Beruflich Dokumente
Kultur Dokumente
The UPS has an internal battery supply. The nominal rating voltage of battery supply is
24V, 48V, 72V for 1KVA, 2KVA and 3KVA UPS individually no matter what model of
the 1KVA, 2KVA and 3KVA UPS.
To reduce the risk of electric shock, install this UPS in a temperature and humidity
controlled indoor area free of conductive contaminants. Ambient temperature must not
exceed 40°C (104°F)
The AC output of the UPS need a disconnect switch such as a breaker which has to be
provided by others.
The over-current protection for the output AC circuit has to be provided by others. All of
our UPS have an electronic protection of AC output short circuit.
When replacing batteries, replace with the same number of the: LC-R129
(PANASONIC), REW45-12 (YUASA), HR9-12 (BB), and HR1234F2 (CSB).
CAUTION! Do not dispose of battery or batteries in fire. The battery may explode.
CAUTION! A battery can present a risk of electrical shock and high short circuit current.
The following precautions should be observed when working on batteries:
1-1
Determine if the battery is inadvertently grounded. If inadvertently grounded, remove
source of ground. Contact with any part of a grounded battery can result in electrical
shock. The likelihood of such shock will be reduced if such grounds are removed
during installation and maintenance (applicable to UPS and a remote battery supply
not having a grounded supply circuit).
This UPS contains batteries, which are potentially hazardous to user, even when the
UPS is not connected to the utility power.
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) this device may not cause harmful interference, and (2)
this device must accept any interference received, including interference that may
cause undesired operation.
1-2
[2, 3KVA MODELS] Federal Communications Commission Interference Statement
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions
manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
1-3
2. INTRODUCTION
BYPASS
PFC Control
Circuit LED Board Control Board
To Control Board
To Auxiliary Power
Battery Bank
To Control Board
To Control Board
Auxiliary
To External Battery Bank Power
2-1
In case the utility power failure, the AC-DC converter and charger will be off duty.
The DC-DC converter works and converts the battery voltage into DC-BUS
voltage. The DC-AC inverter converts the DC-BUS voltage into AC voltage. This
is so called “ON-BATTERY mode”.
The auxiliary power circuit supplies the designated power to all the control
circuits.
Because the DC-AC inverter is always working, the DC-DC converter can work
rapidly and replace the AC-DC converter while the utility power fails. Furthermore,
the bypass relay continuously keeps in the position of inverter output to supply the
regulated power for the load. There is no power failure to loading equipment.
2-2
The control board consists of protection circuit, detection circuit and control
circuit, which control the output voltage to be a sine wave.
Bypass Relay:
It is used to select the output of UPS to be the input utility voltage or the
inverter output voltage.
DC-DC Converter:
It converts the battery voltage into DC-BUS voltage.
Battery Bank:
It is one set of batteries connected in series. According to the different capacity
of UPS, the battery bank has different number of batteries in series.
Charger:
It converts the AC voltage drawing from the utility power into DC voltage,
which properly charges the battery and keep it with full energy.
Aux. Power (Auxiliary Power):
This circuit converts either the output of charger or battery bank voltage into
±12V and 20V and supply the demand power of control circuits in the AC-DC
Converter, DC-AC Inverter and control board.
2-2 FEATURE
The UPS, available in 1KVA, 2KVA and 3KVA, is an advanced on-line UPS
providing reliable and consistent sine-wave quality power to vital equipment. It
supports personal computers, networks, servers, telecommunication equipment
and a variety of other facilities. With its outstanding protection features, the unit
keeps your applications safe and running smoothly at all times.
PFC (Power Factor Correction)
With this function, the investment in the capacity of circuit breakers can be
reduced, specially it will be highly regarded as an important feature in critical load
applications.
Complete Protection
On-line double conversion design, pure sine wave output and zero transfer time
provide best protection. With a built-in surge, spike and line noise protection, the
UPS prevents destructive hardware damage and extends system life. The EMI/RFI
filtering design prevents electrical noise from affecting computer operation and
data files. Besides, the UPS provides built-in Fax/Network cable (RJ11/RJ45)
jacks protecting your hardware from surge, spikes and line-noise which travel
along communication lines, therefore providing you a complete “back door”
protection.
