VOLTAGE DROP CALCULATION ( MCC23 → FINAL CIRCUITS)

FEEDER VOLTAGE DROP


BREAKER RATING

CUMULATIVE VOLTAGE
TABULATED CURRENT
CORRECTION

NO. OF SETS PHASE


(In)

SELECTED CABLE
FACTORS

MINIMUM CABLE
LOAD CURRENT

SIMULTANEOUS

NO. OF CORES
DEMAND kVA
REF/CKT NO

VD FACTOR
OVERLOAD

DROP IN %
AMPACITY

SIZE(mm2)
CAPACITY
VOLTAGE

LENGTH
CORRECTION @
TEMPERATURE
SR. NO

(VD1)
It ≥ Iz

IN %
GROUPING

(Iz)
FROM TO REMARKS

(It)
Ib

FACTOR
In ≥ Ib

50°C

(Cg)
(Ca)
AF

AT
1 L1/1, L2/1, L3/1 MCC23 CHILLED WATER PU (02-225) 400 3.3 4.76 100 16 0.9 0.72 NO 18.1 38 1 4 4 18 8.7 0.19 3.04
2 L1/2, L2/2, L3/2 MCC23 PMP-01 (02-225) 400 18.75 27.06 100 50 0.9 0.72 NO 59.1 67 1 4 10 12 3.5 0.28 3.13
3 L1/3, L2/3, L3/3 MCC23 PMP-02 (02-225) 400 18.75 27.06 100 50 0.9 0.72 NO 59.1 67 1 4 10 10 3.5 0.24 3.09
4 L1/4, L2/4, L3/4 MCC23 PMP-03 (02-225) 400 18.75 27.06 100 50 0.9 0.72 NO 59.1 67 1 4 10 9 3.5 0.21 3.06
5 L1/5, L2/5, L3/5 MCC23 PMP-04 (02-225) 400 18.75 27.06 100 50 0.9 0.72 NO 59.1 67 1 4 10 9 3.5 0.21 3.06

Breaker rating changed to 100AT.


6 Changed to 35mm2 from 10mm2 due
L1/6, L2/6, L3/6 MCC23 PMP-05 (02-225) 400 54.45 78.59 100 100 0.9 0.72 NO 125.5 142 1 4 35 19 1.1 0.41 3.26 to It<Iz

Breaker rating changed to 100AT.


Changed to 35mm2 from 10mm2 due
7 L1/7, L2/7, L3/7 MCC23 PMP-06 (02-225) 400 54.45 78.59 100 100 0.9 0.72 NO 125.5 142 1 4 35 20 1.1 0.43 3.28 to It<Iz
Breaker rating changed to 100AT.
Changed to 35mm2 from 10mm2 due
8 L1/8, L2/8, L3/8 MCC23 PMP-07 (02-225) 400 54.45 78.59 100 100 0.9 0.72 NO 125.5 142 1 4 35 21 1.1 0.45 3.30 to It<Iz
9 L1/9, L2/9, L3/9 MCC23 FCU 01 (02-225) / 3 Phase 400 2.77 4.00 100 20 0.9 0.72 NO 22.4 38 1 4 4 8 8.7 0.07 2.92
10 L1/10, L2/10, L3/10 MCC23 FCU 02 (02-213), 3 Phase 400 2.77 4.00 100 20 0.9 0.72 NO 22.4 38 1 4 4 25 8.7 0.22 3.07
11 L1/11, L2/11, L3/11 MCC23 FCU 03 (02-213), 3 phase 400 2.77 4.00 100 20 0.9 0.72 NO 22.4 38 1 4 4 25 8.7 0.22 3.07
12 L1/12 MCC23 FCU 05 (02-219) 230 0.41 1.78 100 20 0.9 0.72 NO 22.3 47 1 3 4 89 8.7 0.60 2.25
13 L2/12 MCC23 FCU 06 (02-211) 230 0.27 1.17 100 20 0.9 0.72 NO 22 47 1 3 4 29 8.7 0.13 1.77
14 L3/12 MCC23 FCU 73 (02-226) 230 0.2 0.87 100 20 0.9 0.72 NO 22 47 1 3 4 27 8.7 0.09 1.73
15 L1/13 MCC23 FCU 74 (02-226) 230 0.28 1.22 100 20 0.9 0.72 NO 22 47 1 3 4 17 8.7 0.08 1.72
16 L2/13 MCC23 FCU 80 (02-229) 230 0.16 0.70 100 20 0.9 0.72 NO 22 47 1 3 4 24 8.7 0.06 1.71
17 L3/13 MCC23 FCU 101 (02-203) 400 5.68 8.20 100 20 0.9 0.72 NO 23 38 1 4 4 14 8.7 0.25 3.10
TOTAL kVA 256.96 MAXIMUM VOLTAGE DROP IN THIS SHEET (3 Phase) 0.45
Chilled Water Pumps after applying demand factor 146.9445 18.61 Total loads minus the chilled water pumps MAXIMUM VOLTAGE DROP IN THIS SHEET (1 Phase) 0.60
Total DF 0.64 165.55 Total demand load without 15% margin
Demand load with 15% margin 190.39

1. FEEDER VOLTAGE DROP IN % (VD1) - Voltage drop between equipments in the "FROM" and "TO" columns
2. MAX. VOLTAGE DROP IN FINAL CIRCUITS % (VD2) - Highest Voltage drop among the branch circuits of Panels in the "TO" column including the final circuits connected to it

3. Voltage drop Equation: Current (Ib) x Length of the cable in Mtrs (L) x VD Factor(V/A/kM) x 100%
400 x 1000
4. Minimum Cable Ampacity (Iz): As per BS7671 appendix 4.5, equation 2, 3 &4