Sie sind auf Seite 1von 24

AL-ANDALOSIA FOR AIR OUTLETS

CIRCULAR CEILING DIFFUSER & JET DIFFUSER:-


Circular ceiling diffuser and jet diffuser are always considered as a heavy duty air distribution
devices having a wide range of applications in heating , air conditioning and ventilation
systems. Circular ceiling diffuser provide an unusually uniform horizontal airflow patterns,
while jet diffuser provide an efficient spot projection for air projection for air direction and
orientation.

With uniformly assembled oncentric rings, this does not only produce optimum performance,
but also assure uniformity of appearance when different sizes are used in the same area.
Circular ceiling diffuser and jet diffuser are always suitable for most of the HVAC applications,
but they are especially well suited to factories , warehouses, convention halls, coliseums,
shopping malls and other applications where ceiling are high and conditions are variable.

TYPE CCD:
This type is suitable for flush installation in ceiling; they can be used for supply or extract
air.the design consists of a conical core followed by continuously concentric rings to adjust the
air flow pattern. This design feature will assure little turbulance in the air stream and allow for
the distribution of the smudge pattern . it also provides excellent air distribution efficiency.
MATERIAL &FINISH:-
The diffuser is fabricated from aluminum. Diffusers are available in white polyester powder
coating finish or any other RAL standard colour upon customer request.

2
AL-ANDALOSIA FOR AIR OUTLETS

DEFINITIONS:-

• THROW: is the horizontal distance between the center of the diffuser and the
point at which the terminal velocity of the air stream occurs.
(tabulated values of throw in the table represent the minimum and
the maximum throw in feet).
• MINIMUM THROW: is the distance between the center of the diffuser and the
point at which the terminal velocity is 200 (corresponding to a residual velocity of 75
FPM) .
• MAXIMUM THROW : is the distance between the center of the diffuser and the
point at Which the terminal velocity is 100 FPM
(corresponding to a
residual velocity of 35 FPM). An average value of throw
can be taken for general applications such as resturants, offices, apartments etc. and results
in a residual velocityof 55 FPM .

CFM: : the air flow rate in cubic feet per minute .

• NECK VELOCITY : is the air stream velocity measured in feet per minute (FPM).

• TOTAL PRESSURE: is the sum of static pressure and velocity pressure gives in
inches
water guage.
• NC level(Db): is the noise criteria based on 10 Db room attenuation and
measured
at 10 FT away from diffuser face ( deduce 3 Db for 20 FT
distance
and 7 Db for 30 FT distance).

• The sound caused by an air outlets is directly proportional to the velocity of air passing
through it(see table 1).

NECK VELOCITY(FPM) SOUND LEVEL- NC


300-600 Less than 20
700-600 Less than 30
900-700 Less than 35
1100-900 Less than 40
1600-1100 Less than 40
Table 1
This table gives the approximate noise level (NC-Value) of a diffuser as a function of the
diffuser neck velocity.

3
AL-ANDALOSIA FOR AIR OUTLETS

RECOMMENDED NOISE CRITERIA FOR ROOMS

TYPE OF AREA NC TYPE OF AREA NC


LEVEL(Db) LEVEL(Db)
AUDITORIUMS SPORT ACTIVITYIES INDOOR
Concert and opera Halls. Studios for sound Coliseums 30-40
Reproduction 20-25 Bowling alleys, gumnasiums 35-45
Legitimate theaters.Multi- purpose Halls 25-30 Swimming pools 40-55
Movie Theaters. Lecture halls. Planetoruim TRANPORTATION
TV audience stadios 30-35 Ticket Sales Offices 30-40
Lobbies. 35-45 Lounges, waiting rooms 35-50
CHURCHES & SCHOOLS HOTELS
Sanctuaries 20-30 Individual rooms or suits , bell rooms, 30-40
Libraries , school and classrooms 30-40 banquet rooms .
Laboratories 35-45 Halls & corridors lobbies 35-45
Recreation Halls, corridors and Halls 35-50 Grages, kitchens and laundries 40-50
Kitchens 40-50 MANUFACTERING AREAS
HOSPITAL AND CLINICS Foreman's office 40-50
Private rooms 25-35 Assembly lines , light Machinery 55-75
Operating rooms. Wards 30-40 Foundries, heavy Machinery 55-75
Halls, Corridors, laboratories, lobbies and waiting 35-45
rooms 40-50 OFFICES
Washrooms and toilets Board room 20-30
RESTURANTS & LOUNGES 35-45 Conference Room 25-35
Restaurants 35-50 Tabulation and computation 40-60
Cocktail lounges 35-50 BUBLIC BUILDINGS
Night clubs 40-50 Bublic libraries , Meseums 30-40
Cafeterias Post offices, general banking areas, 35-45
SRORES DETAIL 35-45 lobbies
Clothing Stores , department stories(upper floors) 40-50
Department Stories (main floor)
supermarkets

Table 2 Recommended range of noise criteria from ASHREA GUIDE

Table 3 Gives the listed sizes available with the amount of CFM range for each size.
Listed size CFM range
6" dia. 60-315
8" dia. 105-560
10" dia. 165-870
12" dia. 225-1255
14" dia. 320-1710
16" dia. 420-2240
18" dia. 530-2830
20" dia. 660-3500
24" dia. 940-4950

4
AL-ANDALOSIA FOR AIR OUTLETS
SELECTION PROCEDURE
In general the selection of diffuser starts from a given quantity of air to be handled by the
diffuser.
Limitations and restrictions on sound level and pressure drop are other factors that one has to
consider.
1. knowing the ceiling height , table 4 , will read the maximum permissible CFM that could
be handled by the diffuser and hence the total CFM can be divided over the most
reasonable number of diffusers which would best fit the application.
Remember that round diffuser has uniform pattern and it is always best to center it in a
square
area .
Total CFM
No. of diffusers = ‫ــــــــــــــــــــــــــــــــــــــــــــــــــــــــ‬
Max. permissible CFM

CEILING MAXIMUM MAXIMUM


HEIGHT TEMP. CFM PER
(FT) DIFFERENTIAL DIFFUSER
8 20º F 800
10 26º F 2000
12 30º F 3000
14 30º F 5000
16 30º F 6400
Table 4

2. determine from table the maximum allowable neck velocity which keeps the
application as silent as required . recommended Sound levels could be read from
table

Remember that:
CFM = AK x Average velocity.

3. Refer to the selection table ( Basic performance Data) on next page to determine the
size of the diffuser which would best fit your application. The table also reads area
factor AK, velocity pressure , total pressure , and throw.

