AL-ANDALOSIA FOR AIR OUTLETS

VOLUME CONTROL DAMPER OPPOSED BLADE

1. Casing
2. Blade
3. plastic Gear
4. Drive Arm
5. Hand Locking Quadrant
- ١-
AL-ANDALOSIA FOR AIR OUTLETS

VOLUME CONTROL DAMPER OPPOSED BLADE


The Description

• The Dampers are made from Extruded Aluminum.


• Opposed Blade action via-Gears.
• Gears made from specific plastic temperature resistance o 70º c.
• Galvanized steel drive arm.
• Hand locking quadrant from galvanized steel.
• Case depth 120 mm.- blade pitch 100 mm.
• Aero foil blade.
• The damper can be power operated by electric actuator.
• Dimension X gives position of drive arm.

Types of VCD

L W No. of Position of
(mm) (mm) Blades Drive Arm X
(mm)
200 204 2 52
300 304 3
400 404 4
500 504 5 252
600 604 6
700 704 7
800 804 8
900 904 9 452
1000 1004 10

- ٢-
AL-ANDALOSIA FOR AIR OUTLETS

VOLUME CONTROL DAMPER

Volume control dampe r sub-division


If the L dimension is greater than 2000 mm , then 2 damper can be provides
for installation side.

Sub-divided on L Dimension
(L=2L +60)

L Dimension sub-Division

L1 (mm) L (mm) W (mm)


24600 1200
2860 1400 W
3260 1600 Dimension
3660 1800 standard
4060 2000

- ٣-
AL-ANDALOSIA FOR AIR OUTLETS

PERFORMANCE DATA

Pressure drop Vs. Face


Velocity in position.

- ٤-
AL-ANDALOSIA FOR AIR OUTLETS

ROUND VOLUME CONTROL DAMPER


(LOWPRESSURE) RVCD-LP

STANDARD MATERIALS & CONSTRUCTION

• Frame : 18 gauge galvanized steel.


• Blade : 18 gauge galvanized steel.
• Ope ration: Hand quadrant for manual operation.
• Regulation: Lower and upper parts of a rapid regulator set.

Diameter range L B
0-9-7/8" Dia.+B 1-6/9"
9-7/8"-23-5/8" Dia.+B 2"
23-5/8"-35-7/16" Dia.+B 2-7/8"
35-7/16"- up Dia.+B 4"

- ٥-
AL-ANDALOSIA FOR AIR OUTLETS

ROUND VOLUME CONTROL DAMPER


(HIGH PRESSURE) RVCD-HP

STANDARD MATERIALS & CONSTRUCTION

• Frame : 18 gauge galvanized steel.


• Blade : 18 gauge galvanized steel.
• Ope ration: Hand quadrant for manual operation.
• Axle : 1/2" square bar 'U' bolted to blade.

Diameter range L B
0-9-7/8" Dia.+B 1-6/9"
9-7/8"-23-5/8" Dia.+B 2"
23-5/8"-35-7/16" Dia.+B 2-7/8"
35-7/16"- up Dia.+B 4"

- ٦-
AL-ANDALOSIA FOR AIR OUTLETS

PERFORMANCE CURVE

Model : RVD-HP (Round Type)

STATIC PRESSURE DROP CHART

DETERMI NI NG STATIC
PRESSURE DROP

To determine static pressure drop


through an open damper pressure drop
chart from the left side . given the CFM
of airflow through the damper , follow
the CFM line to the diagonal line with
the damper size required , then down to
the static pressure drop of the unit.

Example:
The pressure drop of an 8" damper with
1000 CFM flow is 0.11 inches w.g.

- ٧-
AL-ANDALOSIA FOR AIR OUTLETS

DETERMI NI NG LEAKAGE

To determine damper leakage, enter damper leakage chart from the right side. Given the
static pressure the damper will encounter in closed position, move horizontally to the
diagonal line, then go straight down the chart to CFM of leakage per inch of perimeter.
Example:
Damper operating 1" W.G. static pressure will leak 0.08 CFM per inch of perimeter. total
leakage on an 8" round will be 8 x 3.14 x 0.08 CFM per inch perimeter = 2 CFM leakage .
Static pressure and CFM are corrected to 0.075Ib./cu.ft. Air density.

- ٨-