CURRENT TRANSFORMER(CT)

Power Swing Technical 220KV SUBSTATION KEMAR, HIRIYADKA


DATE:07/03/2017
Services
CLINT:M/s, KPTCL Page |1
PROJECT: Renovation And Up-Gradation Of Protection System In 220 KV SS

Name Plate Details


Highest System Voltage 123 kV Insulation Level 230 / 550 kV
RATED S.T.C 31.5 KA for 1 sec Rated frequency 50 Hz
Nominal System Voltage 110 kV Core 1 Core 2 Core 3
RATIO Primary (Amp) 400 - 200 400 - 200 400 - 200
Secondary (Amp) 1 1 1
Secondary Terminals 1s1-1s2-1s3 2s1-2s2-2s3 3s1-3s2-3s3
Rated Burden - 10 VA 30 VA
Accuracy Class PS 0.2 5P
ALF / ISF @ Lower Tap - <5 20
Min knee point voltage @ 600 / 1A 800 V - -
Max Rct at 75 deg c @ 600 / 1A 4Ω - -
Max lext at Vk / 4 30 mA - -
Purpose Dist/Diff protec Metering Back up protec
OC 6635 /1/7/16
Sl no OC 6635 /1/8/16
OC 6635 /1/9/16
Make Mehru Electrical And Mechanical Engineers (P) Ltd.
Mf year 2016

Ratio Primary Secondary condition


condition Core 1 Core 2 Core 3
200 / 1A P1 – P2 1s1-1s2 1s1-1s2 1s1-1s2
400 / 1A P1 – P2 1s1-1s3 1s1-1s3 1s1-1s3

Insulation Resistance Test: (All Values in GΩ)


Reference Applied Measured values
voltage OC 6635 /1/7/16 OC 6635 /1/8/16 OC 6635 /1/9/16
Primary - earth 889 GΩ 973 GΩ 832 GΩ
Primary – core1 5000 V 571 GΩ 675 GΩ 483 GΩ
Primary – core2 488 GΩ 619 GΩ 579 GΩ
Primary – core3 748 GΩ 691 GΩ 499 GΩ

Test performed by: Power Swing Witnessed by: SRES Witnessed by: KPTCL
Name: Name: Name:
Signature &: Signature &: Signature &:
Date Date Date
CURRENT TRANSFORMER(CT)

Power Swing Technical 220KV SUBSTATION KEMAR, HIRIYADKA


DATE:07/03/2017
Services
CLINT:M/s, KPTCL Page |2
PROJECT: Renovation And Up-Gradation Of Protection System In 220 KV SS

Core 1 – Earth >1 GΩ >1 GΩ >1 GΩ


Core 2 – Earth >1 GΩ >1 GΩ >1 GΩ
Core 3 – Earth >1 GΩ >1 GΩ >1 GΩ
Core 1 – Core 2 500 V >1 GΩ >1 GΩ >1 GΩ
Core 1 – Core 3 >1 GΩ >1 GΩ >1 GΩ
Core 2 – Core 3 >1 GΩ >1 GΩ >1 GΩ

Winding Resistance Test: (All Values in Ω)


Reference Measured values
OC 6635 /1/7/16 OC 6635 /1/8/16 OC 6635 /1/9/16
1s1 - 1s2 2.5 Ω 2.6 Ω 2.4 Ω
1s1 - 1s3 3.5 Ω 3.8 Ω 3.5 Ω
2s1 - 2s2 2.3 Ω 2.3 Ω 2.2 Ω
2s1 - 2s3 3.3 Ω 3.5 Ω 3.4 Ω
3s1 - 3s2 4.1 Ω 4.2 Ω 4.1 Ω
3s1 - 3s3 6.6 Ω 6.7 Ω 6.6 Ω

Polarity Test:
Reference Forward
OC 6635 /1/7/16 OC 6635 /1/8/16 OC 6635 /1/9/16
1s1 - 1s3 OK OK OK
2s1 - 2s3 OK OK OK
3s1 - 3s3 OK OK OK

Ratio Test:
Applied Current: 200 A Measured Sec. in values A
Sl no C1 C2 C3
OC 6635 /1/7/16 1.009 1.010 1.010
OC 6635 /1/8/16 1.000 1.000 1.002
OC 6635 /1/9/16 1.004 1.004 1.005

Test performed by: Power Swing Witnessed by: SRES Witnessed by: KPTCL
Name: Name: Name:
Signature &: Signature &: Signature &:
Date Date Date
CURRENT TRANSFORMER(CT)

Power Swing Technical 220KV SUBSTATION KEMAR, HIRIYADKA


DATE:07/03/2017
Services
CLINT:M/s, KPTCL Page |3
PROJECT: Renovation And Up-Gradation Of Protection System In 220 KV SS

Applied Current: 400 A Measured Sec. in values A


Sl no C1 C2 C3
OC 6635 /1/7/16 1.004 1.004 1.006
OC 6635 /1/8/16 1.001 1.001 1.001
OC 6635 /1/9/16 0.999 1.001 1.000

Knee Point Voltage:


Applied Sec Measured Leakage Current(mA)
Voltage(V) OC 6635 /1/7/16 OC 6635 /1/8/16 OC 6635 /1/9/16
C1 C2 C3
80 2.5 2.7 2.8
160 3.6 4.0 4.9
240 4.6 5.1 5.8
320 5.8 6.1 6.6
400 6.9 7.7 8.4
480 7.3 8.0 9.7
560 8.3 9.1 10.9
640 9.3 10.4 12.1
720 10.3 12.0 14.3
800 12.3 14.1 17.4
880 14.6 17.4 21.9
960 18.4 22.2 28.2
1040 25.4 31.7 35.6
1120 42.7 47.9 55.6

Capacitance and Tan- Delta Test: (Using Mode UST)


Sl no OC 6635 /1/7/16 OC 6635 /1/8/16 OC 6635 /1/9/16
kV 2 5 10 2 5 10 2 5 10
Hz 50.00 50.00 50.00 50.00 50.00 50.00 50.00 50.00 50.00
pF 365.90 365.90 365.91 372.74 372.75 372.84 381.21 381.20 381.21
Tan ᵟ% 0.1523 0.1526 0.1527 0.1348 0.1348 0.1346 0.1548 0.1549 0.1547
mA 239.1µ 595.4µ 1.1839 235.3µ 590.2µ 1.1567 239.7µ 599.8µ 1.1439

Test performed by: Power Swing Witnessed by: SRES Witnessed by: KPTCL
Name: Name: Name:
Signature &: Signature &: Signature &:
Date Date Date