POWER SYSTEMS

The Eltek range of plug in


power supplies has been
specifically developed to meet
the DC powering requirements
for telecommunications and
industrial applications. High
efficiency, low weight and
volume are achieved through
the utilisation of switch mode
technology.

The SMPS 1000 SI offers the


following features:

• ‘Hot’ plug in facilitating


installation and service
• Power factor corrected input
providing reduced harmonics
and minimal input power
requirements
• Automatic Over Temperature
de-rating for increased
reliability
• Parallel operation to provide
power requirements and/or
redundancy
• Alarm and Control Facilities
for local and remote
monitoring

SMPS 1000 SI • Compliant with


International Standards
Switch Mode Power Supply
SMPS 1000 S I OTHER SPECIFICATIONS

Efficiency: > 91%


Switch Mode Power EMC - Emission:
EMC - Immunity:
According to EN 50081 - 1
According to EN 50082 - 2
Safety: According to IEC 950
Supply Isolation: 3.0 KVAC - input and output
1.5 KVAC - input and earth
1.0 KVDC - output and earth
The Eltek range of plug in switch mode power supplies has Protection: Output Power Limiting
been specifically developed to provide high quality, reliable Non-destructive Short Circuit Protection
DC power for communication applications. High Output Voltage Shut Down
Metering: Front panel test points for output
SPECIFICATION current
Volt Free Alarm: Common Output operated under one
INPUT of the following conditions:
Module Failure
Voltage: 230 V -10%, +20% Single phase Low Input Voltage
Over Voltage 300 V for 10 minutes and High Output Voltage Shut Down
Operation: 345 V for 400 mS Over Temperature
Frequency: 45 to 65 Hz Operation: Output voltage adjustment via front
Harmonics: According to IEC 1000-3-2 panel potentiometer
Current: 4.3 Amps at 230 V LED indicators: Unit Healthy, Module Fail, Output Limit
Power Factor: > 0.995 Operating Temp: -10˚C to + 30˚C (14˚F to 86˚F)
Total Harmonic +30˚C to 55˚C (86˚F to 131˚F) with
Distortion: <9% typically 7% temperature dependant power limiting
Protection: Fuse, Soft Start Storage Temp: -25˚C to + 85˚C (-13˚F to 185˚F)
Humidity: 5 to 95% RH non-condensing
OUTPUT Dimensions: 66.8 mm W x 266 mm (6U) H x 220 mm D
(2.6 in W x 10.5 in H x 8.7 in D)
Voltage: 48 V Nominal Weight: <2.8 Kg (<6.2 lb)
Maximum Current: 20 Amp Housing: IP20
Active Current Cooling: Convection
Share: ±5%
Voltage Static: ±0.5% for full load and input FUNCTIONAL
Regulation: variation
Dynamic ±1.0% for 10-90% or 90-10% load The SMPS 1000 SI supports the following control functions:
Response: variation. Recovery time < 10 mS • External Shut Down Input
Hold Up Time: > 10 mS • Remote Output Voltage Adjust for temperature
Ripple < 100 mV peak to peak, 30 MHz compensation, boost charging and battery testing
and Noise: bandwidth. • Current share bus for increased reliability in parallel
< 2 mV psophometric operation
• Remote sense for cable voltage drop compensation

Eltek Energy AS. Eltek (UK) Ltd. Eltek Energy (USA) Inc. Eltek SGS Pvt. Ltd.
Power Systems Division Power Systems Division P.O. Box 251 899 Udyog Vihar
P.O. Box 1500 Eltek House Unit 2, 6A Phase 1, Gurgaon
N-3007 Drammen 2 Maxted Road 999 Willow Grove Street 122016 (Haryana)
Norway Hemel Hempstead Hackettstown India
Tel: +47 32203200 Herts HP2 7DX New Jersey 07840-251 Tel: +91 124346996
Fax: +47 32203210 England Power Systems Tel: +1 9088524727 Fax: +91 124346997
Tel: +44 1442 219355 Fax: +1 9088520428
Fax: +44 1442 245894

Eltek Energy France. Eltek (Far East) Ltd. Eltek Polska Sp. z.o.o. Gertek Stromversorgungen Eltek Power Eltek Middle East.
Place Francois Mitterand Rm. 812 Eight ul.Szczawiowa 53 B GmbH. Supplies Ptd. Ltd. P.O. Box 33090
01 Tour Crédit Lyonnais Commercial Tower 70-010 Szczecin P.O. Box 1135 194 Pandan Loop ≠07 Dubai
59777 Euralille 8 Sun Yip Street Poland Friedrich-Luber-Str. 31 19 Pantec Ind. Complex United Arab Emirates
France Chaiwan, Hong Kong Tel: +48 914825787 D-90592 Schwartzenbruck Singapore 128383 Tel: +971 4 481637
Tel: +33 3 20 12 52 10 Tel: +85 228982689 Fax: +48 914825786 Germany Tel: +65 7732326 Tel/Fax: +971 4 485802
Fax: +33 3 20 12 52 25 Fax: +85 228983189 Tel: +49 9128 9164 86 Fax: +65 7753602