of the circuit of the logical 4. Replace with a new product.
EI flashes connection outputs, or
AND connection output
auxiliary monitor output
5. Error in the wiring of the auxiliary 5. Check the wiring to X1.
monitor output
6. Impermissible high ambient 6. Check the ambient temperature and spacing
temperature around the G9SX.
1. Error in the wiring of OFF-delayed 1. Check the wiring to S44 and S54.
safety relay contact outputs
2. Incorrect set values for OFF-delay 2. Check the settings of the OFF-delay time setting
Fault involved with
time switch.
OFF-delayed safety
ED 3. Failure of the circuit of OFF-delayed 3. Replace with a new product.
outputs
flashes safety relay contact outputs
4. Impermissible high ambient 4. Check the ambient temperature and spacing
temperature around the G9SX.
22
D40A/G9SX-NS
ERR Other
Fault Expected causes of the fault Check points and measures to take
indicator indicator
1. Error in the wiring of the logical AND 1. Check the wiring to T41 and T42.
connection input
Note: 1. Make sure that the wiring length for the
T41, T42 terminal is 100 meters or less.
2. Make sure that the logical AND
Fault involved with logical connection signal is branched for 4 units
AND AND connection input or fewer.
flashes
2. Incorrect setting for the logical AND 2. Confirm the set value of the logical AND
connection input connection preset switch.
Lights 3. Failure of the circuit of the logical 3. Replace with a new product.
AND connection input
All Supply voltage outside the 1. Supply voltage outside the rated 1. Check the supply voltage to the Units.
indicators rated value value
except
PWR flash
When indicators other than the ERR indicator flash, check and take necessary actions referring to the following table.
ERR Other
Fault Expected cause of the fault Check points and measures to take
indicator indicators
T1 The input status between input 1 and Check the wiring from safety input devices to the
Mismatch between input 1 input 2 is different, due to contact failure G9SX. Or check the input sequence of safety input
T2 and input 2. or a short circuit of safety input devices. After removing the fault, turn both safety
Off flash
device(s) or a wiring fault. inputs 1 and 2 to the OFF state.
(Expansion Unit)
ERR Other
Fault Expected cause of the fault Check points and measures to take
indicator indicators
Fault involved with safety
1. Welding of relay contacts
--- relay outputs of Replace with a new product.
2. Failure of the internal circuit
Lights Expansion Units
23
D40A/G9SX-NS
Application Examples
PL/safety category Model Stop category Reset
Non-contact Door Switch D40A
PLe/3 equivalent 1 Manual
Non-contact Door Switch Controller G9SX-NSA222-T03-@ (24 VDC)
Note: 1. The above PL is only the evaluation result of the example. The PL must be evaluated in an actual application by the customer after
confirming the usage conditions.
2. The above PL is the evaluation result concerning the guard. The PL for emergency stop switch and other safety functions must be
separately evaluated.
3. Stopping time is required between when an opening of the guard is detected and when the motor M stops. Use after risk assessment to
prevent operators from approaching hazardous areas too closely during this period.
● Application Overview
• The S2 monitors the guard, and stop command is sent to the motor controller when the guard is opened.
• The power supply to the motor M1 is turned OFF after OFF-delay time.
• The power supply to the motor M1 is kept OFF while the guard is opened.
• The power supply to the motor M1 is turned ON again when the reset switch S3 is pressed while the guard is closed.
Guard
S2
Non-contact
Door Switch
Feedback Loop
Actuator
+24 V
11 KM1
S14
Motor controller
S3 KM2
12
S1 KM1
+24 V
KM2
Brown
White
Black
blue
NC NC NC NC
AND
A1 T11 T12 T21 T22 T31 T32 T33 Y1 D1 D2 D3 D4 T41 T42
OFF M1 Timing chart
G9SX-NSA222-T03
Emergency stop
+24 V
switch operation
Non-contact
Door Switch S2
A2 S14 S24 S44 S54 L1 X1 X2
Reset switch S3
KM1 KM2 PLC etc.
G9SX S14
24
D40A/G9SX-NS
● Application Overview
• The S3 monitors the guard 2, and stop command is sent to the motor controller when the guard 2 is opened.
• The power supply to the motor M1 is turned OFF after OFF-delay time.
• The power supply to the motor M1 is kept OFF while the guard 2 is opened.
• The power supply to the motor M1 is turned ON again when the guard 2 is closed.
Guard 1
23
S3
S2
Non-contact
Door Switch
24 Feedback Loop
Actuator
Guard 2
11
S1 S14
Motor controller
KM1
12
KM2 KM1
open
+24 V KM2
Brown
White
Black
Blue
NC NC NC
AND
A1 T11 T12 T21 T22 T31 T32 T33 Y1 D1 D2 D3 D4 T41 T42
OFF M1
G9SX-NSA222-T03
+24 V
Control circuit
Timing chart
Note: For details on Non-contact Door Switch wiring, refer to pages 17 and 18 or Rotation of motor
to the User’s Manual.
OFF-delay time OFF-delay time
25
D40A/G9SX-NS
● Application Overview
• The S3 monitors the guard, and the power supply to the motor M2 is turned OFF immediately when the guard is opened.
• The power supply to the motor M2 is kept OFF while the guard is opened.
• The power supply to the motor M2 is turned ON again when the guard is closed.
Feedback Loop
11 21
KM1
12 22
KM2
S1
KM1
S2
+24 V KM2
NC
S3
Non-contact
Door Switch
Feedback Loop
Actuator
Guard
Timing chart
KM3
Emergency stop
KM4 switch operation
G9SX-BC202 (Unit 1)
+24 V +24 V
White
Black
Reset switch S2
Blue
AND
A1 D1 D2 D3 D4 T31 T32 T33 T41 T42 Unit 1 S14, S24
OFF
Non-contact
Door Switch S3
S3: Non-contact Door Switch
Unit 2 S14, S24
KM3, KM4: Contactor
M2: 3-phase motor KM3, KM4 N.C. contact
Note: For details on Non-contact Door Switch wiring, refer to KM3, KM4 N.O. contact
pages 17 and 18 or to the User’s Manual.
Rotation of motor M2
26
D40A/G9SX-NS
● Application Overview
• The S2 monitors the guard, and the power supply to the motor M1 is turned OFF immediately when the guard is opened.
• The power supply to the motor M1 is kept OFF while the guard is opened.
• The power supply to the motor M1 is turned ON again when the reset switch S3 is pressed while the guard is closed.
G9SP-N20S
G1 T0 T1 T2 T3 T4 G2
27
D40A/G9SX-NS
Safety Precautions
Refer to the “Precautions for All Switches” and “Precautions for All Safety Door Switches”.
Indication and Meaning for Safe Use
Precautions for Safe Use
Indicates a potentially hazardous situation <D40A/G9SX-NS@>
which, if not avoided, will result in minor 1. Disconnect the G9SX-NS from the power supply when wiring the
D40A.
WARNING or moderate injury, or may result in
1. Turn OFF the load power supply before wiring. Failure to do so
serious injury or death. Additionally there
may cause electric shock.
may be significant property damage.
2. Devices connected to the product may operate unexpectedly.
2. Do not operate the product in atmospheres containing flammable
Precautions Supplementary comments on what to do
or explosive gas. Arcs or heating of relays during switching may
for Safe Use or avoid doing, to use the product safely. cause fire or explosion.
3. Wire conductors correctly and verify the operation of the product
Precautions Supplementary comments on what to do before using the system in which the product is incorporated.
or avoid doing, to prevent failure to Incorrect wiring may lead to loss of safety functions.
for Correct operate, or undesirable effect on product 4. Do not dismantle, repair, or modify the product. Doing so may lead
Use to loss of safety functions.
performance.
<D40A>
5. Auxiliary monitoring outputs are NOT safety outputs. Do not use
auxiliary monitoring outputs as safety outputs. Such incorrect use
!WARNING will cause loss of safety function of D40A and peripheral devices.
Serious injury may possibly occur due to breakdown of 6. After installing the D40A, qualified personnel must confirm the
safety outputs. installation, and must conduct test operations and maintenance.
Do not connect loads beyond the rated value to the The qualified personnel must be qualified and authorized to
safety outputs. secure safety at each phases of design, installation, running,
maintenance, and disposal of the system.
Serious injury may possibly occur due to loss of required 7. A qualified person in charge, who is familiar with the machine in
safety functions. which the D40A is to be installed, must conduct and verify the
Wire the D40A and G9SX-NS properly so that supply installation.
voltages or voltages for loads do NOT touch the safety 8. Be sure to inspect the D40A daily and every 6 months. Otherwise,
outputs accidentally. serious injury may possibly occur due to system malfunctions.
