Beruflich Dokumente
Kultur Dokumente
Volume 4-13
Thermal Analysis
PO Box 25007
Denver CO 80225-0007
12. DISTRIBUTION / AVAILABILITY STATEMENT
Available from the National Technical Information Service, Operations Division
5285 Port Royal Road, Springfield, Virginia 22161
13. SUPPLEMENTARY NOTES
14. ABSTRACT
Thermography allows for nonintrusive measurement of temperature and thermal characteristics or thermal
patterns of plant equipment. The intent is to detect abnormal temperatures or changes in temperature that may
indicate problems in their incipient stages. Serious failures and outages may be avoided when problems can be
identified and remedied early. Early detection permits more effective maintenance planning and scheduled
outages. Thermography can be used to troubleshoot, perform pre- and postoutage measurements, verify
successful installation or repair, and predict problems.
15. SUBJECT TERMS: Thermography, infrared, temperature, operations and maintenance, inspections.
16. SECURITY CLASSIFICATION OF: 17. LIMITATION 18. NUMBER 19a. NAME OF RESPONSIBLE PERSONT
OF ABSTRACT OF PAGES Hydropower Technical Resources Group
a. REPORT b. ABSTRACT c. THIS PAGE UL 93 19b. TELEPHONE NUMBER (include area
UL UL UL code)
303-445-2300
Standard Form 298 (Rev. 8/98)
Prescribed by ANSI Std. 239-18
Facilities, Instructions, Standards, and Techniques
Volume 4-13
Thermal Analysis
iii
FIST 4-13
Thermal Analysis
iv
FIST 4-13
Thermal Analysis
Table of Contents
Page
v
FIST 4-13
Thermal Analysis
Appendices
Appendix A – Glossary of Thermography Terms ........................................... 45
vi
FIST 4-13
Thermal Analysis
Figures
Page
Figure 1. Transformer bushing with incorrect washer that does not
allow correct connection ............................................................................. 2
Figure 2. High-side connection from transformer, illustrating a “barber
pole” effect where only part of the cable strands carry the current ............ 2
Figure 3. Thermographic maintenance process .............................................. 7
Figure 4. Visible and IR spectrum .................................................................. 14
Figure 5. Qualitative IR image of a main circuit breaker enclosure
illustrating indirect imaging ........................................................................ 16
Figure 6. Radiation sources............................................................................. 19
Figure 7. Image quality contributors ............................................................... 31
Figure 8. Spot size of hand-held radiation thermometer................................. 32
Figure 9. Field of view of an IR camera ......................................................... 33
vii
FIST 4-13
Thermal Analysis
1.0 Introduction
1.1 What Thermal Analysis Does
Thermal analysis allows for nonintrusive analysis of temperature and thermal
characteristics or thermal patterns of plant equipment and structures. The intent is to
describe different methods used to dynamically detect abnormal thermal conditions or
changes in temperature that may indicate problems in their incipient stages. Using
different technologies will be discussed to detect dynamic changes in heating; however,
using thermal imaging cameras is preferred. Identifying and remedying problems early
may avoid serious failures and outages. Early detection permits more effective
maintenance planning and scheduled outages. Thermal analysis can be used to
troubleshoot, perform pre- and postoutage thermal comparisons, verify successful
installation or repair, and predict problems with equipment.
Two examples of imminent failures, located and avoided using thermography, are shown
in figures 1 and 2.
1
Maintenance Technology Magazine, June 2001, May 2004, and May 2005.
1
FIST 4-13
Thermal Analysis
52.2°C 52.8°C
50 50
40
40
SP01 30
30
SP02
20
20
10
10
5.3°C 8.1°C
2
FIST 4-13
Thermal Analysis
2.0 Scope
Thermal analysis instruments and processes described in this Facilities Instruction,
Standards, and Techniques (FIST) volume apply to all maintenance programs at
Reclamation power facilities. All appropriate electrical and mechanical features of the
facility should be considered for thermal analysis.
This FIST volume outlines thermal analyses processes and recommends equipment to
monitor and monitoring schedules that may be adopted locally. When discussing thermal
analysis, several forms of technology can be used. These technologies include:
This FIST will guide managers and maintenance staff in thermal analysis technology
development and use. Establishing a thermal analysis process using these guidelines and
executing thermal inspections and analysis on a regular basis will help ensure that
Reclamation’s expectations are in accordance with industry standards and that equipment
is in sound condition. Although thermal analysis is extremely useful as a standalone
maintenance technique in a predictive maintenance (PdM) program, it is not a substitute
for other appropriate testing and maintenance techniques, including visual inspections.
This FIST volume is intentionally broad and does not intend to cover all technical aspects
of thermal analysis theory or use. While the use of a thermal imaging camera is highly
recommended, alternative means of conducting thermal analysis are discussed in a
general sense to aid in establishing a more comprehensive program. Many
comprehensive sources of technical information, existing in the marketplace, are
referenced in this volume.
This volume provides some basic thermal analysis concepts and principles to ground the
reader who is developing a thermal analysis process. Sufficient information is provided
to help the process developer make reasonable decisions. Technical thermal analysis
content in this document focuses on:
3
FIST 4-13
Thermal Analysis
NFPA 70B also indicates that the inspection should be performed using instruments that
use a scanning technique to produce an image of the equipment being inspected;
however, this FIST discusses other equipment that can be used to perform thermal
analysis of equipment.
3.1 Standards
NFPA 70B, Recommended Practice for Electrical Equipment Maintenance, National
Fire Protection Association, 2010.
InterNational Electrical Testing Association (NETA), Maintenance Testing Specifications
for Electrical Power Distribution Equipment and Systems.
4
FIST 4-13
Thermal Analysis
5
FIST 4-13
Thermal Analysis
4.1 Goals
Thermal analysis should be an integrated part of the overall maintenance program and not
considered as a replacement for visual inspection. 2 However, it is recognized that there
are cases where thermal imaging cameras alone will not be adequate to perform thermal
analysis on the entire system based on the ability to gain access to equipment while the
system is operational. In these cases, other technologies will be used to document the
temperature rise of the equipment.
Thermal analysis can be used as a suitable predictive maintenance tool as well as a tool to
augment Reclamation’s preventive maintenance (PM) practices. When used in
Reclamation’s PM practices, the following steps should be considered: 3
• If a problem is found, develop a followup action work order for a more indepth
assessment, which may include a quantitative inspection using a thermal imaging
camera to determine the magnitude of the problem ( i.e., the temperature
difference taking into account the wind and circuit loading).
4.2 Contracting
When establishing a thermal analysis process, it is important to decide whether to
perform thermal analysis inspection using in-house expertise or to contract it out. The
analysis should be based on the criticality of the equipment to the facility mission,
accessibility of the equipment, the overall benefits associated with maintenance savings
from an enhanced PM practice or benefit from a predictive maintenance practice based
2
NFPA 70B, section 11.17.1.4.
3
Refer to FIST 6-2 for work order management.
6
Figure 3. Thermographic maintenance process.
Thermal Analysis
FIST 4-13
7
FIST 4-13
Thermal Analysis
on thermal analysis, and type of analysis to be performed. Contracting the work out only
should be considered if a full thermographic analysis (using a thermal imaging camera) is
being performed.
In-house and contracting alternatives each have their advantages and disadvantages:
In-house Contracting
Advantages • Equipment and expertise • Others own and maintain
always available. thermographic equipment.
• Consistent results. • More extensive and recent
• Familiarity with equipment experience.
being inspected. • May be more cost effective.
• No need to maintain in-house
7
expertise for scanning.
Disadvantages • Costly to procure and maintain • Equipment and expertise not as
thermal analysis equipment. readily available.
• Equipment may be infrequently • Results may not be consistent
used and will become with different thermographers
outdated. and thermography equipment.
• Operators will not have as • Contractor may not be familiar
frequent experience as with facility and plant
contractors. equipment.
• Certification or annual training
costs.
4
NFPA 70B, section 11.17.1.3.