2-3
Intelligent design
Integrated with a microprocessor, the UPS is able to perform intelligent functions.
The UPS triggers over-voltage protection function and transfers to “On- Battery
mode” even when utility voltage exceeds 275V. In addition, the UPS can accept
large voltage variation of 130V to 275V. Wide input voltage range means less
battery power usage frequency and longer battery life-span. Besides,
programmable outlet design, suitable for power management, is also included in
this unit.
Network Management
Build-in communication interface port supporting RS232 protocols enhances the
reliability and manageability of the UPS over all major operating systems,
including Windows 95/98, Windows NT, Netware, UNIX, and others. Besides, the
UPS also supports the Simple Network Management Protocol and Hyper Text
Transfer Protocol via plugging a SNMP/HTTP adapter into the build-in SNMP
slot
2-4
2-3 SPECIFICATION
2-5
2-4 ANNOTATION AND SYMBOL
The two signs shown on the manual indicating important instruction need to be
followed.
!
Read before Operation Maybe Dangerous/Follow Instructions
2-6
2-5 FRONT PANEL
OVERLOAD
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
OVERLOAD
B. 10 100% B. 5
ON
B. 11 FAULT 75%
TEST
A. 1
50%
B. 1 BYPASS
OFF A. 2
25%
B. 2 LINE
B. 3 B. 4
ONLINE LOAD BATT. ON BATT.
B. 7 B. 6
2-7
2-6 OPERATION PANEL
A. Button:
1. ON/TEST Switch: The button is used for turning on the UPS, it can also
perform the battery test function in “ON-LINE mode”. In
“ON-BATTERY mode”, this button can turn off the buzzer for silence.
2. Line LED: This LED indicates the condition of input line. If the input
voltage is too low, too high, or out of frequency, this LED will flash.
When line is blackout, this LED will light off.
5. Level LEDs: The four LEDs indicate that the current battery capacity in
“ON-BATTERY mode” or the current load level of the UPS in
“ON-LINE mode”.
6. Battery LED: When this LED lights up, “Level LEDs” will show the
current battery capacity.
7. Load LED: When this LED lights up, “Level LEDs” will show the load
level of the UPS.
8. Battery Low: This LED indicates that the UPS is in the “Battery Low”
condition.
9. Battery Replace: After Battery test, This LED indicates that the batteries
are weak and it is suggested to the users to replace the batteries.
10. Overload: This LED indicates that the load level exceeds the rating, after
a limited period of time, the UPS will transfer to “BYPASS mode” and
this LED will still light on to alarm the user.
2-8
2-7 REAR PANEL
The rear panel is explained as follows: (Please refer to Fig 2-2, 2-3)
2-9
communication port is used to communicate PC and UPS.
Please refer to section four for more detailed information.
2-10
2-8 INSTALLATION
Unpacking
z Please read this user manual before installing the UPS.
z This UPS contains batteries which are potentially hazardous to user, even
when the UPS is not connected to the utility power.
z Before unpacking the UPS, check the packing box. If there is any visible
damage, contact your dealer at once.
-This unit is to operate by any individuals with previous training.
-This unit should be installed by service personnel.
Before Installation
z Avoid exposing the UPS to direct sunlight or other heat source. The UPS
should be facing away from direct sunlight glare.
z Choose a well-ventilated area to position your UPS to allow adequate
dissipation of heat.
z Ensure the UPS surrounding area is clean and free from moisture.
z Do not put heavy objects on the cable or power cord.
Installation
Notice:
- AC output need a disconnect device such as a breaker which has to be provided
by others.
- The wire length of output power cord connected to the output receptacle or
pressure terminal should be less then 10 meters.
- The UPS provide with pressure terminal connector for field installed wiring,
the terminal connector should be applied a 13.8 lb-in (1.554 N-m) of
tightening torque.
- The over current protection and short circuit protection for the AC output is
provided by internal circuits of UPS and breaker.
- Concerning about the battery voltage, ambient temperature and other
specifications of the UPS, please refer to the specification section of this
manual.
- Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized
personnel away batteries.
- When replacing batteries, replace with the same type and number.
2-11
1. Connecting to utility power (Refer to Fig 2-6, Fig 2-7)
(1) Connect the IEC plug of power cord to the IEC 320 connector on the UPS.