Serious injury may possibly occur due to damage to 9. Connect the D40A to only appropriate components or devices
safety outputs. complying with relevant safety standards corresponding to the
Provide protective circuits against counter-electromotive required level of safety category. Conformity to requirements of
force if inductive loads are connected to safety outputs. the safety category must be determined for the entire system. It is
recommended to consult an authorized certification body
Serious injury may possibly occur due to loss of safety
regarding assessment of conformity to the required safety level.
functions.
Use appropriate devices referring to the information <G9SX-NS@>
provided below. 10. Use the G9SX within an enclosure with a IP54 degree of
protection or higher according to IEC/EN 60529.
The machine may start operating and may result in
11. Do not apply DC voltages exceeding the rated voltages, nor any
serious injury or death.
AC voltages to G9SX-NS@.
Do not put the actuator close to the switch when the door
12. Use a DC supply satisfying the requirements given below to
is open.
prevent electric shock.
• A DC power supply with double or reinforced insulation, for
Control device Requirements
example, according to IEC/EN 60950 or EN 50178, or a
Emergency stop Use approved device with direct opening transformer according to IEC/EN 61558.
switch mechanism complying with IEC/EN 60947-5-1. • A DC supply satisfying the requirements for class 2 circuits or
Use approved device with direct opening limited voltage/current circuits stated in UL 508.
Safety door switch, mechanism complying with IEC/EN 60947-5-1 13. Properly apply the specified voltages to the inputs. Applying
Safety limit switch and capable of switching micro loads of 24 VDC, inappropriate voltages may cause the product to fail to perform its
5 mA. specified function, which could lead to the loss of safety functions
Non-contact The G9SX-NS must be used with D40A or damages to the product.
Door Switch Non-contact Door Switches. 14. Auxiliary error outputs and auxiliary monitoring outputs are NOT
safety outputs. Do not use these outputs as safety outputs.
Use approved devices with forcibly guided Such incorrect use will cause loss of safety functions of the G9SX
Relay with contacts complying with EN 50205. and its relevant system. Also logical AND connection outputs can
forcibly guided For feedback, use devices with contacts only be used for logical AND connections with the G9SX-@.
contacts capable of switching micro loads of 24 VDC, 15. After installing the G9SX-NS@, qualified personnel must confirm
5 mA. the installation, and must conduct test operations and
Use contactors with forcibly guided mechanism maintenance. The qualified personnel must be qualified and
to input the signal to the Feedback/Reset input authorized to secure safety at each phases of design, installation,
of the G9SX-NS through the NC contact of the running, maintenance, and disposal of system.
contactor. 16. A qualified person in charge, who is familiar with the machine in
For feedback, use devices with contacts which G9SX-NS@ is to be installed, must conduct and verify the
Contactor capable of switching micro loads of 24 VDC, installation.
5 mA. 17. Perform daily and 6-month inspections for the G9SX-NS@.
Failure to open contacts of a contactor cannot Otherwise, the system may fail to work properly, resulting in
be detected by connecting NC contact of the serious injury.
contactor without a forcibly guided mechanism
to the Feedback/Reset input.
Evaluate whether devices used are appropriate
Other devices to satisfy the requirements of the safety
category level.
28
D40A/G9SX-NS
D1 D2 D3 D4
G9SX-NS202-@
G9SX-NSA222-T03-@
6. Disconnect the G9SX-NS@ from the power supply when replacing
the D40A. Devices connected to the G9SX-NS@ may operate
unexpectedly.
7. Adhesion of solvent such as alcohol, thinner, trichlorobenzene or
gasoline on the product should be avoided.
Such solvents make the marking on D40A illegible and cause
deterioration of parts.
8. Do not use the D40A in a magnetic field of 1.5 mT or higher. The
D40A may not function properly.
9. Do not use the D40A in the water or in an environment
continuously exposed to water. Water may penetrate into the
D40A. (The IP67 degree of protection for this switch means that it
has been checked for penetration of water after having been left
in water for a fixed period of time.)
10. Do not use the switch or actuator as a stopper. Protect the switch
and the actuator by installing a stopper. Separate the switch and
the actuator to a distance of 1 mm or more.
11. Install the actuator and switch at an appropriate distance so that
they do not create a gap that provides access to the hazard.
Correct Incorrect
29
D40A/G9SX-NS
12. Where two or more Switches are mounted side-by-side, they must <G9SX-NS@>
be no closer than 25 mm. 19. Mounting
Mount the G9SX-NS to a DIN rail using End Plates (PFP-M, not
included with the product) so that the G9SX-NS does not fall off of
25 mm min.
the rails due to vibration or other causes, especially when the
length of DIN railing is short compared to the width of the
G9SX-NS@.
