SYSTEM
1 of 68
CONTENTS:
DESCRIPTION
* Scope
* Applicable Codes, Standard and Reference Document
* Design Parameter
* Co-efficient Transmission (U-value) for Roof, wall, partition and floor
* Internal load details
* HVAC Data Gathering sheet
* Ventilation, Exhaust and Pressurization
* Computer Generated Heating and Cooling load calculation
* Equipment selection
* Equipment Data Schedule
* Sequence of Operation
* Computerized Duct sizing calculation
* Heater Sizing
* Battery room and Toilet exhaust fan sizing
* Sizing of sand trap louver & fresh air filter
* Air Balancing and Air Diffusion system
2 of 68
1 SCOPE:
Scope of work includes the provision of HVAC system for the following building
(Zones):
1 BATTARY ROOM
2 STORE ROOM
3 FIRE FIGHTING ROOM
4 AC/DC ROOM
5 TELECOM
6 PASSAGE
7 CONTROL ROOM
8 OFFICE
9 TOILET
10 KITCHEN
11 33KV SWGR ROOM
12 BASEMENT
2 APPLICABLE CODES,
CODES STANISCOSAD AND REFERENCE DOCUMENT:
3 of 68
3 DESIGN PARAMETER:
4 of 68
4 CO-EFFICIENT OF TRANSMISSION (U-VALUE) FOR ROOF, WALL, DOOR
PARTITION AND FLOOR:
The resistance values are taken from ASHRAE Fundamentals 1997 table # 1, 4 ,
unless other wise mentioned.
5 of 68
5 INTERNAL LOAD DATA:
Internal loads involve components of cooling loads which arises from sources internal to the
conditioned space. The following components shall be dealt with in the proceeding items :
5.1 LIGHTING :
The details of the lighting loads in each room is taken from actual lighting load calculation.
The Summary of lighting load is enclosed for reference.
Formula
Qs = 3.41 x qw x Fu x Fs x CLF
Where :
Qs = Sensible cooling load in BTU/Hr.
CLF = 1, Since lights will be turned on more than 16 Hrs. per day.
6 of 68
5.3 EQUIPMENT HEAT GAIN :
The heat gain are due to the heat dissipated by equipment's inside the building.
The actual load dissipation from the each panel is taken from the each equipment
manufacturer & as summarized by the Electrical Engineer.
7 of 68
Wall Partition Light. Equip. Nos. of
People
SE SW NW NE Wall Watts Watts
Avg. Height of wall : 5.9 m Avg. Height of wall : 8.95 m
Width of the wall :27.5 m Width of the wall 12.5 m
Area =5.9 M x27.5 M Area =8.95 M x12.5 M
2
162.25 M 111.88 M2
2
1746.62 Ft 1204.33 Ft2
835 1170 -
8 of 68
Wall Partition Light. Equip. Nos. of
People
SE SW NW NE Wall Watts Watts
Avg. Height of wall : 4.27m - -
Width of the wall : 8.3m
Area = 8.3 M x4.27 M
2
35.44 M
2
381.52 Ft
1382 4800 1
4 x1.5
area=6 M2
86 500 1
Avg. Height of wall : 5.2m Avg. Height of wall : 5.2m Avg. Height of wall : 5.2m 5.4 x .8
Width of the wall 4.64 m Width of the wall :3.5 m Width of the wall 4.64 m
Area =5.2M X4.64m Area =5.2M X3.5m Area =5.2M X4.64m area=4.3 M2
2 2 2
24.13 M 18.20 M 24.13 M
2 2 2
259.74 Ft 195.92 Ft 259.74 Ft
1814 26400 1
- 47 x 2.23
area=104.8 M2
1037 15000 -
9 of 68
132/33KV SUBSTATION
HVAC Load Analysis
for
Prepared By:
10 of 68
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
132/33KV SUBSTATION
11 of 68
C:\disc top 6.032_33kv Substation_rev_lighting.CHV Wednesday, February 11, 2009, 10:54 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Page 3
Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 12 0.090 No Yes
2 12 0.102 No No
Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 G 0.250 M
2 A 0.105 M
3 A 0.300 M
Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.250 8 10
2 0.133 8 12
3 0.300 3 10
12 of 68
C:\disc top 6. 132_33kv Substation_rev_lighting.CHV Wednesday, February 11, 2009, 10:54 PM
Chvac - Full Commercial HVAC Loads Calculati
AH 132/33KV SUBSTATION
Page 4
Zone Input
Zone 1: Battery Room (377.6592 sq.ft) (Group 0)
Air Handler number: 1 Zone occurrences: 1
Zone length: (feet) 19.68 Zone width (feet): 19.19
Lighting Watts: 835 Equipment Watts: 1,170
Number of people in zone: 0 People profile number: 1
Lighting profile number: 2 Equipment profile number: 3
Ceiling height (feet): 16.70 Heating safety factor (%): 10
Sensible safety factor (%): 10 Latent safety factor (%): 10
Sensible heat per person (Btuh): 315 Latent heat per person (Btuh): 325
Cooling ventilation method: Direct Cooling ventilation value: 1,350.000
Cooling infiltration method: Direct Cooling infiltration value: 0.000
Heating ventilation method: Direct Heating ventilation value: 1,350.000
Heating infiltration method: Direct Heating infiltration value: 0.000
Winter exhaust air CFM: 1,350 Summer exhaust air CFM: 1,350
Minimum supply CFM: 1,350 Latent Btuh equipment load: 0
Ceil. exposed to plenum (sq.ft): 0 Exposed floor slab perimeter (ft): 78
Both heating and cooling loads are calculated for this zone.
17 of 68
C:\disc top 6 132_33kv Substation_rev_lighting.CHV Wednesday, February 11, 2009, 10:54 PM
H 132/33KV SUBSTATION
Page 9
Check Figures
Total Building Supply Air (based on a 20° TD): 19,613 CFM
Total Building Vent. Air (20.01% of Supply): 3,925 CFM
Total Conditioned Air Space: 6,109 Sq.ft
Supply Air Per Unit Area: 3.2107 CFM/Sq.ft
Area Per Cooling Capacity: 162.8971 Sq.ft/Ton
Cooling Capacity Per Area: 0.0061 Tons/Sq.ft
Heating Capacity Per Area: 28.15 Btuh/Sq.ft
Total Heating Required With Outside Air: 171,992 Btuh
Total Cooling Required With Outside Air: 37.50 Tons
18 of 68
C:\disc top 6.2_33kv Substation_rev_lighting.CHV Wednesday, February 11, 2009, 10:54 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
UTH 132/33KV SUBSTATION
Page 10
Control And
1,434 7,889 21,904 1,073 Direct Direct
7 Protection Room
3 702 1,579 0 93 93
12am August
18,817 0.49 1.10 0 702 316
Check Figures
Total Air Handler Supply Air (based on a 20° TD): 19,613 CFM
Total Air Handler Vent. Air (20.01% of Supply): 3,925 CFM
Total Conditioned Air Space: 6,109 Sq.ft
Supply Air Per Unit Area: 3.2107 CFM/Sq.ft
Area Per Cooling Capacity: 162.8971 Sq.ft/Ton
Cooling Capacity Per Area: 0.0061 Tons/Sq.ft
Heating Capacity Per Area: 28.15 Btuh/Sq.ft
Total Heating Required With Outside Air: 171,992 Btuh
Total Cooling Required With Outside Air: 37.50 Tons
Note: Due to the system's negative latent gain, tonnage is based solely on sensible gain.