5
Contact the Hydropower Technical Services Group, 86-68440, at 303-445-2300 for more information.
6
Contact the Hydropower Technical Services Group, 86-68440, at 303-445-2300 for more information.
7
In-house expertise in interpreting results is still advised.
8
FIST 4-13
Thermal Analysis
4.4 Documentation
The local thermal analysis process should be documented for clarity and continuity.
Documentation should define:
9
FIST 4-13
Thermal Analysis
equipment, camera settings, and the distance from the equipment to the thermal imaging
equipment. Copies of the previous job hazard analysis’ (JHA) also should be made
available to personnel performing thermal analysis inspections to ensure that all
appropriate information is on the present JHA.
• Equipment to be inspected.
8
Short wave infrared (SWIR) equipment is now classified as MWIR (mid-wave infrared).
10
FIST 4-13
Thermal Analysis
Once the benchmarks are completed, ensure these records are available for comparison to
all subsequent thermal analysis surveys conducted. Significant temperature variations
from the benchmarked temperatures should trigger further investigation. This should
include a thermographic survey, if hand-held radiation thermometers are used to collect
data.
When problem areas are discovered during an inspection performed by an individual who
has not completed certification, it is important to have a certified operator perform a
quantitative review of the problem. This inspection should be performed prior to making
decisions on outages and repair strategies. Certification is critical when the results are
used for official records pertaining to contract performance, such as performing a core
loop test during a rewind. The credibility of the operator is enhanced by certification.
When contractors are used, certification of their thermographers should be required.
Basic training in thermal analysis, including functionality and inspection techniques, may
be acquired from contractors or by contacting thermographers at the TSC. Training in
the science of thermography also is provided by vendors such as:
11
FIST 4-13
Thermal Analysis
For specific temperature measurements and analyses, the thermographer must have
knowledge of the material being imaged, the limitations of the thermographic equipment,
inspection techniques, and the analysis software, if applicable. For consistency and
accuracy, thermography inspections should be performed by personnel who have an
understanding of thermographic technology, electrical and mechanical equipment
maintenance, and the safety issues involved. 9 If circumstances require certification, the
thermographer will be certified at least to an ASNT Level II thermographer, or
equivalent. Level II certification is defined as:
9
NFPA 70B, section 11.17.1.1.
10
American Society of Nondestructive Testing, Columbus, Ohio.
11
ASNT, SNT-TC-1A recommended recertification intervals are 3 years for Level I and Level II and
5 years for Level III. Certifications from vendors, such as the Infrared Training Center, have recertification
set at 5 years.
12
FIST 4-13
Thermal Analysis
Proper selection of the equipment is needed for the diagnostics. Often, the terms
“thermal imager” and “IR camera” are used interchangeably without distinguishing
whether the equipment can calculate temperatures quantitatively; and these terms also
include the term “radiometer.” IR thermographic cameras, called “thermal imagers,” are
capable of showing temperature gradients of the target and, therefore, identify hot spots
but do not have the capability of calculating temperature quantitatively. “Radiometers”
calculate quantitative temperatures. Hand-held radiation thermometers display
temperature values but do not display a thermal image of the equipment being surveyed.
Thermal imaging cameras display a two-dimensional image, where as hand-held
radiation thermometers only display point temperatures. Since the hand-held radiation
thermometers are only point measurement devices, it is critical to understand how the
distance from the target can affect the measurement. When determining if a hand-held
radiation thermometer will be adequate to perform thermal analysis on a given piece of
equipment, the user must determine the distance between the instrument and the target.
The greater the distance between instrument and the target, the measurement area
becomes larger, thus increasing the error in the measurements. Refer to section 7.3.1 and
figure 8 (shown later within this document) for additional information on spot size.
Hand-held radiation thermometers also do not allow the user to adjust for reflected or
transmitted radiation, increasing the likelihood of obtaining incorrect data.
13
FIST 4-13
Thermal Analysis
objects in proximity with the object under test. IR radiation is electromagnetic radiation
with properties similar to visible light. The speed of IR radiation is equal to visible light.
The major difference between IR and visible light is the wavelength, λ, measured in
micrometers (µm). Figure 4 shows the relationship of the visible light spectrum to the
IR spectrum.
visible infrared
MWI LWIR
.4 .75 3 5 7 12
Figure 4. Visible and IR spectrum.
IR cameras of the MWIR type with a wavelength range of 3.0–5.5 µm and of the
LWIR type with wavelength range of 7.0 –15.0 µm are acceptable for Reclamation work.
The LWIR type camera is preferred because the MWIR type camera typically uses an
intercooler that takes several minutes to cool the detector before the camera can be used
to acquire images or perform scanning. Also, LWIR is not affected by sun glints
(momentary flashes), although it is affected by continuous solar reflections. The
LWIR equipment is better suited for outdoor IR work, such as in substations and
switchyards.
The price of IR thermal analysis systems can be quite high, especially thermal imaging
equipment; however, the cost of misdiagnosing problems also should be considered.
When choosing a system, considerations should include the value of being able to
accurately determine a quantitative temperature, thus reducing investigation and repair
time, and the financial impact of a forced outage should a faulty component fail to be
recognized. A “pricier” system may be the most cost effective in the long run.
Regardless of the type of camera selected, the system used is no better than the training
provided to the operator or thermographer. Do not skimp on training.
Many thermal imaging cameras offer similar specifications that meet the needs of a
thermal analysis program. It is recommended to use the equipment to perform a thermal
imaging survey of your facility to determine if the hardware is ergonomically designed
and easy to use before you purchase the equipment. Typically, a manufacturer will send
out a representative or the hardware for your demonstration prior to purchase.
14
FIST 4-13
Thermal Analysis
Once the survey is complete, have the vender demonstrate the software package that is
used to create reports and manipulate images. Once the demonstration is over, ask to use
the software package to determine if the software is intuitive and easy to use. Ensure that
the options within the software perform as expected and that the program operates
without errors on the operating system you plan to use. Open images and attempt to
make changes to the image, changing parameters such as emissivity, palette colors, and
other options that are available. If additional data is stored with the image, such as audio
or text notes, ensure that this information is easy to access.
15
FIST 4-13
Thermal Analysis
6.2 Thermograms
Thermograms are thermal maps of surfaces where color hues represent the distribution of
thermal energy. The image captured represents the total IR energy coming from the
object or target, consisting of emitted, reflected, and transmitted IR energy, and
modulated by the intervening atmosphere.
Thermograms may be “qualitative” in that they represent the thermal energy without
correction for variables—thus, giving an approximate surface temperature. Qualitative
12
IR Thermography — Level I Curriculum, EPRI.
13
Adapted from Guideline for Developing and Managing an Infrared Thermography Program, EPRI
(1004019).
16
FIST 4-13
Thermal Analysis
thermograms are highly beneficial and can provide a wealth of information, even without
knowing the actual temperature values. Thermograms also may be “quantitative” in that
they correct for all variables, providing a nearly true surface temperature using numerical
values in addition to thermal imaging. In short, a qualitative inspection does not produce
numerical data; however, these inspections can yield highly valuable information.
Qualitative thermograms take less time and, in most cases, require simpler equipment.
Qualitative thermograms may provide sufficient information for comparison purposes
(e.g., comparing phases) and often can find the root cause of a problem.
Interpretation is somewhat subjective and may not provide sufficient detail to really
understand a complex problem; however, the purpose of qualitative analysis is to alert
employees of a problem that will require further investigation.
Quantitative thermograms provide more accurate temperature data and are needed for
identifying trends or determining the severity of the problem. However, they require
more sophisticated equipment, increased thermographer training and experience, take
more time, and may confuse the thermographer with too much information. A hand-held
radiation thermometer is not to be used to obtain high-accuracy quantitative temperature
measurements because they cannot account for the necessary parameters to adjust for
background radiation and other variables necessary to determine an accurate temperature
value.
