Sie sind auf Seite 1von 13

Electrical Power and Energy Systems 60 (2014) 245–257

Contents lists available at ScienceDirect

Electrical Power and Energy Systems


journal homepage: www.elsevier.com/locate/ijepes

Differential relaying scheme for tapped transmission line connecting


UPFC and wind farm
L.N. Tripathy, Manas Kumar Jena, S.R. Samantaray ⇑
School of Electrical Science, Indian Institute of Technology Bhubaneswar, India

a r t i c l e i n f o a b s t r a c t

Article history: This paper presents a differential relaying scheme for a tapped transmission line in presence of Unified
Received 1 April 2013 Power Flow Controller (UPFC) and wind-farm together. The process starts at retrieving the fault current
Received in revised form 22 January 2014 signal at the respective busses connecting the lines involving fault and pre-processing it using multi-res-
Accepted 25 February 2014
olution based Wavelet transform to derive third level approximate coefficients (CA3). Further the Dis-
crete Fourier Transform (DFT) is used to compute the RMS value of the signal from the reconstructed
signals expressed in terms of Wavelet approximate coefficients. Once the RMS value of the signal is esti-
Keywords:
mated the operating (tripping) and restraining signals are computed for fault detection and classification
Teed transmission line
Discrete Wavelet Transform (DWT)
in transmission lines including UPFC and wind-farm. The proposed scheme has been extensively tested
Discrete Fourier Transform (DFT) on faulted conditions with wide variations in operating parameters and the test results indicate that it
Unified Power Flow Controller (UPFC) can reliably detect and classify faults including the ability to discriminate internal faults from external
Wind-farm faults in transmission lines with a response time of less than two cycles from fault inception.
Ó 2014 Elsevier Ltd. All rights reserved.

1. Introduction transient state and thus, has significant impact on the performance
of existing protection schemes. When Static Synchronous Series
In order to optimize the operational aspects of generation, Compensator (SSSC) of the UPFC consumes active power, the
transmission and distribution of electric power the transmission apparent resistance will increase and when SSSC consumes reac-
networks are very often pushed to their physical limits. However, tive power, the apparent reactance will increase. Compared to
to meet the electric market demand the utilities are forced to rely Static Synchronous Compensator (STATCOM), UPFC has greater
on the already existing networks. Thus, with such increasing stress influence on the apparent resistance due to the active power
on the existing transmission lines, the use of Flexible AC Transmis- injection and consumption by both SSSC and STATCOM. For a
sion Systems (FACTS) devices [1] becomes an important and effec- phase-to-phase fault, there is a tendency for the distance relay to
tive option. FACTs devices offer a versatile alternative to under-reach and also for the earth element to mal-operate. Fur-
conventional reinforcement methods [2]. Among them, the Unified ther, when SSSC injects reactive power into the system, it behaves
Power Flow Controller (UPFC) [3–5] is an important FACTS device like a series capacitor and the apparent impedance decreases. On
which is used extensively for improving the utilization of the exist- the other hand, when SSSC consumes reactive power it appears like
ing transmission system. The UPFC offers new horizons in terms of series inductance and the apparent impedance increases [3].
power system control with the potential to independently control Hence, depending upon the operating condition of UPFC during
three important power system parameters, for instance bus volt- the fault, the distance relay may under reach or over reach.
age, line active power and line reactive power. While the use of In recent years, integration of wind-farms to the grids at differ-
the UPFC improves the power transfer capability and stability of ent levels of voltage across the world has been increased and the
a power system, certain other problems emerge in the field of share of such farms in the transmission system also rising day by
power system protection in particular the transmission line pro- day. Integration of wind-farms improves the reliability of the
tection [6], affecting greatly the reach of the distance relay. Due power network. The challenges that power system encounter due
to presence of UPFC in a fault loop the voltage and current signals to integration of wind-farm is primarily due to uncontrollable
at the relaying point is affected in steady state as well as in wind speed which results in variation of voltage, frequency and
output power. The frequency and voltage fluctuations due to speed
⇑ Corresponding author. Tel.: +91 9437305131; Fax: +91 674 2301983. variation have been solved to a greater extent by power electron-
E-mail address: sbh_samant@yahoo.co.in (S.R. Samantaray). ics-based control arrangement provided in each generating unit

http://dx.doi.org/10.1016/j.ijepes.2014.02.024
0142-0615/Ó 2014 Elsevier Ltd. All rights reserved.
246 L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257