20 of 68
C:\disc top 132_33kv Substation_rev_lighting.CHV Wednesday, February 11, 2009, 10:54 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
AN
Page 12
Zone 2-Store Room peaks (sensible) in August at 8pm, Air Handler 1 (PACU-1&2), Group 0, 19.7 x 19.2,
Construction Type: 22 (Medium)
Roof-1-12-No.Clg-L 378 0.50 27.5 0.102 1,059 3.672 1,387
Wall-1-NE-A-M 320 0.83 20.6 0.105 695 3.780 1,211
Wall-2-SE-A-M 329 0.83 23.3 0.105 806 3.780 1,242
Lights-Prof=2 1,037 0.010 3,538
People-Prof=1 1.0 1.000 315 325
Floor slab 78 9.000 700
Sub-total 6,413 325 4,540
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 7,054 358 4,994
Zone 3-Fire Fighting peaks (sensible) in August at 8pm, Air Handler 1 (PACU-1&2), Group 0, 19.7 x 19.2,
Construction Type: 22 (Medium)
Roof-1-12-No.Clg-L 378 0.50 27.5 0.102 1,059 3.672 1,387
Wall-1-SE-A-M 320 0.83 23.3 0.105 786 3.780 1,211
Lights-Prof=2 1,037 0.010 3,538
Equipment-Prof=3 500 1.000 1,706 0
People-Prof=1 1.0 1.000 315 325
Floor slab 8 9.000 70
Sub-total 7,404 325 2,668
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 8,145 358 2,935
Zone 4-Ac/dc Room peaks (sensible) in August at 12am, Air Handler 1 (PACU-1&2), Group 0, 25.6 x 13.8,
Construction Type: 22 (Medium)
Plenum 352 s:3, w:3 0.750 792 2.250 792
Wall-1-SW-A-M 336 0.83 24.2 0.105 852 3.780 1,269
Lights-Prof=2 1,382 0.010 54
Equipment-Prof=3 4,800 1.000 16,378 0
People-Prof=1 1.0 1.000 315 325
Floor slab 81 9.000 731
21 of 68
C:\disc top 6.0 132_33kv Substation_rev_lighting.CHV Wednesday, February 11, 2009, 10:54 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Page 13
Zone 5-Telecom peaks (sensible) in August at 12am, Air Handler 1 (PACU-1&2), Group 0, 25.6 x 15.7,
Construction Type: 22 (Medium)
Plenum 402 s:3, w:3 0.750 905 2.250 905
Lights-Prof=2 1,382 0.010 47
Equipment-Prof=3 1,000 1.000 3,412 0
People-Prof=1 2.0 1.000 630 650
Floor slab 80 9.000 721
Sub-total 4,994 650 1,625
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 5,493 715 1,788
Zone 6-Passage peaks (sensible) in August at 12am, Air Handler 1 (PACU-1&2), Group 0, 280.7 x 1.0,
Construction Type: 22 (Medium)
Plenum 281 s:3, w:3 0.750 632 2.250 632
Wall-1-SW-A-M 109 0.83 24.2 0.105 276 3.780 412
Lights-Prof=2 518 0.010 18
Floor slab 100 9.000 898
Sub-total 926 0 1,942
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 1,019 0 2,136
Zone 7-Control And Protection Room peaks (sensible) in August at 12am, Air Handler 1 (PACU-1&2),
Group 0, 50.8 x 28.2, Construction Type: 22 (Medium)
Plenum 1,434 s:3, w:3 0.750 3,227 2.250 3,227
Wall-1-NE-A-M 667 0.83 21.5 0.105 1,504 3.780 2,521
Lights-Prof=2 5,184 0.010 179
Equipment-Prof=3 4,120 1.000 14,058 0
People-Prof=1 3.0 1.000 945 975
Floor slab 158 9.000 1,424
Sub-total 19,913 975 7,172
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 21,904 1,073 7,889
Zone 8-Office peaks (sensible) in August at 12am, Air Handler 1 (PACU-1&2), Group 0, 15.4 x 15.1,
Construction Type: 22 (Medium)
Plenum 233 s:3, w:3 0.750 524 2.250 524
Lights-Prof=2 1,037 0.010 35
Equipment-Prof=3 200 1.000 682 0
People-Prof=1 1.0 1.000 315 325
22 of 68
C:\disc132_33kv Substation_rev_lighting.CHV Wednesday, February 11, 2009, 10:54 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
132/33KV SUBSTATION
Page 14
Zone 9-Toilet peaks (sensible) in August at 9pm, Air Handler 1 (PACU-1&2), Group 0, 9.8 x 11.5,
Construction Type: 22 (Medium)
Roof-1-12-Susp.C-L 113 0.50 22.5 0.090 228 3.240 365
Partition-1-2 128.7072 8/12 0.133 137 1.596 205
Lights-Prof=2 96 0.010 328
Floor slab 42 9.000 381
Sub-total 693 0 951
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 762 0 1,046
Zone 10-Kitchen peaks (sensible) in August at 9pm, Air Handler 1 (PACU-1&2), Group 0, 6.6 x 4.9,
Construction Type: 22 (Medium)
Roof-1-12-Susp.C-L 32 0.50 22.5 0.090 65 3.240 105
Partition-1-2 66.6496 8/12 0.133 71 1.596 106
Lights-Prof=2 86 0.010 293
Equipment-Prof=3 500 1.000 1,706 0
People-Prof=1 1.0 1.000 315 325
Floor slab 23 9.000 209
Sub-total 2,451 325 420
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 2,696 358 462
Zone 11-33kv Swgr Room peaks (sensible) in August at 12am, Air Handler 1 (PACU-1&2), Group 0, 59.0
x 18.0, Construction Type: 22 (Medium)
Roof-1-12-Susp.C-L 1,062 0.50 21.0 0.090 2,007 3.240 3,441
Wall-1-NE-A-M 319 0.83 21.5 0.105 720 3.780 1,207
Wall-2-SW-A-M 319 0.83 24.2 0.105 811 3.780 1,207
Wall-3-NW-A-M 1,044 0.83 22.3 0.105 2,446 3.780 3,948
Partition-4-2 46.374 8/12 0.133 49 1.596 74
Lights-Prof=2 1,814 0.010 6,190
Equipment-Prof=3 26,400 1.000 90,081 0
People-Prof=1 2.0 1.000 630 650
Sub-total 102,934 650 9,877
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 113,227 715 10,865
Zone 12-Basement peaks (sensible) in August at 12am, Air Handler 1 (PACU-1&2), Group 0, 59.0 x 18.0,
Construction Type: 22 (Medium)
23 of 68
C:\disc 32_33kv Substation_rev_lighting.CHV Wednesday, February 11, 2009, 10:54 PM
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
132/33KV SUBSTATION
Page 15
24 of 68
C:\disc top 6h 132_33kv Substation_rev_lighting.CHV Wednesday, February 11, 2009, 10:54 PM
32/33KV SUBSTATION
Page 16
25 of 68
C:\disc to132_33kv Substation_rev_lighting.CHV Wednesday, February 11, 2009, 10:54 PM
7 VENTILATION, EXHAUST AND PRESSURIZATION :
Where :
Qs = Sensible heat gain, BTU/Hr.