20. The following space must be provided around the G9SX-NS@ to
13. Check that the machine is stopped whenever the interlocked enable applying the rated current to the outputs of the G9SX-
guard door is open. NS@, to ensure sufficient ventilation, and to enable wiring:
1. At least 25 mm between side surfaces of the G9SX-NS@
2. At least 50 mm above the top surface of the G9SX-NS@ and
below the bottom surface of the G9SX-NS@.
50 mm min.
14. Do not mount the switch and actuator on magnetic materials,
otherwise it may affect the operating distance.
Distance from surface of
Operating distance
magnetic body
Reduce to approx. 90% of
0 to 5 mm
original value.
5 mm or longer No influence.
15. Tighten all screws to the specified torque by using non-magnetic
25 mm min. 25 mm min.
M4 screws with a maximum diameter of 7 mm and washer for the 50 mm min.
installation of the switch and actuator. After installation and using,
the actuator and switch fixing screws must be coated with tamper
proof varnish or similar 21. Wiring
compound. Using anaerobic locking compounds can have a 1. G9SX-NS@-RT (with Screw Terminals)
detrimental effect on the plastic switch case if the compounds • Use the following to wire the G9SX-NS@-RT.
come into contact with the switch case.
Solid wire 0.2 to 2.5 mm2 (AWG24 to
Actuator (steel wire) AWG12)
Stranded wire 0.2 to 2.5 mm2 (AWG24 to
(flexible wire) AWG12)
• Tighten each screw to the specified torque of 0.5 to 0.6 N·m,
or the G9SX-NS@ may malfunction or generate heat.
• Strip the wire for no longer than 7 mm.
2. G9SX-NS@-RC (with Spring-cage Terminals)
1.0 N·m • Use the following to wire the G9SX-NS@-RC.
Switch Solid wire 0.2 to 2.5 mm2 (AWG24 to
16. Wiring (steel wire) AWG12)
1. Use the following to wire to the product. Stranded wire 0.2 to 2.5 mm2 (AWG24 to
Stranded wire (flexible wire): 0.2 to 2.5 mm2 (AWG24 to (flexible wire) AWG12)
AWG12) • Strip the wire for no longer than 7 mm.
Solid wire (steel wire): 0.2 to 2.5 mm2 (AWG24 to AWG12) 3. Logical AND Connections
2. When an auxiliary output is not used, cut off the wiring and • Use VCTF cables or shielded cables for logical AND connect
cover it with tape so that it does not contact other terminals. ions between Units.
3. When you use an additional cable of 20m or longer, use a 22. Connecting G9SX-EX@-@ Expansion Units
multiconductor cable to group the white, black, brown, and blue 1. Remove the terminating connector from the connector on the
lines together. G9SX-NSA222-T03@. Insert the connector on the connecting
17. Handle cables with care cable of Expansion Unit into the connector on the G9SX-NSA222-
1. For bending cables, it is recommended to bend them with a T03-@.
radius of bend no less than six times the cable outer diameter. 2. Connect the terminating connector to the connector on the
2. Do not apply a tensile strength of 50N or greater to the cables. Expansion Unit at the end position.
18. If there is any machine that has a large surge current (e.g., When the G9SX-NSA222-T03-@ is used without Expansion
amotor) near D40A, connect a surge absorber to D40A between
Units, leave the terminating connector on the G9SX-NSA222-
the blue and the other cables (white, black, brown, and yellow),
respectively. T03-@.
Suggested surge absorber's specification is as follows: 3. Do not remove the terminating connector or connecting cables
• Peak pulse power: 600W (10/1000 ms) or more (Per of Expansion Units while the system is operating.
IEC61000-4-5(surge immunity)) 4. Before applying the supply voltage, confirm that the connectors
• Breakdown voltage: 27-33V are locked firmly.
5. All of the Expansion Units must be supplied with its specified
voltages within 10 s after the connected G9SX-NSA222-T03-@
is supplied with voltage.
Otherwise, the G9SX-NSA222-T03-@ will detect a power
supply error for the Expansion Units.
23. Use cables with a length of less than 100 m total to connect the
safety inputs, feedback/reset inputs, and logical AND connection
inputs and outputs.
30
D40A/G9SX-NS
24. Set the time duration of OFF-delay to an appropriate value that Switch and Actuator Operation
does not cause the loss of safety functions of system.
