Sie sind auf Seite 1von 406

PCS-902

Line Distance Relay


Instruction Manual

NR Electric Co., Ltd.


Preface

Preface

Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.

Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore, this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.

Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.

This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.

Health and Safety


The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.

When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.

Before working in the terminal strip area, the equipment must be isolated.

Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.

Qualified personnel are individuals who:

 Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;

 Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;

 Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;

 Are trained in emergency procedures (first aid).

Instructions and Warnings


The following indicators and standard definitions are used:

PCS-902 Line Distance Relay i


Date: 2011-03-07
Preface

DANGER!

It means that death, severe personal injury, or considerable equipment damage will occur if safety
precautions are disregarded.

WARNING!

It means that death, severe personal, or considerable equipment damage could occur if safety
precautions are disregarded.

CAUTION!

It means that light personal injury or equipment damage may occur if safety precautions are
disregarded. This particularly applies to damage to the device and to resulting damage of the
protected equipment.

WARNING!

The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.

WARNING!

During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.

Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.

In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.

DANGER!

Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.

WARNING!

 Exposed terminals

Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous

ii PCS-902 Line Distance Relay


Date: 2011-03-07
Preface

 Residual voltage

Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.

CAUTION!

 Earth

The earthing terminal of the equipment must be securely earthed

 Operating environment

The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.

 Ratings

Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.

 Printed circuit board

Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.

 External circuit

When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.

 Connection cable

Carefully handle the connection cable without applying excessive force.

Copyright

Version: R1.01 NR ELECTRIC CO., LTD.

69 Suyuan Avenue. Jiangning, Nanjing 211102, China

P/N: EN_XLBH5102.0086.0012 Tel: +86-25-87178185, Fax: +86-25-87178208

Website: www.nrelect.com, www.nari-relays.com

Copyright © NR 2011. All rights reserved Email: nr_techsupport@nari-relays.com

We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.

The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.

We reserve the rights to make technical improvements without notice.

PCS-902 Line Distance Relay iii


Date: 2011-03-07
Preface

Documentation Structure

The manual provides a functional and technical description of this relay and a comprehensive set
of instructions for the relay’s use and application.

All contents provided by this manual are summarized as below:

1 Introduction
Briefly introduce the application, functions and features about this relay.

2 Technical Data
Introduce the technical data about this relay, such as electrical specifications, mechanical
specifications, ambient temperature and humidity range, communication port parameters, type
tests, setting ranges and accuracy limits and the certifications that our products have passed.

3 Operation Theory
Introduce a comprehensive and detailed functional description of all protective elements.

4 Supervision
Introduce the automatic self-supervision function of this relay.

5 Meaurement and Recording


Introduce the management function (measurment and recording) of this relay.

6 Hardware
Introduce the main function carried out by each plug-in module of this relay and providing the
definition of pins of each plug-in module.

7 Settings
List settings including system settings, communication settings, label settings, logic links and etc.,
and some notes about the setting application.

8 Human Machine Interface


Introduce the hardware of the human machine interface (HMI) module and a detailed guide for the
user how to use this relay through HMI. It also lists all the information which can be view through
HMI, such as settings, measurements, all kinds of reports etc.

9 Configurable Function
Introduce how to make system configuration, function configuration, binary input and binary output
configuration, LED indicator configuration and programming logic through PCS-PC software.

10 Communication
Introduce the communication port and protocol which this relay can support, IEC60970-5-103,
IEC61850 and DNP3.0 protocols are introduced in details.

iv PCS-902 Line Distance Relay


Date: 2011-03-07
Preface

11 Installation
Introduce the recommendations on unpacking, handling, inspection and storage of this relay. A
guide to the mechanical and electrical installation of this relay is also provided, incorporating
earthing recommendations. A typical wiring connection to this relay is indicated.

12 Commissioning
Introduce how to commission this relay, comprising checks on the calibration and functionality of
this relay.

13 Maintenance
A general maintenance policy for this relay is outlined.

14 Decommissioning and Disposal


A general decommissioning and disposal policy for this relay is outlined.

15 Manual Version History


List the instruction manual version and the modification history records.

Typographic and Graphical Conventions

Deviations may be permitted in drawings and tables when the type of designator can be obviously
derived from the illustration.

The following symbols are used in drawings:

&

AND gate

≥1

OR gate

Comparator

BI
Binary signal via opto-coupler

SET I>
Input signal from comparator with setting

EN
Input signal of logic setting for function enabling

PCS-902 Line Distance Relay v


Date: 2011-03-07
Preface

SIG
Input of binary signal except those signals via opto-coupler

XXX
Output signal

Timer
t
t
Time (optional definite-time or inverse-time characteristic)

10ms 0ms
Timer [delay pickup (10ms), delay dropoff (0ms), non-settable]
[XXX] 0ms
Timer (delay pickup, settable)
0ms [XXX]
Timer (delay dropoff, settable)
[XXX] [XXX]
Timer (delay pickup, delay dropoff, settable)
IDMT
Timer (inverse-time characteristic)

---xxx is the symbol

vi PCS-902 Line Distance Relay


Date: 2011-03-07
1 Introduction

1 Introduction

Table of Contents
1 Introduction ...................................................................................... 1-a
1.1 Application....................................................................................................... 1-1
1.2 Function ........................................................................................................... 1-3
1.3 Features ........................................................................................................... 1-5

List of Figures
Figure 1.1-1 Typical application of PCS-902 ............................................................................1-1

Figure 1.1-2 Functional diagram of PCS-902...........................................................................1-2

PCS-902 Line Distance Relay 1-a


Date: 2011-07-06
1 Introduction

1-b PCS-902 Line Distance Relay


Date: 2011-07-06
1 Introduction

1.1 Application
PCS-902 is a digital line distance protection with the main and back-up protection functions, which
is designed for overhead line or cables and hybrid transmission lines of various voltage levels.

PCS-902 Optical fibre channel or PLC channel PCS-902

Communication channel via direct dedicated fibre, MUX or PLC

Figure 1.1-1 Typical application of PCS-902

Main protection of PCS-902 comprises of pilot distance protection (PUTT, POTT, blocking and
unblocking) and pilot directional earth-fault protection ( selectable for independent communication
channel or sharing channel with POTT), which can clear any internal fault instantaneously for the
whole line with the aid of protection signalling. DPFC distance protection can perform extremely
high speed operation for close-up faults. There is direct transfer trip (DTT) feature incorporated in
the relay.

PCS-902 also includes distance protection (3 forward zones and 1 reverse zone distance
protection with selectable mho or quadrilateral characteristic), 4 stages directional earth fault
protection, 4 stages directional phase overcurrent protection, 2 stages voltage protection
(under/over voltage protection), breaker failure protection, frequency protection, thermal overload
protection, etc. Moreover, a backup overcurrent and earth fault protection will be automatically
enabled when VT circuit is failure. In addition, stub overcurrent protection is provided for one and a
half breakers arrangement when transmission line is put into maintenance.

PCS-902 has selectable mode of single-phase tripping or three-phase tripping and configurable
auto-reclosing mode for 1-pole, 3-poles and 1/3-pole operation.

PCS-902 with appropriate selection of integrated protection functions can be applied for various
voltage levels and primary equipment such as cables, overhead lines, interconnectors and
transformer feeder, etc. It also supports configurable binary inputs, binary outputs, LEDs and IEC
61850 protocol.

PCS-902 Line Distance Relay 1-1


Date: 2011-07-06
1 Introduction

BUS

52

81

51G 51P
85 21D 21 67G 67P 50BF 49 FR
VT VT

59
50G 50P

FL
Data Transmitt/Receive 51G 51P
27

50S
(Only for one and a half breakers arrangement)
TB
SO
25 79
TF

LINE

Figure 1.1-2 Functional diagram of PCS-902

No. Function ANSI


1 Pilot protection 85
2 DPFC distance protection 21D
3 Distance protection 21
4 Earth fault protection 67G
5 Definite-time earth-fault protection 50G
6 Inverse-time earth-fault protection 51G
8 Phase overcurrent protection 67P
9 Definite-time phase overcurrent protection 50P
10 Inverse-time phase overcurrent protection 51P
11 Overvoltage protection 59
12 Undervoltage protection 27
13 Frequency protection 81
14 Breaker failure protection 50BF
15 Thermal overload protection 49
16 Stub overcurrent protection 50STB
17 Switch onto fault SOTF
18 Phase overcurrent protection when VT circuit failure 51PVT
19 Earth fault protection when VT circuit failure 51GVT
20 Synchronism check 25

1-2 PCS-902 Line Distance Relay


Date: 2011-07-06
1 Introduction

21 Automatic reclosure 79
22 Fault recorder FR
23 Fault location FL

1.2 Function
1. Protection Function

 Distance protection

 Three zones forward phase-to-ground distance elements (mho or quadrilateral


characteristic)

 One pilot zone phase-to-ground distance element (mho or quadrilateral characteristic)


with weakinfeed distance element

 One zone reverse phase-to-ground distance element (mho or quadrilateral characteristic)

 Three zones forward phase-to-phase distance elements (mho or quadrilateral


characteristic)

 One pilot zone phase-to-phase distance element (mho or quadrilateral characteristic)


with weakinfeed distance element

 One zone reverse phase-to-phase distance element (mho or quadrilateral characteristic)