5
AL-ANDALOSIA FOR AIR OUTLETS

SUPPLY AIR ROUND CEILING DIFFUSER


PERFORMANCE DATA
Neck Velocity 300 400 500 600 700 800 1000 1200 1400 1600
Neck Neck Area (FPM)
Size Area facto
(inches (FT²) r
) (FT²) Velocity Pressure 0.007 0.01 0.016 0.023 0.031 0.041 0.064 0.091 0.123 0.161
(inches W.G) 1
Air flowrate(CFM) 60 80 100 120 135 155 195 235 275 315
6" 0.196 0.13 Total pressure 0.025 0.04 0.061 0.082 0.106 0.132 0.201 0.282 0.380 0.480
drop 1
Throw (FT) 3-5 3-6 3-6 4-6 4-6 4-6 5-7 5-7 6-8 7-10
NC <20 <20 <20 <20 <20 25 30 35 39 45
Air flowrate(CFM) 105 140 175 210 245 280 350 420 490 560
8" 0.349 0.22 Total pressure 0.021 0.03 0.052 0.071 0.100 0.122 0.183 0.271 0.370 0.480
drop 2
Throw (FT) 4-6 4-6 5-7 6-8 6-8 6-8 7-10 7-11 8-13 9-14
NC <20 <20 <20 20 25 29 33 38 42 46
Air flowrate(CFM) 165 220 275 325 380 435 545 655 765 870
10" 0.545 0.25 Total pressure 0.040 0.06 0.092 0.122 0.181 0.242 0.361 0.500 0.710 0.950
drop 1
Throw (FT) 4-6 6-9 7-10 7-10 7-11 8-13 9-14 10-16 12-18 15-
22
NC <20 <20 <20 21 26 30 34 39 43 47
Air flowrate(CFM) 225 315 395 470 550 630 785 940 1100 1255
12" 0.785 0.38 Total pressure 0.026 0.04 0.072 0.101 0.152 0.201 0.313 0.490 0.670 0.870
drop 1
Throw (FT) 6-8 7-10 7-11 7-11 8-13 9-14 10-16 14-21 15-23 19-
27
NC <20 <20 <20 32 28 32 36 41 45 48
Air flowrate(CFM) 320 430 535 640 750 855 1070 1285 1500 1710
1.07 0.50 Total pressure .034 0.05 0.080 0.112 0.156 0.201 0.313 0.460 0.600 0.80
14" drop 1
Throw (FT) 6-8 8-13 9-15 10-16 11-17 12-18 15-23 19-2 19-27 21-
31
NC <20 <20 <20 24 29 33 37 42 46 49
Air flowrate(CFM) 420 560 700 840 980 1120 1400 1680 1960 2240
16" 1.40 0.59 Total pressure 0.043 0.07 0.106 0.140 0.202 0.262 0.413 0.593 0.800 0.980
drop 5
Throw (FT) 7-11 9-14 9-15 11-17 12-18 15-23 16-25 19-27 21-31 25-
36
NC <20 <20 20 25 30 34 38 43 47 50
Air flowrate(CFM) 530 710 885 1060 1240 1415 1770 2125 2480 2830
18" 1.77 0.75 Total pressure 0.033 0.05 0.082 0.113 0.166 0.220 0.350 0.530 0.710 0.950
drop 2
Throw (FT) 8-13 9-14 10-16 12-18 14-12 17-24 19-27 21-31 22-33 26-
38
NC <20 <20 21 26 31 35 39 44 48 51
Air flowrate(CFM) 660 850 1100 1300 1530 1750 2150 2650 3050 3500
2.18 0.96 Total pressure 0.040 0.06 0.092 0.131 0.182 0.251 0.450 0.640 0.820 0.930
20" drop 5
Throw (FT) 8-14 11- 14-20 17-21 19-25 22-28 29-34 34-40 41-47 43-
16 50
NC <20 <20 21 27 32 36 40 45 49 52
Air flowrate(CFM) 940 1250 1570 1850 2200 2500 3130 3850 4320 4950
24" 3.14 1.23 Total pressure 0.045 0.07 0.105 0.135 0.195 0.265 0.460 0.690 0.790 0.960
drop 0
Throw (FT) 10-15 14- 17-23 20-26 24-30 27-34 35-41 43-50 46-52 51-
20 58
NC <20 <20 22 28 33 37 41 46 50 53

6
AL-ANDALOSIA FOR AIR OUTLETS

RETURN AIR ROUND CEILING DIFFUSER

PERFORMANCE DATA

Neck Velocity 300 400 500 600 700 800 1000 1200 1400 1600
Neck Neck (FPM)
Size Area
(inches) (FT²) Velocity Pressure 0.007 0.01 0.016 0.023 0.031 0.041 0.064 0.091 0.123 0.161
(inches W.G) 1
Air flowrate(CFM) 60 80 100 120 135 155 195 235 275 315
6" 0.196 Total pressure 0.029 0.04 0.076 0.108 0.146 0.18 0.294 0.421 0.569 0.749
drop 8
NC <20 <20 <20 <20 21 26 32 37 41 46
Air flowrate(CFM) 105 140 175 210 245 280 350 420 490 560
8" 0.349 Total pressure 0.020 0.03 0.053 0.077 0.100 0.123 0.207 0.293 0.394 0.519
drop 4
NC <20 <20 <20 21 26 30 34 39 43 47
Air flowrate(CFM) 165 220 275 325 380 435 545 655 765 870
10" 0.545 Total pressure 0101 0.03 0.050 0.071 0.096 0.120 0.196 0.281 0.379 0.477
drop 9 3
NC <20 <20 <20 22 27 31 36 41 45 48
Air flowrate(CFM) 225 315 395 470 550 630 785 940 1100 1255
12" 0.785 Total pressure 0.018 0.02 0.045 0.064 0.086 0.112 0.176 0.249 0.339 0.443
drop 9
NC <20 <20 <20 23 29 33 37 42 46 49
Air flowrate(CFM) 320 430 535 640 750 855 1070 1285 1500 1710
1.07 Total pressure 0.017 0.02 0.042 0.061 0.083 0.108 0.170 0.242 0.328 0.430
14" drop 8
NC <20 <20 <20 25 30 34 38 43 47 50
Air flowrate(CFM) 420 560 700 840 980 1120 1400 1680 1960 2240
16" 1.40 Total pressure 0.016 0.02 0.041 0.059 0.079 0.103 0.162 0.231 0.314 0.411
drop 5
NC <20 <20 21 26 31 35 39 44 48 51
Air flowrate(CFM) 530 710 885 1060 1240 1415 1770 2125 2480 2830
18" 1.77 Total pressure 0.015 0.02 0.040 0.057 0.077 0.099 0.156 0.224 0.303 0.397
drop 5
NC <20 <20 22 27 32 36 40 45 49 52
Air flowrate(CFM) 660 850 1100 1300 1530 1750 2150 2650 3050 3500
2.18 Total pressure 0.014 0.02 0.036 0.052 0.071 0.091 0.143 0.205 0.277 0.363
20" drop 4
NC <20 <20 21 28 33 37 41 46 50 53
Air flowrate(CFM) 940 1250 1570 1850 2200 2500 3130 3850 4320 4950
24" 3.14 Total pressure 0.013 0.02 0.031 0.046 0.064 0.082 0.130 0.185 0.246 0.326
drop 2
NC <20 <20 23 29 34 38 42 47 51 55

7
AL-ANDALOSIA FOR AIR OUTLETS

CIRCULAR CEILING DIFFUSER

Selection for CCD- supply air

size Vmax Vmin A eff C C1 C2 LWA max LWA min LWNC max LWNC min
m³/hr m³/hr m² mm mm mm dB (A) dB (A) NC NC
6" 290 70 .009 146 234 298 40 < 20 31 <20
8" 430 110 .016 197 285 349 40 <20 33 <20
10" 650 180 .026 248 336 400 40 <20 34 <20
12" 830 290 .038 299 387 451 40 <20 35 <20
14" 1080 395 .054 349 437 501 40 <20 35 <20
16" 1295 505 .073 400 488 552 40 <20 36 <20
18" 1585 650 .096 451 539 603 40 <20 37 <20
20" 1800 790 .115 502 590 654 40 <20 37 <20

The table gives a guide for selection diffuser sizes.


To determine the max. Volume rate Vmax it has been assumed that the power level should
always equal 40 db (A), if higher sound level are permitted the max. Volume flow rate can be
increased.
For the recommended min. volume flow rate Vmin the effective discharge velocity Veff must not
be less than 2m/s.

How to determine the volume flow rate

V= Veff X 3600 x Aeff

Vm³/hr: volume flow rate


Lwa dB (A):A-weighted sound power level
Lwanc : NC rating of sound power level
m²: Effective area of diffuser
Aeff
Veff m/s: Effective velocity

8
AL-ANDALOSIA FOR AIR OUTLETS
Square & rectangular flush ceiling diffusers
OUTSANDING FEATURES:

All extruded aluminum construction.


1-2-3-4 way throws patterns.
Inner section easily removable and locks in
place
without the use of tools.
Available in square, rectangular or round
necks.
Standard finish – Anodized or electro-static
painted.
Model 4 SCD SCD 2Model
Four way square Diffuser Two way corner throw
square Neck with opposed Square Diffuser
Blade damper. - square Neck with opposed
Model 4 RCD Blade damper.
Four way rectangular
Diffuser – rectangular
neck with opposed
Blade damper.

Model 4 SCD Model 2 SCD


Four way square Diffuser Two way square Diffuser
with opposed Blade square Neck with opposed
damper Blade damper.
With round neck.
Model 4 RCD
Two way rectangular
Diffuser – rectangular
neck with opposed
Blade damper.

Model 3 SCD Model 1 SCD


Three way square Diffuser One way square Diffuser
square Neck with opposed square Neck with opposed
Blade damper. Blade damper.
Model 3 RCD
Three way rectangular Model 1 RCD
Diffuser – rectangular One way rectangular
neck with opposed Diffuser – rectangular
Blade damper. neck with opposed
Blade damper.

9
AL-ANDALOSIA FOR AIR OUTLETS

CFM – TD Relations

PERFORMANCE NOTES & SYMBOLS

CFM : Volume of air in cubic feet per minute.


FPM : Velocity of air in feet per minute.
AK : Effective outlet area in sq. ft.
Pt. : total pressure in inches of water. Equals the sum of static pressure plus velocity
pressure.

Throw : is the distance measured horizontally in feet that the air stream travels from outlet b
at a given terminal velocity . the throw is based on maximum terminal velocity of
50 fpm and minimum terminal velocity of 100 fpm.
NC : Noise Criteria are based on sound power level . to determine NC values in the room
due to diffuser , subtract the room attenuation from the NC rating which are gives in
the performance tables.

10
AL-ANDALOSIA FOR AIR OUTLETS

PERFORMANCE DATA

MODEL 4SCD FOUR-WAY THROW


SQUARE DIFFUSER

NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
6"x6" TOTAL CFM 50 75 100 125 150 175 200 225
CFM each side – a 13 19 25 32 38 44 50 57
AK= 0.13 Throw each side – a 2-3 3-5 4- 7 5- 9 6- 11 7- 13 8- 15 9- 17
9"x9" TOTAL CFM 112 168 224 280 336 392 448 504
CFM each side – a 28 42 56 70 84 98 112 126
AK= 0.28 Throw each side – a 2-3 3-5 4- 8 5- 10 6- 12 7- 14 9- 17 9- 18
12"x12" TOTAL CFM 200 300 400 500 600 700 800 900
CFM each side – a 50 75 100 125 150 175 200 225
AK= 0.5 Throw each side – a 2-4 4-7 5-9 6- 11 7- 14 8- 16 10- 19 11- 21
15"x15" TOTAL CFM 312 468 624 780 936 1092 1248 1404
CFM each side – a 78 117 156 159 235 273 312 351
AK= 0.79 Throw each side – a 3-5 4-8 5- 10 7- 13 8- 16 10- 19 11 12- 24
18"x18" TOTAL CFM 450 675 900 1125 1350 1575 1800 2025
CFM each side – a 113 169 225 281 338 394 450 507
AK= 0.13 Throw each side – a 3-5 4-8 5-10 7- 13 9- 17 10- 20 12- 24 13- 26
21"x21" TOTAL CFM 612 918 1224 1530 1836 2142 2448 275
CFM each side – a 153 229 306 382 459 535 612 689
AK= 1.54 Throw each side – a 3-5 4-8 6- 11 7- 13 9- 18 11- 21 13- 25 14- 28
24"x24" TOTAL CFM 800 1200 1600 2000 2400 2800 3200 3600
CFM each side – a 200 300 400 500 600 700 800 900
AK= 2 Throw each side – a 3-6 5-9 6- 12 7- 14 10- 19 11- 22 13- 26 15- 30

11
AL-ANDALOSIA FOR AIR OUTLETS

ERFORMANCE DATA

MODEL 1SCD ONE-WAY THROW


SQUARE DIFFUSER

NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
6"x6" TOTAL CFM 50 75 100 125 150 175 200 225
Throw 3- 5 4- 7 5- 10 7- 13 8- 15 9- 18 10- 20 12- 23
AK= 0.13
9"x9" TOTAL CFM 112 168 224 280 336 392 448 504
Throw 3- 6 4- 8 6- 12 8- 15 9- 18 11- 21 12- 23 13- 26
AK= 0.28
12"x12" TOTAL CFM 200 300 400 500 600 700 800 900
Throw 4- 7 6- 11 7- 14 9- 18 10- 20 12- 24 14- 28 16- 31
AK= 0.5
15"x15" TOTAL CFM 312 468 624 780 936 1092 1248 1404
Throw 4- 7 5- 10 8-15 9- 18 11- 22 13- 26 15- 29 17- 33
AK= 0.79
18"x18" TOTAL CFM 450 675 900 1125 1350 1575 1800 2025
Throw 5- 10 7- 14 10-19 12- 23 14- 28 17- 33 19- 37 21- 42
AK= 0.13
21"x21" TOTAL CFM 612 918 1224 1530 1836 2142 2448 2754
Throw 6- 11 9- 17 11-22 14- 27 17- 33 19- 38 21- 42 24- 48
AK= 1.54
24"x24" TOTAL CFM 800 1200 1600 2000 2400 2800 3200 3600
Throw 6- 12 10- 19 13- 25 16- 31 19- 37 22- 34 25- 49 28- 55
AK= 2

21
AL-ANDALOSIA FOR AIR OUTLETS

ERFORMANCE DATA
MODEL 1RCD CONT.

NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
6"x9" TOTAL CFM 300 450 600 750 900 1050 1200 1350
Throw 4- 8 6- 12 8- 16 10- 20 12- 24 14- 28 16- 32 18- 36
AK= 0.19
6"x12" TOTAL CFM 250 375 500 625 750 875 1000 1125
Throw 4- 8 6- 12 8- 16 10- 20 12- 24 14- 27 16- 31 18- 35
AK= 0.25
6"x15" TOTAL CFM 300 450 600 750 900 1050 1200 1350
Throw 4- 8 6- 12 9- 17 11- 21 13- 25 15- 30 17- 34 19- 38
AK= 0.32
6"x18" TOTAL CFM 350 525 700 875 1050 1225 1400 1575
Throw 4- 8 7- 13 9- 18 11- 22 14- 27 16- 32 19- 37 21- 41
AK= 0.38
6"x21" TOTAL CFM 400 600 800 1000 1200 1400 1600 1800
Throw 5- 9 7- 14 10- 19 12- 23 14- 28 17- 33 19- 38 21- 42
AK= 0.44
6"x24" TOTAL CFM 375 563 750 938 1125 1313 1500 1688
Throw 5- 9 7- 14 9- 18 12- 23 14- 27 16- 32 18- 36 21- 41
AK= 0.5
9"x12" TOTAL CFM 438 657 875 1095 1313 1533 1750 1969
Throw 5- 9 7- 14 9- 18 12- 23 14- 27 16- 32 18- 37 20- 42
AK= 0.38
9"x15" TOTAL CFM 500 750 1000 1250 1500 750 2000 2250
Throw 5- 10 8- 15 10- 19 12- 24 15- 29 17- 34 20- 39 22- 44
AK= 0.47
9"x18" TOTAL CFM 525 786 1048 1310 1572 1834 2096 2363
Throw 5- 10 8- 15 10- 20 13- 25 15- 30 18- 35 20- 40 23- 45
AK= 0.57
9"x21" TOTAL CFM 600 900 1200 1500 1800 2100 2400 2700
Throw 6- 11 8- 16 11- 22 14- 27 16- 32 19- 37 22- 34 24- 48
AK= 0.66

23
AL-ANDALOSIA FOR AIR OUTLETS

PERFORMANCE DATA

MODEL 3SCD THREE- WAY THROW


SQUARE DIFFUSER

NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
6"x6" TOTAL CFM 50 75 100 125 150 175 200 225
CFM each side – a 19 28 38 47 56 66 75 85
AK= 0.13 Throw each side – a 13 19 25 32 38 44 50 56
2- 3 3- 5 4- 7 4- 8 5- 10 6- 11 7- 13 8- 15
2- 3 2- 4 3- 5 3- 6 4- 8 5- 9 5- 10 6- 11
9"x9" TOTAL CFM 112 168 224 280 336 392 448 504
CFM each side – a 42 63 84 105 126 147 168 189
AK= 0.28 Throw each side – a 28 43 56 70 85 98 112 126
2- 4 3- 6 4- 8 5- 10 6- 11 7- 13 8- 15 9- 17
2- 3 3- 5 4- 7 4- 8 5- 10 6- 12 7- 13 8- 15
12"x12" TOTAL CFM 200 300 400 500 600 700 800 900
CFM each side – a 75 113 150 188 225 263 300 338
AK= 0.5 Throw each side – a 50 75 100 125 150 175 200 225
3- 5 4- 7 5- 9 6- 12 7- 14 8- 16 9- 18 10- 20
2- 4 3- 6 4- 8 5- 10 6- 12 7- 14 8- 16 9- 18
15"x15" TOTAL CFM 312 468 624 780 936 1092 1248 1404
CFM each side – a 117 175 235 293 350 410 469 527
AK= 0.79 Throw each side – a 78 118 150 195 235 272 312 351
3- 6 4- 8 6- 11 7- 13 8- 16 10- 19 11- 21 13- 25
3- 5 4- 7 5- 9 6- 11 7- 14 8- 16 10- 19 11- 21
18"x18" TOTAL CFM 450 675 900 1125 1350 1575 1800 2025
CFM each side – a 169 253 338 422 506 591 675 760
AK= 0.13 Throw each side – a 113 169 225 281 338 394 450 506
4- 7 5- 9 7- 13 8- 16 10- 19 11- 22 13- 25 14- 28
3- 5 4- 8 5- 10 6- 12 8- 15 9- 17 10- 20 11- 22
21"x21" TOTAL CFM 612 918 1224 1530 1836 2142 2448 2754
CFM each side – a 230 345 459 574 689 804 919 1033
AK= 1.54 Throw each side – a 153 230 306 382 459 535 612 689
4- 7 5- 10 7- 13 9- 17 10- 20 12- 23 13- 26 15- 29
3- 6 4- 8 6- 11 7- 14 8- 16 10- 19 11- 22 13- 25
24"x24" TOTAL CFM 800 1200 1600 2000 2400 2800 3200 3600
CFM each side – a 300 450 600 750 900 1050 1200 1350
AK= 2 Throw each side – a 200 300 400 500 600 700 800 900
4- 8 6- 11 8- 15 10- 19 11- 22 13- 26 15-30 17- 33
3- 6 5- 9 6- 12 8- 15 9- 18 11- 21 12-24 14- 27

14
AL-ANDALOSIA FOR AIR OUTLETS

PERFORMANCE DATA

MODEL 3RCD THREE WAY THROW


RECTANGULAR DIFFUSER

NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
6"x9" TOTAL CFM 75 113 150 190 225 263 300 338
CFM each side – a 28 43 56 70 85 98 112 125
AK= 0.19 CFM each side – b 24 35 47 60 70 83 94 107
Throw each side – a 2- 3 2- 4 3- 5 3- 6 4- 8 5- 9 5- 10 6- 11
Throw each side – b 1- 2 2- 3 2- 4 3- 5 3- 6 4- 7 4- 8 5- 10
6"x12" TOTAL CFM 100 150 200 250 300 350 400 450
CFM each side – a 50 75 100 125 150 175 200 225
AK= 0.25 CFM each side – b 25 38 50 63 75 88 100 113
Throw each side – a 2- 3 2- 4 3- 6 4- 7 4- 8 5- 10 6- 11 7- 13
Throw each side – b 1- 2 2- 3 2- 4 3- 5 3- 6 4- 7 4- 8 5- 9
6"x15" TOTAL CFM 125 188 250 313 375 438 500 563
CFM each side – a 79 118 156 195 235 273 312 352
AK= 0.32 CFM each side – b 24 35 47 59 70 83 94 106
Throw each side – a 2- 4 3- 5 4- 7 5- 9 5- 10 6- 12 7- 14 8- 15
Throw each side – b 1- 2 2- 3 2- 4 3- 5 6- 3 4- 7 14- 8 5- 9
6"x18" TOTAL CFM 150 225 300 375 450 552 600 675
CFM each side – a 113 169 225 281 338 394 450 506
AK= 0.38 CFM each side – b 19 28 38 47 56 66 75 85
Throw each side – a 2- 4 3- 6 4- 8 5- 10 6- 12 7- 14 8- 16 9- 18
Throw each side – b 1- 2 2- 3 2- 4 2- 4 3- 5 3- 6 4- 7 4- 8
6"x21" TOTAL CFM 175 263 350 438 525 612 700 788
CFM each side – a 154 230 306 382 459 535 612 694
AK= 0.44 CFM each side – b 11 17 22 28 33 39 44 47
Throw each side – a 3- 6 5- 9 7- 13 7- 14 9- 17 10- 20 12- 23 13- 26
Throw each side – b 1- 2 1- 2 2- 3 2- 4 2- 4 3- 5 3- 6 3- 6
6"x24" TOTAL CFM 200 300 400 500 600 700 800 900
CFM each side – a 50 75 100 125 150 175 200 225
AK= 0.5 CFM each side – b 150 225 300 375 450 525 600 675
Throw each side – a 2- 3 2- 4 3- 5 3- 6 4- 7 4- 8 5- 9 5- 10
Throw each side – b 1- 2 5- 10 7- 13 8- 16 10- 20 12- 23 13- 26 15- 29
9"x12" TOTAL CFM 150 225 300 375 450 525 600 675
CFM each side – a 50 75 100 125 150 175 200 225
AK= 0.38 CFM each side – b 50 75 100 125 150 175 200 225
Throw each side – a 2- 4 3- 6 4- 8 5- 10 6- 12 7- 14 8- 16 9- 18
Throw each side – b 2- 4 3- 6 4- 8 5- 10 12- 6 7- 14 8- 16 9- 18
9"x15" TOTAL CFM 188 282 375 469 563 657 750 844
CFM each side – a 79 118 156 195 235 273 312 355
AK= 0.47 CFM each side – b 55 82 110 137 164 192 219 245
Throw each side – a 3- 6 5- 9 6- 11 7- 14 9- 17 10- 19 11- 22 13- 25
Throw each side – b 2- 4 3- 6 4- 8 5- 10 6- 12 7- 14 13- 16 9- 17
9"x18" TOTAL CFM 225 338 450 562 675 788 900 1013
CFM each side – a 113 169 225 281 338 394 450 507
AK= 0.57 CFM each side – b 56 85 113 140 169 197 225 253
Throw each side – a 3- 6 5- 9 6- 12 8- 15 9- 18 11- 21 12- 24 14- 27
Throw each side – b 2- 4 3- 5 4- 7 4- 8 5- 10 6- 12 7- 13 8- 15

15
AL-ANDALOSIA FOR AIR OUTLETS
PERFORMANCE DATA
MODEL 3RCD CONT.
NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
9"x21" TOTAL CFM 262 393 524 655 786 917 1048 1179
CFM each side – a 152 230 306 382 459 535 612 684
AK= 0.66 CFM each side – b 55 82 109 137 163 191 218 248
Throw each side – a 4- 7 6- 11 7- 14 9- 18 11- 21 13- 25 14- 28 16- 31
Throw each side – b 2- 3 3- 5 3- 6 4- 7 5- 9 5- 10 6- 11 7- 13
9"x24" TOTAL CFM 300 450 600 750 900 1050 1200 1350
CFM each side – a 100 150 200 250 300 350 400 450
AK= 0.76 CFM each side – b 100 150 200 250 300 350 400 450
Throw each side – a 2- 4 3- 6 4- 8 5- 10 6- 12 7- 14 8- 16 9- 18
Throw each side – b 2- 4 3- 6 4- 8 5- 10 6- 12 7- 14 8- 16 9- 18
12"x15" TOTAL CFM 250 375 500 625 750 875 1000 1125
CFM each side – a 78 118 156 195 235 273 312 349
AK= 0.63 CFM each side – b 86 129 172 215 258 301 344 388
Throw each side – a 3- 5 4- 7 5- 10 6- 12 8- 15 9- 17 10- 19 11- 21
Throw each side – b 3- 6 4- 8 6- 11 7- 13 8- 16 10- 19 11- 21 12- 24
12"x18" TOTAL CFM 300 450 600 750 900 1050 1200 1350
CFM each side – a 114 169 225 281 338 394 450 513
AK= 0.76 CFM each side – b 93 140 188 235 281 328 375 419
Throw each side – a 3- 6 5- 9 6- 12 7- 14 9- 17 10- 20 12- 23 13- 26
Throw each side – b 3- 5 4- 7 5- 10 6- 12 7- 14 9- 17 10- 19 11- 21
12"x21" TOTAL CFM 350 525 700 875 1050 1225 1400 1575
CFM each side – a 154 230 306 382 459 535 612 693
AK= 0.88 CFM each side – b 98 148 197 242 296 345 394 441
Throw each side – a 4- 7 5- 10 7- 14 9- 17 10- 20 12- 23 14- 27 15- 30
Throw each side – b 2- 4 3- 6 4- 8 5- 10 6- 12 7- 14 8- 16 9- 18
12"x24" TOTAL CFM 400 600 800 1000 1200 1400 1600 1800
CFM each side – a 150 225 300 375 450 525 600 675
AK= 1.0 CFM each side – b 125 188 250 313 375 438 500 563
Throw each side – a 4- 8 6- 11 8- 15 10- 19 12- 23 13- 26 15- 30 17- 34
Throw each side – b 4- 7 5- 9 7- 13 8- 16 10- 19 11- 22 13- 25 14- 27
15"x18" TOTAL CFM 375 563 750 938 1125 1313 1500 1688
CFM each side – a 113 169 225 281 338 394 450 506
AK= 0.95 CFM each side – b 131 197 263 328 394 460 525 591
Throw each side – a 3- 5 4- 8 6- 11 7- 13 8- 16 9- 18 11- 21 12- 23
Throw each side – b 3- 6 5- 9 6- 12 8- 15 9- 18 11- 21 12- 24 14- 27
15"x21" TOTAL CFM 438 657 876 1095 1314 1533 1750 1969
CFM each side – a 154 230 306 382 459 535 612 689
AK= 1.1 CFM each side – b 142 214 285 357 428 499 569 640
Throw each side – a 4- 7 5- 10 7- 13 8- 16 10- 19 11- 21 12- 24 14- 27
Throw each side – b 3- 6 5- 9 6- 12 8- 15 9- 17 10- 20 12- 23 13- 26
15"x24" TOTAL CFM 500 750 1000 1250 1500 1750 2000 2250
CFM each side – a 200 300 400 500 600 700 800 900
AK= 1.26 CFM each side – b 150 225 300 375 450 525 600 675
Throw each side – a 4- 7 6- 11 7- 14 9- 18 11- 21 12- 24 14- 28 16- 31
Throw each side – b 3- 6 4- 8 6- 11 7- 13 8- 16 9- 18 11- 21 12- 24
18"x21" TOTAL CFM 525 786 1048 1310 1572 1834 2096 2363
CFM each side – a 153 230 306 382 459 535 612 686
AK= 1.32 CFM each side – b 186 278 371 464 557 650 742 839
Throw each side – a 3- 6 4- 8 6- 11 7- 14 8- 16 10- 19 11- 22 12- 24
Throw each side – b 4- 7 5- 10 7- 13 9- 17 10- 20 12- 23 13- 26 15- 30
18"x24" TOTAL CFM 600 900 1200 1500 1800 2100 2400 2700
CFM each side – a 250 375 500 625 750 875 1000 1125
AK= 1.5 CFM each side – b 175 263 350 438 525 613 670 788
Throw each side – a 4- 8 6- 12 8- 16 10- 20 12- 23 14- 27 16- 31 18- 35
Throw each side – b 3- 6 5- 9 6- 11 7- 14 9- 17 10- 19 11- 21 13- 25

16
AL-ANDALOSIA FOR AIR OUTLETS

PERFORMANCE DATA

MODEL 2SCD TWO-WAY THROW


SQUARE DIF FUSER

NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
6"x6" TOTAL CFM 50 75 100 125 150 175 200 225
CFM each side – a 25 38 50 63 75 88 100 113
AK= 0.13 Throw each side – a 2- 4 3- 6 4- 7 5- 9 6- 11 7- 13 8- 15 8- 16
9"x9" TOTAL CFM 112 168 224 280 336 392 448 504
CFM each side – a 56 84 112 140 168 196 224 252
AK= 0.28 Throw each side – a 2- 4 4- 7 5- 9 6- 12 7- 14 8- 16 9- 18 11- 21
12"x12" TOTAL CFM 200 300 400 500 600 700 800 900
CFM each side – a 56 150 200 250 300 350 400 450
AK= 0.5 Throw each side – a 3- 5 4- 9 6- 11 7- 14 9- 17 10- 19 11- 22 13- 25
15"x15" TOTAL CFM 312 468 624 780 936 1092 1248 1404
CFM each side – a 156 234 312 390 468 546 624 702
AK= 0.79 Throw each side – a 4- 7 5- 10 13-7 8- 16 11- 19 11- 22 13- 25 14- 28
18"x18" TOTAL CFM 450 675 900 1125 1350 1575 1800 2025
CFM each side – a 225 338 450 563 675 788 900 1013
AK= 0.13 Throw each side – a 4- 8 6- 11 7- 14 9- 18 11- 21 13- 25 14- 28 16- 31
21"x21" TOTAL CFM 612 918 1224 1530 1836 2142 2448 2754
CFM each side – a 306 459 612 765 918 1071 1225 1377
AK= 1.54 Throw each side – a 5- 9 6- 12 8- 16 10- 20 13- 25 15- 29 17- 33 19- 37
24"x24" TOTAL CFM 800 1200 1600 2000 2400 2800 3200 3600
CFM each side – a 400 600 800 1000 1200 1400 1600 1800
AK= 2 Throw each side – a 5- 10 7-14 10- 19 12- 23 14- 28 17- 33 19- 37 21- 42

17
AL-ANDALOSIA FOR AIR OUTLETS

PERFORMANCE DATA

MODEL 2RCD TWO-WAY THROW


RECTANGULAR DIFFUSER

NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
6"x9" TOTAL CFM 75 113 150 190 225 260 300 338
CFM each side – a 38 57 75 95 113 130 150 169
AK= 0.19 Throw each side – a 3- 5 4- 7 5- 9 6- 11 7- 13 8- 15 9- 17 10- 20
6"x12" TOTAL CFM 100 150 200 250 300 350 400 450
CFM each side – a 50 75 100 125 150 175 200 225
AK= 0.25 Throw each side – a 3- 5 4- 8 5- 10 6- 12 8- 15 9- 18 10- 20 11- 22

6"x15" TOTAL CFM 125 188 250 312 375 438 500 563
CFM each side – a 63 94 125 156 188 219 250 282
AK= 0.32 Throw each side – a 3- 5 4- 7 5- 9 6- 12 79- 14 9- 17 10- 19 11- 22
6"x18" TOTAL CFM 150 225 300 375 450 525 600 675
CFM each side – a 75 113 150 188 225 263 300 338
AK= 0.38 Throw each side – a 3- 5 4- 8 5- 10 7- 13 8- 15 9- 18 10- 20 12- 23
6"x21" TOTAL CFM 175 263 350 438 525 612 700 788
CFM each side – a 88 132 175 219 263 306 350 394
AK= 0.44 Throw each side – a 3- 6 4- 8 6- 11 7- 14 8- 16 10- 19 11- 22 16- 25
6"x24" TOTAL CFM 200 300 400 500 600 700 800 900
CFM each side – a 100 150 200 250 300 350 400 450
AK= 0.5 Throw each side – a 3- 6 5- 9 6- 12 8- 15 9- 18 10- 20 12- 23 13- 26
9"x12" TOTAL CFM 150 225 300 375 450 525 600 675
CFM each side – a 75 113 150 188 225 263 300 338
AK= 0.38 Throw each side – a 3- 5 4- 8 5- 10 7- 13 8- 15 9- 18 10- 20 7- 23
9"x15" TOTAL CFM 188 282 375 470 563 657 750 844
CFM each side – a 94 141 188 235 283 328 375 422
AK= 0.47 Throw each side – a 3- 6 4- 8 6- 11 7- 13 8- 16 18- 19 11- 21 12- 24
9"x18" TOTAL CFM 225 338 450 562 675 788 900 1013
CFM each side – a 113 169 225 281 338 394 450 507
AK= 0.57 Throw each side – a 3- 6 4- 8 6- 11 7- 14 8- 16 10- 19 11- 22 12- 24

18
AL-ANDALOSIA FOR AIR OUTLETS

PERFORMANCE DATA
MODEL 2RCD CONT.
NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
9"x21" TOTAL CFM 262 393 524 655 786 917 1048 1179
CFM each side – a 131 196 262 328 393 459 524 590
AK= 0.66 Throw each side – a 3- 6 5- 6 6- 12 8- 15 9- 18 10- 20 12- 23 13- 26

9"x24" TOTAL CFM 300 450 600 750 900 1050 1200 1350
CFM each side – a 150 225 300 375 450 525 600 675
AK= 0.76 Throw each side – a 4- 7 5- 10 7- 13 8- 16 10- 19 11- 22 13- 25 14- 28

12"x15" TOTAL CFM 250 375 500 625 750 875 1000 1125
CFM each side – a 125 188 250 313 375 438 500 563
AK= 0.63 Throw each side – a 3- 6 5- 9 6- 12 8- 15 9- 18 10- 20 12- 23 13- 26

12"x18" TOTAL CFM 300 450 600 750 900 1050 1200 1350
CFM each side – a 150 225 300 375 450 525 600 675
AK= 0.76 Throw each side – a 3- 6 5- 9 6- 12 8- 16 10- 19 11- 22 13- 25 14- 28

12"x21" TOTAL CFM 350 525 700 875 1050 1225 1400 1575
CFM each side – a 175 263 350 438 525 613 700 788
AK= 0.88 Throw each side – a 4- 7 5- 10 7- 13 8- 16 10- 20 12- 23 13- 26 15- 30

12"x24" TOTAL CFM 400 600 800 1000 1200 1400 1600 1800
CFM each side – a 200 300 400 500 600 700 800 900
AK= 1.0 Throw each side – a 4- 7 6- 11 7- 14 9- 18 11- 21 13- 25 17- 28 16- 32

15"x18" TOTAL CFM 375 563 750 938 1125 1313 1500 1688
CFM each side – a 188 282 375 469 563 657 750 844
AK= 0.95 Throw each side – a 3- 6 5- 10 7- 13 8- 16 10- 19 12- 23 13- 26 15- 29

15"x21" TOTAL CFM 438 657 876 1095 1313 1533 1750 1969
CFM each side – a 219 329 438 548 657 767 875 985
AK= 1.1 Throw each side – a 4- 7 6- 11 8- 15 10- 19 12- 23 13- 26 15- 30 17- 33

15"x24" TOTAL CFM 500 750 1000 1250 1500 1750 2000 2250
CFM each side – a 250 375 500 625 750 875 1000 1125
AK= 1.26 Throw each side – a 4- 8 6- 12 8- 16 10- 20 12- 24 14- 28 16- 32 18- 36

18"x21" TOTAL CFM 525 786 1048 1310 1572 1834 2096 2363
CFM each side – a 263 393 524 655 786 917 1048 1182
AK= 1.32 Throw each side – a 4- 8 6- 12 8- 15 10- 19 12- 23 14- 27 15- 30 17- 34

18"x24" TOTAL CFM 600 900 1200 1500 1800 2100 2400 2700
CFM each side – a 300 450 600 750 900 1050 1200 1350
AK= 1.5 Throw each side – a 4- 8 6- 12 8- 16 10- 20 12- 24 14- 28 16- 32 18- 36

19
AL-ANDALOSIA FOR AIR OUTLETS

ERFORMANCE DATA

MODEL 2SCD TWO-WAY THROW


SQUARE DIFFUSER

NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
6"x6" TOTAL CFM 50 75 100 125 150 175 200 225
CFM each side – a 25 38 50 63 75 88 100 113
AK= 0.13 Throw each side – a 2- 4 3- 6 4- 7 5- 9 6- 11 7- 13 8- 15 8- 16
9"x9" TOTAL CFM 112 168 224 280 336 392 448 504
CFM each side – a 56 84 112 140 168 196 224 252
AK= 0.28 Throw each side – a 2- 4 4- 7 5- 9 6- 12 7- 14 8- 16 9- 18 11- 21
12"x12" TOTAL CFM 200 300 400 500 600 700 800 900
CFM each side – a 56 150 200 250 300 350 400 450
AK= 0.5 Throw each side – a 3- 5 4- 9 6- 11 7- 14 9- 17 10- 19 11- 22 13- 25
15"x15" TOTAL CFM 312 468 624 780 936 1092 1248 1404
CFM each side – a 156 234 312 390 468 546 624 702
AK= 0.79 Throw each side – a 4- 7 5- 10 13-7 8- 16 11- 19 11- 22 13- 25 14- 28
18"x18" TOTAL CFM 450 675 900 1125 1350 1575 1800 2025
CFM each side – a 225 338 450 563 675 788 900 1013
AK= 0.13 Throw each side – a 4- 8 6- 11 7- 14 9- 18 11- 21 13- 25 14- 28 16- 31
21"x21" TOTAL CFM 612 918 1224 1530 1836 2142 2448 2754
CFM each side – a 306 459 612 765 918 1071 1225 1377
AK= 1.54 Throw each side – a 5- 9 6- 12 8- 16 10- 20 13- 25 15- 29 17- 33 19- 37
24"x24" TOTAL CFM 800 1200 1600 2000 2400 2800 3200 3600
CFM each side – a 400 600 800 1000 1200 1400 1600 1800
AK= 2 Throw each side – a 5- 10 7-14 10- 19 12- 23 14- 28 17- 33 19- 37 21- 42

20
AL-ANDALOSIA FOR AIR OUTLETS

ERFORMANCE DATA

MODEL 1SCD ONE-WAY THROW


SQUARE DIFFUSER

NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
6"x6" TOTAL CFM 50 75 100 125 150 175 200 225
Throw 3- 5 4- 7 5- 10 7- 13 8- 15 9- 18 10- 20 12- 23
AK= 0.13
9"x9" TOTAL CFM 112 168 224 280 336 392 448 504
Throw 3- 6 4- 8 6- 12 8- 15 9- 18 11- 21 12- 23 13- 26
AK= 0.28
12"x12" TOTAL CFM 200 300 400 500 600 700 800 900
Throw 4- 7 6- 11 7- 14 9- 18 10- 20 12- 24 14- 28 16- 31
AK= 0.5
15"x15" TOTAL CFM 312 468 624 780 936 1092 1248 1404
Throw 4- 7 5- 10 8-15 9- 18 11- 22 13- 26 15- 29 17- 33
AK= 0.79
18"x18" TOTAL CFM 450 675 900 1125 1350 1575 1800 2025
Throw 5- 10 7- 14 10-19 12- 23 14- 28 17- 33 19- 37 21- 42
AK= 0.13
21"x21" TOTAL CFM 612 918 1224 1530 1836 2142 2448 2754
Throw 6- 11 9- 17 11-22 14- 27 17- 33 19- 38 21- 42 24- 48
AK= 1.54
24"x24" TOTAL CFM 800 1200 1600 2000 2400 2800 3200 3600
Throw 6- 12 10- 19 13- 25 16- 31 19- 37 22- 34 25- 49 28- 55
AK= 2

21
AL-ANDALOSIA FOR AIR OUTLETS

ERFORMANCE DATA

MODEL 1RCD ONE-WAY THROW


SQUARE DIFFUSER

NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
6"x9" TOTAL CFM 75 113 150 190 225 260 300 338
Throw 3- 6 5- 9 6- 12 8- 15 9- 17 10- 20 12- 23 12- 26
AK= 0.19
6"x12" TOTAL CFM 100 150 200 250 300 350 400 450
Throw 4- 7 5- 10 7- 13 8- 16 10- 19 11- 22 13- 25 15- 29
AK= 0.25
6"x15" TOTAL CFM 125 188 250 312 375 438 500 563
Throw 4- 7 5- 10 7- 13 9- 17 10- 20 12- 23 13- 26 15- 30
AK= 0.32
6"x18" TOTAL CFM 150 225 300 375 450 525 600 675
Throw 4- 7 5- 10 7- 14 9- 17 10- 20 12- 24 14- 27 15- 30
AK= 0.38
6"x21" TOTAL CFM 175 263 350 438 525 612 700 788
Throw 4- 8 6- 11 8- 15 9- 18 11- 22 13- 25 15- 29 17- 33
AK= 0.44
6"x24" TOTAL CFM 200 300 400 500 600 700 800 900
Throw 4- 8 6- 12 8- 16 10- 19 12- 23 14- 27 16- 31 18- 35
AK= 0.5
9"x12" TOTAL CFM 150 225 300 375 450 525 600 675
Throw 4- 7 5- 10 7- 14 9- 17 10- 20 12- 24 14- 27 15- 30
AK= 0.38
9"x15" TOTAL CFM 188 282 375 470 563 656 750 844
Throw 4- 7 5- 10 7- 14 9- 17 10- 20 13- 25 14- 28 16- 31
AK= 0.47
9"x18" TOTAL CFM 225 338 450 562 675 788 900 1013
Throw 4- 8 6- 11 8- 15 10- 19 11- 22 13- 25 15- 29 17- 33
AK= 0.57
9"x21" TOTAL CFM 262 393 524 655 786 917 1048 1179
Throw 4- 8 6- 11 8- 15 10- 19 12- 23 14- 27 15- 30 17- 34
AK= 0.66

22
AL-ANDALOSIA FOR AIR OUTLETS

ERFORMANCE DATA
MODEL 1RCD CONT.