25. Logical AND connections between Units (Refer to “Functions” on Switch and Actuator Mounting Directions
page 19.)
1. To use logical AND connection inputs, enable the logical AND
connection input for the G9SX-NS@ that will receive the inputs.
2. Connect the logical AND connection inputs appropriately to the
logical AND connection outputs of the G9SX-@.
3. When configuring the safety system, be sure to consider that
the delay of response time caused by logical AND connection Switch
Switch
does not degrade the safety functions of the system. (Refer to Actuator Actuator
“Response Time and Operating Time” on page 12.)
26. To determine safety distance to hazards, take into account the Switch and Actuator Operating Directions
delay of safety outputs caused by the following time:
1. Response time of safety inputs
2. Response time of D40A Non-contact Door Switch inputs
3. Response time of logical AND connection input
(Refer to “Response Time and Operating Time” on page 12.)
4. Preset OFF-delay time
5. Accuracy of OFF-delay time
27. Start the rest of the system after 5 s or longer has passed since
applying supply voltage to all G9SX-@ in the system. Correct Correct Correct Incorrect
28. Be sure to ground the A2 terminal of the power supply to help
prevent malfunctions caused by noise. Also, connect a surge
absorber to each end of the coil on inductive loads to reduce noise Safety Categories
generation. When sharing a power supply with a Light Curtain, You can use the D40A with the G9SX-NS@ for applications in PLd
use a DC power supply that will not fail for a momentary power and Safety Category 3 environments defined in the EN ISO13849-1
interruption of 20 ms or less.
European standard and the ISO 13849-1 international standard.
29. Devices connected to the G9SX-NS may operate unexpectedly.
When replacing the G9SX-NS, disconnect it from power supply. Compliance was determined using circuit examples specified by
30. Adhesion of solvent OMRON and may not be applicable to all conditions.
Do not allow organic solvents, such as alcohol, thinner, Safety categories are determined for the overall safety control
trichloroethane, or gasoline, to come into contact with the product. system. Confirm compliance sufficiently with your application.
Such solvents make the markings on G9SX-NS illegible and
cause deterioration of parts. Requirements for Safety Category 3 (ISO 13849-1)
31. Do not mix AC and DC circuits for contact outputs in a single
G9SX-EX@-@. When using AC and DC circuits, connect at least 1. Connect external input D1-D2 and external output D3-D4 to D40A
two G9SX-EX@-@ Units and use them respectively as dedicated Switches.
DC-circuit and AC-circuit contact outputs. 2. Input two channels for external inputs T11-T12 and T21-T22.
32. Safety Application Controller’s Relay durability depends greatly 3. Input external inputs T11-T12 and T21-T22 from switches with
on the switching condition. Confirm the actual conditions of direct opening mechanisms. For limit switches, make sure at least
operation in which the Relay will be used in order to make sure the one of the switches has a direct opening mechanism.
permissible number of switching operations. 4. Input the NC signal from the contactor to T31-T32 for a manual
When the accumulated number of operation exceeds its reset and to T31-T33 for an auto reset. (Refer to “Application
permissible range, it can cause failure of reset of safety control Examples” on page 24)
circuit. In such case, please replace the Relay or the Safety 5. Make sure to connect the A2 terminal to ground.
Application Controller immediately.
If the Relay or the Safety Application Controller is used Approved Standards
continuously without replacing, then it can lead to loss of safety
<D40A>
function.
• EN ISO 13849-1 PLd/Safety Category 3 (used with G9SX-NS@)
• EN 61508 SIL 3 (used with G9SX-NS@)
• EN 60947-5-3 (PDF-M) (used with G9SX-NS@)
• EN1088
• UL 508
• CAN/CSA C22.2 No.14
• KOSHA certification (excluding connector model)
31
Warranty and Application Considerations
Read and Understand this Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any
questions or comments.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR
COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT,
WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS
UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND
MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in
the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING
THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE
PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty.
It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual
performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with your
OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
OMRON ASIA PACIFIC PTE. LTD. OMRON (CHINA) CO., LTD. © OMRON Corporation 2009 All Rights Reserved.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Room 2211, Bank of China Tower, In the interest of product improvement,
Alexandra Technopark, 200 Yin Cheng Zhong Road, specifications are subject to change without notice.
Singapore 119967 PuDong New Area, Shanghai, 200120, China CSM_7_1_0214 Printed in Japan
Tel: (65) 6835-3011/Fax: (65) 6835-2711 Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 Cat. No. C140-E1-01 0906-3M (0906) (O)