FRAME LV 804 R
SPECIFICATIONS & OPTIONS
STANDARDS WINDINGS & ELECTRICAL PERFORMANCE
STAMFORD AC generators are designed to meet the All generator stators are wound to 2/3 pitch. This
performance requirements of IEC EN 60034-1. Other eliminates triplen (3rd, 9th, 15th …) harmonics on the
international standards, including BS5000, VDE 0530, voltage waveform and is found to be the optimum design
NEMA MG1-32, AS1359, CSA C22.2, UL and CE; as well for trouble-free supply of non-linear loads. The 2/3 pitch
as a wide range of international Marine Certification design avoids excessive neutral currents sometimes seen
Approvals, can be met on request. For clarification with higher winding pitches. A fully connected damper
regarding compliance please contact Cummins Generator winding reduces oscillations during paralleling. This
Technologies. winding, with the 2/3 pitch and carefully selected pole and
tooth designs, ensures very low levels of voltage waveform
DESCRIPTION distortion.
2
FRAME LV 804 R
WINDING 12
RATINGS REFER TO SALES AND SERVICE BRIEFING
MAXIMUM ALTITUDE 1000 METRES ABOVE SEA LEVEL
MAXIMUM AMBIENT TEMPERATURE 40º C
Continuous development of our products entitles us to change specification details without notice,
therefore they must not be regarded as binding.
3
FRAME LV 804 R WDG 12 50 Hz
380 V
98.0
97.5
97.0
1.0
96.5
96.0 0.9
95.5 0.8
95.0
% 94.5 P.F.
94.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2290.0 kVA
2290 kVA
400 V 98.0
97.5
97.0
1.0
96.5
0.9
96.0
95.5 0.8
95.0
% 94.5 P.F.
94.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2410 kVA
415 V
98.0
97.5
97.0
1.0
96.5
0.9
96.0
0.8
95.5
95.0
% 94.5
P.F.
94.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2410 kVA
440 V 98.0
97.5
97.0 1.0
96.5 0.9
96.0 0.8
95.5
95.0
94.5
% 94.0
P.F.
93.5
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2265 kVA
4
FRAME LV 804 R WDG 12 60 Hz
416 V
97.5
97.0
96.5
1.0
96.0
0.9
95.5
95.0 0.8
94.5
94.0
% 93.5
P.F.
93.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2600.0 kVA
2600 kVA
440 V 97.5
97.0
96.5 1.0
96.0 0.9
95.5
0.8
95.0
94.5
94.0
% 93.5 P.F.
93.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2750 kVA
460 V
97.5
97.0
96.5 1.0
96.0 0.9
95.5 0.8
95.0
94.5
94.0
% 93.5
P.F.
93.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2875 kVA
480 V 97.5
97.0
1.0
96.5
0.9
96.0
95.5 0.8
95.0
94.5
94.0
% 93.5
P.F.
93.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
3000 kVA
5
FRAME LV 804 R WDG 12 50Hz
FULL WAVE RECTIFIED AVR
LOCKED ROTOR MOTOR STARTING CURVE
380V 400V 415V 440V
30.0
PER CENT TRANSIENT VOLTAGE DIP
25.0
20.0
15.0
10.0
5.0
0.0
0 500 1000 1500 2000 2500 3000 3500 4000 4500
LOCKED ROTOR kVA
NOTE 1
100000 THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO ADJUST THE VALUES
FROM CURVES BETWEEN THE 0.001 SECONDS AND THE MINIMUM CURRENT POINT IN
SYMMETRIC
RESPECT OF NOMINAL OPERATING VOLTAGE
380V X 0.95
400V X 1.00
415V X 1.04
440V X1.10
CURRENT (Amps)
NOTE 2
THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO CONVERT THE
VALUES CALCULATED IN ACCORDANCE WITH NOTE 1 TO THOSE APPLICABLE
TO THE VARIOUS TYPES OF SHORT CIRCUIT
3 PHASE 2 PHASE L-L 1 PHASE L-N
INSTANTANEOUS X 1.0 X 0.87 X 1.30
MINIMUM X 1.0 X 1.80 X 3.20
SUSTAINED X 1.0 X 1.50 X 2.50
MAX SUSTAINED DURATION 10 SEC 5 SEC 2 SEC
6
FRAME LV 804 R WDG 12 60Hz
FULL WAVE RECTIFIED AVR
LOCKED ROTOR MOTOR STARTING CURVE
416V 440V 460V 480V
30.0
PER CENT TRANSIENT VOLTAGE DIP
25.0
20.0
15.0
10.0
5.0
0.0
0 500 1000 1500 2000 2500 3000 3500 4000 4500
LOCKED ROTOR kVA
NOTE 1
100000
THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO ADJUST THE VALUES
SYMMETRIC FROM CURVES BETWEEN THE 0.001 SECONDS AND THE MINIMUM CURRENT POINT IN
RESPECT OF NOMINAL OPERATING VOLTAGE
416V X 0.87
440V X 0.92
460V X0.96
CURRENT (Amps)
480V X1.00
NOTE 2
THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO CONVERT THE
VALUES CALCULATED IN ACCORDANCE WITH NOTE 1 TO THOSE APPLICABLE
TO THE VARIOUS TYPES OF SHORT CIRCUIT
3 PHASE 2 PHASE L-L 1 PHASE L-N
INSTANTANEOUS X 1.0 X 0.87 X 1.30
MINIMUM X 1.0 X 1.80 X 3.20
SUSTAINED X 1.0 X 1.50 X 2.50
MAX SUSTAINED DURATION 10 SEC 5 SEC 2 SEC
ALL OTHER TIMES ARE UNCHANGED
1000
0.001 0.01 0.1 1 10
TIME (secs)
SUSTAINED SHORT CIRCUIT = 14073 Amps
7
FRAME LV 804 R
WINDING 12 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
kVA 2100 2210 2210 2075 2290 2410 2410 2265 2445 2575 2575 2420 2515 2650 2650 2490
kW 1680 1768 1768 1660 1832 1928 1928 1812 1956 2060 2060 1936 2012 2120 2120 1992
Efficiency (%) 95.8 95.9 96.0 96.1 95.7 95.8 95.9 96.0 95.5 95.6 95.7 95.9 95.5 95.6 95.7 95.9
kW Input 1754 1844 1843 1728 1914 2013 2011 1887 2047 2154 2152 2019 2107 2218 2215 2077
60Hz Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
kVA 2385 2520 2635 2750 2600 2750 2875 3000 2780 2940 3067 3200 2860 3025 3163 3300
kW 1908 2016 2108 2200 2080 2200 2300 2400 2224 2352 2454 2560 2288 2420 2530 2640
Efficiency (%) 95.4 95.6 95.7 95.8 95.3 95.5 95.6 95.7 95.2 95.4 95.5 95.6 95.1 95.3 95.5 95.6
kW Input 2000 2109 2203 2296 2182 2304 2405 2507 2336 2466 2569 2677 2405 2539 2651 2762
© 2009 TD_LV804R.12.GB_03.09_09_GB