Difference between 0.2S-Class & 0.

2-Class CT (For Measuring)


0.2S-Class is more accurate at low currents/load than 0.2-Class CT
Both (0.2S-Class & 0.2-Class) have maximum errors of  0.2% at 100% and 120% of rated current.
0.2S-Class CT (These values are found in IEC Standard 60044, Tables 11 and 12.)
1) 0.2S-Class has  0.75% at 1% load/current.
2) 0.2S-Class has  0.35% at 5% load/current.
3) 0.2S-Class has  0.2% at 20% or more load/current.
0.2-Class CT (These values are found in IEC Standard 60044, Tables 11 and 12.)
1) 0.2-Class has  0.75% at 5% load/current.
2) 0.2-Class has  0.35% at 20% or more load/current.
Standards have introduced 0.2S, for tariff metering purposes.
These special CTS (0.2S-Class) guarantee the declared accuracy even at much lower load currents and
are suitable for industries for tariff metering purposes, but some definite error can be defined even
with a load as low as 1%.
LIMITS OF CURRENT (RATIO) ERROR AND PHASE DISPLACEMENT
Percentage Current (Ratio) Error Phase Displacement at Percentage of Rated
Accuracy at Percentage of Rated Current Current (Minutes : Second)
Class 1% 5% 20% 100% 120% 1% 5% 20% 100% 120%
0.1 - 0.4 0.2 0.1 0.1 - 15 : 0.45 8 : 0.24 5 : 0.15 5 : 0.15
0.2 - 0.75 0.35 0.2 0.2 - 30 : 0.90 15 : 0.45 10 : 0.3 10 : 0.3
0.2S 0.75 0.35 0.2 0.2 0.2 30 : 0.9 15 : 0.45 10 : 0.3 10 : 0.3 10 : 0.3
0.5 - 1.5 0.75 0.5 0.5 - 90 : 2.7 45 : 1.35 30 : 0.9 30 : 0.9
0.5S 1.5 0.75 0.5 0.5 0.5 90 : 2.7 45 : 1.35 30 : 0.9 30 : 0.9 30 : 0.9
1.0 - 3.0 1.5 1.0 1.0 - 180 : 5.4 90 : 2.7 60 : 1.8 60 : 1.8

Accuracy Percentage Current (Ratio) Error Phase Displacement at Percentage of Rated


Class at Percentage of Rated Current Current (Minutes : Second)
- - 50% 100% 120% - - 50% 100% 120%
3.0 - - 3.0 3.0 3.0 - - - - -
5.0 - - 5.0 5.0 5.0 - - - - -

Different Accuracy Class PTS (For Measuring)


For Measuring Voltage Transformer, the accuracy class is designed by the highest permissible
percentage voltage error at rated voltage and with rated burden prescribed for the accuracy class
concerned.
The standard accuracy class for Measuring Voltage Transformer shall be 0.1, 0.2, 0.5, 1.0 and 3.0
LIMITS OF VOLTAGE ERROR AND PHASE DISPLACEMENT
The voltage error and phase displacement at rated frequency shall not exceed the value given below
table at any voltage between 80% To 120% of rated voltage and of burden between 25% - 100% of
rated burden at a power factor of 0.8 lagging.

Accuracy % Voltage Ratio Phase Displacement


Class Error (Minutes)
0.1  
0.2  
0.5  
1.0  