Depending on the equipment used, the actual temperature of the component may be two,
three, or even more times higher than the temperature being recorded by the noncontact
IR measuring equipment. 14 This depends on the physical construction and material of the
object being surveyed.
Apparent temperatures seen in the thermogram include all temperatures—both the direct
temperature of the target and temperatures from ambient air and reflected radiation. To
obtain accurate temperature values, it is recommended that the thermographer obtain
Level II thermography training. Level II training provides the information and guidance
needed to correctly use the thermal imaging device, accounting for all variables, to obtain
accurate temperature measurements.
14
Electrical Applications, InfraMation 2004 IR Clinic, Las Vegas, Nevada.
17
FIST 4-13
Thermal Analysis
Activity Strategy
Comparison of the temperature or thermal pattern of one object to a similar object that is
known to be operating properly is one way of detecting irregularities. The similar object
must be subjected to the same conditions as the target object—for example, same
manufacturer, same load, same emissivity, and same environmental conditions.
15
Common Sense Approach to Thermal Imaging, Holst, chapter 11.
16
Common Sense Approach to Thermal Imaging, Holst, chapter 11.
18
FIST 4-13
Thermal Analysis
6.2.3 Radiation
Thermal analysis equipment detects radiated heat energy of the types shown in figure 6:
• Emitted
• Reflected
• Transmitted
Each of these radiated energy types plays a role in thermal analysis and should be
understood. The IR equipment receives all three types of energy, but not all indicate the
true temperature of the target. These energy types generate three of the four apparent
sources of temperature difference (emittance, reflectivity, geometric, and transmittance
differences). Geometric difference refers to the variations in shape of the target, the
surface texture of the target, and if there are natural cavities created due to the shape of
the target. All four temperature differences must be recognized and factored into the
inspection so that accurate measurement and comparison of emitted radiation is
determined.
TARG
E
SURFA T
CE
on
adiati
cted R iation
Refle te d Rad iation
Em it d Rad
r a n s mitte
T
Thermal Analysis
Instrumentation
The atmosphere is composed of many different gasses, particles, etc., which can absorb,
reflect, or otherwise redirect the radiation from the target to the measuring equipment,
imager, or radiometer. The resulting reduction in the target radiation reaching the
IR measuring device is attributed to atmospheric transmittance.
19
FIST 4-13
Thermal Analysis
If viewing a target from a long distance, the atmospheric transmittance must be included
in the target temperature calculation.17 However, for most IR inspections performed in
the relatively close distances of powerplants and switchyards, atmospheric conditions
(weather) can be ignored unless the weather is really bad— in which case, the inspection
should be postponed.
6.2.6 Blackbody
A blackbody is an ideal body that completely absorbs all radiant energy striking it and,
therefore, appears perfectly “black” at all wavelengths. The radiation “emitted” by a
blackbody is “blackbody radiation.” A perfect blackbody has an emissivity of unity
(i.e., 1.0) and a reflectivity of zero at all wavelengths. Blackbodies are used to calibrate
IR measurement devices.
6.2.7 Emissivity
Emissivity is a property of a material that describes its ability to radiate energy compared
to a blackbody at the same temperature. High emissivity indicates an increased
efficiency of the object to act as a heat radiator. See appendix E for methods to
determine or enhance emissivity of a target and appendix F for a table of material
emissivity. Most experienced thermographers will not rely on emissivity tables when
conducting quantitative temperature measurements; instead, the thermographer will
perform various checks to determine the emissivity for each target. The tables are
approximate and can lead to errors if not used correctly.
Emissivity values range from zero to one and are affected by surface characteristics such
as age, paint, dust, dirt, dew, frost, chips, scratches, and weathering effects. Generally,
smooth surfaces produce low emissivity while rough surfaces produce high emissivity.
For accurate IR readings, ideally, the emissivity of the target should be as high as
possible so that most of the energy measured is emitted from the target itself rather than
being reflected.
Emissivity also is affected by viewing angle and temperature. Care should be taken to
point the IR measuring device as close to perpendicular to the target surface as possible.
When taking temperature measurements of objects with low emissivity, it is important to
ensure that the recorded temperature is the temperature of the object and is not affected
by the reflection of the thermographer or other equipment in the area.
17
Common Sense Approach to Thermal Imaging, Holst, chapter 12.
20
FIST 4-13
Thermal Analysis
The emissivity of the target and surrounding environment are impossible to know exactly
and can be time consuming and difficult to determine. Therefore, it is very difficult to
determine accurate temperatures, and inspections tend to be mostly qualitative. 18 If
quantitative values are required, the thermographer should determine the emissivity of the
target object experimentally by comparing an object of known emissivity to the target
object and adjusting the emissivity accordingly.
6.2.8 Reflectivity
Reflectivity is a property of a material that describes its ability to reflect energy from a
source other than the target but on the same side of the target as the IR measuring device
(see figure 6). Reflected energy usually is added to the radiated energy from the target.
Therefore, reflected energy will be detected by the IR measuring device, and the
temperature displayed by the device will not indicate the true temperature of the target.
Reflectivity typically is a problem when attempting to perform IR thermal analysis on
objects with a smooth surface and a low emissivity. Materials that have a low emissivity
are reflective to IR radiation.
6.2.9 Transmissivity
Transmissivity is a property of a material that describes its ability to transmit energy from
a source other than the target but on the opposite side of the target from the IR measuring
device (see figure 6). Transmitted energy will be detected by the IR measuring device.
Transmitted energy results in a false or inaccurate target temperature. This is important
where targets are transparent to IR energy but is rarely a problem in powerplant
applications. Opaque objects do not transmit IR energy. It must be pointed out that,
although glass and many plastics are transmissive to visible light, they are opaque to IR
and will appear black in an IR camera viewfinder.
The thermographer must be aware of the effects of these apparent differences and make
provisions to eliminate their effects to arrive at true temperatures. Techniques for
accomplishing this include:
18
Common Sense Approach to Thermal Imaging, Holst, chapter 12.
21
FIST 4-13
Thermal Analysis
• Arresters
• Batteries and connections and battery chargers
• Buswork, ducts, enclosures, insulators
• Bushings
• Cables, potheads, and stress cones
19
Note that temperature is not proportional to I2R; the relationship between current and temperature is
more complex.
22
FIST 4-13
Thermal Analysis
• Circuit breakers
• Coupling capacitors
• Current transformers
• Distribution panels
• Electrical connections
• Exciters and voltage regulators
• Fuses
• Generator components, as needed
• Lighting
• Motors and lead boxes
• Potential transformers
• Switches (disconnect)
• Switchgear
• Power transformers
• Transmission lines
It is recognized that some of the equipment listed above may not be accessible while the
equipment is energized to perform an IR thermal analysis survey. In these cases, other
technology, including labels and paints that change color based on operating temperature,
should be used to monitor operating temperatures. The paint or label should be applied
while the equipment is under clearance and then periodically monitored, typically during
annual maintenance, from a safe distance. When using labels or paints, it is critical that
those individuals tracking the temperatures of this equipment understand what the
maximum temperature is or how the paint or label appears when the maximum
temperature is reached. If paints or labels are used to document the operating
temperatures of the equipment, it is essential that the paints or tapes be irreversible.
Irreversible temperature recording labels and paints are available from numerous
manufacturers and can be found easily online.
20
Adapted from Academy of Infrared Thermography.
23
FIST 4-13
Thermal Analysis
21
Common Sense Approach to Thermal Imaging, Holst, chapter 11.
22
Ports are openings with covers, and windows are openings with lens materials transparent to
IR energy.
23
NFPA 70B, section 11.17.5.3.
24
FIST 4-13
Thermal Analysis
• Air compressors
• Bearings and seals
• Brakes
• CO 2 systems
• Cooling system heat exchangers
• Engines, gasoline and diesel
• Gear boxes
• Heat exchangers
• Motor bearing housings
• Piping
• Pivot pins, hinges, and linkages
• Pumps
• Servomotors
• Valves
• Vessels and tanks
Heating, ventilating, and air Air leaks, energy loss, clogged condenser/heat
conditioning (HVAC) systems exchanger tubes, and refrigerator and air conditioner
efficiency
Mechanical drive turbines and High lube oil temperature, high bearing temperatures,
small turbine generator units drain valve blockage, steam trap blockage, faulty
stop/control valve operation, and leaking shaft seals
24
Academy of Infrared Thermography, with modifications.
