Technical Focus

European
Grid Codes
Focusing on

The Story So Far


In just a few short years from now furthermore, the gas and coal power small generators, diesel or gas;
the UK demand for electricity will be stations are being decommissioned to reciprocating or turbine, are connected
uncomfortably close to the combined align with emissions legislations from to the grid and are increasing in their
generating power of both home and Brussels, and any nuclear alternatives percentage contribution.
imported power. There has been will take years to come on line.
significant investment in renewables The grid, as we know it now, is
and wind in particular for the ‘green’ Consequently, there is an fixed in volts and frequency and fairly
imperative and this has improved understandable requirement for immovable. The grid of the future with
where in 2017 a reported 52% of embedded or distributed power increasing wind power input and lighter
demand was supplied from generation sources to secure supplies generators (say 30kW to 5mW) will
renewable sources. and to export (Either partly, wholly, be less so and subjected to volts and
or as part of a smart supply) to keep frequency excursions exceeding what
Some renewable sources are more the country running through all power we see now.
reliable than others and cycles. All of this means that relatively

1 | www.meccalte.com
World-class Synchronous Alternators | 2
Focusing on

The Way Forward


It is with all of this in mind that requirements. The need for the codes The genset and alternator specifically
Transmission System Operators is nevertheless vital to secure reliable must consider this in its design and
(TSO) and Distribution System power supplies in the future. size selection.
Operators (DSO) in their own
countries are applying their technical
Static state Dynamic State
requirements for such connected
The static requirements in terms of In extreme conditions the generator
generators. These are called the Grid
voltage, frequency, power factor and is required to NOT disconnect from
Codes and their purpose is to ensure
kVA are quite straight forward, but it the grid… even if the grid happens
the stability of power supply.
is the dynamic requirements where to disappear.
For example, if a fault occurs in a very special attention is necessary. Looking
below at the original generator We are talking of short periods and
high voltage part of the network, and
requirements of EN60034- 1 and then while Grid Codes are not yet agreeing,
shuts down a particular region, the
EN50160-A70 Terna specification the standard referred to here is a
transient effects in the transmission
right you can see that the operating period of 150ms. After the grid returns
line should not cause a daisy chain
window of voltage / frequency has the realigning of generator to grid
of smaller generators disconnecting
widened significantly. can impart significant stress, if not
from the grid thus exacerbating the
catastrophic failure to the alternator
power loss of the original fault.
In the main the conditions are: and even the engine. This event is
The problem is European wide and called a Fault Ride Through (FRT) or
• Voltage within +10% 15% Low Voltage Ride Through (LVRT).
even further, and there are moves to
standardise on what the Grid Codes Again the alternator design and
• Frequency within +3% -5%
should be, although in all likelihood selection is key.
there will remain differences as it • Lagging & Leading power factor
seems too difficult to align all of the

Vo/fo=1,15
V

Vo/fo=1,1

Prescriptions of EN60034-1:
47,5 Hz
(zone A) 51,5 Hz
Voltage: ± 5% Vn +10% Vn
Frequency: ± 2% Fn

Vo/fo=0,9
New prescriptions for Voltage:
EN50160-A70 Terna Specification
Hz
Voltage: -15% +10% Vn
Vo/fo=0,85

New prescriptions for Frequency:


EN50160-A70 Terna Specification
Frequency: -5% +3% Fn
-15% Vn

3 | www.meccalte.com
Voltage Characteristic cos Ψ
Minimum voltage value
U/U 0.95
°
100%

Overexcited
70%

45% 1

Underexcited
15%

0 150 700 1.500 3.000


Time in ms
0.95
Fault instant

For type-1 generating unit, synchronous generator directly connected to the network (only through the generator
transformer), the power station shall not disconnect even in the conditions shown in the pictures

cos Ψ

0.95
Overexcited

1
1
Underexcited

P/Pn

0.95

The reactive power of the generating plant must be adjustable. Any reactive power value resulting from the
characteristic must automatically adapt within 10 seconds for inductive load and adjustable between 10 and 60
seconds for capacitive load

World-class Synchronous Alternators | 4


Focusing on

Typical
Demands For
Alternators
Alternators operating to these a LVRT ‘speed up’ creates tremendous
requirements must either satisfy the mechanical and electrical forces on
demands within the standard design both engine and alternator.
of the machine or be redesigned
to comply. The latter does have
Mecc Alte…
an effect on cost, availability and
stock flexibility. This does appear
Leading the Way
to be a route taken by a number Typically the design aspects of the
of manufacturers. Mecc Alte alternators for the frame,
the shaft and disc hubs, are more
But, with Mecc Alte the standard robust than for the competitors.
design can withstand the rigours
the standards as we now In machine selection (refer to the
understand them. chart below) the machines inertia
A Grid Code compliant generator must
constant must be specifically
comply with both static and dynamic
There are specific conditions to designed or fundamentally able to
requirements of the appropriate Grid Code.
address during a LVRT event. In the resist speed changed associated In dynamic response the connection must
1st instance the voltage at the point with pole slip in LVRT. remain while the Low Voltage Ride Through
of generator connection drops and (LVRT) occurs, and survive the huge forces
the load is effectively lost onto the The copper headers are low profile with
trying to change the concentric alignment
alternator. The driver unit will likely mechanical spacing between phases of the stator.
overspeed can cause pole slip, but to enhance cooling but to also resist
this will depend on the inertia of the the magnetic forces seen in fault
genset and the reactance values of conditions or re-sync with the grid.
the chosen alternator. In the 2nd Tests of up to 100 consecutive short
instance the fault clears and the circuits have passed without failure
genset – still connected to the grid, to the integrity of the windings,
must instantaneously realign to grid and also the robustness of the
frequency and voltage. This, following mechanical design.