QL = Latent heat gain, BTU/Hr.
o
To = Design outside ambient temperature - 110 F
o
TR = Room design temperature. 77 F
Wo = Outside Air Humidity ratio # W.V / # water
Wi = Room air humidity ratio # W.V / # Water.
CFM = Ventilation rate requirement.
Please refer to the Computer Generated Calculation Sheets enclosed with this document for the details.
7.1.2
7 1 2 Exhaust
a) Battery room
From SES-K-100 clause No. 10.11 the recommended air changes for the Battery room is 12. Hence No. of
air changes considered in the calculation is 12 AC/Hr. The detailed calculation of the Battery room exhaust
system is enclosed.
b) Toilet room
From SES-K-100 clause No. 10.11 the recommended air changes for the Toilet room is 10. Hence No. of
air changes considered in the calculation is 10 AC/Hr. The detailed calculation of the toilet room exhaust
system is enclosed.
26 of 68
7.2 PRESSURIZATION
3
p = Air density in lb/ft
= 0.0686 at102Deg.F
27 of 68
Qexh= Exhaust air in Battery room +Exhaust air Toilet room+Kitchen+fire fighting
= 1350+ 244+ 194+ 1125= 2913 CFM
(Ref. To detailed calculation of Battery room and
toilet room exhaust fan sizing) = 2913 CFM
Make-up air required to pressurize the conditioned space.= Qp ={Qexh + (Po/P1) Qexh + (Po/P1) Qx + Qx}
Where: Qp = Air required to pressurize the space to required
static pressure in CFM
Qexh = Exhaust air by Powered Exhaust fan - in cfm
Qx = Ex-filtration of the air from the space in cfm.
Po = Outside static pressure acting on wall in In. of w.g.
Pi = Inside static pressure of the conditioned space In.w.g.
7.2.4 Assumptions:
In this design, for the purpose of analysis, following assumptions are made:
Design Static pressure inside the conditioned space to be positive relative to atmosphere.
As per SES-K-100 & SES-P-119.43, the required pressure inside the conditioned space
shall be maintained at 0.2 inches of w.g.
Surface pressure relative to the static pressure is equivalent to the static pressure acting
on the building wall. I.e. P0=Pv = 0.0995 in of W.G
Qexh = 2913 cfm (Exhaust in Battery room&Toilet room)
Qx = 31 cfm
Qp =
Qp = {Qexh + (Po/P1) Qexh + (Po/P1) Qx + Qx}
Qp = {2913+(0.0995/0.2995)x2913+{(0.0995/0.2995) x 31+ 31}
Qp = 3910 CFM
Note: As per SES-K-100, Sec.-10, minimum of 10% of supply air required for fresh
air make up. From air balancing table enclosed, required make up is greater
than the Qp indicated above.
Fresh
F h Air
Ai is
i considering
id i as follows
f ll :
Summary is as below:
Total Supply Total Outside Exhaust Air %.O.A. % Press.
Area
Air - CFM Air CFM CFM - -
SWGR and Cont. Build. 19,613 3,925 2,913 20.0% 5.9%
28 of 68
7.3 AIR BALANCING:
Say = 1350 Pa
29 of 68
Exfiltration (Qx)
PW = Wind surface pressure relative to static pressure, in undisturbed flow, in, water.
QX = Ex-filtration in CFM
QX/L = Stack co-efficient, (CFM)2 (Sq. in )-2 (F)-1 = (( Ax ΔT) + (BxV2)1/2
0 = Stack co-efficient
= 0.0156 (Ref. ASHRAE fundamentals 1997 chapter 25, Table 6
ΔT = Indoor temp. - Outdoor temp. = 77-109 = -32OF
1 = Wind co-efficient, (CFM)2 (Sq. in)-2 (mph)-2
= 0.0119 (shielding class-1) ASHRAE fundamentals 1977,
= chapter 25 table 7
V = Wind speed = 15 mph
L = Leakage area In2
QX/L = ((0.0156 x -43) + (0.0119 x 152))1/2 CFM/In2
= (2.01)1/2 = 1.42 CFM/In2
Use 0.12 in2/ft2 for (Double door & single door weather stripped Ref. ASHRAE fundamentals.
Room Name Door Designation Door Area M2 [Ft]2 Leakage Area (in)2 Leakage Air
cfm
BATTARY ROOM Ds 2.6 [28] - 0
STORE ROOM Dd 3.7 [39.8] 5.00 7
FIRE F. ROOM Ds 2.6 [28] - 0
AC/DC ROOM Ds 2.6 [28] - 0
TELECOM ROOM Ds 2.6 [28] - 0
PASSAGE Dd 3.7 [39.8] 5.00 7
CONTROL ROOM Dd 3.7 [39.8] - 0
OFFICE 2.6 [28] - 0
TOILET 2.6 [28] - 0
KITCHEN 2.6 [28] - 0
33KV SWGR ROOM Dd+2Ds 8.9 [95.7] 12 17
BASEMENT - 0
Note: Ds - Single Door Total CFM = 31
Dd - Double Door
30 of 68
HVAC SYSTEM SEQUENCE OF OPERATION :
CHANGEOVER SWITCH
PACU-1 will be the duty unit, whereas PACU-2 will be the standby unit. When
PACU-1 fails to operate, PACU-2 will be switched on automatically and vice-versa.
Corresponding motorized volume dampers will open for the unit in operation while
close in the "failed" or standby unit.
7- D S CHANGEOVER
A 7 days timer will alternate the running of duty unit and standby unit every 7 days.
If the running unit fails, the change over switch shall automatically run the standby
unit and vice-versa.
SMOKE DETECTION
Presence of smoke will be detected by duct mounted smoke detector to shutdown
the HVAC system and close the combination of motorized fire and smoke
damper(s) (MF/SD-1 & MF/SD-2). A time delay will be provided so that MF/SD-1 &
MF/SD-2 will be fully opened before the HVAC system is restarted with the unit
selector switch.