25
FIST 4-13
Thermal Analysis
6.3.2.2 Modifications
Most mechanical equipment has safety shrouds or enclosures, which can limit the view of
moving parts. Solid shrouds and covers must be removed to conduct an inspection. This
poses a safety problem and may disrupt the thermal equilibrium, giving a measurement
that may not accurately represent normal operating conditions. Inspection ports similar
to those described for electrical equipment can be installed to allow the use of thermal
imaging tools, or using heat sensitive tapes and paints on nonexposed surfaces also will
allow monitoring of equipment temperatures.
6.4 Safety
As with any O&M activity, personnel safety is of utmost importance when conducting
thermal analysis surveys. Since inspections are performed while the equipment is in
operation and under load, risk always exists in the form of electrical and mechanical
energy, as well as physical hazards, when attempting the inspection.
If the inspection does include exposing the thermographer to hazardous energy sources, it
must be conducted in accordance with FIST Volume 1-1, Hazardous Energy Control
Program, including the Facility Supplement, Reclamation Safety and Health Standards
(RSHS), and arc-flash protection procedures (NFPA 70E).
26
FIST 4-13
Thermal Analysis
• Heavy and cumbersome cameras and accessories pose risk, and precautions
should be used to ensure safety. Care must be exercised when climbing with
thermographic equipment or maneuvering through tight spaces.
• The thermographer’s attention is very focused on the camera, the image, and
target being inspected, and this may make them oblivious to risks around them.
The thermographer must be protected from a variety of hazards involving loss of
footing, head and body obstructions, energized parts, and mechanical energy. It
is recommended that the thermographer be accompanied by an assistant who
helps protect the thermographer from these hazards and that the thermographer
adopt a Stop and Look practice and not be in motion when making a
measurement.
27
FIST 4-13
Thermal Analysis
7.1 Basics
Thermographers should do several things before conducting inspections. 25
• Read the instruction manuals and understand all the features of the device.
o Some software packages will allow the user to adjust range, span, and
emissivity of images from the software.
o While several variables may be changed in the software, the thermographer
should rely on the hardware to take good measurements and not rely on the
software to fix shortcomings in thermal images.
25
IR Thermography – Level I Curriculum, EPRI.
28
FIST 4-13
Thermal Analysis
Of the listed technologies, the thermal imaging camera provides the best information and
greatest accuracy. Using thermal imaging, one image contains information of thousands
of points allowing the thermographer to better monitor equipment. Inexpensive cameras
have a thermal sensitivity of less than 0.2 °C with an accuracy of 2 °C providing quality
information that is easy to trend. Typically, as the price of the camera increases, so does
the quality of the image and accuracy of the readings; but in most maintenance
applications, inexpensive cameras are adequate for capturing data. When a thermal
imaging camera is not available, a hand-held radiation thermometer can be used.
In instances when the thermographer would be exposed to arc flash or other dangerous
conditions while conducting inspections, IR viewing panes, inspection grills, or
inspection ports can be installed on exiting equipment. Typically, IR viewing panes are
used in electrical applications to create a sealed barrier between the thermographer and a
potential arc flash hazard. When thermal analysis on mechanical equipment is to be
performed, without removing shields or barriers that would typically block the view of
the thermographer, inspection grills can be used to allow safe visual access to the
equipment.
The IR windows allow a portion of the thermal radiation to be transmitted to the camera,
but it is important to compensate for the attenuation of the image through the viewing
panes. The view pane characteristics need to be investigated to determine the amount of
attenuation of the infrared signal if performing quantitative measurements. This will
include examining a known target without the IR viewing pane in place and then
comparing the measurement of the target when viewing through the viewing pane. After
the test has been performed, the transmissivity can be calculated and programmed into
the camera.
Thermography should be used whenever possible, however there are instances where it is
not possible to use the thermal imaging camera typically due to the safety of the
employee. For example, there may not be a location that an IR viewing pane can be
installed to allow employees to safely monitor the temperature of electrical equipment
while it is operating. In this case, the use of non-reversible temperature labels can
provide information regarding the operating temperature of the equipment. The labels
can be configured and purchased in several form factors providing 1–10 different
temperature readings. The labels are typically accurate to within 3 °F over a temperature
range of between 105–500 °F.
29
FIST 4-13
Thermal Analysis
The labels should be stored in a cool, dry area until they are installed. The labels use an
adhesive backing to stick to equipment. If the indicated temperature is reached, the
indicator will turn black. Employees can monitor the labels during routine inspections to
determine operating temperature of the equipment. Labels should be ordered based on
the maximum allowable operating temperature of the equipment. If a label has changed
color, the label should be replaced at the time of visual inspection, and additional
maintenance will need to be performed on the equipment based on the operating
temperature. For example, an unmanned IR camera can be set up to monitor the actual
operating temperature of the equipment if necessary. The old label can be placed in a
maintenance log book as a record of the operating temperature. Labels that have not
changed color should be replaced at least every 5 years to ensure that they are in proper
working order.
Although the distance measurement may not be critical for qualitative inspections, a
value will need to be assigned in most cameras. The distance to the target should be
measured or approximated, and the value programmed into the camera. Using a valid
approximation for distance will allow the data to be trended over the life of the
equipment. If quantitative measurements are warranted, then a more accurate value for
distance will need to be measured. The distance to the object is important because the
camera will use this value to approximate the attenuation of the IR signal based on
environmental conditions.
Camera settings are important to get an accurate inspection because some things cannot
be manipulated in the thermogram after the fact. Typically, focus, temperature range,
and distance to target cannot be manipulated in the software.
30
FIST 4-13
Thermal Analysis
data and create reports, the above parameters within the thermograms can be modified to
improve the quality of the image. Modifying these parameters allows the user to create
similar images that can be trended over time or compared to similar equipment. Refer to
the software instruction manual for additional information for your specific software
package and version.
When using hand-held radiation thermometers, it is critical to understand and take into
account the spot size for your specific equipment. Hand-held radiation thermometers
typically have a spot size ratio ranging from 6:1 to 110:1. For comparison, thermal
imaging cameras have a spot size ratio ranging from 63:1 to 889:1 with the typical spot
size being approximately 250:1. The spot size of a thermal imaging camera can be
changed depending on work to be performed by using different lenses. Figure 8 is an
example of how the actual spot size changes based on spot size ratio and the distance
from the target. Assuming the employee is 6 feet from the equipment under test, the
31
FIST 4-13
Thermal Analysis
actual spot size can vary from 0.65 inch to 12 inches. If the actual target size is 0.5 inch,
then with a spot size ratio of 110:1, the employee would need to be within 55 inches of
the target to only measure the temperature of the target. If the spot size ratio was 12:1,
then the employee would need to be within 6 inches of the target to only measure the
temperature of the target.
It is important to understand the device’s spot size ratio, sometimes called the distance-
to-spot ratio or instantaneous measurement field of view (IMFOV), which determines the
maximum distance the thermographer can be from the target and still get a good reading.
For example, a spot size ratio of 250 to 1 means that, at 250 inches (about 21 feet), the
spot size to be measured must be a minimum of 1 inch. If the thermographer cannot get
within 21 feet, a telephoto lens should be used. If the spot size or target is less than
1 inch (for example, ½ inch), the device would need to be closer than approximately
10½ feet for accurate temperature readings, or a telephoto lens would be required. For
¼ inch, the device would need to be closer still. The target should be larger than the spot
size to ensure accurate data.