of the wind-farm. The output power of a generating unit has a non- Decomposition, system studied, proposed method, results analysis,
linear relationship with the wind speed and when the speed is be- Discussion and conclusions.
yond the limit, the farm cannot contribute to the grid. Due to
under/over voltage conditions a group of turbines may trip while
2. Wavelet transform based decomposition
others may remain in operation. The transmission system that con-
nects such farms will be exposed to such a continuously changing
Wavelet transform is a powerful tool for fault transient analysis
environment. Thus, the protection becomes a serious concern for
and Discrete Wavelet Transform (DWT) [16,17] is a special case of
the transmission system integrated with wind-farms [7]. Further,
WT that provides a compact representation of a signal in time and
when both UPFC [8] and wind-farms are integrated together in
frequency domain that can be computed efficiently. It provides
the transmission line the protection become more critical and
multi-resolution analysis of the signal i.e. analyzes the signal at dif-
the performance of the conventional relaying scheme is greatly
ferent frequencies giving different resolutions. It allows long time
affected.
interval window for more precise low-frequency information and
Due to growth of power system size and complexity, the multi
short time interval window for high-frequency information. It does
terminal based tapped transmission lines are increasingly used.
not use time–frequency region, rather it uses a time-scale region.
However, different teed configurations pose special difficulties
Wavelet transform decomposes a signal into a set of basis func-
and bring new challenges to the transmission line protection. Com-
tions, known as wavelets. Wavelets are obtained from a single pro-
bined effect of multi terminal based tapped transmission line along
totype wavelet called mother wavelet by dilations and shifting. The
with UPFC and wind-farms together makes the protection require-
continuous wavelet transform of a signal x(t) is given by
ments more demanding and challenging over conventional relaying
Z 1
schemes. The conventional distance relaying schemes are based on 1 ðt  bÞ
tripping decision using single end data and thus, fails to provide CWTðx; b; aÞ ¼ pffiffiffi xðtÞw dt ð1Þ
a 1 a
unit protection for complex transmission networks including FACTs
and wind-farms. Some of the protection schemes for transmission where wa;b ðtÞ ¼ w ðtbÞ
a
is the mother wavelet, a = dilation parameter
line using current differential principle have been proposed to solve (Scale factor), b = translation parameter.
the problems associated with tapped transmission lines [9–11]. Discrete Wavelet Transform (DWT) transforms [19–21] is a dis-
However, none of these schemes could provide reliable protection crete time signal to a discrete wavelet representation. It converts
as they might fail either in detecting high resistance faults or differ- an input series x0, x1, . . ., xn into one high-pass wavelet coefficient
entiating internal faults from external ones. In [12], the protection series and one low-pass wavelet coefficient series (of length n/2
scheme of simple tapped transmission line is presented. However, each) given by:
this research work does not address the protection issues for FACTs
X
k1
based transmission lines with wind integration. Looking at the Hi ¼ x2in  sn ðzÞ ð2Þ
aforementioned problems, there is a strong motivation to build a n¼0
new differential relaying scheme for protection of the complex
transmission network including UPFC and wind-farm. X
k1
The wide-area protection scheme needs a robust and reliable Gi ¼ x2in  t n ðzÞ ð3Þ
communication platform. Communications requirements needed n¼0

for power system protection are more stringent [13] and channel
where sn(Z) and tn(Z) are called wavelet filters, k is the length of the
delay is one of the major concern. Modern day high speed commu-
filter, and i = 0,. . ., [n/2]1.
nication networks, typically use Synchronized Optical Network
Features are extracted by pre-processing the current signal of
(SONET) or Synchronized Digital Hierarchies (SDH) standard for
each phase at different substations using wavelet transform. The
communication with transmission rates of the order of 274.2 Mbps
db4 (Daubechies-4) mother wavelet is selected as it is well suited
or 155.5 Mb/s, respectively. They permit ‘‘network protection ‘‘that
for power system fault and transient analysis. In the proposed
is, during failure of a communication link, communication services
scheme a sampling frequency of 20 kHz (400 samples per cycle
are restored by reconfiguring flow of information in alternate
in 50 Hz system) is considered. The signal is decomposed into three
paths. A typical example is self healing ring architecture used with
levels of decomposition resulting in ‘‘a-1 (0–10 kHz) and d-1 (10–
SONET [13]. In such networks, synchronization by delay equalizers
20 kHz)’’ at level 1, ‘‘a-2 (0–5 kHz) and d-2 (5–10 kHz)’’ at level 2,
become difficult due to channel asymmetry. Due to channel asym-
and ‘‘a-3 (0–2.5 kHz) and d-3 (2.5–5 kHz)’’ at level 3 as shown in
metry, communication delays for transmission and reception paths
Fig. 1. The approximate coefficient ‘‘a-3’’ contains fundamentals
are not identical. Thus, the current samples are time stamped by a
(50 Hz), third (150 Hz), fifth (250 Hz) and seventh (350 Hz) har-
global positioning system (GPS) which enables retrieving signals
monic components of the faulted current signals. The third level
with same time-stamp and thus, providing immunity to channel
reconstructed current signal (A-3) of each phase at each substation
delays, asymmetry, etc. Further, dynamic estimate of the channel
are derived from approximate coefficient (a-3) of respective phases
delay can be easily maintained by subtracting the GPS time stamp
at each substation. The RMS values of the fundamental current sig-
at the sending end from the receiving end time stamp. This permits
nal is extracted from reconstructed current signal (A-3) using Dis-
back up operation even during GPS failure modes. The proposed
crete Fourier Transform (DFT) and are used to compute operating
scheme can reliably work on the communication platform , which
and restraining functions for effective and reliable relaying
is highly suitable for wide-area protection schemes [13,14].
decision.
The proposed differential relaying scheme is based on pre-pro-
cessing the faulted current signals using Wavelet transform [15–
17] and approximate coefficients are reconstructed to compute 3. System studied
the operating and restraining signals for final decision making
using Discrete Fourier Transform (DFT) [18] . The scheme is exten- The studied 500 kV, 50 Hz power system is illustrated in Fig. 2.
sively tested on various fault conditions with wide variations in In this system there are three substations and the UPFC is located
operating conditions and provides effective protection measure at midpoint of the transmission line (distributed model). and the
with a speed response of 1.65 cycles from fault inception. The wind-farm is connected as substation-2. Hence, the system con-
following sections deal with Wavelet Transform based sists of three sources (wind farm as one of the source), UPFC and
L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257 247

d1(n)
X(n) H0
(10-20KHz)
(0-20KHz)
d2(n)
H0
(5-10KHz)
d3(n)
G0 H0 (2.5-5KHz)

a1(n)
G0
(0-10KHz) a3(n)

a2(n) (0-2.5KHz)
G0
(0-5KHz) Used for
reconstruction

Fig. 1. Three level wavelet decomposition tree.

Bus-1 500KV Bus-2


Transmission line
200 k.m 200 k.m
Wind Farm
UPFC
(DFIG)

Substation-1 Internal Faults 70 k.m Substation-2


Bus-3

t
ul
Relay

Fa
al
rn
te
Ex
Substation-3

Fig. 2. Simulated teed transmission system.

associated components. The transmission line parameters and the line. The details of the UPFC modelling and its controller are
source parameters are given below derived from [3].
Transmission line parameter: The wind-farm consists of 40 numbers of wind turbines each of
R1 = 0.01537(X/km): Positive sequence resistance capacity 1.5 MW, totalling 60 MW connected to the 500 kV system
R0 = 0.04612(X/km): Zero sequence resistance through a 575 V/500 kV, 70 MVA transformer at substation-2. Wind
L1 = 0.8858  103(H/km):Positive sequence inductance turbines use a Doubly-Fed Induction Generator (DFIG) consisting of
L0 = 2.654  103(H/km): Zero sequence inductance a wound rotor induction generator and an AC/DC/AC IGBT-based
C1 = 13.06  109(F/km): Positive sequence capacitance PWM converter. The stator winding is connected directly to the
Source parameter: 50 Hz grid while the rotor is fed at variable frequency through the
V1 = 500 kV\ d1° (substation-1), 50 Hz, short-circuit level AC/DC/AC converter. The DFIG technology allows extracting maxi-
1500 MVA, d1 = 12° mum energy from the wind for low wind speeds by optimizing
V2 = 500 kV\ d2° (substation-2), 50 Hz, 60 MW the turbine speed, while minimizing mechanical stresses on the
Wind-farm is connected through a 575 V/500 kV, 70 MVA trans- turbine during gusts of wind. The optimum turbine speed produc-
former, d2 = 8° ing maximum mechanical energy for a given wind speed is propor-
V3 = 500 kV\ d3° (substation-3 voltage), 50 Hz, short-circuit tional to the wind speed. For wind speeds lower than 10 m/s the
level 1500 MVA, d3 = 0° rotor is running at sub- synchronous speed. At high wind speed it
The 100-MVA UPFC is installed in the middle of the transmis- is running at hyper synchronous speed. The details of the DFIG
sion line of length 400 km (at 200 km from relaying end). The based wind-farm modeling and its controller are derived from [7] .
most common operating mode of the UPFC is automatic power The proposed study is tested on wide variations in fault param-
flow control mode. In this mode of operation, series injection eters as well as operating conditions of the power network and are
voltage is dynamically adjusted to maintain the power flow in given as follows:
the line to the reference settings. Thus, in this proposed scheme,
automatic power flow control mode of UPFC is considered [3].  Variation in fault resistance (Rf) from 0 to 150 X.
UPFC consists of two 48-pulse voltage source inverters which  Variation in fault location: 30%, 50%,70% and 90% of the line
are connected through two 2500 lF common DC capacitors. The from substation-1.
first inverter known as STATCOM connects into the transmission  Variation in fault inception angle(FIA): 0°, 30°, 60°, 90°, 120°, 150°.
system through a 500/20 kV D/Y shunt transformer and injects  Different types of fault: a–g, b–g, c–g, a–b, b–c, c–a, ab–g, bc–g,
or consumes reactive power to the transmission system to regu- ca–g, a–b–c.
late the voltage at the connecting point. Another inverter known  UPFC series injected voltage (Vse) varied for 0–15% of the nor-
as static synchronous series compensator (SSSC) connects into the mal voltage.
system through a 20 kV/60 kV Y/Y series transformer to inject an  Variation in wind speed: 5 m/s, 10 m/s, 15 m/s, 20 m/s, 25 m/s.
almost sinusoidal voltage of variable magnitude and angle in ser-  Reverse power flow.
ies with the transmission line to regulate the power flow through  Variation in source impedance.
248 L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257

4. Proposed method Iop ¼ ðIa1  Ia2  Ia3 Þ ð4Þ

Fig. 3 illustrates the schematic of the proposed relaying scheme. Ires ¼ ðIa1 þ Ia2 þ Ia3 Þ=3 ð5Þ
The system consists of two 500 kV Substation with 1500 MVA
short-circuit level, connected to a wind farm of 60 MW where Ia1, Ia2, Ia3 are the fundamental values of reconstructed cur-
(1.5 MW  40) capacity through a teed transmission line and rent signals of a-phase of substation-1, 2 and 3, respectively. The
transformer. The current signals from each substation are retrieved spectral energies (expressed in the fundamental current square)
using Current Transformer (CT) and brought to the signal process- of Iop and Ires are computed using the moving average window of
ing unit through Analogue to Digital converter (ADC). The third le- half cycle length to obtain the operating signal (Eopf) and restraining
vel reconstructed current signal (A-3) of each phase at each signal (Eref) and are given by:
substation are derived from approximate coefficient (a-3) of the X2
respective phases at each substation using DWT. The RMS values Eopf ¼ Iop ð6Þ
of the fundamental current signal is extracted from the recon- N

structed current signal (A-3) using DFT and are used to compute
X
the operating (Eopf) and restraining quantity (Eref) to achieve an Eref ¼ I2res ð7Þ
effective relaying decision. N
The fundamental operating and restraining quantity for the dif-
ferential relay are found out as follows: where N is the number of samples in the sliding window.

500KV
Bus-1 Bus-2
Transmission
line
200 k.m 200 k.m Wind
UPFC Farm
(DFIG)

Substation-1 70 k.m Substation-2

COMMUNICATION
COMMUNICATION
COMMUNICATION

Bus-3
CHANNEL
CHANNEL
CHANNEL

Substation-3

EXTRACTION OF THIRD LEVEL APPROXIMATE COEFFICIENT OF


CURRENT SIGNALS(a-3) FROM INSTANTANEOUS CURRENT
SIGNALS USING DWT

EXTRACTION OF RECONSTRUCTED CURRENT SIGNALS (A-3)


FROM THIRD LEVEL APPROXIMATE COEFFICIENT OF CURRENT
SIGNALS(a-3)

EXTRACTION OF RMS VALUE OF FUNDAMENTAL CURRENT


SIGNALS FROM A-3 USING DFT

CALCULATION OF OPERATING(Eopf) AND RESTRAINING


QUANTITY(Eref)

COMPARISION BETWEEN OPERATING AND RESTRAINING


QUANTITY

FINAL RELAYING DECISION

Fig. 3. Proposed relaying scheme.


L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257 249

The discrimination between internal and external fault can be signals and it is observed that the faulted phase get affected due
achieved by comparing the operating signal with the restraining to inception of a–g, a–b, a–b–g, a–b–c faults (created on the trans-
one as follow: mission line at a distance of 100 km from substation-1 with fault
resistance of 1 X and fault inception angle of 0°, initiated at 0.3 s
Eopf P gEref Alarm=Trip Signal
i.e. sample no-6000), respectively. Fig. 4i shows the operating
quantity of the proposed relay which is at higher level compared
Eopf < gEref No  operation
to the restraining quantity in case of internal faults and allows
where g is known as scale factor (threshold) which is set to provide the relay to issue the tripping signal.
the relay with minimum pick-up current. The precise value of g,
which is most suitable for a particular circuit, can be determined
based on the parameters and operating conditions of the system. 5.2. Effect of the inception angle
In our purposed scheme the value of scale factor g is considered
as ‘3’. The selection of threshold depends upon the configuration Fig. 5 shows the variation of spectral energies (Eopf, Eref) with re-
of the system and its operating conditions. The threshold has been spect to different fault inception angles for a A–G fault at 30% of the
selected after series of observations including extreme operating line from substation-1. It is observed that fault inception angle has
conditions and found to work effectively under such circumstances. marginal impact on Eopf and Eref. Thus, the fault inception angle
This includes wide variations in UPFC control parameters, wind does not affect the performance of the proposed differential relay-
speed, fault locations, fault resistance, internal and external fault ing scheme.
situations. Further, the threshold selected is at the lowest end for
obtaining reliable performance considering wide variations in oper-
ating conditions. 5.3. Effect of the fault resistance

5. Simulation results and discussion Faults with high resistance generally affect the performance of
the conventional relaying scheme. Many algorithms related to teed
Sim-Power Systems (SIMULINK) is used to model the studied transmission line connecting both UPFC and wind-farm fails to de-
power system equipped with UPFC and connected to the wind- tect faults with high resistance. In order to test the effect of the
farms through a tapped transmission line. The performance of change in fault resistance (RF), the validation is carried out for an
the proposed differential relaying scheme is observed under the A–G fault at 30% from the Substation-1 with zero fault inception
following faulted conditions as follow. angle with different values of RF (RF = 0–150°X). Fig. 6 confirms
that the magnitude of both Eref and Eopf are changing as RF is
5.1. Internal fault increasing from 0 to 150 X. However, Eopf stays at much higher le-
vel compared to Eref for each fault resistance and thus, makes the
Different types of internal faults are simulated on the transmis- relaying scheme reliable against in-zone internal faults. It has been
sion line and the proposed differential scheme is validated . The found that the impact of high resistance fault (RF = 0–150 X) has no
snapshot of the fault currents are shown in Fig. 4a for fault current significant effect on the performance of the proposed relaying
with UPFC alone connected to transmission line for A–G fault scheme.
100 km from substation-1 and Fig. 4b for fault current with
wind-farm alone connected to transmission line for A–G fault
100 km from substation-1. It is observed that the fault current sig- 5.4. Effect of wind speed
nal is more distorted in case of wind-farm integration compared to
only UPFC in the line. Further, the voltage at the Shunt inverter ter- The output power of a wind farm has a nonlinear relationship
minal of the UPFC for A–G fault before UPFC (100 km from substa- with the wind speed which greatly affect the conventional relaying
tion-1) is shown in Fig. 4c and the voltage at the series inverter scheme. The purposed relaying scheme is tested under different
terminal of UPFC for A–G fault before UPFC (100 km from substa- wind speed (varies from 5 m/s to 25 m/s) at faulted condition. It
tion-1) is shown in Fig. 4d. The series inverter terminal voltage in- is observed that the operating and restraining quantities vary with
creases after the fault inception compared to pre-fault situation as respect to wind speed as shown in Fig. 7. However, during internal
the series inverter tries to feed the fault occurring on the transmis- fault condition the operating quantity is always greater than the
sion line. Figs. 4e–4h show the reconstructed third level current restraining quantity and thus, making the relay reliable.