(2) Plug the other end of the power cord into a two-pole, three-wire, grounding
receptacle only. Avoid using extension cords and adapter plug.
After that, the fan (in rear panel) will run and all LEDs will light for about 2-3
sec. Meanwhile the CPU inside the UPS setups the initial parameters. User
also can check whether all LEDs are normal or not. The UPS is set in
“STANDBY mode” initially, after a ‘beep’ is heard, the load LED lights on
and the line LED shows AC utility status. Shown as (Fig 2-4)
OVERLOAD
100%
FAULT 75% ON
TEST
50%
BYPASS
OFF
25%
LINE
2-12
Fig. 2-5.1 (1KVA)
2-13
5. Connecting the RS-232
Connect the interface signal cable between the RS-232 port on the rear panel of
UPS and COM1 or COM2 of computer if necessary.
Fig 2-6
Fig 2-7
2-14
2-9 OPERATION
1. Cold start when utility is not present
Even when there is no utility power, you can still turn on OVERLOAD
100 %
the UPS. Just press the 1/TEST button and hold for 2~4 FAULT 75% ON
TEST
second, the UPS will start up after you hear a “beep”. BYPASS
50%
OFF
The battery LED and on-battery LED will light on and LINE
25%
the UPS runs on “ON-BATTERY mode”. Shown as ONLINE LOAD BATT ON BATT.
.
100 %
can normally turn on the UPS after pushing the 1/TEST FAULT 75% ON
TEST
OFF
The bypass LED will extinguish after shortly light on. LINE
25%
When the on-line LED lights on, the UPS is running on ONLINE LOAD BATT ON BATT.
.
4. UPS self-test
If press the 1/TEST button when the UPS is in “ON-LINE mode”, it will make
the UPS shift to “ON-BATTERY mode” and automatically perform a self-test
for about 10 seconds. The self-test function will check the condition of the
battery. After self-test is finished and test is O.K, the UPS will return to “ON-
LINE mode”.
5. Silence function
The buzzer can be turned “On” or “Off” by toggling the 1/TEST button when
the UPS is in “ON-BATTERY mode”.
2-15
6. If certain abnormal condition occurs, the UPS will send the
following messages:
ON-BATTERY mode: When the UPS is in “ON-BATTERY mode”, the on-
battery LED will light on, buzzer beep half second every 2 seconds and then the
UPS will start supplying power to load through batteries. Refer to (Fig 2-8)
7. De-rating power
In the range of 130Vac to 160Vac, the UPS load capacity will decrease. This
function provides a wider operating power voltage range.
2-10 PLACEMENT
Enclosure Mounting
Install the mounting bracket. See Fig 2-10.1.
Vertical Installation
The UPS is rack mountable as well as standing alone. You can mount the
UPS on the shelf, or you can erect the UPS with the supporting stands as
Fig 2-10.2.
Vertical Bracket
2-16
3. ASSEMBLING
3.1 MECHANICAL DRAWING FOR 1KVA
3-1
3.3 MECHANICAL DRAWING FOR 3KVA
3-2
3.4 WIRING DIAGRAM FOR 1KVA
13 13 13 12 9 7 3
6
L
CN1
2 1 CN2
N
G1
2
1
4
CORE
13 14 11 10 8
21
5
13
22
O/PL WI2
CNM2 WI1 O/PN
O/P L2
WI5 WI3
O/P L1
WI4 WP1
WP2
WP3
IP/L
IP/N
15
G
FAN1
16
( EXT BATT+ )
CNS1
( BATT- )
CNS3
CNS2( BATT+ )
17
18
18
CNE1
20 19 19
3-3
3.5 WIRING DIAGRAM FOR 2KVA
9 11 12 8 10 7
14
N N
- -
13 ++
G
13 L L
1
13
13
2
13 5
6 3
CORE
4
CNM2
O/P N WP1
22
CNI8 WP2
CNN2 CNN1 CNN3
O/P N
CNI9
23
CNI2
CNI13
CNI11
CORE O/P L1
CNI12
O/P L2
15
FAN2
16 CNI7
17
CNI6
20
20
18
18
21
CNE1
19
19
3-4
3.6 WIRING DIAGRAM FOR 3KVA
14 10 11 12 9 8 7
N N
- -
CORE + +
G
L L
1
6 2
13 3
5
13
WI2
CNI4
WI3
CNI1
WP1
CNP2
CNP3
4
#12 CNI2 #12
CNI3 #12
WP2
CNM2 #12
13
WI5
#12
13 WI4
WP3
#12
13 25
CNN1 CNN3 CORE CNP4
CNN2
16
17
15 FAN3
CNI7
21
CNI6
21
22
22
EXT. BATT+
CNF2
23
BATT-
CNF3
TO WS5 BATT-
WS4
(#10)
WS5
(#10) TO F Board CNF4
TO WS4 BATT+
FAN1 FAN2
24
CNF4
CNF1
24
#10
CNE1
20 20 19 18
3-5
4. COMMUNICATION INTERFACE
The UPS provides RS-232 and Dry contact protocols in one D-sub 9
connector. Using proper UPS management software and cable, the UPS can
be managed in LAN/ Intranet/ Internet environment. The pin assignment of
the D-sub 9 connector is defined as follows:
ASSIGNMENT DESCRIPTION
PIN
RS-232 Dry Contact
1 Low battery (Open collector)
2 UPS TxD (typical RS-232 level)
3 UPS RxD (typical RS-232 level) Remote Shutdown (5~12V)
4 Reserved for PNP
5 GND GND
6 Reserved for PNP Reserved
7 Reserved for PNP Reserved
8 Utility Fail (Open collector)
9
Open Collector
6 7 8 9
1 2 3 4 5
GND
4-1
4-1 RS-232/USB
6. Providing the power switch function for computer to turn on/off the
utility power on schedule for power saving
HARDWARE:
BAUD RATE---------------- 2400 bps
DATA LENGTH------------- 8 bits
STOP BIT-------------------- 1 bit
PARITY----------------------- NONE
CABLING:
Standard D-sub 9 cable (UPS side: male, PC side: female)
4-2
4-2 Dry Contact
Pin6, 7 Reserved.
The pin is normally open. When utility fails, pin8 and pin5 are
Pin8
connected via photo coupler.
Cabling:
The users must use the special cable. The connection is described as
follows:
PC (female) UPS (male)
Pin1------------------Pin1 (battery Low)
Pin3------------------Pin5 (GND)
Pin4------------------Pin3 (Shutdown)
Pin7------------------Pin6
Pin7------------------Pin7
Pin8------------------Pin8 (AC Fail)
The communication port on the rear panel of the UPS may be connected to
a computer. This port allows the computer to monitor the UPS and control
the operation of the UPS in some cases.
Some computers may have a special connector to link this communication
port, or require a special plug-in card, or need special UPS monitoring
software. Contact your dealer for details of different interface kits.
Caution:
Every time when you connect your UPS and computer, please make sure the
utility exists.
4-3
4-3 SNMP CARD
2. On the rear panel of UPS built-in a SNMP slot (Please refer to Figure
2-2), this optional interface unit can integrate UPS into the network and
then you can easily monitor the UPS status. Once you install SNMP
card in the UPS, you can’t get any information from UPS via RS232. i.e.
3. The SNMP card also supports SHTTP protocol, you can use browser
Microsoft IE or Netscape Communicator to monitor or configure UPS.
Besides, SNMP card supports Telnet and FTP for remote monitoring and
firmware upgrading.
Specification:
Auto detecting 10/100M Network speed.
Supporting protocol: TCP/IP, UDP, HTTP, ICMP, ARP, TELNET,
BOOTP, DHCP, FTP and SNMPv1.
Remote firmware upgradeable and configurable.
Web server built-in, allow monitoring/controlling UPS via browser.
VT100 terminal mode or Telnet to configure SNMP.
Function:
Schedule: Shutdown/Restart UPS, testing and control outlets.
Testing: Scheduled testing battery can insure the UPS can work
normally during power failure.
Event log: Auto-record the power event.
Historical records: Keep records of UPS status in specified interval.
Event handling: configure special action for each power event to meet
your requirement.
On/ Off UPS: setup the power on/off timer.
Outlet control: configure UPS outlets.