7.3.2 Distance
The physical distance of the IR thermal equipment to the target is one parameter that
cannot be corrected after the image is taken and saved. The distance to the target is an
important variable in determining apparent temperatures. The distance should be
measured or estimated and entered into the camera. Using a laser distance device is
an easy way to measure the distances between the thermographer and equipment. Never
use a metal tape measure to determine the distance between the thermographer and
equipment when working near energized equipment. The discussion above on spot size
shows that the correct distance is very important to obtain quality IR images and proper
analysis. The distance from the IR thermal equipment to the target needs to be reported
32
FIST 4-13
Thermal Analysis
on the PM forms. To simplify the process, it is possible to mark the floor in front of the
equipment so the thermographer always maintains the same distance from the target,
allowing for repeatable measurements.
IFOV relates directly to spatial resolution of the instrument used. IFOV is the smallest
area that can be accurately seen at a given instance.
Figure 9 illustrates the field of view and the relation to the instantaneous field of view
when using a thermal imaging camera.
Field of view
33
FIST 4-13
Thermal Analysis
allow the user to change the emissivity, then it will only provide accurate results for
objects with the preprogrammed emissivity. Coatings may be added to equipment
included in the thermal analysis program that will change the emissivity of the object.
Some cameras and the associated analyzing software programs can adjust emissivity after
the image is saved. However, if the emissivity is set prior to imaging, quicker analysis
may be made in the field as to the severity of any anomalies found. Emissivity tables are
provided in many publications and also can be found in appendix F. These tables should
be used sparingly and with caution. The best emissivity value for a given target is
established in the field using accepted practices for determining the target’s emissivity.
See appendix E.
Generally, shiny surfaces do not emit radiation energy efficiently and can be hot while
appearing cool in an IR thermographic image or on the readout of the hand-held radiation
thermometer. Likewise, direct reflections of sun rays from shiny surfaces into the camera
can be misread as hot spots. One method of determining if the spot observed in a camera
is an anomaly or is the result of a reflection is to move around the target when possible.
Usually, when conducting outdoor inspections, if the “hot” spot goes away or diminishes
significantly, then the “hot” spot was probably a reflection. If the hot spot remains,
measure it.
Do not rely on this technique for all targets. Targets may be large or shaped so that hot
spots on the front side may be completely obscured when viewed from the back side.
The technique of moving around then will not accurately locate all anomalies. The
thermographer must be aware of unusual conditions that may influence the IR radiation
measured by the test instrument. This points out the need for training and experience. It
also emphasizes the need to have the thermographer familiar with the workings of the
equipment being inspected.
7.3.7 Calibration
Have the thermal analysis instrumentation calibrated periodically, according to the
manufacturer’s recommendations. This will help ensure the instruments are working
properly and recording accurate thermograms and/or temperatures.
34
FIST 4-13
Thermal Analysis
7.4 Environmental
7.4.1 Weather
Weather significantly affects timing and techniques of IR inspections. 27 Measures must
be taken to reduce the effects of weather, particularly where quantitative temperatures are
desired.
Currently, there are no recognized standard wind correction factors. For qualitative
measurements, wind speed of less than 15 miles per hour (mph) is probably adequate for
inspection. For quantitative measurements, wind speed must be even lower—less than
10 mph and preferably less than 5 mph. 28
Commercial devices (anemometers) are available for measuring wind, and they should be
used for outdoor inspection to determine if it is possible to quantitatively determine
temperature. Wind speed may be estimated using the following scale:
27
NFPA 70B, section 21.17.3.1.
28
Common Sense Approach to Thermal Imaging, Holst.
29
Electrical Applications, InfraMation 2004 IR Clinic.
35
FIST 4-13
Thermal Analysis
1
Beaufort Wind Scale
Wind Speed
Beaufort
Number Name mph kph m/s Description
Since there is no reliable way to correct for wind quantitatively (i.e., using correction
factors), the following guidance is given for wind conditions: 30
• Always be aware of the wind and know that the wind will affect the temperature
rise, often significantly.
Qualitative inspections are not affected in the same way by wind. As long as all
components being surveyed are affected equally by the wind—for example, three phases
of buswork—then the thermal signatures will be comparable. It is critical that electrical
30
Wind Effects on Electrical Hot Spots—Some Experimental IR Data, Madding, 2002.
36
FIST 4-13
Thermal Analysis
equipment be examined at full load. Partial loads may have a noted anomaly with no
wind; but in the presence of a wind, the anomaly may be completely obscured.
Solar loading will affect the apparent temperature, and transient solar loading (for
example, passing clouds) is even more difficult to address. Early morning, evening, or
nighttime inspections will provide more accurate IR results. However, many systems
often are not loaded as heavily at night or during off-peak hours. Extra care should be
exercised in analyzing the results because light loads may not adequately heat a problem
area.
Studies have shown that there are no simple load correction factors. However, if used
cautiously, published factors can provide some reasonable correction.
1
Load Correction
Percent Load Multiplication Factor
100 1
80 1.4
70 1.8
60 2.2
50 3
40 4.3
30 7
1
Adapted from figure 6, Important Measurements
That Support IR Surveys in Substations, Madding
et al., 2002, InfraMation.
37
FIST 4-13
Thermal Analysis
It is important to record the loading as part of the IR inspection, but care should be taken
that it is the steady state load. At least 45 minutes should expire after a load change
before performing an IR inspection.32
Another goal of load correction is to be able to calculate a safe loading level for a given
maximum allowable temperature rise. In other words, the allowable temperature rise
determines the maximum safe load.
31
Important Measurements That Support IR Surveys in Substations, Madding et al., 2002, InfraMetrics.
32
The Relationship Between Current Load and Temperature for Quasi-Steady State and Transient
Conditions, Lyon et al., 2002.
38
FIST 4-13
Thermal Analysis
Reliable testing processes and evaluations should identify all problems of concern with
no problems overlooked. There should be no errors, as in number 2 above; and no false
callouts relating to outcome, as in number 3. 34 Great care must be used when using a
hand-held radiation thermometer to ensure all problems and nonproblems are correctly
recorded. Using hand-held radiation thermometers requires considerably more time to
perform a quality thermal inspection.
1
Electrical Equipment Severity Criteria
Temperature Difference
from Reference Implication
33
Important Measurements That Support IR Surveys in Substations, Madding et al., 2002, InfraMetrics.
34
Nondestructive Testing Handbook, Third Edition, ASNT.
39
FIST 4-13
Thermal Analysis
Temperature specifications vary depending on the exact type of equipment. Even in the
same class of equipment (i.e., cables), there are various temperature ratings. Heating is
related to the square of the current; therefore, the load current will have a major impact
on the difference in temperature or ∆T. In the absence of consensus standards for ∆T, the
values in the above table will provide reasonable guidelines.35
Temperature Difference
from Ambient Implication
10–24 °C above Normal operating conditions — no action is warranted
In CARMA, it should be possible to find what was inspected, when the inspection took
place, under what conditions, who performed the inspection, thermal analysis equipment
35
NETA Maintenance Testing Specifications 2005 for Electrical Power Distribution Equipment.
36
IR Thermography – Level I Curriculum, EPRI.
40
FIST 4-13
Thermal Analysis
used, and what was found during the inspection. If equipment scheduled for inspection
was not inspected, an explanation should be recorded. Corrective work orders should be
generated when problems are found.
Records of corrective work, with feedback provided to the thermographer, will improve
the diagnostic process. Followup thermal analysis inspections should be preformed to
verify that the corrective actions or repairs were successful in eliminating the problem.
8.2.2 Reports
Reports are often required for management awareness or to document a special problem.
There is no required format for a thermal analysis report, but it should include the
following recommended topics:
• Executive Summary
• Names of Responsible Individuals
• Inspection Date and Time
• Weather Conditions
• Inspection Equipment Used
• Identity of the Equipment or Structures Inspected
• Operating/Loading Conditions of the Equipment or Structure
• Inspection Procedure
• Data Analysis Techniques
• Data
• Thermograms and Associated Visual Photos
• Results
• Conclusions
• Recommendations
• Appendices
Some software packages used to analyze thermograms also provide assistance in report
writing. An example report is shown in appendix D.