 Blinder for mho characteristic distance element

 Power swing blocking releasing, selectable for each of above mentioned zones

 Deviation of Power Frequency Component (DPFC) distance protection

 Current protection

 Four stages phase overcurrent protection, selectable time characteristic (definite-time or


inverse-time) and directionality (forward direction, reverse direction or non-directional)

 Four stages directional earth fault protection, selectable time characteristic (definite-time
or inverse-time) and directionality (forward direction, reverse direction or non-directional)

 Breaker failure protection

 Optional instantaneously re-tripping

 One stage with two delay timers

 Thermal overload protection

 Stub overcurrent protection

 Switch onto fault (SOTF)

 Via distance measurement elements

 Via dedicated earth fault element

PCS-902 Line Distance Relay 1-3


Date: 2011-07-06
1 Introduction

 Backup protection when VT circuit failure

 Phase overcurrent protection when VT circuit failure

 Earth fault protection when VT circuit failure

 Voltage protection

 Two stages overvoltage protection

 Two stages undervoltage protection

 Frequency protection (optional)

 Four stages overfrequency protection

 Four stages underfrequency protection

 f/dt block criterion for underfrequency protection

 Control function

 Synchro-checking

 Automatic reclosure (single shot or multi-shot (max. 4) for 1-pole AR and 3-pole AR)

 Pilot scheme logic

 Phase-segregated communication logic of distance protection

 Weak infeed logic of pilot distance protection

 Weak infeed logic of pilot directional earth fault protection

2. Logic

 User programmable logic

3. Additional function

 Fault location

 Fault phase selection

 Parallel line compensation for fault location

 VT circuit supervision

 CT circuit supervision

 Self diagnostic

 DC power supply supervision

 Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events and 1024 device logs.

 Disturbance recorder including 64 disturbance records with waveforms (The file format of

1-4 PCS-902 Line Distance Relay


Date: 2011-07-06
1 Introduction

disturbance recorder is compatible with international COMTRADE file.)

 Clock synchronization

– PPS(RS-485)

– IRIG-B(RS-485)

– PPM(DIN)

– SNTP(PTP)

– IEEE1588

– SNTP(BC)

– PPS(DIN)

4. Monitoring

 Number of circuit breaker operation (single-phase tripping, three-phase tripping and


reclosing)

 Channel status

 Frequency

5. Communication

 2 RS-485 communication rear ports conform to IEC 60870-5-103 protocol or DNP3.0 protocol

 1 RS-485 communication rear ports for clock synchronization

 Up to 4 Ethernet ports (depend on the chosen type of MON plug-in module) conform to IEC
61850 protocol, DNP3.0 protocol or IEC 60870-5-103 protocol over TCP/IP

 Up to 2 Ethernet ports via optic fiber (ST interface or SC interface, depend on the chosen type
of MON plug-in module) conform to IEC 61850 protocol, DNP3.0 protocol or IEC 60870-5-103
protocol over TCP/IP

 GOOSE communication function (optional NET-DSP plug-in module)

6. User Interface

 Friendly HMI interface with LCD and 9-button keypad on the front panel.

 1 front multiplex RJ45 port for testing and setting

 1 RS-232 or RS-485 rear ports for printer

 Language switchover – English+ selected language

 Auxiliary software - PCSPC

1.3 Features
 The intelligent device integrated with protection, control and monitor provides powerful

PCS-902 Line Distance Relay 1-5


Date: 2011-07-06
1 Introduction

protection function, flexible protection configuration, user programmable logic and


configurable binary input and binary output, which can meet with various application
requirements.

 High-performance hardware platform and modularized design, MCU (management control


unit)+DSP (digital signal processor). MCU manages general fault detector element and DSP
manages protection and metering. Their data acquisition system is completely independent in
electronic circuit. DC power supply of output relay is controlled by the operation of fault
detector element operates, this prevents maloperation due to error from ADC or damage of
any apparatus.

 Fast fault clearance for faults within the protected line, the operating time is less than 10 ms
for close-up faults, less than 15ms for faults in the middle portion of protected line and less
than 25ms for remote end faults.

 The unique DPFC distance element integrated in the protective device provides extremely
high speed operation and insensitive to power swing.

 Self-adaptive floating threshold which only reflects deviation of power frequency component
improves the protection sensitivity and stability under the condition of load fluctuation and
system disturbance.

 Advanced and reliable ‘power swing blocking releasing′ feature which ensure distance
protection operate correctly for internal fault during power swing and prevent distance
protection from maloperation during power swing

 Flexible automatic reclosure supports various initiation modes and check modes

 Multiple setting groups with password protection

 Powerful PC tool software can fulfill protection function configuration, modify setting and
waveform analysis.

1-6 PCS-902 Line Distance Relay


Date: 2011-07-06
2 Technical Data

2 Technical Data

Table of Contents
2 Technical Data .................................................................................. 2-a
2.1 Electrical Specifications ................................................................................. 2-1
2.1.1 AC Current Input ................................................................................................................ 2-1

2.1.2 AC Voltage Input ................................................................................................................ 2-1

2.1.3 Power Supply ..................................................................................................................... 2-1

2.1.4 Binary Input ........................................................................................................................ 2-1

2.1.5 Binary Output ..................................................................................................................... 2-2

2.2 Mechanical Specifications ............................................................................. 2-2


2.3 Ambient Temperature and Humidity Range .................................................. 2-3
2.4 Communication Port ....................................................................................... 2-3
2.4.1 EIA-485 Port ...................................................................................................................... 2-3

2.4.2 Ethernet Port ...................................................................................................................... 2-3

2.4.3 Optical Fibre Port ............................................................................................................... 2-3

2.4.4 Print Port ............................................................................................................................ 2-4

2.4.5 Clock Synchronization Port ................................................................................................ 2-4

2.5 Type Tests ........................................................................................................ 2-4


2.5.1 Environmental Tests ........................................................................................................... 2-4

2.5.2 Mechanical Tests................................................................................................................ 2-5

2.5.3 Electrical Tests ................................................................................................................... 2-5

2.5.4 Electromagnetic Compatibility ............................................................................................ 2-5

2.6 Certifications ................................................................................................... 2-6


2.7 Protective Functions....................................................................................... 2-6
2.7.1 Fault Detector .................................................................................................................... 2-6

2.7.2 Distance Protection ............................................................................................................ 2-6

2.7.3 Phase Protection................................................................................................................ 2-7

PCS-902 Line Distance Relay 2-a


Date: 2011-07-06
2 Technical Data

2.7.4 Earth Fault Protection ........................................................................................................ 2-7

2.7.5 Overvoltage Protection ...................................................................................................... 2-7

2.7.6 Undervoltage Protection..................................................................................................... 2-7

2.7.7 Overfrequency Protection .................................................................................................. 2-7

2.7.8 Underfrequency Protection ................................................................................................ 2-8

2.7.9 Breaker Failure Protection ................................................................................................. 2-8

2.7.10 Thermal Overload Protection ........................................................................................... 2-8

2.7.11 Stub Overcurrent Protection ............................................................................................. 2-8

2.7.12 Auto-reclosing .................................................................................................................. 2-8

2.7.13 Transient Overreach ........................................................................................................ 2-9

2.7.14 Fault Locator .................................................................................................................... 2-9

2-b PCS-902 Line Distance Relay


Date: 2011-07-06
2 Technical Data

2.1 Electrical Specifications


2.1.1 AC Current Input
Phase rotation ABC
Nominal frequency (fn) 50±5Hz, 60±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In~40In
Thermal withstand
-continuously 4In
-for 10s 30In
-for 1s 100In
-for half a cycle 250In
Burden < 0.15VA/phase @In < 0.25VA/phase @In
Accuracy ±0.5%In
Number Up to 7 current input according to various applications

2.1.2 AC Voltage Input


Phase rotation ABC
Nominal frequency (fn) 50±5Hz, 60±5Hz
Rated Voltage (Un) 100V~130V
Linear to 1V~170V
Thermal withstand
-continuously 200V
-10s 260V
-1s 300V
Burden at rated < 0.20VA/phase @Un
Accuracy ±0.5%Un
Number Up to 6 voltage input according to various applications

2.1.3 Power Supply


Standard IEC 60255-11:2008
Rated Voltage 110Vdc/125Vdc, 220Vdc/250Vdc
Operating Range 80%~120% of rated voltage
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
Burden
Quiescent condition <30W
Operating condition <35W

2.1.4 Binary Input


Rated Voltage 24V 48V 110V 125V 220V 250V
Rated current drain 1.2mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 55%~70% of rated voltage

PCS-902 Line Distance Relay 2-1


Date: 2011-07-06
2 Technical Data

Dropoff voltage <55% of rated voltage


Maximum permissible voltage 120% of rated voltage
Withstand voltage
2000Vac, 2800Vdc
-continously
Response time for logic input ≤1ms
Number Up to 36 binary input according to various hardware configurations

2.1.5 Binary Output


Contact Type Trip output Signal output
Output mode Potential free contact
5A@380Vac 8A@380Vac
Continuous carry
5A@250Vdc 8A@250Vdc
Pickup time <8ms (typical 5ms) <10ms
Dropoff time <5ms <10ms
0.6A@48Vdc 0.7A@48Vdc
Breaking capacity (L/R=40ms) 0.2A@110Vdc 0.3A@110Vdc
0.1A@220Vdc 0.2A@220Vdc
Burden 300mW 240mW
Making capacity 2000VA 3040VA
380Vac
Maximal system voltage
250Vdc
Test voltage across open contact 1000V RMS for 1min 1200V RMS for 1min
6A@3s 10A@3S
Short duration current
15A@0.5s 20A@0.5S
Number Up to 55 binary output according to various hardware configurations

