Sie sind auf Seite 1von 4

Jhajjar KT Transco Pvt Ltd

Lux Measurement in 400/220/132KV Substation


Kabulpur,Rohtak
Lux Measurement Model no. HTC LX 101 A Date: 15/10/2019

Limit ( as per JKTPL


SL.No Location Maintenance Manual)
Measure Value (Lux)
1 400KV Dia 1 20 32
2 400KV Dia 2 20 37
3 400KV Dia 3 20 28
4 400KV Dia 4 20 30
5 220KV Bay 1-3 20 35
6 220KV Bay 4-6 20 30
7 220KV Bay 7-9 20 30
8 220KV Bay 10-12 20 30
9 220KV Bay 13-14 20 30
10 132 kV Bay 1-3 20 35
11 133 kV Bay 4-6 20 25
12 134 kV Bay 7-9 20 30
13 135 kV Bay 11-12 20 30
14 Control Room 300 320
15 Conference Room 250 290
16 Test Lab 250 260
17 Incharge Room 150 170
18 SIC Room 150 190
19 Independent Engineers Room 150 170
20 Indoor Store Room 100 140
21 Doctors Room 150 180
22 Maintenance Room 150 170
23 Pantry 100 120
24 LTDB Room 150 190
25 Open Store 50 70
26 Kiosk 1 K1 300 330
27 Kiosk 1 K2 300 340
28 Kiosk 1 K3 300 315
29 Kiosk 1 K4 300 350
30 Kiosk 1 K5 300 350
31 Kiosk 2 K1 300 310
32 Kiosk 2 K2 300 340
33 Kiosk 2 K3 300 330
34 Kiosk 2 K4 300 340
35 Kiosk 2 K5 300 310
36 Kiosk 2 K6 300 315
37 Kiosk 2 K7 300 370
38 Kiosk 4K1 300 350
39 Kiosk 4K2 300 360
40 Kiosk 4K3 300 350
41 Kiosk 4K4 300 340
42 Pump House 150 175
43 Corridor First Floor 100 120
44 Corridoor Ground floor 100 115
station

Remarks
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK