Motor Savings Analysis - Replace Existing Page: 1

INPUTS
Motor Characteristics
Existing Motor Energy-Efficient Motor
Description: Old Standard Efficiency GE - Value Line ODP
- NEMA Design B
Size (HP) / Speed (RPM) (Poles): 30,0 HP 1200 RPM 30,0 HP 1200 RPM
Enclosure / Voltage (Volts): ODP 460 Volts ODP 460 Volts
Load (%): 90,3 90,3
Efficiency (%): 88,8 92,6
Full load RPM: 1175 RPM 0 RPM
Centrifugal load: False
Old Motor Efficiency Loss (%): 0

Costs/Use
Existing Motor Energy-Efficient Utility Data
Motor
Dealer discount (%): N/A 0 Energy price (COP/kWh): 619,890015
Purchase price (COP): N/A 6.223.230 Demand charge (COP/kW/mo.): 8
Installation cost (COP): N/A 526.581 Power factor (%): N/A
Motor rebate (COP): N/A 0 Rebate program: <None>
Peak months: 12 12 Simple payback criteria, yrs: 0
Hours use/yr: 6000 6000
RESULTS - SAVINGS
Existing Motor Energy-Efficient Motor Energy Savings
Differential cost (COP): 6.749.811 Energy (kWh/yr): 5.650
Energy use (kWh/yr): 136548 130898 Demand (kW): 0,9
Energy cost (COP/yr): 84.644.896 81.142.608 Energy savings (COP/yr): 3.502.290
Demand charge (COP/yr): 2.185 2.094 Demand savings (COP/yr): 90
Greenhouse Gas Emissions Reduction Total savings (COP/yr): 3.502.380
State: tonnes CO2/yr:: 0,00 Simple payback (yrs): 1,9

03/28/2019 copyright 2002 WSU