2.2 Mechanical Specifications


Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Way Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Chassis color Silver grey
Weight per device Approx. 15kg
Chassis material Aluminum alloy
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated frontplate
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (With cover)
Other sides IP30
Rear side, connection terminals IP20

2-2 PCS-902 Line Distance Relay


Date: 2011-07-06
2 Technical Data

2.3 Ambient Temperature and Humidity Range


Standard IEC 60255-1:2009
Operating temperature -40°C to +70°C
Transport and storage temperature
-40°C to +70°C
range
Permissible humidity 5%-95%, without condensation
Pollution degree 2
Altitude <3000m

2.4 Communication Port


2.4.1 EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable

2.4.2 Ethernet Port


Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850
Safety level Isolation to ELV level

2.4.3 Optical Fibre Port


2.4.3.1 For Station Level

Characteristic Glass optical fiber


Connector type ST, SC
Fibre type Multi mode
Transmission distance <2km
Wave length 1310nm
Transmission power Min. -20.0dBm
Minimum receiving power Min. -30.0dBm
Margin Min +3.0dB

2.4.3.2 For Process Level

Characteristic Glass optical fiber


Connector type LC
Fibre type Multi mode

PCS-902 Line Distance Relay 2-3


Date: 2011-07-06
2 Technical Data

Transmission distance <2km


Wave length 1310nm
Transmission power Min. -20.0dBm
Minimum receiving power Min. -30.0dBm
Margin Min +3.0dB

2.4.3.3 For Pilot Channel

Characteristic Glass optical fiber


Connector type FC
Fibre type Single mode
Transmission distance <40km (1310nm), <100km (1550nm)
Wave length 1310nm, 1550nm
Transmission power Min. -18.0dBm
Minimum receiving power Min. -38.0dBm
Margin Min +3.0dB

2.4.3.4 For Synchronization Port

Characteristic Glass optical fiber


Connector type ST
Fibre type Multi mode
Wave length 820nm
Minimum receiving power Min. -25.0dBm
Margin Min +3.0dB

2.4.4 Print Port


Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level

2.4.5 Clock Synchronization Port


Type RS-485
Transmission distance <500m
Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level

2.5 Type Tests


2.5.1 Environmental Tests

Dry cold test IEC60068-2-1:2007


Dry heat test IEC60068-2-2:2007
Damp heat test, cyclic IEC60068-2-30:2005

2-4 PCS-902 Line Distance Relay


Date: 2011-07-06
2 Technical Data

2.5.2 Mechanical Tests

Vibration IEC 60255-21-1:1988 Class I


Shock and bump IEC 60255-21-2:1988 Class I

2.5.3 Electrical Tests

Standard IEC 60255-27:2005


Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category Ⅲ

Insulation resistance
Isolation resistance >100MΩ@500VDC
measurements

2.5.4 Electromagnetic Compatibility


IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80~1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test
Common mode: 4kV
Differential mode: 2kV
IEC 60255-22-6:2001
Conducted RF Electromagnetic
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
Disturbance
kHz~80MHz
Power Frequency Magnetic Field IEC 61000-4-8:2001
Immunity class V, 100A/m for 1min, 1000A/m for 3s
IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s

PCS-902 Line Distance Relay 2-5


Date: 2011-07-06
2 Technical Data

Damped oscillatory magnetic field IEC 61000-4-10:2001


immunity class V, 100kHz & 1MHz–100A/m

Auxiliary power supply performance IEC60255-11: 2008


- Voltage dips Up to 500ms for dips to 40% of rated voltage without reset
-Voltage short interruptions 100ms for interruption without rebooting

2.6 Certifications
 ISO9001:2000

 ISO14001:2004

 OHSAS18001:1999

 ISO10012:2003

 CMMI L4

 EMC: 2004/108/EC, EN50263:1999

 Products safety(PS): 2006/95/EC, EN61010-1:2001

2.7 Protective Functions


2.7.1 Fault Detector
2.7.1.1 DPFC Current Element

Setting range 0.050In~30.000In (A)


Accuracy ≤2.5% of setting or 0.02In whichever is greater

2.7.1.2 Neutral Current Element

Setting range 0.050In~30.000In (A)


Accuracy ≤2.5% of setting or 0.02In whichever is greater

2.7.1.3 Overvoltage Element

Setting range Un~2Unn (V)