NECKSIZE Neck VELOCIY 200 300 400 500 600 700 800 900
AK FPM
TOTAL PRESSURE .019 .039 .067 .10 .14 .19 .24 .30
6"x9" TOTAL CFM 300 450 600 750 900 1050 1200 1350
Throw 4- 8 6- 12 8- 16 10- 20 12- 24 14- 28 16- 32 18- 36
AK= 0.19
6"x12" TOTAL CFM 250 375 500 625 750 875 1000 1125
Throw 4- 8 6- 12 8- 16 10- 20 12- 24 14- 27 16- 31 18- 35
AK= 0.25
6"x15" TOTAL CFM 300 450 600 750 900 1050 1200 1350
Throw 4- 8 6- 12 9- 17 11- 21 13- 25 15- 30 17- 34 19- 38
AK= 0.32
6"x18" TOTAL CFM 350 525 700 875 1050 1225 1400 1575
Throw 4- 8 7- 13 9- 18 11- 22 14- 27 16- 32 19- 37 21- 41
AK= 0.38
6"x21" TOTAL CFM 400 600 800 1000 1200 1400 1600 1800
Throw 5- 9 7- 14 10- 19 12- 23 14- 28 17- 33 19- 38 21- 42
AK= 0.44
6"x24" TOTAL CFM 375 563 750 938 1125 1313 1500 1688
Throw 5- 9 7- 14 9- 18 12- 23 14- 27 16- 32 18- 36 21- 41
AK= 0.5
9"x12" TOTAL CFM 438 657 875 1095 1313 1533 1750 1969
Throw 5- 9 7- 14 9- 18 12- 23 14- 27 16- 32 18- 37 20- 42
AK= 0.38
9"x15" TOTAL CFM 500 750 1000 1250 1500 750 2000 2250
Throw 5- 10 8- 15 10- 19 12- 24 15- 29 17- 34 20- 39 22- 44
AK= 0.47
9"x18" TOTAL CFM 525 786 1048 1310 1572 1834 2096 2363
Throw 5- 10 8- 15 10- 20 13- 25 15- 30 18- 35 20- 40 23- 45
AK= 0.57
9"x21" TOTAL CFM 600 900 1200 1500 1800 2100 2400 2700
Throw 6- 11 8- 16 11- 22 14- 27 16- 32 19- 37 22- 34 24- 48
AK= 0.66

23
AL-ANDALOSIA FOR AIR OUTLETS

ERFORMANCE DATA

MODEL 4CCD ROUND NECK SIZES


SQUARE DIFFUSER

Neck size Fits on Neck Velocity 200 300 400 500 600 700 800 900
square neck FPM
(inches)
5 dia. Total pressure WG. .003 .007 .012 .018 .026 .036 .047 .059
TOTAL CFM 28 41 55 68 82 95 109 123
CFM each side 7 10 14 17 20 24 27 31
AK=.159 9X9
Throw each side 1- 2 2- 3 2- 3 2- 4 3- 5 3- 5 2- 7 4- 7
6 dia. Total pressure WG. .004 .009 .015 .024 .034 .045 .06 .075
TOTAL CFM 40 59 78 98 118 137 157 177
CFM each side 10 15 19 25 30 34 39 45
AK=.211 9X9 Throw each side 1- 2 1- 2 2- 3 2- 4 2- 4 3- 5 3- 5 4- 6

8 dia. Total pressure WG. .007 .016 .028 .043 .062 .083 .11 .14
TOTAL CFM 70 105 140 175 210 245 280 315
CFM each side 10 26 35 44 53 61 70 79
AK=.238 9X9 Throw each side 1- 2 2- 3 2- 4 3- 5 3- 6 4- 7 4- 8 5- 9

10 dia. Total pressure WG. .006 .013 .023 .035 .05 .067 .086 .11
TOTAL CFM 109 164 218 273 327 382 436 491
CFM each side 28 41 55 68 82 96 109 123
AK=.45 12X12 Throw each side 2- 4 3- 5 3- 6 4- 8 5- 9 6- 11 6- 12 7- 14

12 dia. Total pressure WG. .005 .012. .02 .031 .043 .058 .075 .094
TOTAL CFM 157 236 314 393 471 550 628 707
CFM each side 40 59 79 98 118 138 157 177
AK=.683 15X15
Throw each side 2- 4 3- 5 4- 7 4- 8 5- 10 6- 11 7- 13 7- 14

14 dia. Total pressure WG. .009 .019 .032 .049 .069 .093 .12 .15
TOTAL CFM 214 321 428 535 642 749 856 963
AK=.696 15X15 CFM each side 54 80 107 134 160 187 214 241
Throw each side 2- 4 3- 5 4- 7 5- 9 5- 10 6- 12 7- 14 8- 15
16 dia. Total pressure WG. .008 .017 .029 .045 .063 .084 .11 .134
TOTAL CFM 279 416 558 697 832 976 1116 1256
AK=.977 CFM each side 70 104 140 174 208 244 279 314
18X18 Throw each side 3- 5 4- 8 4- 8 7- 13 8- 15 9- 17 10- 20 11- 22

8 dia. Total pressure WG. .003 .006 .011 .017 .024 .033 .042 .054
TOTAL CFM 70 105 140 175 210 245 280 315
CFM each side 18 26 35 44 53 61 70 79
AK=.347 21X21 Throw each side 2- 3 2- 4 3- 5 3- 6 4- 7 4- 8 5- 9 5- 10

24
AL-ANDALOSIA FOR AIR OUTLETS

ERFORMANCE DATA

MODEL 4CCD ROUND NECK SIZES CONT.

Neck size Fits on Neck Velocity 200 300 400 500 600 700 800 900
(inches) square neck FPM
10 dia. Total pressure WG. .003 .007 .014 .021 .03 .039 .051 .064
TOTAL CFM 109 164 218 273 327 382 436 491
CFM each side 28 41 55 68 82 96 109 123
AK=.496 21X21
Throw each side 2-4 3-5 4- 7 4- 8 5- 10 6- 11 7- 13 8- 15
12 dia. Total pressure WG. .004 .009 .016 .024 .034 .046 .059 .074
TOTAL CFM 157 236 314 393 471 550 628 707
CFM each side 40 59 79 98 118 138 157 177
AK=.699 21X21 Throw each side 2- 4 3- 5 4-7 4- 8 5- 10 6- 12 7- 13 8- 15

14 dia. Total pressure WG. .005 .01 .018 .028 .033 .053 .069 .086
TOTAL CFM 214 321 428 535 642 749 856 963
CFM each side 54 80 107 134 160 187 214 241
AK=.952 21X21 Throw each side 2- 4 3- 6 4- 7 5-9 6- 11 7- 13 7- 14 8- 16

16 dia. Total pressure WG. .005 .012 .020 .031 .044 .059 .076 .095
TOTAL CFM 279 416 558 697 832 976 1116 1256
CFM each side 70 104 140 174 208 244 279 314
AK=1.13 21X21 Throw each side 3- 5 4- 8 5- 10 7-13 8- 15 9- 17 10- 20 11- 22

18 dia. Total pressure WG. .007 .015 .025 .038 .054 .072 .092 .11
TOTAL CFM 354 531 708 885 1062 1239 1416 1593
AK=1.29 21X21 CFM each side 89 133 177 221 265 310 354 399
Throw each side 3-6 4- 8 6- 11 7-13 8- 16 10- 19 11- 21 12- 24

20 dia. Total pressure WG. .009 .02 .034 .052 .073 .098 .13 .16
TOTAL CFM 436 654 872 1090 1308 1526 1744 1962
AK=1.35 21X21 CFM each side 109 164 218 272 327 382 436 491
Throw each side 3-6 5-9 6-12 8-15 9-17 10- 20 12- 23 13- 26

25