41
FIST 4-13
Thermal Analysis
Records should be kept on training and certification if required for personnel performing
IR inspections.
Records of all IR training, including formal and on-the-job, should be kept. These
records should include dates, locations, number of hours of inspection, and source and
qualifications of instruction.
42
FIST 4-13
Thermal Analysis
43
FIST 4-13
Thermal Analysis
44
FIST 4-13
Thermal Analysis
Appendix A
Glossary of Thermography Terms
Adapted from Guideline for Developing and Managing and Infrared Thermography (IR)
Program, Appendix A, Electric Power Research Institute, September 2001.
Absolute temperature scale: Temperature scales that are measured from absolute zero.
Rankine and Kelvin scales are both absolute.
Absolute zero: The point on the Kelvin and Rankine temperature scales that indicates
zero. Commonly known as the temperature at which no molecular activity occurs.
Aperture: The term used by some infrared (IR) manufacturers referring to dynamic
range, as with the Agema 400 series. Also used by pyroelectric vidicon (PEV)
imagers and some other thermal detector-based imagers to refer to the variable
opening size of the lens.
Area: A software tool that allows for measurement of an area in the radiometric image.
The area can often be defined as a box, circle, or other shape within which the
measured radiometric temperature can be displayed as the average, maximum, or
minimum.
Attenuation: Decrease in signal magnitude during energy transmission from one point
to another. This loss may be caused by absorption, reflection, scattering of energy, or
other material characteristics or may be caused by an electronic or optical device
such as an attenuator or IR windows.
Background: The source of radiation that reflects off of the target that the
thermographic instrument is viewing.
Background temperature: The temperature of the source of radiation that reflects off of
the target that the thermal analysis instrument is viewing. Most quantitative thermal
analysis instruments provide a means for correcting measurements for this reflection.
Blackbody: An object that absorbs 100 percent of the radiant energy striking it. The
absorption and emission of a blackbody are both equal to 1.
45
FIST 4-13
Thermal Analysis
British thermal unit (Btu): A unit of energy defined as the amount of heat required to
raise the temperature of a pound of air-free water by 1 degree Fahrenheit (°F) at sea
level (standard pressure). A Btu is equal to approximately 1,055.06 joules.
Calibration check: The simple process used in the field to check the performance of a
radiometric system by comparing it to a known temperature reference, often the tear
duct of a person, an ice water bath, a boiling water bath, or a calibrated blackbody
reference source.
Calorie: Commonly referred to as the amount of heat needed to raise the temperature of
1 gram of water 1 degree Celsius (°C). The modern definition is the amount energy
equal to about 4.2 joules. Symbol is c or cal.
Cavity radiator: A hole, crack, scratch, or cavity that will have a higher emissivity than
the surrounding surface because reflectivity is reduced. A cavity seven times deeper
than it is wide will have an emissivity approaching 98.
Celsius scale: A temperature scale where water boils at 100 °C and freezes at 0 °C (both
at standard pressure). Celsius scale was formerly called the Centigrade scale.
Composition: The way in which the image is composed; that is, what details are
included in the image. Composition is also called framing.
Conduction: Heat transfer from molecule to molecule or atom to atom, not requiring the
movement of the substance. This is the only way heat is transferred in solids. Heat
transfer by conduction also is present in fluids (liquids and gasses) when atoms or
molecules of different energy levels come in contact with each other. Heat always
travels from warmer to cooler.
Conductor: A material or substance that conducts heat well when compared with
materials that don't conduct well (insulators). Most metals are good heat conductors.
Conservation of Energy Law: Another name for the First Law of Thermodynamics.
For radiometry, it refers to the fact that the sum of the reflected, absorbed, and
transmitted radiation striking a surface will equal the total radiation striking the
surface (R+A+T= 1).
Convection: The type of heat transfer that takes place in a moving medium and is almost
always associated with transfer between a solid and a moving fluid, whereby energy
is transferred from higher temperature sites to lower temperature sites.
46
FIST 4-13
Thermal Analysis
Convective heat transfer coefficient: A value that represents the relative efficiency
with which an object transfers heat between a surface and a fluid. This coefficient is
often determined by experimentation, but typical values can be found in charts.
Data: The thermal information gathered by the IR system, stored either in an analog or
digital format. For qualitative thermal analysis, thermograms contain the data; where
as for quantitative thermal analysis, actual temperature values may be recorded.
Data capture rate: The rate at which the thermal data or information can be gathered by
the IR system and stored either in an analog or digital format. Data typically has
been captured at a rate of 30 or 60 frames per second; new high speed systems are
capable of capture rates over 500 Hertz (Hz).
Density: The mass of a substance per unit volume. In United States units, it is weight in
pounds per cubic foot.
Dew point temperature: The temperature at which a gas condenses into its liquid state
at a given temperature and humidity.
Diffuse reflector: Surface that reflects a portion of the incident radiation in such a
manner that the reflected radiation is equal in all directions. A mirror is not a diffuse
reflector.
Distance to object or target: The distance from the thermal radiometric system to the
target; the value may be used by the system software, especially on short wave
sensing systems, to correct for atmospheric attenuation.
Dynamic range: The amount of radiometric data in a single stored image. Data stored
as an 8-bit image has 256 thermal levels and cannot be adjusted after it is stored.
Data stored as either a 12- or 14-bit image can be adjusted after it is stored, although
only 8 bits can be viewed as an image at any one time.
Emittance: The property of a material in situ or in place describing its ability to radiate
energy in comparison to a blackbody at the same temperature. Emittance values
range from zero to one but can change with angle of view, temperature, wavelength,
and other factors.
Energy: A measure of the ability to do work. Energy can take various forms; thermal
energy is most often measured in Btu or calories.
Fahrenheit scale: A temperature scale where water boils at 212 °F and freezes at 32 °F
(both at standard pressure). Used primarily in the United States.
47
FIST 4-13
Thermal Analysis
Filter: A semitransparent covering that is installed over the lens or detector to provide
for selective transmission of various wavelengths. Filters also can provide protection
of the primary lens.
Flame filter: A filter used to restrict wavelengths to those transmitted through a flame so
that you can see through it; the exact spectral characteristics of the flame must be
defined.
Focal Plane Array (FPA): An IR imaging system that uses a matrix type detector such
as 240 x 320 pixels; can be either radiometric or qualitative.
Forced convection: Heat movement as a result from an outside force such as wind,
pumps, or fans.
Fourier's Law: The equation that describes conductive heat transfer through a material,
where energy transfer equals the product of thermal conductivity, area, and
temperature difference.
Framing: The way in which the image is composed; that is, what details are included in
the image. Also called composition.
Graybody: An object that radiates energy proportional to but less than a blackbody at
the same temperature.
Heat: Also known as thermal energy is energy transferred from regions of higher
temperature to areas of lower temperature when a material changes temperature.
Hertz (Hz): The International System of Units (SI) unit of frequency defined as 1 cycle
per second.
High temperature filter: A filter used to restrict overall radiation so that higher
temperatures can be viewed or measured.
48
FIST 4-13
Thermal Analysis
Instantaneous measurement field of view (IMFOV): The smallest detail that you can
get an accurate temperature measurement upon at a set distance. This can be used to
determine the maximum distance from a target.
Insulator, insulation: Loosely defined as a material that restricts the flow of heat,
especially in comparison with materials that conduct heat well (conductors).
Isotherm: A software tool that allows for measurement of all areas of similar apparent
temperature, or radiosity, in the radiometric image. Typically, the isotherm level and
span can be adjusted to display the information in a false color overlaying the thermal
image.
Kelvin scale: Absolute temperature scale related to the Celsius (or Centigrade) relative
scale. The kelvin unit is equal to 1 °C; 0 kelvin = -273.15 °C. The degree sign and
the word “degrees” are not used when expressing kelvin temperatures.
Kilocalories: One thousand calories. Commonly used for expressing the energy value of
foods. Symbol is Kcal or C.
Kirchhoff’s Law: For an opaque object, radiant energy absorbed equals radiant energy
emitted.
Latent energy: Energy used to make or break the bonds of the state (solid, liquid, gas)
of a material.
Latent heat of fusion: The energy used to create or break the bonds in the solid state of
a material.
Latent heat of vaporization: The energy used to create or break the bonds in the
gaseous state of a material.
Level: The term used to describe the thermal level setting of the IR imager; level
generally can be adjusted higher or lower to improve or highlight a thermal image.
Contrast with the terms span and range.
Long wave (LWIR): (Also abbreviated as LW.) Thermal radiation generally accepted
to have wavelengths between 8–15 micrometers (µm). See also “Shortwave.”
49
FIST 4-13
Thermal Analysis
Narcissus: The situation in which an IR system sees its own detector in a reflective
surface, usually dramatically affecting the temperatures being viewed or displayed;
however, this typically only occurs if the camera has a cooled sensor.
Newton's Law of Cooling: The rate of heat transfer for a cooling object is proportional
to the temperature difference between the object and its surroundings.
Palette: The arrangement of colors or gray shades used to display the thermal levels.
See “Saturation palette” and “Stepped palette.”
Phase change: The process matter goes through when it changes from one state to
another (i.e., a solid to a liquid or a liquid to a gas).
Planck’s curves: A set of curves that describe the relationships among the temperature
of a blackbody and the amount of energy it radiates as well as the distribution of the
wavelengths of that energy.
Psychometric Chart: A graph showing the relationships among dew point, relative
humidity, and air temperature.
Quasi-steady state heat flow: A thermal condition that is assumed to be steady state for
the purpose of analysis.
Radiosity: All radiation coming from a surface including that which is emitted,
reflected, or transmitted.
50
FIST 4-13
Thermal Analysis
Range: The term used with many IR thermographic systems that describes the preset
range of temperatures that can be viewed and/or measured; generally, most systems
offer several ranges allowing the user to select the proper temperature range for the
scene being viewed.
Rankine scale: Absolute temperature scale related to the Fahrenheit relative scale. The
Rankine unit is equal to 1 °F; 0 Rankine = -459.67 °F; the degree sign and the word
“degrees” is not used in expressing Rankine temperatures. It is a nonmetric scale,
which is used exclusively in the United States.
Realbody: An object that radiates less energy than a blackbody at the same temperature,
but emitted energy varies with wave length.
Reflectivity: Ratio ρ of the intensity of the total energy reflected from a surface to total
radiation on that surface; (ρ = 1 - ε - τ); for a perfect mirror, this approaches 1.0; for a
blackbody, the reflectivity is 0. Technically, reflectivity is the ratio of the intensity of
the reflected radiation to the total radiation, and reflectance is the ratio of the
reflected flux to the incident flux. In IR thermography, the two terms often are used
interchangeably.
Relative humidity: The amount of water vapor in a volume of air compared to that
which it would contain at the same temperature when saturated. For shortwave
sensing systems, this parameter is important so that atmospheric attenuation can be
accounted for.
Relative scale: A temperature scale that compares temperatures to something other than
absolute zero—typically, the boiling and freezing points of water. Fahrenheit and
Celsius scales are both relative.
Saturation palette: A display palette that clearly shows when data is saturated, or out of
the active measurement span or range, by displaying it as a different color. The
palette, thus, can be easily used to show data that is above or below a certain
threshold.
Second Law of Thermodynamics: Heat cannot flow from a cooler object to a warmer
one unless additional work or energy is added. Also stated as heat cannot be totally
changed into mechanical work.
Shortwave: Thermal radiation generally accepted to have wavelengths between 2–6 µm.
See also “Midwave.”
51
FIST 4-13
Thermal Analysis
Slit Response Function (SRF): A test used to determine spatial and measurement
resolution for IR systems.
Solar filter: A filter used to reduce the effects of the shortwave lengths emitted by the
sun, which cause solar glint or reflections.
Span: The term used to describe the adjustable band of temperatures being viewed or
measured. Contrast with the terms “Level” or “Range.”
Specific heat: The amount of heat required to raise a unit mass of a given substance by a
unit temperature.
Specular reflector: A surface that reflects radiation at an angle equal to the angle of
incidence; a “mirror” image.
Spot: A software tool that allows measurement of a spot in the radiometric image.
Usually, the temperature of this spot represents the average temperature of a very
small number of pixels.
Stack effect: The phenomenon, related to natural convection, in which air moves in
response to changes in building height.
Steady state heat flow: A hypothetical thermal condition where temperature difference
across a material or system are unchanging.
Stepped palette: A display palette with clear delineations between colors or shades of
gray as opposed to a continuous palette. When using a stepped palette, each separate
color or shade of gray represents a discrete temperature band.
System parameters: Corrections that can be made in the system software, such as
distance to object and relative humidity that improve the accuracy of the radiometric
measurement.
52
FIST 4-13
Thermal Analysis
Thermal conductivity: The symbol for thermal conductivity is ‘k.’ It is the measured
ability of a material to conduct thermal energy. It is defined as the rate at which heat
flows through a material of unit area and thickness, with a temperature gradient over
a unit of time. In United States units, it is the amount of heat that flows through
1 square foot of material that is 1 inch thick, induced by a 1 °F temperature difference
in 1 hour.
Thermal diffusivity: The rate at which heat energy moves throughout the volume of an
object. It is the ratio of the thermal conductivity to the thermal capacitance of the
material.
Thermodynamics: The study of energy; how it changes, and how it relates to the states
of matter.
Transient heat flow: A thermal condition where the heat flow through a material or
system is changing over time.
Transparent filter: A highly transparent filter used to protect the primary lens from
damage.
Wien’s Displacement Law: The law that describes the relationship between the
temperature of a blackbody and the peak wavelength of radiation it gives off. At
higher temperatures, there is a displacement to shorter wave lengths. The law is
stated as b/T = µm where b is Wien’s Constant (5,215.6 μm • R), T is the blackbody
absolute temperature (R), and µm is the peak wavelength. SI value is 2,897 μm • K.
8-bit system: An IR system capable of storing data that can be divided into 256 thermal
levels.
12-bit system: An IR system capable of storing data that can be divided into
4,096 thermal levels.
14-bit system: An IR system capable of storing data that can be divided into
16,384 thermal levels.
53
FIST 4-13
Thermal Analysis
Appendix B
Helpful Operations Hints
Below is a list of helpful hints that will be useful to perform a quality thermal imaging
survey.
1. Circuit loading must be taken into account when inspecting electrical equipment.
Comparative inspections should be done when the load is similar to the last
inspection to make a fair comparison. See Section 8, “Evaluating Results,” for
more information.
2. Inspections should take place during periods of maximum possible loading but
not less than 40 percent of rated load of the equipment being inspected.37 A
10-percent temperature rise may be negligible near full load but may be
significant on lightly loaded circuits.
4. A front-surface mirror (i.e., one that has the reflective surface on the front surface
of the glass) can be used to inspect the backside of a component. An everyday
mirror with the reflective surface on the back of the glass cannot be used for IR
inspection because it has internal reflections. 38
5. It is useful to compare one phase of a circuit to the other phases because: 1) the
emissivities are similar, 2) heat generation and dissipation effects should be
similar, 3) all phases are the same distance from the IR temperature device, and
4) all phases are (hopefully) equally loaded.
7. Surge arresters and bushings are best inspected at night because reflections
associated with daylight will be reduced.
9. Large vertical motors usually show several vertical hot “stripes” on the side of
the casing, while horizontal motors show hot spots on the middle of the casing in
an even pattern.
37
National Fire Protection Association 70B, section 21.17.5.2.
38
Common Sense Approach to Thermal Imaging, Holst, chapter 11.
55
FIST 4-13
Thermal Analysis
Remember, heating patterns on an enclosure are most likely the result of indirect
heating because the heat source is much hotter than the temperatures recorded on
the enclosure surface.