COOLING
The main controller will energize the lead compressor (Compr. No. 1) when the
room temperature is above the set point. The second compressor (Compr. No. 2)
will be energized as well when further cooling is required. BOTH Compressors will
run until the set point of the main controller is achieved.
HEATING
When the room temperature is below the set point of the main controller, this
controller will send signal to the 2-stage controller to energize the electric duct
heater in 1 or 2 stages as required until the desired room temperature is achieved.
DEHUMIDIFICATION
Space air humidity conditions are measured by a duct mounted temperature /
humidity detector and the measured humidity values are transmitted to the DDC
(MEC) controller via analog module. The controller compares the actual values with
required humidity values (50%) and if the humidity is higher, the controller overrides
the temperature control process and operates the compressors to de-humidify the
air to maintain the set point (adjustable 0-100%). As selected on the local user
interface on the HVAC control panel. During dehumidifying process the controller
retains the control of the heater to maintain the room dry bulb conditions.
31 of 68
NO AIRFLOW and FAN BELT FAILURE
AFS-1 and AFS-2 shall have two functions, one is to shut-off the corresponding
electric heater in the event of no airflow. The other is to give only an indication light
on the HVAC control panel when there is fan belt failure then automatically the
standby unit shall take over. The indicating light should not lit when one PACU is
shut down for standby.
DIRTY FILTER
Differential pressure switches DPS will measure the pressure drop across the filter
and if the pressure differential setting is reached, a lamp will glow sending signal to
the HVAC control panel to indicate that the filters are dirty and require replacement
/ cleaning.
HI/LO PRESSURE
The high discharge and low suction pressure of the compressor will be monitored
through indicating lamps on the HVAC control panel.
ANTI-RECYCLE PROTECTION
A minimum of 10 minutes time delay shall project the compressor from restarting in
case of power failure. This shall be accomplished in two equal stages. The first one
shall be taken care by a 5-minute time delay relay installed in the HVAC control
panel in the event of power failure. The second one shall be activated by a built-in
5-minute time delay normal condition, the compressor shall always start from a 5-
minute time delay at the beginning of another cooling cycle.
32 of 68
DUCT SIZING
CALCULATION
33 of 68
132/33KV SUBSTATION
HVAC Duct Sizing
for
34 of 68
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 2
35 of 68
C:\disc top 6.02DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 3
Fan Data
Fan description:
Fan static pressure (in.wg): 0.000
Fan CFM: 0
Fan efficiency: 0
Fan RPM: 0
Number of blades: 0
Fan blast width (in): 0
Fan blast height (in): 0
Length to first fitting (ft): 1.0
36 of 68
C:\disc top 6.02DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 4
Fan Data
Fan description:
Fan static pressure (in.wg): 0.000
Fan CFM: 0
Fan efficiency: 0
Fan RPM: 0
Number of blades: 0
Fan blast width (in): 0
Fan blast height (in): 0
Length to first fitting (ft): 1.0
37 of 68
C:\disc top 6.0UCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 5
40 of 68
C:\disc top 6.02\DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 8
41 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 9
43 of 68
C:\disc top 6.02\ALDUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 11
44 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 12
ST-120 27.3 EF 0.085 Rect Rect ---- 0.000 0.021 0.088 0.118
ST-480 24.0 0 -0.017 CR9-6 1 0.190 0.020 0.000 0.012 1.351 0.621
1,579 26.0 22 ---- 0.021 0.033 1.440 0.739
6,418 14.0 Galv Rect SR5-5-MN 0.014 0.001 0.021
ST-130 21.9 EF 0.110 Rect Rect ---- 0.000 0.015 0.088 0.118
ST-120 20.0 0 -0.015 ---- 0.000 0.013 1.379 0.593
1,579 20.0 22 ---- 0.015 0.027 1.467 0.712
4,131 11.5 Galv Rect SR5-5-MN 0.139 0.015 0.015
ST-140 21.9 EF 0.110 Rect Rect ---- 0.000 0.000 0.088 0.118
ST-130 20.0 0 0.000 ---- 0.000 0.006 1.385 0.587
1,579 20.0 22 ---- 0.000 0.006 1.474 0.706
4,131 5.5 Galv Rect *SR5-5-MN 0.000
ST-170 19.7 EF 0.090 Rect Rect ---- 0.000 0.035 0.123 0.083
ST-450 18.0 0 -0.023 CR9-5 1 0.460 0.034 0.000 0.007 1.411 0.562
1,327 18.0 24 ---- 0.035 0.042 1.534 0.645
2,808 7.5 Galv Rect SR5-5-MN 0.010 0.001 0.035
ST-180 12.0 EF 0.085 Rect Rect ---- 0.000 0.143 0.166 0.041
ST-170 10.0 0 -0.101 ---- 0.000 0.012 1.523 0.449
928 12.0 24 ---- 0.143 0.155 1.689 0.490
729 14.0 Galv Rect SR5-5-MN 3.948 0.143 0.143
ST-190 12.0 EF 0.085 Rect Rect ---- 0.000 0.143 0.166 0.041
ST-170 10.0 0 -0.101 ---- 0.000 0.005 1.516 0.456
928 12.0 24 ---- 0.143 0.148 1.682 0.497
729 6.0 Galv Rect SR5-5-MN 3.948 0.143 0.143
ST-230 41.5 EF 0.090 Rect Rect ---- 0.000 0.253 0.000 0.207
ST-490 26.0 0 -0.253 CR9-5 1 0.460 0.083 0.000 0.015 1.239 0.733
2,088 57.6 20 *CR3-1 1 0.936 0.170 0.253 0.268 1.239 0.940
