European
Grid Codes
Focusing on
1 | www.meccalte.com
World-class Synchronous Alternators | 2
Focusing on
Vo/fo=1,15
V
Vo/fo=1,1
Prescriptions of EN60034-1:
47,5 Hz
(zone A) 51,5 Hz
Voltage: ± 5% Vn +10% Vn
Frequency: ± 2% Fn
Vo/fo=0,9
New prescriptions for Voltage:
EN50160-A70 Terna Specification
Hz
Voltage: -15% +10% Vn
Vo/fo=0,85
3 | www.meccalte.com
Voltage Characteristic cos Ψ
Minimum voltage value
U/U 0.95
°
100%
Overexcited
70%
45% 1
Underexcited
15%
For type-1 generating unit, synchronous generator directly connected to the network (only through the generator
transformer), the power station shall not disconnect even in the conditions shown in the pictures
cos Ψ
0.95
Overexcited
1
1
Underexcited
P/Pn
0.95
The reactive power of the generating plant must be adjustable. Any reactive power value resulting from the
characteristic must automatically adapt within 10 seconds for inductive load and adjustable between 10 and 60
seconds for capacitive load
Typical
Demands For
Alternators
Alternators operating to these a LVRT ‘speed up’ creates tremendous
requirements must either satisfy the mechanical and electrical forces on
demands within the standard design both engine and alternator.
of the machine or be redesigned
to comply. The latter does have
Mecc Alte…
an effect on cost, availability and
stock flexibility. This does appear
Leading the Way
to be a route taken by a number Typically the design aspects of the
of manufacturers. Mecc Alte alternators for the frame,
the shaft and disc hubs, are more
But, with Mecc Alte the standard robust than for the competitors.
design can withstand the rigours
the standards as we now In machine selection (refer to the
understand them. chart below) the machines inertia
A Grid Code compliant generator must
constant must be specifically
comply with both static and dynamic
There are specific conditions to designed or fundamentally able to
requirements of the appropriate Grid Code.
address during a LVRT event. In the resist speed changed associated In dynamic response the connection must
1st instance the voltage at the point with pole slip in LVRT. remain while the Low Voltage Ride Through
of generator connection drops and (LVRT) occurs, and survive the huge forces
the load is effectively lost onto the The copper headers are low profile with
trying to change the concentric alignment
alternator. The driver unit will likely mechanical spacing between phases of the stator.
overspeed can cause pole slip, but to enhance cooling but to also resist
this will depend on the inertia of the the magnetic forces seen in fault
genset and the reactance values of conditions or re-sync with the grid.
the chosen alternator. In the 2nd Tests of up to 100 consecutive short
instance the fault clears and the circuits have passed without failure
genset – still connected to the grid, to the integrity of the windings,
must instantaneously realign to grid and also the robustness of the
frequency and voltage. This, following mechanical design.
5 | www.meccalte.com
Focusing on
Specifying
Alternators
From 64kVA to 2380kVA (50Hz), the Mecc Alte products will satisfy the requirements
of EN50160-A70 Terna and (UE) 2016/631. There is a 15% ÷ 30% derate to the usual
published powers which is derived from the combination of undervoltage up to -15%,
overfrequency at +1.5Hz and leading power factor at 0.95.
A full list of the powers available are shown below: