Device Setup

Device Setup
Identity
Tag ECLIPSE
Long Tag LIT-121011
Descriptor
Date 01/01/2001
Message
Date/Time/Initials
Factory Identity
Manufacturer MAGNETROL
Product Name Model 706
Magnetrol S/N 75863102001
Hardware Version 2
Firmware Version Ver 1.0fA
Cfg chng count 148
Final asmbly num 0
Device ID 12815082
Universal Revision 7
Fld dev rev 1
Software rev 1
Num req preams 5
Basic Config
Level Units ft
Probe Model 7Y1 Sngl Flex Std
Probe Mount Flange
Probe Length 24,45 ft
Measurement Type Level Only
Level Offset 0,00 ft
Dielectric Range Above 10
I/O Config
PV is Level
4 mA Set Point (LRV) 0,00 ft
20 mA Set Point (URV) 24,00 ft
Failure Alarm 3.6 mA
Damping 0s
Variable Selection
SV is Distance
TV is Level
QV is Level
Local Display Config
Language English
Status Symbol Hide
Long Tag View
PV Bar Graph View
Measured Values
Upr Level View
Distance Hide
% Output View
Analog Output View
Upr Echo Strength Hide
Elec Temp Hide
Advanced Config
Sensitivity 18
Blocking Distance 0,45 ft
Failure Alarm Delay 0s
Level Trim 0,00 ft
HF Cable Length Integral
Buildup Detection Off
New User Password 0
Safety Zone Settings
Safety Zone Alarm None
Threshold Settings
Lvl Thresh Mode Auto Largest
Lvl Thresh Value 60
EoP Thresh Mode Fixed Value
EoP Thresh Value 18
End-of-Probe Settings
EoP Polarity Negative
EoP Analysis Off
Echo Rejection
Reject Curve State Enabled
Reject Curve Mode Level
Saved Media Location 20,31 ft
Compensation
Compensation Mode Off
Analog Output
Poll Address 0
Analog Output Mode Enabled (PV)
4mA Trim Value 1309
20mA Trim Value 7138
Fdbk 4mA Trim Value 630
Fdbk 20mA Trim Value 3184
Factory Config
Fiducial Gain 22
Fid Thresh Value 24
Elec Temp Offset -5 °F
Ifc Boundary Offset 0,00
NAPValue 3875536896
Factory Param 2 0,00
Factory Param 3 0,00
Factory Param 4 0,00
Factory Calib
Window 232
Fiducial Ticks 1364
Conversion Factor 1705
Scale Offset -139
Diagnostics
Present Status
NE 107 Simulation Mode Off
Add'l Device Status
Status 0
Software Error []
RAM Error []
ADC Failure []
EEPROM Error []
Analog Board Error []
Analog Output Error [ ]
Spare Indicator 1 []
Default Parameters []
Status 1
No Probe []
No Fiducial []
No Echoes []
Echo Lost []
Spare Indicator 2 []
EoP Above PrbeEnd [ ]
Lvl Below PrbeEnd []
EoP Below PrbeEnd []
Status 2
Safety Zone Alarm []
Config Conflict []
High Volume Alarm []
High Flow Alarm []
Spare Indicator 3 []
Initializing []
Analog Output Fixed []
Config Changed []
Status 3
Spare Indicator 4 []
Spare Indicator 5 []
Spare Indicator 6 []
Ramp Interval Error []
High Elec Temp []
Low Elec Temp []
Calibration Req'd []
Echo Reject Invalid []
Status 4
Spare Indicator 7 []
Inferred Level []
Adjust Analog Outpt []
Totalizer Data Lost []
No Probe Target []
Low Supply Voltage []
Dry Probe []
Spare Indicator 8 []
Status 5
Low Echo Strength []
Low Ifc Echo Str []
Spare Indicator 9 []
Spare Indicator 10 []
Sequence Record []
NAMUR NE 107 Setup
NE 107 Mapping
ROW 0
Indicator Software Error
Mapping Failure
Indicator Safety Zone Alarm
Mapping Failure
Indicator Spare Indicator 7
Mapping No Effect
ROW 1
Indicator RAM Error
Mapping Failure
Indicator Config Conflict
Mapping Failure
Indicator Inferred Level
Mapping Out of Spec
ROW 2
Indicator ADC Failure
Mapping Failure
Indicator High Volume Alarm
Mapping Failure
Indicator Adjust Analog Outpt
Mapping Out of Spec
ROW 3
Indicator EEPROM Error
Mapping Failure
Indicator High Flow Alarm
Mapping Failure
Indicator Totalizer Data Lost
Mapping Out of Spec
ROW 4
Indicator Analog Board Error
Mapping Failure
Indicator Spare Indicator 3
Mapping No Effect
Indicator No Probe Target
Mapping Out of Spec
ROW 5
Indicator Analog Output Error
Mapping Failure
Indicator Initializing
Mapping Function Check
Indicator Low Supply Voltage
Mapping Out of Spec
ROW 6
Indicator Spare Indicator 1
Mapping No Effect
Indicator Analog Output Fixed
Mapping Function Check
Indicator Dry Probe
Mapping No Effect
ROW 7
Indicator Default Parameters
Mapping Failure
Indicator Config Changed
Mapping Function Check
Indicator Spare Indicator 8
Mapping No Effect
ROW 8
Indicator No Probe
Mapping Failure
Indicator Spare Indicator 4
Mapping No Effect
Indicator Low Echo Strength
Mapping Maintenance req'd
ROW 9
Indicator No Fiducial
Mapping Failure
Indicator Spare Indicator 5
Mapping No Effect
Indicator Low Ifc Echo Str
Mapping Maintenance req'd
ROW 10
Indicator No Echoes
Mapping Failure
Indicator Spare Indicator 6
Mapping No Effect
Indicator Spare Indicator 9
Mapping No Effect
ROW 11
Indicator Echo Lost
Mapping Failure
Indicator Ramp Interval Error
Mapping Out of Spec
Indicator Spare Indicator 10
Mapping No Effect
ROW 12
Indicator Spare Indicator 2
Mapping No Effect
Indicator High Elec Temp
Mapping Out of Spec
Indicator Sequence Record
Mapping No Effect
ROW 13
Indicator EoP Above PrbeEnd
Mapping Failure
Indicator Low Elec Temp
Mapping Out of Spec
ROW 14
Indicator Lvl Below PrbeEnd
Mapping Failure
Indicator Calibration Req'd
Mapping Out of Spec
ROW 15
Indicator EoP Below PrbeEnd
Mapping Failure
Indicator Echo Reject Invalid
Mapping Out of Spec
Event History
Event Log
ROW 0