4-4
5. MAINTENANCE AND TROUBLESHOOTING
5.1 MAINTENANCE
z Normally, the life of battery is 3 years. But extreme operating
condition and environment may shorten its life-span.
z To replace batteries, contact qualified personnel.
z When UPS has been unused for a period of time, the batteries will
discharge slightly. It is recommended to charge the UPS once every 3
months.
z Use a vacuum cleaner to get rid of any dust that may rest on the
opening of the fan.
z Unplug the UPS when it is not used for a long time.
z When cleaning the plastic case or front panel, only use a soft, dry cloth.
If the case or front panel is very dirty, use a neutral, non-abrasive
detergent. Do not use alcohol or ammonia based solutions.
z When moving your UPS, always handle it with care.
z Avoid spilling liquid on the UPS.
z The equipment should be repaired and installed by individuals with
previous training.
When installing this equipment, it should be noted that the leakage current
of the UPS and its loads must not exceed 3.5mA in total for safety.
5-1
4. Load power detection of the inverter and bypass path; overload
protection.
5. Over temperature detection.
6. Connecting the LED to display the UPS status.
7. Offering the driving signal to the inverter driver circuit.
8. Offering RS-232 communication signals.
9. Offering soft start function.
10. Enable and disable the beeping of the buzzer.
11. Control of the bypass relay.
12. Shutdown UPS.
13. Detection of the utility power failure.
14. Output frequency (50Hz/60Hz) selection of Auto detection for the
output frequency according to the frequency of AC input voltage.
PCB LIST
CONTROL
5505001495 5505001495 5505001495
BOARD
POWER STAGE
5505001514 5505001511 5505001530
BOARD
5-2
5.3 TROUBLESHOOTING
WARNING MESSAGE
Indicate the UPS is under abnormal condition follow the instruction below to
solve the problem:
100%
OFF
25%
LINE
Input Abnormal
50 %
UPS detects a battery fault, the buzzer beep 0.1 BYPASS
OFF
25 %
Battery Replace
FAULT 75% ON
50%
BYPASS
level condition, the UPS alarm will beep half second 25%
OFF
LINE
capacity. .
Battery Low
5-3
5.3-4 Overload Turn into Bypass: OVERLOAD
FAULT 75 % ON
limited period, the overload LED will light on and TEST
50 %
OFF
25 %
mode” 100%
OFF
is happened, the overload LED will flash and the UPS LINE
25%
alarm will sound continuously. When remove short ONLINE LOAD BATT ON BATT.
.
circuit, the UPS output will recover. If short UNINTERRUPTIBLE POWER SUPPLIES
BATT. LOW REPLACE
BATT.
When the UPS inner components overheat, the UPS will protect itself by
thermo-switches. This status is so-called “O.T.P”
When under (or over) voltage is happened in the UPS output. This kind of fault
will be detected by the microprocessor in the UPS and is so-called “U.V.P”
(“O.V.P”).
When under (or over) bus voltage is happened in the UPS and is so-called “Bus
U.V.P” (“Bus O.V.P”).
5-4
5.3-6 Charge Voltage too High:
1. Check the charge voltage is over limit OVERLOAD
100%
LINE
ON
1. Restart the UPS FAULT 75 %
TEST
50 %
2. If problem remains replace the power BYPASS
OFF
25 %
Output OVP
ON
1. Restart the UPS FAULT 75 %
TEST
50 %
2. If problem remains replace the power BYPASS
OFF
25 %
Output UVP
OFF
25 %
LINE
BUS OVP
5-5
5.3-10 BUS UVP: BUS Under Voltage OVERLOAD
Protection 100%
ON
1. Restart the UPS FAULT 75 %
TEST
50 %
2. If problem remains replace the power BYPASS
OFF
25 %
BUS UVP
FAULT ON
continuous beeping to warn user. 75 %
TEST
50 %
OFF
25 %
LINE
OTP
100%
50 %
BYPASS
OFF
25 %
LINE
100%
Refer to 5.3-1 and 5.3-8
FAULT 75 % ON
TEST
50 %
BYPASS
OFF
25 %
LINE
5-6
5.3-14 Bus OVP & Input Voltage Abnormal
OVERLOAD
FAULT 75 % ON
TEST
50 %
BYPASS
OFF
25 %
LINE
FAULT 75 % ON
TEST
50 %
BYPASS
OFF
25 %
LINE
FAULT 75 % ON
TEST
50 %
BYPASS
OFF
25 %
LINE
5-7