4
Fault current with UPFC alone connected to transmission line
x 10
1.5

1 A-G Fault at 0.3 Second


(6000 Sample)
Magnitude of I a

0.5

-0.5

-1
0.2 0.25 0.3 0.35 0.4 0.45 0.5
Time in Second

Fig. 4a. Fault current with UPFC alone connected to transmission line for A–G fault 100 km from substation-1.
250 L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257

Fault current with Wind-Farm alone connected to Transmission line


4
x 10
1.5

Magnitude of I a
Fault inception at 0.3 Second
(6000 Samples)
0.5

-0.5

-1
0.2 0.25 0.3 0.35 0.4 0.45 0.5
Time in Second

Fig. 4b. Fault current with wind-farm alone connected to transmission line for A–G fault 100 km from substation-1.

Shunt Inverter terminal voltage for A-G fault before UPFC in perunit
3
Va
Vb A-G fault at 6000 Sample
Voltage Magnitude

2
Vc

-1

-2
5000 5500 6000 6500 7000 7500 8000 8500 9000
Sample

Fig. 4c. Shunt inverter terminal voltage of UPFC for A–G fault before UPFC (100 km from substation-1).

Series Inverter terminal voltage for A-G fault before UPFC in perunit
1
Va A-G Fault at
Voltage Magnitude in PU

6000 Sample
Vb
0.5 Vc

-0.5

-1
5000 5500 6000 6500 7000 7500 8000 8500 9000
Sample

Fig. 4d. Series inverter terminal voltage of UPFC for A–G fault before UPFC (100 km from substation-1).

5.5. Discrimination between internal and external faults 5.6. Effect of variation in source impedance

In order to check the reliability and stability of the proposed In order to study the impact of variation in source impedance
relaying scheme, a LL–G internal and external fault (AC–G) is cre- on the proposed relaying scheme, the fault conditions are simu-
ated on the transmission line. Faults outside the zone of protection lated for different values of source impedance and the result is
are defined as external faults as mentioned in Fig. 2. It is observed shown in Fig. 10. For a particular type of fault (A–G fault at a dis-
that the operating quantity suddenly jumps and stays well above tance of 100 km from substation-1) the source impedance are var-
the restraining quantity after the inception of fault as shown in ied and the operating and restraining quantities are compared. It is
Fig. 8 and thus, the relaying scheme becomes more dependable. observed that with increase in source impedance of substation-1
The same fault was created at external relay zone (Fig. 9) and it for a A–G fault at a distance 100 km from substation-1, both oper-
is observed that both operating and restraining quantities increase ating and restraining quantities vary marginally but the operating
however, the operating quantity remains well below the restrain- quantity is always greater than the restraining quantity and the re-
ing quantity and thus, the proposed scheme becomes selective. lay becomes more dependable.
L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257 251

Fault current of different phases for A-G Fault


7000
Current in a-phase
Current in b-phase
6000 Current in c-phase

Magnitude of fault Current


5000

4000

Fault Inception at 6000 Samples


3000 or 0.3 Second

2000

1000

0
4000 5000 6000 7000 8000 9000 10000
Samples

Fig. 4e. Magnitude of different phase currents for a–g fault at a distance 100 km from substation-1.

Fault current of different phases for Internal a-b fault


9000

8000 Current in a-phase


Current in b-phase
Magnitude of fault Current

7000 Current in c-phase

6000

5000

4000 a-b fault at 6000 Samples


or 0.3 Second
3000

2000

1000

0
4000 5000 6000 7000 8000 9000 10000
Samples

Fig. 4f. Magnitude of different phase currents for a–b fault at a distance 100 km from substation-1.

Fault current of different phases for Internal a-b-g fault


10000
Current in a-phase
9000 Current in b-phase
Current in c-phase
Magnitude of fault Current

8000
7000

6000
5000
a-b-g fault at 6000 Samples
or 0.3 Seconds
4000
3000

2000
1000

0
4000 5000 6000 7000 8000 9000 10000
Samples

Fig. 4g. Magnitude of different phase currents for a–b–g fault at a distance 100 km from substation-1.
252 L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257

Fault current of different phases for Internal a-b-c fault


12000
Current in a-phase
Current in b-phase
10000 Current in c-phase

Magnitude of fault Current


8000

6000

a-b-c fault at 6000 Samples


4000 or 0.3 Second

2000

0
4000 5000 6000 7000 8000 9000 10000
Samples

Fig. 4h. Magnitude of different phase currents for a–b–c fault at a distance 100 km from substation-1.

7
E opf and Eref for Internal a-g fault
x 10

3.5 Operating Current


Restraining current
Magnitude of E opf and E ref

2.5

2
Internal a-g fault at
1.5 6000 samples(0.3 Second)

0.5

0
4000 5000 6000 7000 8000 9000 10000
Samples

Fig. 4i. Eopf and Eref for a–g fault at a distance 100 km from substation-1.

Effect of fault inception angle for internal A-G solid fault on E opf and E ref
7
x 10
3.5
Eopf
Eref
3
Magnitude of Eopf , E ref

2.5

1.5

0.5
0 20 40 60 80 100 120 140 160 180
Fault Inception Angle (FIA) in degree

Fig. 5. Effect of fault inception angle on Eopf and Eref for internal A–G fault at a distance 100 km from substation-1.
L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257 253

Effect of fault Resistance for internal A-G solid fault on E opf and E ref
7
x 10
3.5
Eopf
3 Eref

2.5

Eopf and E ref 2

1.5

0.5

0
0 50 100 150
Fault Resistance in Ohm

Fig. 6. Effect of fault resistance on Eopf and Eref for internal A–G fault at a distance 100 km from substation-1.

Effect of Wind Speed for internal A-G fault on E opf and E ref
7
x 10
4

3.5
Eopf
Eopf and E ref

3 Eref

2.5

1.5

1
5 10 15 20 25
Wind Speed in meter per second

Fig. 7. Effect of different wind speed on Eopf and Eref for internal A–G fault (fault resistance = 1 O) at a distance 100 km from substation-1.

7 Eopf and E ref for Internal a-c-g fault


x 10
7

Operating Current
6 Restraining current
Magnitude of Eopf , E ref

4
Internal a-c-g fault at 6000 samples
(0.3 Seconds)
3

0
4000 5000 6000 7000 8000 9000 10000
Samples

Fig. 8. Variation of Eopf and Eref for internal AC-G fault (fault resistance = 1 O) at a distance 100 km from substation-1.
254 L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257

5 E opf and E ref for external a-c-g fault


x 10
8

7 Operating Current
Restraining current

Magnitude of Eopf , E ref 5


External a-c-g fault at 6000 Samples
4 (0.3 Seconds)

0
4000 5000 6000 7000 8000 9000 10000
Samples

Fig. 9. Variation of Eopf and Eref for external AC-G fault(fault resistance = 1 X) at a distance 100 km from substation-1.

Effect of Source Impedance for internal A-G fault on E opf and E ref
7
x 10
5
Eopf
Eref
4.5

4
Eopf and E ref

3.5

2.5

1.5
4.2 4.4 4.6 4.8 5 5.2 5.4 5.6 5.8 6
Sending End Source Impedance 'Z' in Ohm

Fig. 10. Effect of source impedance on Eopf and Eref for internal A–G fault(fault resistance = 1 O) at a distance 100 km from substation-1.

Table 1
6. Performance assessment Types of fault verses decision output.

Types of fault a-Phase b-Phase c-Phase


The previous section deals with the development of a differen-
tial relaying scheme for transmission line protection in presence of a–g 1 0 0
b–g 0 1 0
UPFC and wind-farm. To assess the performance of the proposed
c–g 0 0 1
intelligent relaying scheme, three statistical metrices are consid- a–b 1 1 0
ered and defined as follows b–c 0 1 1
c–a 1 0 1
(i) Dependability: Dependability is defined as the measure of the a–b–g 1 1 0
b–c–g 0 1 1
certainty that the relays will operate correctly for all the c–a–g 1 0 1
faults for which they are designed to operate. a–b–c 1 1 1

Dependability ¼ Total number of fault cases predicted=


Total number of actual fault cases:
Table 2
(ii) Security: Security is defined as the measure of the certainty Dependability, security and yield comparisons for different types of faults.
that the relays will not operate incorrectly (mal-operate) Types of fault Dependability (%) Security (%) Yield (%)
for any other power system disturbance.
L–G 99.86 100 99.86
L–L 99.21 99.6 99.32
Security ¼ Total numberof external faults predicted as external fault= L–L–G 98.8 100 99.46
Total number of external faults L–L–L 99.78 99.46 99.6
L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257 255

Table 3
Dependability comparison with variations in fault parameters.

Types of Dependability (%) RF = 1 X, Dependability (%) RF = 50 X, Dependability (%) RF = 100 X, Dependability (%) RF = 150 X,
fault FIA = 30° FIA = 45° FIA = 60° FIA = 90°
L–G 100 99.56 99.78 98.69
L–L 99.23 98.79 99.23 98.79
L–L–G 100 99.84 99.63 98.99
L–L–L 99.87 99.12 99.69 99.58

Table 4
Performance comparison between proposed differential scheme and distance relaying approach.

Types of Fault location (45% of total line length from Fault location (85% of total line length from Fault location (95% of total line length from
fault substation-1) substation-1) substation-1)
Dependability (%) Dependability (%) Dependability (%)
Distance relaying Differential scheme Distance relaying Differential scheme Distance relaying Differential scheme
(single_end (both_end information) (single_end (both_end information) (single_end (both_end information)
information) information) information)
L–G 99.42 99.86 52.16 99.42 15.62 99.88
L–L 98.56 99.98 46.28 99.42 18.24 98.13
L–L–G 99.62 99.87 39.78 98.99 17.42 98.96
L–L–L 98.96 99.59 45.46 99.86 14.52 99.74

(iii) Yield: Yield indicates how many fault cases are exactly pre- is carried out on total 400 fault cases (100 for each category of
dicted against the same fault situations (That means a-g fault), with wide variations in operating conditions. Dependability
fault must be predicted a-g and so on) of the proposed relaying scheme is found to be close to 99% in all
the test cases which is the most significant result compare to exist-
Yield ¼ Total number of correct fault cases predicted= ing relaying schemes. The overall security is 99.5% as some cases of
L–L and L–L–L external faults which are predicted as internal fault
Total numberof fault cases predicted:
by the proposed relaying scheme. Yield of the scheme is close to
The proposed relaying scheme is tested for different types of 99.5% in all types of fault. Out of all the above performance indices
internal and external faults. The final relaying decision logic ‘1’ (i.e. dependability, security and yield), dependability is the most
indicates the internal fault condition at which the relay issues a important attribute of any relaying scheme. If there is a fault in
tripping signal, whereas the logic ‘0’ indicates no fault or external the line within the zone of protection, then the protection scheme
fault condition at which the relay restrains. Table 1 depicts the pos- has to operate otherwise the relay should not operate. In order to
sible digital output structure against each fault situation. test the robustness of the proposed relaying scheme different types
Table 2 summarizes the performance of the proposed relaying of faults (L–G, L–L, L–L–G, L–L–L, Total 120 cases: 30 cases from
scheme for different types of fault. The performance assessment each fault category) are simulated with different values of fault

7
Eopf and E ref for Internal a-g fault
x 10
4
Operating Current
Eopf and E ref

3 Restraining current

2 Fault inception at 6000 Samples

0
4000 5000 6000 7000 8000 9000 10000
Samples

Digital output
6
Eopf/Eref
Decision Output

5
Digital output
4 Issue of Tripping Signal
Fault at 6000 sample Threshold
3

1
4000 5000 6000 7000 8000 9000 10000
Samples

Fig. 11. Response Time of the proposed relaying scheme for internal A–G fault(fault resistance = 1 O) at a distance 100 k.m from substation-1.
256 L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257

Eopf and E ref for Internal a-g fault under reverse power flow condition
6
x 10
10

8 Operating Current

Eopf and E ref


Restraining current
6
Fault inception at 6000 Samples
4

0
4000 5000 6000 7000 8000 9000 10000
Sample

Digital output

6
Decision Output

Eopf/Eref
5 Digital output
4 Fault at 6000 sample Issue of Tripping Signal Threshold
3
2
1
4000 5000 6000 7000 8000 9000 10000
Sample

Fig. 12. Response of Eopf and Eref for internal A–G fault (fault resistance = 1 X) at a distance 100 km from substation-1 under reverse power flow condition.

resistances RF and FIA. Table 3 depicts the test results under wide 7. Conclusions
variations in RF (1–150 X) and FIA (30–90°). It is observed that
the dependability becomes more than 98 % considering high resis- A combined wavelet and DFT based differential relaying scheme
tance faults (150 X) and FIA of 90°. This shows the effectiveness of for transmission line protection including UPFC and wind-farm is
the proposed differential scheme for transmission line protection proposed. The scheme works on a set threshold of the computed
including UPFC and wind-farms. operating and restraining signals to issue or suppress the tripping
To compare the effectiveness of the proposed differential relay- signal. The proposed differential scheme is validated for detecting
ing scheme with the conventional relaying scheme, different types and classifying faults including wide variations in fault location,
of faults (30 cases from each type of fault) are simulated at differ- fault resistance, fault inception angle, source impedance and re-
ent location of the transmission line and the performance results verse power flow including variations in UPFC and wind-farm
are depicted in Table 4. It is observed that the distance relaying parameters. It is observed that the relaying scheme is highly effec-
scheme with mho characteristics [22] fails measurably (depend- tive in providing unit protection compared to distance relaying
ability below 20%) for remote end faults compared to the proposed scheme using single end data. The test results indicate that the
differential relaying scheme (dependability close to 99%). This hap- proposed relaying scheme is highly selective in discriminating
pens as the proposed scheme uses both end data providing abso- internal and external faults within two cycles from fault inception.
lute unit protection for the studied transmission network.While
evaluating the speed of the proposed relay it is observed that the
relay is able to issue the tripping signal within 2 cycle from the
fault inception. Fig. 11 shows the response time of the proposed References
relaying scheme and issue of tripping signal in case of an A–G fault
[1] Hingorani NG, Gyugyi L. Understanding FACTS concepts and technology of
at 30% of the line from the substation-1 with zero fault inception flexible AC transmission systems. New York: IEEE Press; 2000.
angle (at sample no = 6000). The relay issues the tripping signal [2] Dash PK, Pradhan AK, Panda G, Liew AC. Adaptive relay setting for flexible AC
once Eopf exceeds the threshold. The threshold value of ‘3’ is se- transmission systems (FACTS). IEEE Trans Power Del 2000;15(1):38–43.
[3] Xiaoyao Zhou, Haifeng Wang, Aggarwal RK, Beaumont Phil. Performance
lected after series of observations including extreme operating evaluation of a distance relay as applied to a transmission system With UPFC.
conditions and found to work effectively under such circum- IEEE Trans Power Del 2006;21(3):1137–47.
stances. This includes wide variations in, fault inception, fault loca- [4] El-Zonkoly AM, Desouki H. Wavelet entropy based algorithm for fault
detection and classification in FACTS compensated transmission line. Int J
tions, fault resistance, internal and external fault situations. Thus, Electr Power Energy Syst 2011;33(8):1368–74.
the threshold is selected on lowest values which can perform con- [5] Ghorbani Amir, Mozafari Babak, Ranjbar Ali Mohammad. Digital distance
sidering all operating conditions. It is observed from Fig. 11 that protection of transmission lines in the presence of SSSC. Int J Electr Power
Energy Syst 2012;43(1):712–9.
the fault inception is at 6000th sample and the tripping signal is is- [6] Amir Ghorbani, Mojtaba Khederzadeh, Babak Mozafari. Impact of SVC on the
sued at 6657th sample. Thus, the response time is 1.65 cycle (657 protection of transmission lines. Int J Electr Power Energy Syst
samples) from the fault inception (1 cycle being 400 samples), 2012;42(1):702–9.
[7] Pradhan AK, Joos Geza. Adaptive distance relay setting for lines connecting
which includes the processing time of both DWT and DFT. Further,
wind farms. IEEE Trans Energy Convers 2007;22(1).
the same fault situation is repeated under reverse power flow con- [8] Dash PK, Pradhan AK, Panda G. Distance protection in the presence of unified
dition considering power angle of d1 = 8° and d2 = 20°. Fig. 12 power flow controller. Int J Electr Power Energy Syst 2000;54(3):189–98.
[9] Ito H, Shuto I, Ayakawa H, Beaumont P, Okuno K. Development of an improved
shows the response of operating and restraining quantity for re-
multifunction high speed operating current differential relay for transmission
verse power flow condition. It is observed from Fig. 12 that as soon line protection. Int Conf DPSP IEE Conf 2001;479:511–4.
as the fault is incepted, the operating quantity starts increasing and [10] koglin HJ, Albert M, Igel M, Lobos T, Waclawek Z. Differential protection of
exceeds the threshold. Hence, the proposed scheme is reliable for multi-terminal lines without synchronization. IEEE Conf 2001;479:133–9.
[11] Forford Thorleif, Messing Lars, Stranne Gunnar. An analogue multi-terminal
all possible types of fault including reverse power flow situation. line differential protection. Int Conf on DPSP, IEE Conf 2004;249:399–403.
L.N. Tripathy et al. / Electrical Power and Energy Systems 60 (2014) 245–257 257

[12] Bhalja B. Maheshwari R.P. Wavelet Transform Based Differential Protection [18] Nam Soon-Ryul, Park Jong-Young, Kang Sang-Hee, Kezunovic Mladen. Phasor
Scheme for Tapped Transmission Line, Industrial Technology, 2006 ICIT 2006. estimation in the presence of DC offset and CT saturation. IEEE Trans Power
IEEE International Conference. Del October 2009;24(4).
[13] Michel G et al. Digital communications for relay protection. <http://www. [19] Duan JD, Zhang BH, Ha HX. A novel approach to faulted phase selection using
pes-psrc.org/>. current traveling waves and wavelet analysis. Proc Int Conf Power Syst
[14] Adamaik MG, Apostolov AP, Begovic MM, Henville CF, Martin KE, Michel GL, Technol 2002;2:1146–50.
et al. Wide area protection–technology and infrastructures. IEEE Trans Power [20] Silveira PM, Seara R, Zurn HH. An approach using wavelet transform for fault
Del 2006;21(2):601–9. type identification in digital relaying. IEEE-PES Summer Meeting
[15] Mallat SG. A Theory for multi-resolution signal decomposition: the wavelet 1999;2:937–42.
representation. IEEE Trans Pattern Anal Machine Intell 1989;1(7):674–93. [21] Hajjar Ammar A. A high speed noncommunication protection scheme for
[16] Dash PK, Samantray SR. Phase selection and fault section identification in power transmission lines based on wavelet transform. Int J Electr Power
thyristor controlled series compensated line using discrete wavelet transform. Energy Syst, Electr Power Syst Res 2013;96(2013):194–200.
Int J Electr Power Energy Syst November 2004;26(9):725–32. [22] Abdelaziz AY, Abdel Rahman M, Moussa MS. Distance protection for multi-
[17] Megahed I, Moussa AM, Bayoumy AE. Usage of wavelet transform in the terminal transmission lines. 2nd International IEEE Conference on Electric
protection of series-compensated transmission lines. IEEE Trans Power Del Jul. Power and Energy Conversion Systems (EPECS) 2011(2013):1–6.
2006;21(3):1213–21.

Das könnte Ihnen auch gefallen