Sie sind auf Seite 1von 1

1

en Function
IH: 15365 - 16364 b Function: the time switch automatically opens and closes a circuit according to a
daily program established by the position of captive segments on a moving dial.

1 Contact status 5 Fixed mark


display switch
24 h 87
6543
6 Scale in hours

21
1C 2 Segment support 50

12 11 10 9
0

24 23 22 21
ARM and SRM moving dial

0
3
14 1
20 1
18 17 16 15 9
auto
3 Inscription perm

in minutes

4 Manual switch for


forcing ON or OFF

2
Applications

b For loads less than 3500 W. b For loads exceeding 3500 W, use in conjunction with a

3
contactor.

Programming
b Program the status change order of the output
contact by pulling out or pushing down the blue
captive segments on the moving dial:
v pushed segments: load on, contact between 6543
87
21

50
terminals 2 and 3,
3 12 11 10 9

0
24 23 22 21

v pulled segments: load off, contact between


14 1 0

terminals 2 and 1.
20 1
9 18 17 16 15
b Setting limits: gap between two segments = 30 min.

b In the above example, the jumpers are pushed


in from 9 a.m. to 10 p.m.: the load is on during this
period.

456
Setting Selecting ON, Characteristics
1558892BE-01/2009

b To set the hour, turn OFF or b Supply voltage: 230 V ± 10 %


the graduated dial 6 in b Frequency: 50-60 Hz / 50 Hz (16364)
the direction shown to automatic mode b Output contact rating: 16 A/250 Va cosφ = 1; 4 A/250 Va cosφ = 0.6
bring the figure for the b Consumption: 2.5 VA
b Using switches 1
required hour opposite b Quartz motion
and 4 in conjunction b Operating reserve: 150 hours for ref. 15365
the fixed mark 5 . with one another, the
b To set the minutes, do b 48 possible switchings in the day
switch can be set for b Minimum time between 2 switchings: 30 minutes
the same with dial 3 . automatic operation, b Type of setting: 1 B STU according to EN 60730
b Check proper forced on, or forced off: b Operating temperature: -10°C to +50°C
operation of switching by v switch on "perm": b Maximum capacity of connection terminals: 2 x 2,5 mm2
rotating the switch 1 . permanent on or off b Overall dimensions: 6 modules of 9 mm.
Réalisation : SEDOC 04 76 18 04 11

b The quartz motion (using switch 1 ), Acceptable power


(ARM) starts after a few v switch on "auto": incandescent lamp 230 V 1100 W
minutes preset program. halogen lamp 230 V 1100 W
non compensated fluorescent tube/serial compensated 15 x 40 W - 10 x 58 W - 6 x 100 W
fluorescent tube with conventional ballast
parallel compensated fluorescent tube with 2 x 40 W (4.7 μF) - 1 x 58 W (7.0 μF)
conventional ballast
dual-mounted fluorescent tube with conventional ballast 5 x (2 x 58 W) - 3 x (2 x 100 W)
parallel compensated sodium vapour lamp relay by contactor CT
parallel compensated HQL fluorescent balloon relay by contactor CT