11. Most mechanical components are painted, and this affects the emissivity. Flat
paint emissivity values are typically in the 0.90 range. Glossy paint emissivity is
usually high, but it may produce different results between midwave infrared
(MWIR) and long-wave infrared (LWIR) equipment. Metallic paints have
emissivities as low as 0.3 or less. 39
12. The simple act of opening an enclosure door or removing a protective covering
can quickly change the temperature of a component, thus giving a reading not
typical of normal operating conditions.
Keep a copy of this checklist with the camera to ensure that the necessary steps have been
completed and that all hardware is with the camera.
39
Mechanical Applications, InfraMation 2004 IR Clinic.
56
FIST 4-13
Thermal Analysis
• Aim the instrument as close as possible to perpendicular with the target surface.
(Angles of incidence exceeding 45 degrees can cause errors.)
• Check for thermal reflections from other point sources off the target surface.
• Keep instrument as far away as possible from very hot objects and energized
equipment.
• Keep accurate records and trend data.
57
FIST 4-13
Thermal Analysis
Appendix C
Hardware and Software Features
When selecting, specifying, and procuring an infrared (IR) imaging system, many factors
must be considered to arrive at the hardware and software that is appropriate for use. The
following has been adapted from criteria identified by IRINFO.ORG
(http://www.irinfo.org) and is based on the Bureau of Reclamation’s experience to date.
It may be used to compare imaging systems.
Comparison of Specifications
Imager 1 Imager 2
OBJECTIVE SPECIFICATIONS
Environment
Operating Temperature Limits
Imaging
Spectral Response
Visual Field of View
Detector Type
Detector Size (Resolution)
Cooling Type
Focus
Minimum Focus Distance
Imager Frame Rate
Visual Camera Resolution
Image Display
Display Type
Color Palettes
Measurement
Measurement Range
Thermal Sensitivity
Emissivity Correction
Spot Measurement Size
Temperature Measure Tools
Reflected Temperature Comparison
Accuracy
59
FIST 4-13
Thermal Analysis
Data Storage
Storage Media (Internal/External/Both)
Storage Media Type (SD, SDHC, CF, etc.)
File Format
Number of Images Stored
Voice Recording
Text Recording
Data Transfer
IEEE 1394 (FireWire)
USB
S-Video
RCA Jack
Others
Power Source
External Power
Battery Type/Run Time
Other Accessories
BlueTooth®
Laser Pointer
Lens Options
Filter Options
Data Interface
Video Format
Video Output
Physical
Dimensions
Weight with Battery
Shock Withstand
Encapsulation
Vibration
60
FIST 4-13
Thermal Analysis
SUBJECTIVE SPECIFICATIONS
OTHER CONSIDERATIONS
Quality of documentation
Equipment Cost
61
FIST 4-13
Thermal Analysis
Appendix D
Sample IR Report
63
FIST 4-13
Thermal Analysis
64
FIST 4-13
Thermal Analysis
65
FIST 4-13
Thermal Analysis
66
FIST 4-13
Thermal Analysis
67
FIST 4-13
Thermal Analysis
Appendix E
Methods of Determining or Enhancing the
Emittance of a Target
Thermographers calculate or determine the emissivity of different targets in a number of
ways. Accurate emissivity values are needed if quantitative temperature measurements
are required. If possible, emissivity enhancement coatings can be applied to target areas.
Coatings, usually in the form of paint, have known emissivities. These coatings are
usually applied to shiny or reflective surfaces to provide a higher known emissivity and
to provide accurate temperature measurements. Most of the coatings today have
emissivities at or near 0.95.
Black electrical tape (3M Scotch 33™) can be used to determine the emissivity of targets.
This tape has been measured and is used as a reference by many thermographers.
Emissivity of the tape is 0.95. This technique requires the tape to be placed on the target
material prior to energizing, loading, or heating the equipment to be monitored.
For the following technique to work properly, the measured target or component
temperature must be raised 20 degrees Fahrenheit (°F) or higher above ambient
temperature. This technique will not work if the target is at ambient temperature.
Place a ½- to 1-inch square of the electrical tape on the target. Measure the background
temperature by setting the emissivity to 1.0 in the infrared (IR) camera and pointing the
camera away from the target. In most cases, defusing the focus will give an average
background temperature. The background temperature also can be measured by using a
piece of cardboard with an aluminum foil cover set next to the target. Again, set the
camera emissivity to 1.0 and the camera slightly out of focus. Measure the temperature
at the center of the cardboard/aluminum foil.
The background temperature should be entered into the camera if the camera being used
allows this. The correct distance to the target should be added to the camera settings.
The thermographer needs to recognize the spot size and ensure that the target size is
adequate and is in focus. Set the camera to an emissivity of 0.95. Once the target is at
temperature, measure the temperature of the taped (or emissivity enhanced) area. Note
the temperature. Move the measuring spot just off of the tape and on to the surface for
which emissivity is to be determined. Adjust the emissivity in the camera, until the
temperature of this spot matches the temperature measured on the tape. Once the
temperatures match, read and record the emissivity. This emissivity now can be used in
the future for this particular equipment and perhaps similar equipment.
Other techniques for increasing emissivity of targets include using the geometry of the
components. For instance, the intersection where a lug or nut meets the connection
surface will form a small cavity that, when viewed in the IR camera, will have an
increased emissivity. All types of cavities will tend to have higher emissivities and
should be used whenever possible.
69
FIST 4-13
Thermal Analysis
Appendix F
Material Emissivity Table
Material Detail Temp °F (°C) Emissivity
Metals
Alloys
20-Ni, 24-CR, 55-FE, Oxidized 392 (200) 0.90
20-Ni, 24-CR, 55-FE, Oxidized 932 (500) 0.97
60-Ni, 12-CR, 28-FE, Oxidized 518 (270) 0.89
60-Ni, 12-CR, 28-FE, Oxidized 1,040 (560) 0.82
80-Ni, 20-CR, Oxidized 212 (100) 0.87
80-Ni, 20-CR, Oxidized 1,112 (600) 0.87
80-Ni, 20-CR, Oxidized 2,372 (1,300) 0.89
Aluminum
Unoxidized 77 (25) 0.02
Unoxidized 212 (100) 0.03
Unoxidized 932 (500) 0.06
Oxidized 390 (199) 0.11
Oxidized 1,110 (599) 0.19
Oxidized at 599 °C (1,110 °F) 390 (199) 0.11
Oxidized at 599 °C (1,110 °F) 1,110 (599) 0.19
Heavily Oxidized 200 (93) 0.20
Heavily Oxidized 940 (504) 0.31
Highly Polished 212 (100) 0.09
Roughly Polished 212 (100) 0.18
Commercial Sheet 212 (100) 0.09
Highly Polished Plate 440 (227) 0.04
Highly Polished Plate 1,070 (577) 0.06
Bright Rolled Plate 338 (170) 0.04
Bright Rolled Plate 932 (500) 0.05
Alloy A3003, Oxidized 600 (316) 0.40
Alloy A3003, Oxidized 900 (482) 0.40
Alloy 1100-0 200–800 (93–427) 0.05
Alloy 24ST 75 (24) 0.09
Alloy 24ST, Polished 75 (24) 0.09
Alloy 75ST 75 (24) 0.11
Alloy 75ST, Polished 75 (24) 0.08
71
FIST 4-13
Thermal Analysis
72
FIST 4-13
Thermal Analysis
73
FIST 4-13
Thermal Analysis
74
FIST 4-13
Thermal Analysis
75
FIST 4-13
Thermal Analysis
76
FIST 4-13
Thermal Analysis
77
FIST 4-13
Thermal Analysis
78
FIST 4-13
Thermal Analysis
79
FIST 4-13
Thermal Analysis
80
FIST 4-13
Thermal Analysis
81
FIST 4-13
Thermal Analysis
82
FIST 4-13
Thermal Analysis
83