87 Caroline Street

St Pauls Square
Birmingham DESIGN NOTES
B3 1UP

Prepared: LM Page:
Project: iLecsys Rail CTS Staging Design
Reviewed: JR
Document No:
Subject: CTS Staging Platform Reactions
F-2487-FJD-REP-000001 Rev 01

Loading:
Cabinet weight: 750 kg
Platform live load: 3 kN/m3
Wind load: 1.788 kN/m2

Reactions:
ULS
Maximum values
Fx Fy Fz Mx My
(kN) (kN) (kN) (kNm) (kNm)
1 8.397 13.26 41.785 -0.557 0.274
2 -0.004 1.474 22.582 -1.382 -0.003
3 -7.722 13.524 46.691 -0.878 -0.250
4 6.226 -9.268 13.836 0.892 0.869
5 0.065 2.549 39.033 -1.937 0.044
6 -5.838 -9.029 14.244 0.985 -0.743

Minimum values
Fx (kN) Fy (kN) Fz Mx My
(kN) (kNm) (kNm)
1 3.764 10.339 32.56 -1.032 -0.025
2 -0.018 1.331 20.902 -1.552 -0.030
3 -12.882 10.04 36.547 -1.372 -0.553
4 2.859 -12.714 9.744 0.012 -0.254
5 -2.172 -8.509 36.031 -4.756 -0.902
6 -8.932 -13.048 9.451 -0.056 -1.801

FJD Consulting Ltd Birmingham Office


SLS
Maximum values
Fx Fy Fz Mx My
(kN) (kN) (kN) (kNm) (kNm)
1 3.254 4.97 15.943 -0.182 0.135
2 -0.001 0.547 8.732 -0.501 -0.001
3 -2.961 5.09 18.133 -0.325 -0.123
4 2.653 -3.259 5.606 0.363 0.370
5 0.036 1.362 15.095 -0.603 0.020
6 -2.482 -3.149 5.783 0.404 -0.314

Minimum values
Fx (kN) Fy (kN) Fz Mx (kNm) My
(kN) (kNm)
1 1.194 3.671 11.843 -0.393 0.002
2 -0.007 0.483 7.985 -0.576 -0.013
3 -5.254 3.541 13.625 -0.544 -0.258
4 1.157 -4.791 3.787 -0.028 -0.129
5 -0.958 -3.553 13.761 -1.856 -0.400
6 -3.857 -4.935 3.653 -0.059 -0.785

All load factored in accordance with BS EN 1990 & UK NA.

All of the above tabulated values are enveloped values for each support location. As such, these
values reflect the worst case actions in each plane of action. Should actual loadcases be
required for each column reaction, these can be provided upon request. Any queries on the
outputs should be raised with the designer.

Design notes:

• As agreed, the model used in the calculation pack has been modified to reflect the
different design as detailed on drawing ref “Kier CTS basic Top + Supports” and also to
include amendments specified over email. Namely these include:
o Larger CTS 2200 x 1590 x 770mm cabinet.
o 2no. U200x60x10 cabinet support members increased to 4no.
o 2no. steel angle cross bracing changed to a K100x100x6 member single
brace.
• Modelling does not account for doubling up of platform ‘U’ members for structural
capacity.
• Connection brackets have not been assessed.
• It is assumed that the cabinet is fixed with 2no. fixings into cross members.
• FRP grade taken as E17.
• It is assumed that CTS cabinet receives full wind loading i.e. elevated platform and kick-
board provides no beneficial protection.
• Cabinet fixing to ‘U’ channel will be limited by pull-through capacity, bearing failure will
not be considered to occur.