Sie sind auf Seite 1von 2

Adhithana Engineering Corporation LLP

MASS FLOW TRANSMITTER

1. General 46.
2. Manufacturer: Refer Attached Instrument Index * 47. Accessories (refer note 4)
3. Model no.: Refer Attached Instrument Index * 48. Name plate / metal tag: SS 

4. Quantity: Refer Attached Instrument Index * 49. Mounting accessories: SS 

5. 50. All installation hardware: SS 

6. Type 51.

7. Principle: Coriolis effect  52. Codes and standards (refer note 3)

8. Application: Flow Density  53. Selection & installation – BS ISO 10790 

9. Sensor mounting: Inline  54. Weather proof – IS 13947 PART I 

Transmitter: Wall mounting Panel mounting Explosion proof – IS 2148/ BS EN 50014 / BS EN


10.  55. -
2" Pipe mounting Integral 50020

11.
12. Features
13. Display on transmitter: LCD 
14. Flow totalizer 
15. Accuracy:  0.2 % of flow rate 
16. Repeatability:  0.1 % 
Alarm contacts: Yes No
17. -
HI LO
18. Rangeability: *
19. Maximum allowable dist between sensor & electronics *
20.
21. Enclosure:
22. Weatherproof to IP 66 
23. Hazardous area classification: Zone 2, Group IIC 
24. Intrinsically safe: Yes No 
25.
26. Signal & power supply details
Power supply: 240 V AC 110 V AC
27. 
24 V DC S
28. Output signal: 1 - 5 V Pulse 4-20 mA 
29. Power consumption *
30. Switch details: -
31. No. Of contacts : 2 NOS. 
32. 2 no + 2 NC 2 Changeover 
33. Contact rating : 24 V DC -
34.
35. Material
36. Wetted parts: SS 316 Hastelloy 
37. Housing: SS 304 Die cast aluminum 
38.
39. Connection & dimensions
Process connection: Threaded Flanged
40. 
Refer Attached Instrument Index
Threaded process connection:
41. -
¼ “ NPT ½ “ NPT ¾ ” NPT
42. Flanged process connection:
43. Flange rating: -
44. Flange size: -
45. Cable entry: ½” NPT (F) -

SH 1 of 2
Adhithana Engineering Corporation LLP
MASS FLOW TRANSMITTER

56. Tests
57. Repeatability, Performance, Calibration & Hydrotest 
58. Vendor shall submit type test certificates for protection class. 
59. Vendor to submit all routine test certificates for Purchaser / Consultant’s review & records. 
60.
61. Drawings
62. The vendor to submit catalogues, data sheet and erection sketch for review and comments by purchaser/ consultant. 
63. The vendor to submit instruction manual for records. 

Notes:
1.0 Bidder to furnish details (*); Required (); Not required (-).
2.0 Counter flanges, gaskets, nuts and bolts for the valve are included in Bidder’s scope.
3.0 Bidder shall indicate all applicable codes & standards
4.0 All accessories shall be supplied as applicable.

SH 2 of 2