5 | www.meccalte.com
Focusing on

Specifying
Alternators
From 64kVA to 2380kVA (50Hz), the Mecc Alte products will satisfy the requirements
of EN50160-A70 Terna and (UE) 2016/631. There is a 15% ÷ 30% derate to the usual
published powers which is derived from the combination of undervoltage up to -15%,
overfrequency at +1.5Hz and leading power factor at 0.95.
A full list of the powers available are shown below:

Generator Type kVA 50Hz Derating for EN50160


ECP34-1.5VS/4 75 15%
ECP34-1S/4 85 15%
ECP34-2S/4 105 15%
ECP34-1L/4 135 15%
ECP34-2L/4 150 15%
ECP34-3L/4 160 15%

ECO38-1S/4 180 15%


ECO38-2S/4 200 15%
ECO38-3S/4 225 15%
ECO38-1L/4 250 15%
ECO38-2L/4 300 15%
ECO38-3L/4 350 15%

ECO40-1S/4 400 15%


ECO40-2S/4 450 15%
ECO40-3S/4 500 15%
ECO40-1L/4 550 15%
ECO40-1.5L/4 625 15%
ECO40-2L/4 680 15%
ECO40-VL/4 750 30%

ECO43-1S/4 800 15%


ECO43-2S/4 930 15%
ECO43-1M/4 1025 30%
ECO43-2M/4 1150 30%
ECO43-2L/4 1300 30%
ECO43-VL/4 1400 15%

ECO46-1S/4 1500 15%


ECO46-1.5S/4 1650 15%
ECO46-2S/4 1800 15%
ECO46-1L/4 2100 15%
ECO46-1.5L/4 2300 15%
ECO46-2L/4 2500 15%
ECO46-VL/4 2800 15%

Compliant And Ready


With the above range to be extended upwards over the next few years, Mecc Alte is your
perfect independent partner for grid power alternators, totally focussed on the needs of
OEM’s to fulfil their obligations now and for the future.

World-class Synchronous Alternators | 6


Mecc Alte SpA France Far East China
Via Roma Mecc Alte International S.A. Mecc Alte (F.E.) PTE LTD Mecc Alte Alternator Haimen LTD
20 – 36051 Creazzo Z.E.La Gagnerie 19 Kian Teck Drive 755 Nanhai East Rd
Vicenza – ITALY 16330 ST.Amant De Boixe Singapore 628836 Jiangsu HEDZ 226100 PRC
T: +39 0444 396111 T: +33 (0) 545 397562 T: +65 62 657122 T: +86 (0) 513 82325758
F: +39 0444 396166 F: +33 (0) 545 398820 F: +65 62 653991 F: +86 (0)513 82325768
E: info@meccalte.it E: info@meccalte.fr E: info@meccalte.com.sg E: info@meccalte.cn
aftersales@meccalte.it aftersales@meccalte.fr aftersales@meccalte.com.sg aftersales@meccalte.cn

United Kingdom Spain India Australia


Mecc Alte U.K. LTD Mecc Alte España S.A. Mecc Alte India PVT LTD Mecc Alte Alternators PTY LTD
6 Lands’ End Way C/ Rio Taibilla, 2 Plot NO: 1, Sanaswadi 10 Duncan Road, PO Box 1046
Oakham Polig. Ind. Los Valeros Talegaon Dry Creek, 5094, South
Rutland 03178 Benijofar (Alicante) Dhamdhere RoadTaluka: Australia
T: +44 (0) 1572 771160 T: +34 (0) 96 6702152 Shirur, District: T: +61 (0)8 8349 8422
F: +44 (0) 1572 771161 F: +34 (0) 96 6700103 Pune - 412208 F: +61 (0)8 8349 8455
E: info@meccalte.co.uk E: info@meccalte.es Maharashtra, India E: info@meccalte.com.au
aftersales@meccalte.co.uk aftersales@meccalte.es T: +91 2137 619600 aftersales@meccalte.com.au
F: +91 2137 619699
E: info@meccalte.in
U.S.A. and Canada Germany
Mecc Alte Inc. Mecc Alte Generatoren GmbH aftersales@meccalte.in
1229 Adam Drive Ensener Weg 21
McHenry, IL, 60051 D-51149 Köln
T: +1 815 344 0530 T: +49 (0) 2203 503810
F: +1 815 344 0535 F: +49 (0) 2203 503796
E: info@meccalte.us E: info@meccalte.de
aftersales@meccalte.us aftersales@meccalte.de www.meccalte.com

Das könnte Ihnen auch gefallen