19,612 17.0 Galv Rect *SR5-5-MN 0.253
ST-240 21.9 EF 0.110 Rect Rect ---- 0.000 0.630 0.091 0.115
ST-230 20.0 0 -0.538 ---- 0.000 0.005 1.783 0.189
1,560 20.0 22 ---- 0.630 0.635 1.875 0.305
4,080 5.0 Galv Rect SR5-5-MN 6.156 0.630 0.630
ST-250 19.7 EF 0.085 Rect Rect ---- 0.000 0.009 0.128 0.078
ST-240 18.0 0 0.029 ---- 0.000 0.008 1.762 0.210
1,285 18.0 24 ---- 0.009 0.016 1.891 0.288
2,720 9.0 Galv Rect SR5-5-MN 0.123 0.009 0.009
ST-260 15.3 EF 0.085 Rect Rect ---- 0.000 0.019 0.153 0.054
ST-250 14.0 0 0.006 ---- 0.000 0.008 1.765 0.208
1,065 14.0 24 ---- 0.019 0.027 1.918 0.261
45 of 68
C:\disc top 6.02DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 13
ST-270 31.7 EF 0.070 Rect Rect ---- 0.000 0.072 0.093 0.113
ST-230 26.0 0 0.021 ---- 0.000 0.004 1.222 0.751
1,547 32.4 20 ---- 0.072 0.076 1.315 0.864
8,478 5.5 Galv Rect SR5-5-MN 0.718 0.072 0.072
ST-280 29.4 EF 0.070 Rect Rect ---- 0.000 0.002 0.099 0.108
ST-270 26.0 0 0.003 ---- 0.000 0.006 1.225 0.748
1,510 28.0 22 ---- 0.002 0.008 1.323 0.856
7,118 8.0 Galv Rect SR5-5-MN 0.024 0.002 0.002
ST-290 26.2 EF 0.085 Rect Rect ---- 0.000 0.003 0.095 0.112
ST-280 24.0 0 -0.007 ---- 0.000 0.007 1.239 0.734
1,538 24.0 22 ---- 0.003 0.010 1.333 0.846
5,758 8.5 Galv Rect SR5-5-MN 0.029 0.003 0.003
ST-300 10.9 EF 0.110 Rect Rect ---- 0.000 0.445 0.161 0.046
ST-480 10.0 0 -0.369 ---- 0.000 0.008 1.699 0.274
981 10.0 26 ---- 0.445 0.453 1.860 0.319
636 7.0 Galv Rect *SR5-5-MN 11.201 0.445 0.445
ST-310 9.7 EF 0.095 Rect Rect ---- 0.000 0.005 0.172 0.035
ST-300 8.0 0 0.006 ---- 0.000 0.009 1.702 0.271
854 8.0 26 ---- 0.005 0.014 1.874 0.305
438 9.5 Galv Rect SR5-5-MN 0.108 0.005 0.005
ST-320 9.7 EF 0.020 Rect Rect ---- 0.000 0.006 0.200 0.007
ST-310 8.0 0 0.022 ---- 0.000 0.001 1.681 0.292
378 8.0 26 ---- 0.006 0.007 1.881 0.298
194 3.5 Galv Rect SR5-5-MN 0.668 0.006 0.006
ST-330 9.7 EF 0.010 Rect Rect ---- 0.000 0.029 0.204 0.003
ST-300 8.0 0 0.013 CR9-5 1 0.460 0.002 0.000 0.001 1.686 0.287
244 8.0 26 ---- 0.029 0.030 1.890 0.289
125 5.5 Galv Rect SR5-5-MN 7.382 0.028 0.029
ST-340 9.7 EF 0.035 Rect Rect ---- 0.000 0.010 0.196 0.011
ST-310 8.0 0 0.013 CR9-5 1 0.460 0.007 0.000 0.003 1.691 0.281
475 8.0 26 ---- 0.010 0.013 1.887 0.292
244 8.0 Galv Rect SR5-5-MN 0.269 0.004 0.010
ST-350 9.7 EF 0.020 Rect Rect ---- 0.000 0.004 0.200 0.007
ST-320 8.0 0 -0.004 CR9-5 1 0.460 0.004 0.000 0.001 1.686 0.286
378 8.0 26 ---- 0.004 0.005 1.886 0.293
194 4.6 Galv Rect *SR5-5-MN 0.004
ST-370 10.9 EF 0.110 Rect Rect ---- 0.000 0.005 0.162 0.045
ST-390 10.0 0 -0.001 ---- 0.000 0.006 1.461 0.511
975 10.0 26 ---- 0.005 0.011 1.623 0.556
632 6.0 Galv Rect SR5-5-MN 0.123 0.005 0.005
ST-380 9.7 EF 0.055 Rect Rect ---- 0.000 0.010 0.189 0.018
ST-370 8.0 0 0.018 ---- 0.000 0.004 1.448 0.525
46 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 14
ST-390 13.1 EF 0.090 Rect Rect ---- 0.000 0.026 0.158 0.049
ST-460 12.0 0 -0.001 ---- 0.000 0.007 1.454 0.519
1,013 12.0 24 ---- 0.026 0.034 1.612 0.568
948 8.0 Galv Rect SR5-5-MN 0.617 0.026 0.026
ST-400 14.2 EF 0.085 Rect Rect ---- 0.000 0.013 0.156 0.051
ST-460 12.0 0 0.010 ---- 0.000 0.009 1.445 0.528
1,038 14.0 24 ---- 0.013 0.022 1.600 0.579
1,141 10.5 Galv Rect SR5-5-MN 0.294 0.013 0.013
ST-410 9.7 EF 0.055 Rect Rect ---- 0.000 0.077 0.189 0.018
ST-400 8.0 0 -0.044 ---- 0.000 0.001 1.490 0.483
616 8.0 26 ---- 0.077 0.078 1.679 0.501
316 2.5 Galv Rect SR5-5-MN 3.207 0.077 0.077
ST-420 9.7 EF 0.055 Rect Rect ---- 0.000 0.077 0.189 0.018
ST-400 8.0 0 -0.044 ---- 0.000 0.002 1.491 0.482
616 8.0 26 ---- 0.077 0.079 1.679 0.500
316 4.0 Galv Rect SR5-5-MN 3.207 0.077 0.077
ST-430 21.9 EF 0.110 Rect Rect ---- 0.000 0.003 0.088 0.118
ST-140 20.0 0 -0.003 ---- 0.000 0.004 1.392 0.580
1,579 20.0 22 ---- 0.003 0.007 1.481 0.698
4,131 3.5 Galv Rect *SR5-1-MN 0.030 0.003 0.003
ST-440 22.9 EF 0.100 Rect Rect ---- 0.000 0.051 0.095 0.112
ST-290 20.0 0 -0.051 CR9-5 1 0.460 0.045 0.000 0.014 1.303 0.669
1,538 22.0 22 ---- 0.051 0.065 1.398 0.781
4,398 14.0 Galv Rect SR5-5-MN 0.055 0.005 0.051
ST-450 19.7 EF 0.105 Rect Rect ---- 0.000 0.007 0.111 0.096
ST-430 18.0 0 0.016 ---- 0.000 0.005 1.381 0.591
1,420 18.0 24 ---- 0.007 0.012 1.492 0.687
3,006 4.5 Galv Rect SR5-5-MN 0.081 0.007 0.007
ST-460 17.5 EF 0.095 Rect Rect ---- 0.000 0.123 0.133 0.074
ST-120 16.0 0 -0.079 ---- 0.000 0.015 1.445 0.527
1,251 16.0 24 ---- 0.123 0.138 1.578 0.601
2,089 16.0 Galv Rect SR5-5-MN 1.876 0.123 0.123
ST-470 9.7 EF 0.055 Rect Rect ---- 0.000 0.010 0.189 0.018
ST-370 8.0 0 0.018 ---- 0.000 0.003 1.446 0.526
616 8.0 26 ---- 0.010 0.012 1.635 0.544
316 5.0 Galv Rect SR5-5-MN 0.400 0.010 0.010
ST-480 28.4 EF 0.085 Rect Rect ---- 0.000 0.151 0.085 0.122
ST-230 26.0 0 -0.067 ---- 0.000 0.016 1.322 0.650
1,604 26.0 22 ---- 0.151 0.167 1.407 0.772
7,054 19.0 Galv Rect SR5-5-MN 1.414 0.151 0.151
ST-490 41.5 EF 0.090 Rect Rect ---- 0.000 0.000 0.000 0.207
47 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 15
* Loss coefficient for indicated fitting was extrapolated due to table extents being exceeded.
48 of 68
C:\disc top 6.02 DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 16
RT-110 39.4 EF 0.070 Rect Rect ---- 0.000 0.130 0.053 0.152
RT-100 26.0 0 -0.077 CR9-5 2 0.460 0.062 0.000 0.012 0.542 0.022
1,543 51.4 20 ---- 0.130 0.143 0.595 0.174
13,061 18.0 Galv Rect SR5-5-MN 0.047 0.006 0.130
* Loss coefficient for indicated fitting was extrapolated due to table extents being exceeded.
49 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 17
SR-110 9.7 EF 0.025 Rect Rect ---- 0.200 0.315 0.200 0.007
ST-450 8.0 0 -0.227 ---- 0.000 0.001 1.609 0.363
386 8.0 26 ---- 0.115 0.317 1.809 0.370
198 6.5 Galv Rect ---- 0.315
4.70 40 30 *SR5-5-MN 1 12.241 0.115
SR-120 6.6 EF 0.025 Rect Rect ---- 0.200 0.314 0.202 0.004
ST-300 6.0 0 -0.273 ---- 0.000 0.001 1.972 0.000
307 6.0 28 ---- 0.114 0.315 2.175 0.004
73 3.0 Galv Rect ---- 0.314
6.60 40 30 SR5-5-MN 1 28.231 0.114
SR-130 19.7 EF 0.015 Rect Rect ---- 0.200 0.246 0.193 0.013
ST-430 16.0 0 -0.141 CR9-5 1 0.460 0.005 0.000 0.001 1.534 0.439
531 20.4 24 ---- 0.046 0.247 1.727 0.452
1,125 4.5 Galv Rect ---- 0.246
10.70 40 30 SR5-5-MN 1 3.404 0.040
SR-140 19.7 EF 0.025 Rect Rect ---- 0.200 0.208 0.187 0.019
ST-170 12.0 0 -0.144 ---- 0.000 0.001 1.556 0.417
638 28.4 24 ---- 0.008 0.209 1.743 0.436
1,350 4.0 Galv Rect ---- 0.208
11.70 40 30 SR5-5-MN 1 0.490 0.008
SR-150 12.0 EF 0.085 Rect Rect ---- 0.200 0.200 0.166 0.041
ST-190 10.0 0 -0.200 ---- 0.000 0.003 1.720 0.253
928 12.0 24 ---- 0.000 0.203 1.886 0.294
729 3.9 Galv Rect ---- 0.200
9.00 40 30 *SR5-5-MN 1
SR-160 12.0 EF 0.085 Rect Rect ---- 0.200 0.200 0.166 0.041
ST-180 10.0 0 -0.200 ---- 0.000 0.005 1.729 0.244
928 12.0 24 ---- 0.000 0.205 1.894 0.285
729 6.0 Galv Rect ---- 0.200
9.00 40 30 *SR5-5-MN 1
SR-170 9.7 EF 0.055 Rect Rect ---- 0.200 0.200 0.189 0.018
ST-420 8.0 0 -0.200 ---- 0.000 0.003 1.694 0.279
616 8.0 26 ---- 0.000 0.203 1.882 0.297
316 5.6 Galv Rect ---- 0.200
6.70 40 30 *SR5-5-MN 1
SR-180 10.9 EF 0.030 Rect Rect ---- 0.200 0.217 0.195 0.011
ST-390 10.0 0 -0.180 ---- 0.000 0.001 1.635 0.338
488 10.0 26 ---- 0.017 0.219 1.830 0.349
316 4.0 Galv Rect ---- 0.217
5.90 40 30 SR5-5-MN 1 1.770 0.017
50 of 68
C:\disc top 6.02 DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 18
SR-200 9.7 EF 0.055 Rect Rect ---- 0.200 0.200 0.189 0.018
ST-410 8.0 0 -0.200 ---- 0.000 0.003 1.693 0.280
616 8.0 26 ---- 0.000 0.203 1.881 0.298
316 5.1 Galv Rect ---- 0.200
6.70 40 30 *SR5-5-MN 1
SR-210 9.7 EF 0.055 Rect Rect ---- 0.200 0.200 0.189 0.018
ST-470 8.0 0 -0.200 ---- 0.000 0.004 1.650 0.322
616 8.0 26 ---- 0.000 0.204 1.839 0.340
316 7.0 Galv Rect ---- 0.200
6.70 40 30 *SR5-5-MN 1
SR-230 15.3 EF 0.085 Rect Rect ---- 0.200 0.200 0.153 0.054
ST-260 12.0 0 -0.200 ---- 0.000 0.003 1.968 0.005
1,065 16.4 24 ---- 0.000 0.203 2.121 0.059
1,360 3.5 Galv Rect ---- 0.200
15.30 40 30 *SR5-5-MN 1
SR-240 19.7 EF 0.025 Rect Rect ---- 0.200 0.207 0.187 0.020
ST-250 16.0 0 -0.148 ---- 0.000 0.001 1.911 0.061
643 20.4 24 ---- 0.007 0.208 2.099 0.081
1,360 3.2 Galv Rect ---- 0.207
16.70 40 30 SR5-5-MN 1 0.400 0.007
SR-250 20.7 EF 0.020 Rect Rect ---- 0.200 0.225 0.191 0.016
ST-240 16.0 0 -0.126 ---- 0.000 0.001 1.910 0.063
582 22.6 24 ---- 0.025 0.226 2.100 0.079
1,360 4.5 Galv Rect ---- 0.225
16.70 40 30 SR5-5-MN 1 1.770 0.025
SR-260 20.7 EF 0.020 Rect Rect ---- 0.200 0.433 0.191 0.016
ST-270 16.0 0 -0.335 ---- 0.000 0.000 1.558 0.415
582 22.6 24 ---- 0.233 0.433 1.748 0.431
1,360 2.5 Galv Rect ---- 0.433
11.70 40 30 SR5-5-MN 1 16.594 0.233
SR-270 20.7 EF 0.020 Rect Rect ---- 0.200 0.323 0.191 0.016
ST-280 16.0 0 -0.231 ---- 0.000 0.000 1.456 0.516
582 22.6 24 ---- 0.123 0.324 1.647 0.532
1,360 2.5 Galv Rect ---- 0.323
11.70 40 30 SR5-5-MN 1 8.778 0.123
51 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
H 132/33KV SUBSTATION
Page 19
SR-290 9.7 EF 0.020 Rect Rect ---- 0.200 0.200 0.200 0.007
ST-350 8.0 0 -0.200 ---- 0.000 0.000 1.886 0.086
378 8.0 26 ---- 0.000 0.200 2.086 0.093
194 1.6 Galv Rect ---- 0.200
6.70 40 30 *SR5-5-MN 1
SR-300 9.7 EF 0.035 Rect Rect ---- 0.200 0.200 0.196 0.011
ST-340 8.0 0 -0.200 ---- 0.000 0.001 1.892 0.080
475 8.0 26 ---- 0.000 0.201 2.088 0.091
244 4.0 Galv Rect ---- 0.200
7.70 40 30 *SR5-5-MN 1
SR-310 6.6 EF 0.065 Rect Rect ---- 0.200 0.200 0.194 0.013
ST-330 6.0 0 -0.210 ---- 0.000 0.001 1.897 0.075
526 6.0 28 ---- 0.000 0.201 2.091 0.088
125 1.5 Galv Rect ---- 0.200
5.60 40 30 *SR5-5-MN 1
SR-320 22.9 EF 0.100 Rect Rect ---- 0.200 0.200 0.095 0.112
ST-440 16.0 0 -0.200 ---- 0.000 0.003 1.506 0.467
1,538 28.0 22 ---- 0.000 0.203 1.601 0.579
4,398 2.5 Galv Rect ---- 0.200
17.90 40 30 *SR5-5-MN 1
* Loss coefficient for indicated fitting was extrapolated due to table extents being exceeded.
