Sie sind auf Seite 1von 4

TRANSFORMER 1

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 11 8,525 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 4 10,300 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 0 0
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 0 0
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 15 18,825 VA
TRANSFORMER 2

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 6 4,650 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 6 15,450 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 0 0
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 3 11,079 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 15 31,179 VA
TRANSFORMER 3

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 6 4,650 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 5 12,875 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 0 0
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 4 14,772 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 15 32,297 VA
TRANSFORMER 4

House House Type Total Connected Load per Household Demand Factor Maximum Number of Total
Area General Lighting Small Air General Lighting, Air Load Typical Maximum
and Appliance Conditioner Convenience Conditioner Demand Household Load
Convenience Loads Unit Receptacle, and Small Unit per Load Demand
Receptacle Appliance Loads Household
25 square Small 600 VA 175 VA 0 100% at 775 VA Not applicable 775 VA 2 1,550 VA
meters
50 square Medium 1,200 VA 1,375 VA 0 100% at 2,575 VA Not applicable 2,575 VA 8 20,600 VA
meters
Medium with 1 – 1,200 VA 1,375 VA 1,840 VA 100% at 2,575 VA 100% at 1,840 4415 VA 0 0
1 Hp ACU VA
Medium with 2 – 1,200 VA 1,375 VA 3,680 VA 100% at 2,575 VA 100% at 3,680 6,255 VA 0 0
1 Hp ACU VA
145 Large 3,480 VA 1,500 VA 0 100% at first 3000 VA Not applicable 3,693 VA 2 7,386 VA
square 35% at 1980 VA
meters Large with 1 – 3,480 VA 1,500 VA 2,300 VA 100% at first 3000 VA 100% at 2,300 5,993 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA
Large with 2 – 3,480 VA 1,500 VA 4,600 VA 100% at first 3000 VA 100% at 4,600 8,293 VA 0 0
1.5 Hp ACU 35% at 1980 VA VA

250 Very Large 6,000 VA 1,500 VA 0 100% at first 3,000 Not applicable 4,050 VA 0 0
square VA
meters 35% at 3000 VA
Very Large with 6,000 VA 1,500 VA 9660 VA 100% at first 3,000 100% at 9660 13,710 VA 0 0
3 – 2 Hp ACU VA VA
35% at 3000 VA
TOTAL 12 29,536 VA