Accuracy ≤2.5% of setting or 0.01Un, whichever is greater

2.7.2 Distance Protection


Setting range (0.000~2Unn)/In (ohm)
Accuracy ≤2.5% of setting or 0.1Ω/In whichever is greater
Resetting ratio 105%
Time delay 0.000~10.000 (s)
Accuracy ≤1%Setting+30ms

2-6 PCS-902 Line Distance Relay


Date: 2011-07-06
2 Technical Data

2.7.3 Phase Protection


Setting range 0.050In~30.000In (A)
Accuracy ≤2.5% of setting or 0.02In whichever is greater
Resetting ratio 95%
Time delay 0.000~20.000 (s)
Accuracy (definite-time characteristic) ≤1% of Setting+30ms (at 2 times current setting)
≤2.5% operating time or 30ms, whichever is greater
Accuracy (inverse-time characteristic)
(for current between 1.2 and 20 multiples of pickup)

2.7.4 Earth Fault Protection


Setting range 0.050In~30.000In (A)
Accuracy ≤2.5% of setting or 0.02In whichever is greater
Resetting ratio 95%
Time delay 0.000~20.000 (s)
Accuracy (definite-time characteristic) ≤1% of Setting+30ms (at 2 times current setting)
≤2.5% operating time or 30ms, whichever is greater
Accuracy (inverse-time characteristic)
(for current between 1.2 and 20 multiples of pickup)

2.7.5 Overvoltage Protection


Setting range Un~2Unn (V)
Accuracy ≤2.5% of setting or 0.01Un, whichever is greater
Resetting ratio 95%
Time delay 0.000~30.000 (s)
Accuracy (definite-time characteristic) ≤1% of Setting+30ms (at 1.2 times voltage setting)
≤2.5% operating time or 30ms, whichever is greater
Accuracy (inverse-time characteristic)
(for voltage between 1.2 and 2 multiples of pickup)

2.7.6 Undervoltage Protection


Setting range 0~Unn (V)
Accuracy ≤2.5% of setting or 0.01Un, whichever is greater
Resetting ratio 105%
Time delay 0.000~30.000 (s)
Accuracy (definite-time characteristic) ≤1%Setting+30ms (at 1.2 times voltage setting)
≤2.5% operating time or 30ms, whichever is greater
Accuracy (inverse-time characteristic)
(for voltage between 0.5 and 0.8 multiples of pickup)

2.7.7 Overfrequency Protection


Setting range 50.00~65.00 (Hz)
Accuracy ≤ 0.02Hz
Resetting ratio 95%
Time delay 0.000~100.000 (s)
Accuracy ≤1%Setting+30ms (at 1.2 times frequency setting)

PCS-902 Line Distance Relay 2-7


Date: 2011-07-06
2 Technical Data

2.7.8 Underfrequency Protection


Setting range 40.00~ 50.00 (Hz)
Accuracy ≤ 0.02Hz
Resetting ratio 105%
Time delay 0.000s ~ 100.000 (s)
Accuracy ≤1%Setting+30ms (at 0.8 times frequency setting)
df/dt blocking setting range 0.200~20.000 (Hz/s)
Accuracy ≤ 0.02Hz/s

2.7.9 Breaker Failure Protection


Pick-up time <20ms
Drop-off time <20ms
Setting range of phase current 0.050In~30.000In (A)
Setting range of zero-sequence current 0.050In~30.000In (A)
Setting range of negative-sequence current 0.050In~30.000In (A)
Accuracy ≤2.5% of setting or 0.02In whichever is greater
Time delay (first) 0.000~10.000 (s)
Time delay (second) 0.000~10.000 (s)

2.7.10 Thermal Overload Protection


Base current setting range 0.050In~30.000In (A)
Accuracy ≤2.5% of setting or 0.02In whichever is greater
Line thermal time constant 0.100~100.000 (min)
Thermal overload coefficient for trip 1.000~3.000
Thermal overload coefficient for alarm 1.000~3.000
Resetting ratio 95%
Drop-off time <30ms
≤2.5% operating time or 30ms, whichever is greater
Time accuracy
(for current between 1.2 and 20 multiples of pickup)

2.7.11 Stub Overcurrent Protection


Setting range 0.050In~30.000In (A)
Accuracy ≤2.5% of setting or 0.02In whichever is greater
Resetting ratio 95%
Time delay 0.000~10.000 (s)
Accuracy ≤1% of Setting+30ms (at 2 times current setting)

2.7.12 Auto-reclosing
Phase difference setting range 0~89 (Deg)
Accuracy 2.0Deg
Voltage difference setting range 0.02Un~0.8Un (V)
Accuracy Max(0.01Un, 2.5%)

2-8 PCS-902 Line Distance Relay


Date: 2011-07-06
2 Technical Data

Frequency difference setting range 0.02~1 (Hz)


Accuracy 0.01Hz
Operating time of synchronism check ≤1%Setting+20ms
Operating time of energizing check ≤1%Setting+20ms
Operating time of auto-reclosing ≤1%Setting+20ms

2.7.13 Transient Overreach


Tolerance for all high-speed protection ≤2%

2.7.14 Fault Locator


Accuracy for multi-phase faults with single end feed < ±2.5%
Tolerance will be higher in case of single-phase fault with high ground resistance.