52 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 20
RR-110 35.0 EF 0.010 Rect Rect ---- 0.000 0.099 0.185 0.020
RT-100 26.0 0 0.087 ---- 0.000 0.001 0.366 0.197
564 39.8 20 ---- 0.099 0.099 0.551 0.218
3,770 7.0 Galv Rect ---- 0.099
32.00 40 30 SR5-5-MN 1 5.473 0.099
* Loss coefficient for indicated fitting was extrapolated due to table extents being exceeded.
53 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 21
54 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 22
55 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 23
Required Attenuation 0 7 13 19 23 25 26 27 40
Actual Attenuation 54 51 55 73 129 176 101 104 30
Additional Attenuation 0 0 0 0 0 0 0 0
57 of 68
C:\disc top 6.0 DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 25
58 of 68
C:\disc top 6. DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 26
ST-410
SR-200
ST-420
59 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
132/33KV SUBSTATION
Page 27
60 of 68
C:\disc top 6.02\ DUCTING.dsw Wednesday, February 11, 2009, 11:28 PM
ELECTRIC DUCT HEATER SIZING EDH-1 :
Data:
Calculation.
Desired heating capacity in KW Total heating required in BTUH.
3520 BTU/Hr./kW
= 50.39 kW
Equipment heat load= 53.69 kw
Consider 50% from Equipment heat load= 26.845 kw
Net heating required = 50.4 - 26.845 =23.6 KW
Take 10% safty
Net heating required = 23.6 X 1.1=28.32 KW
Use Heater Capacity =29 kW
61 of 68
BATTERY ROOM EXHAUST FAN SIZING:
DATA
Notes
Number of Air changes required for the battery room is 12 as per the clause
No.4.1.10 of SES-P-119-19 & clause No.10.9 of SES-K-100. Hence 12 air changes
per hour is considered in calculation.
Calculation
3
Volume of Battery room V= 6x5.9x5.4 M
= 191.16 M3
= 6750.75 Ft3
Fan capacity in CFM = Room volume x No. Of Air changes/Hr
60
= 6750.75x12 / 60
= 1350.15 CFM
p y of
Use fan capacity = 1350 CFM
= 2294 CMH
From load calc. Battery Room CFM= 1350 CFM
Pressure loss through the exhaust duct = 0.51 in.W.G. (Ref. To comp. Cal
enclosed)
62 of 68
FIRE FIGHTING EXHAUST FAN SIZING:
DATA
Notes
Number of Air changes required for the battery room is 10 as per the clause
No.4.1.10 of SES-P-119-19 & clause No.10.9 of SES-K-100. Hence 10 air changes
per hour is considered in calculation.
Calculation
3
Volume of Battery room V= 341463415x5.850609756M
= 178.729 M3
= 6311.75 Ft3
Fan capacity in CFM = Room volume x No. Of Air changes/Hr
60
= 6311.75x10 / 60
= 1051.958 CFM
p y of
Use fan capacity = 1125 CFM
= 1912 CMH
From load calc. Battery Room CFM= 1125 CFM
Pressure loss through the exhaust duct = 0.51 in.W.G. (Ref. To comp. Cal
enclosed)
63 of 68
KITCHEN EXHAUST FAN SIZING:
DATA
Notes
Number of Air changes required for the battery room is 12 as per the clause
No.4.1.10 of SES-P-119-19 & clause No.10.9 of SES-K-100. Hence 12 air changes
per hour is considered in calculation.
Calculation
3
Volume of Battery room V= 2x1.5x4.0030487804878 M
= 12.00915 M3
= 424.1 Ft3
Fan capacity in CFM = Room volume x No. Of Air changes/Hr
60
= 424.1x10 / 60
= 71 CFM
p y of
Use fan capacity = 71 CFM
= 121 CMH
From load calc. Battery Room CFM= 194 CFM
ACTUAL AIR CHANGE= 27 ACH
Pressure loss through the exhaust duct = 0.51 in.W.G. (Ref. To comp. Cal
enclosed)
64 of 68
TOILET EXHAUST FAN SIZING :
DATA
Notes:
Number of Air changes required for the toilet is 6-10 as per the clause No.4.1.11 of
SES-P-119-19 & clause No.10.11 of SES-K-100. Hence 10 air changes per hour is
considered in calculation.
Calculation
3
Volume of Battery room V= 3.46x2.99x4 M
= 41.3816 M3
3
= 1461.38 Ft
Fan capacity in CFM = Room volume x No. Of Air changes/Hr
60
= 1461.38x10 / 60
= 244 CFM
= 414 CMH
Use fan capacity of = 244 CFM FROM LOAD CALCULATION
Pressure loss through the exhaust duct = 0.2 in.W.G. (Ref. To comp. Cal
enclosed)
`
65 of 68
SAND TRAP LOUVER AND FRESH AIR FILTER SIZING :
DATA
Required Fresh Air 3,925 CFM
1852 L/s
From the graph pressure loss across the louver is= 0.40 in.W.G.
66 of 68
AIR DIFFUSION PERFORMANCE INDEX :-
ZONE
S.No. Particulars BATTARY ROOM STORE ROOM FIRE FIGHTING ROOM AC/DC ROOM TELECOM PASSAGE CONTROL ROOM OFFICE TOILET
Metric unit FPS unit Metric unit FPS unit Metric unit FPS unit Metric unit FPS unit Metric unit FPS unit Metric unit FPS unit Metric unit FPS unit Metric unit FPS unit Metric unit FPS unit
1 Room Length M/FT 6.000 19.686 4.000 13.124 31.800 104.336 8.100 26.576 4.500 14.765 4.000 13.124 31.900 104.664 11.150 36.583 4.500 14.765
2 Room width M/FT 5.950 19.522 5.000 16.405 5.500 18.046 4.000 13.124 3.000 9.843 1.960 6.431 16.150 52.988 4.000 13.124 3.000 9.843
3 R
Room Area M2 /FT2
A 35 700
35.700 384 309
384.309 20 000
20.000 215 299 174.900
215.299 174 900 1882 792
1882.792 32 400
32.400 348 785
348.785 13 500
13.500 145 327
145.327 7 840
7.840 84 397
84.397 515 185 5545.946
515.185 5545 946 44 600
44.600 480 117
480.117 13 500
13.500 145 327
145.327
4 Room Char. Length 6.000 19.686 3.000 9.843 5.500 18.046 4.000 13.124 3.200 10.499 3.000 9.843 2.400 7.874 3.300 10.827 3.000 9.843
Supply air stream
5 Supply air to room
38.24 1,350 14.42 509 31.87 1125 41.30 1458 11.22 396 2.07 73 44.73 1579 3.54 125 6.91 244
Cum/Min/CFM
6 Number of Outlets 1 1 1 2 2 1 5 1 1
7 Supply air to outlets
Cum/Min/CFM 38.24 1350.00 14.42 509.00 31.87 1125.00 20.65 729.00 5.61 198.00 2.07 73.00 8.95 315.80 3.54 125.00 6.91 244.00
8 Outlet size MM/In 700x450 28x18 500x250 20x10 750x300 30x12 375x375 15x15 225x225 9x9 150x150 6x6 300x300 12x12 150x150 6x6 300x300 12x12
10 TV/L as per
manufacturer's 3/4 3/4 3/4 - - - - - -
Catalogue
11 Calculated TV - M
6.00 19.69 3.00 9.84 5.50 18.05 4.00 13.12 3.20 10.50 3.00 9.84 2.40 7.87 3.30 10.83 3.00 9.84
/FT
12 Actual TV in FT 24-33 12-18 22-31 14-19 7-10 4-7 8-12 7-11 6-9
13 Sound Level dB 37 <20 37 26 <20 <20 <20 <20 <20
14 Pressure Drop, in W.G
0.013 0.013 0.026 0.066 0.032 0.024 0.032 0.066 0.017
15 Supply register model
SH6-IID SH6-IID SH6-IID CD9-4SD CD9-4SD CD9-4SD CD9-4SD CD9-4SD CD9-4SD
No.
Return Air Stream
16 Return air to outlets
Cum/Min/CFM 38.87 1372 10.57 373 1.76 62 42.10 1486 3.29 116
17 Outlet size MM/In 375X375 15X15 225X225 9X9 150X150 6X6 300X300 12X12 150x150 6X6
18 Number of Return
2 2 1 5 1
registers
19 Sound Level dB 25 <20 <20 <20 <20
20 Pressure Drop, in W.G
-0.269 -0.132 -0.269 -0.097 -0.269
21 Return register model
CD9-4S CD9-4S CD9-4S CD9-4S CD9-4SD
No.
Transfer Air Grilles
27 Air capacity
10.31 364 38.81 1370 10.51 371 3.29 116
Cum/Min/Cfm
28 Exhaust Grille Size 350X300 14X12 700X600 28X16 400X250 16X10 150X150 6X6
29 Exhaust Grille Model
EC14-1D EC14-1D EC14-1D EC14-1D
No.
30 Face velocity 400 FPM 500 FPM 400 FPM 500 FPM
31 Sound Level dB 24 24 24 33
32 Static pressure in.w.g -0.026 -0.042 -0.026 -0.082
Exhaust Air Grilles
27 Air capacity
38.24 1350 31.87 1125 6.91 244
Cum/Min/Cfm
28 Exhaust Grille Size 500X259 20X10 800X300 32X12 300X300 12X12
29 Exhaust Grille Model
EC14-1D EC14-1D EC14-1D
No.
30 Face velocity 500FPM 500 FPM 500 FPM
31 Sound Level dB 28 24 21
32 Static pressure in.w.g -0.059 -0.042 -0.016
67 of 68
AIR DIFFUSION PERFORMANCE INDEX :-
ZONE
S.No. Particulars KITCHEN 33KV SWGR ROOM BASEMENT
Metric unit FPS unit Metric unit FPS unit FPS unit
Metric unit
1 Room Length M/FT 2.000 6.562 18.000 59.058 18.000 59.058
2 Room width M/FT 1.500 4.922 5.500 18.046 5.500 18.046
3 Room Area M2 /FT2 3.000 32.295 99.000 1065.731 99.000 1065.731
4 Room Char. Length 1.500 4.922 4.130 13.551 13.500 44.294
Supply air stream
5 Supply air to room
5.50 194 231.22 8162 124.59 4398
Cum/Min/CFM
6 Number of Outlets 1 6 1
7 Supply air to outlets
5.50 194.00 38.54 1360.33 124.59 4398.00
Cum/Min/CFM
8 Outlet size MM/In 225x225 9x9 300X300 32X16 600x300 24X12
10 TV/L as per
manufacturer's - 3/4 -
Catalogue
11 Calculated TV -
1.50 4.92 4.13 13.55 13.50 44.29
M /FT
12 Actual TV in FT 7-10 24-33 -
13 Sound Level dB <20 37 -
14 Pressure Drop, in
0.032 0.013 0.1
W.G
15 Supply register
CD9-4SD SH6-IID BMO
model No.
Return Air Stream
16 Return air to outlets
444.42 15688 115.38 4073
Cum/Min/CFM
17 Outlet size MM/In 2500X1250 100X50 1000x450 40x18
18 Number of Return
1 1
registers
19 Sound Level dB - -
20 Pressure Drop, in
02
0.2 02
0.2
W.G
21 Return register
BMO BMO
model No.
Transfer Air Grilles
27 Air capacity
Cum/Min/Cfm
28 Exhaust Grille Size
29 Exhaust Grille
Model No.
30 Face velocity
31 Sound Level dB
32 Static pressure
in.w.g
Exhaust Air Grilles
27 Air capacity
5.50 194
Cum/Min/Cfm
28 Exhaust Grille Size 250X250 10X10
29 Exhaust Grille
EC14-1D
Model No.
30 Face velocity 400 FPM
31 Sound Level dB 25
32 Static pressure
-0.026
in.w.g
68 of 68