Manufacturer to be mentioned
Type to be mentioned
1 Standard IEC 62271-100 and IEC 62271-1
2 Service condition Outdoor; Tropical area
3 Type of designation Live Tank
4 Type of arc quenching medium SF6
5 Number of Phases phase 3
7 Rated voltage (Ur) kV rms 170
8 Rated frequency (Fr) Hz 50
9 Rated normal current (Ir) A rms ≥ 1250 or ≥ 2000 or ≥ 2500 or ≥ 4000
10 Rated short-time withstand current (I th) kA rms 31,5 or 40 or 50
11 Rated peak withstand current (I p) kA peak ≥ 2,5 x I th
12 Rated duration of short circuit s ≥1
13 RATED INSULATION LEVEL :
Power frequency withstand voltage, dry for 1 minute
Phase to earth, between the phases and across the open breaker gap kV rms ≥ 325
Impulse withstand voltage (at 1,2/50 microsecond)
Phase to earth, between the phases and across the open breaker gap kV peak ≥ 750
14 Minimum Creepage distance mm/kV 25 or 31
15 OPERATING SEQUENCE AND OPERATING DUTY
- Nominal Sequence
(Not intended for rapid auto reclosing) O - 0.3s - CO - 180s - CO
- Out of phase O - CO
16 Rated making and breaking current to Normal/Reclose
- Making current kA peak ≥ 2,5 x I th
- Breaking current (symmetrical) kA rms 31,5 or 40 or 50
- % dc component % dc > 20
17 Breaking current under out of phase condition kA rms ≥ 25 % x I th
18 Rated capacitive switching currents N/A
19 Radio influence voltage level, measured at 1.1 Ur/√3 at 1 Mhz
- circuit closed to ground μV To be mentioned
- circuit breaker open, grounded terminal μV To be mentioned
20 Classes
- Electrical endurance E1
- Transient Recovery Voltage refer to IEC 62271-100 table 9
- Mechanical endurance M2
- Restrike performance C2
23 Temperature rise at :
- Contacts in SF6 K ≤ 65
- Connection, bolted or equivalent in SF6 K ≤ 75
- Terminal K ≤ 65
MECHANISM
Manufacture
Type
24 Number of interrupters in series per phase pcs 1
25 Number of tripping coils per phase pcs 2
26 Number of closing coils per phase pcs 1
27 Operating mechanism :
- Type motor spring
- Number of stored energy operation 1 ( one for three phase)
28 Protection level of control cubicle min. IP54
29 Supply voltage :
- Control voltage Volt DC 110
- Tripping and closing Coils Volt DC 110
- Motor voltage Volt AC 230 / 400
- Heater Volt AC 230
30 Tolerance range for auxiliary supply voltage
- tripping coil % 85 to 110
- closing coil % 85 to 110
- motor % 85 to 110
31 Mechanical performance
1. Total break time (trip initiation to final arc extinction) ms ≤ 50
2. Opening time (trip initiation to contact separation) without current ms ≤ 40
3. Time interval between opening of interrupters of first and last phase ms ≤4
4. Time interval between opening of interupters of one phase ms N/A
5. Closing time without current ms ≤ 110
6. Time interval between closure of interrupters of the first and last pole ms ≤ 10
7. Time interval between closure of interrupters of one phase ms N/A
8. Time from extinction of main arc to contact make ms ≤ 300
during auto-reclose duty
32 Number of auxiliary contacts (NO/NC) per pole pcs >8
OTHERS
34 Discrepancy device N/A
35 Antipumping device Yes
36 Method of controling voltage distribution between break unit N/A
37 Method of Closing control N/A
38 Value of closing resistor Ohm N/A
39 Insertion time of closing resistor ms N/A
40 SF6 Pressure Indicator per set pcs 1
41 Counter to record number of operation per set pcs 2
42 Seismic acceleration constant consideration g 0,2 or 0,3
43 Leakage rate of SF6 gas per annum % ≤ 0.5
44 Contact resistance across main contacts per phase μ ohm < 80
45 Number of switch operations between two inspections for changing the main-contacts :
- with rated continuous current to be mentioned
- with rated breaking current to be mentioned
47 Material of insulator Silicone Rubber/Porcelain
48 Minimum clearance in air :
- between phase mm to be mentioned (refer to IEC)
- phase to earth mm to be mentioned (refer to IEC)
- live conductor to ground level mm to be mentioned (refer to IEC)
- live insulator to ground level mm to be mentioned (refer to IEC)