Event
Date
Time
Duration

ROW 1
0
Event
Date 01/01/2000
Time 00:00:00
Duration 0s
s
ROW 2
0
Event
Date 01/01/2000
Time 00:00:00
Duration 0s
s
ROW 3
0
Event
Date 01/01/2000
Time 00:00:00
Duration 0s
s
ROW 4
0
Event
Date 01/01/2000
Time 00:00:00
Duration 0s
s
ROW 5
0
Event
Date 01/01/2000
Time 00:00:00
Duration 0s
s
ROW 6
0
Event
Date 01/01/2000
Time 00:00:00
Duration 0s
s
ROW 7
0
Event
Date 01/01/2000
Time 00:00:00
Duration 0s
s
ROW 8
0
Event
Date 01/01/2000
Time 00:00:00
Duration 0s
s
ROW 9
0
Event
Date 01/01/2000
Time 00:00:00
Duration 0s
s
ROW 10
0
Event
Date 01/01/2000
Time 00:00:00
Duration 0s
s
Advanced Diagnostics
Internal Values
Fiducial Ticks 1364
Fiducial Strength 32
Level Ticks 1715
Echo Strength 86
Distance 4,22 ft
EoP Ticks 3052
EoP Strength 38
EoP Distance 7,88 ft
Fdbk Current 17,506 mA
Elec Temperatures
Present Temperature 101 °F
Max Temperature 124 °F
Min Temperature 68 °F