PCS-902 Line Distance Relay 2-9


Date: 2011-07-06
2 Technical Data

2-10 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3 Operation Theory

Table of Contents
3 Operation Theory ............................................................................. 3-a
3.1 System Parameters ......................................................................................... 3-1
3.1.1 General Application ............................................................................................................ 3-1

3.1.2 Function Description .......................................................................................................... 3-1

3.1.3 Settings .............................................................................................................................. 3-1

3.2 Line Parameters .............................................................................................. 3-1


3.2.1 General Application ............................................................................................................ 3-1

3.2.2 Function Description .......................................................................................................... 3-1

3.2.3 Settings .............................................................................................................................. 3-2

3.3 Circuit Breaker Position Supervision ............................................................ 3-2


3.3.1 General Application ............................................................................................................ 3-2

3.3.2 Function Description .......................................................................................................... 3-2

3.3.3 Function Block Diagram ..................................................................................................... 3-2

3.3.4 I/O Signals ......................................................................................................................... 3-3

3.3.5 Logic .................................................................................................................................. 3-4

3.3.6 Settings .............................................................................................................................. 3-5

3.4 Fault Detector (FD) .......................................................................................... 3-6


3.4.1 Application.......................................................................................................................... 3-6

3.4.2 Fault Detector in Fault Detector DSP ................................................................................. 3-6

3.4.3 Protection Fault Detector in Protection Calculation DSP ................................................... 3-8

3.4.4 Function Block Diagram ................................................................................................... 3-10

3.4.5 I/O Signals ....................................................................................................................... 3-10

3.4.6 Logic ................................................................................................................................ 3-10

3.4.7 Settings ............................................................................................................................ 3-10

3.5 Distance Protection ....................................................................................... 3-11

PCS-902 Line Distance Relay 3-a


Date: 2011-07-06
3 Operation Theory

3.5.1 General Application .......................................................................................................... 3-11

3.5.2 Function Description ........................................................................................................ 3-11

3.5.3 DPFC Distance Protection ............................................................................................... 3-16

3.5.4 Mho Distance Protection .................................................................................................. 3-20

3.5.5 Quadrilateral Distance Element ....................................................................................... 3-35

3.5.6 Pilot Distance Zone .......................................................................................................... 3-45

3.5.7 Power Swing Detection .................................................................................................... 3-47

3.5.8 Power Swing Blocking Releasing..................................................................................... 3-48

3.5.9 Distance SOTF Protection ............................................................................................... 3-53

3.6 Optical Pilot Channel (Option) ..................................................................... 3-58


3.6.1 General Application .......................................................................................................... 3-58

3.6.2 Function Description ........................................................................................................ 3-58

3.6.3 Function Block Diagram ................................................................................................... 3-62

3.6.4 I/O Signals ....................................................................................................................... 3-62

3.6.5 Logic ................................................................................................................................ 3-63

3.6.6 Settings ............................................................................................................................ 3-64

3.7 Pilot Distance Protection .............................................................................. 3-64


3.7.1 General Application .......................................................................................................... 3-64

3.7.2 Function Description ........................................................................................................ 3-64

3.7.3 Function Block Diagram ................................................................................................... 3-74

3.7.4 I/O Signals ....................................................................................................................... 3-75

3.7.5 Settings ............................................................................................................................ 3-75

3.8 Pilot Directional Earth-fault Protection ....................................................... 3-76


3.8.1 General Application .......................................................................................................... 3-76

3.8.2 Function Description ........................................................................................................ 3-77

3.8.3 Function Block Diagram ................................................................................................... 3-82

3.8.4 I/O Signals ....................................................................................................................... 3-83

3.8.5 Settings ............................................................................................................................ 3-83

3.9 Current Direction .......................................................................................... 3-84


3.9.1 General Application .......................................................................................................... 3-84

3-b PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.9.2 Function Description ........................................................................................................ 3-85

3.9.3 I/O Signals ....................................................................................................................... 3-89

3.9.4 Settings ............................................................................................................................ 3-90

3.10 Phase Overcurrent Protection ................................................................... 3-90


3.10.1 General Application ........................................................................................................ 3-90

3.10.2 Function Description ...................................................................................................... 3-90

3.10.3 Function Block Diagram ................................................................................................. 3-93

3.10.4 I/O Signals ..................................................................................................................... 3-93

3.10.5 Logic .............................................................................................................................. 3-94

3.10.6 Settings .......................................................................................................................... 3-94

3.11 Earth Fault Protection ................................................................................. 3-97


3.11.1 General Application ........................................................................................................ 3-97

3.11.2 Function Description....................................................................................................... 3-97

3.11.3 Function Block Diagram ............................................................................................... 3-100

3.11.4 I/O Signals.................................................................................................................... 3-100

3.11.5 Logic............................................................................................................................. 3-101

3.11.6 Settings ........................................................................................................................ 3-102

3.12 Overcurrent Protection for VT Circuit Failure ........................................ 3-105


3.12.1 General Application ...................................................................................................... 3-105

3.12.2 Function Block Diagram ............................................................................................... 3-105

3.12.3 I/O Signals ................................................................................................................... 3-105

3.12.4 Logic ............................................................................................................................ 3-106

3.12.5 Settings ........................................................................................................................ 3-106

3.13 Residual Current SOTF Protection .......................................................... 3-106


3.13.1 General Application ...................................................................................................... 3-106

3.13.2 Function Description .................................................................................................... 3-107

3.13.3 Function Block Diagram ............................................................................................... 3-107

3.13.4 I/O Signals ................................................................................................................... 3-107

3.13.5 Logic ............................................................................................................................ 3-108

3.13.6 Settings ........................................................................................................................ 3-108

PCS-902 Line Distance Relay 3-c


Date: 2011-07-06
3 Operation Theory

3.14 Voltage Protection ..................................................................................... 3-108


3.14.1 Overvoltage Protection................................................................................................. 3-108

3.14.2 Undervoltage Protection............................................................................................... 3-114

3.15 Frequency Protection ............................................................................... 3-120


3.15.1 Overfrequency Protection ............................................................................................ 3-120

3.15.2 Underfrequency Protection .......................................................................................... 3-123

3.16 Breaker Failure Protection ....................................................................... 3-126


3.16.1 General Application ...................................................................................................... 3-126

3.16.2 Function Description .................................................................................................... 3-126

3.16.3 Function Block Diagram ............................................................................................... 3-127

3.16.4 I/O Signals ................................................................................................................... 3-127

3.16.5 Logic ............................................................................................................................ 3-128

3.16.6 Settings ........................................................................................................................ 3-129

3.17 Thermal Overload Protection ................................................................... 3-129


3.17.1 General Application ...................................................................................................... 3-129

3.17.2 Function Description .................................................................................................... 3-130

3.17.3 Function Block Diagram ............................................................................................... 3-131

3.17.4 I/O Signals ................................................................................................................... 3-131

3.17.5 Logic ............................................................................................................................ 3-132

3.17.6 Settings ........................................................................................................................ 3-132

3.18 Stub Overcurrent Protection .................................................................... 3-133


3.18.1 General Application ...................................................................................................... 3-133

3.18.2 Function Block Diagram ............................................................................................... 3-134

3.18.3 I/O Signals ................................................................................................................... 3-134

3.18.4 Logic ............................................................................................................................ 3-134

3.18.5 Settings ........................................................................................................................ 3-134

3.19 Pole Discrepancy Protection.................................................................... 3-135


3.19.1 General Application ...................................................................................................... 3-135

3.19.2 Function Description .................................................................................................... 3-135

3.19.3 Function Block Diagram ............................................................................................... 3-135

3-d PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.19.4 I/O Signals ................................................................................................................... 3-135

3.19.5 Logic ............................................................................................................................ 3-136

3.19.6 Settings ........................................................................................................................ 3-137

3.20 Synchrocheck ........................................................................................... 3-137


3.20.1 General Application ...................................................................................................... 3-137

3.20.2 Function Description .................................................................................................... 3-138

3.20.3 I/O Signals ................................................................................................................... 3-143

3.20.4 Logic ............................................................................................................................ 3-144

3.20.5 Settings ........................................................................................................................ 3-146

3.21 Automatic Reclosure ................................................................................ 3-148


3.21.1 General Application ...................................................................................................... 3-148

3.21.2 Function Description .................................................................................................... 3-148

3.21.3 Function Block Diagram ............................................................................................... 3-149

3.21.4 I/O Signals ................................................................................................................... 3-150

3.21.5 Logic ............................................................................................................................ 3-151

3.21.6 Settings ........................................................................................................................ 3-161

3.22 Transfer Trip .............................................................................................. 3-163


3.22.1 General Application ...................................................................................................... 3-163

3.22.2 Function Description .................................................................................................... 3-163

3.22.3 Function Block Diagram ............................................................................................... 3-164

3.22.4 I/O Signals ................................................................................................................... 3-164

3.22.5 Logic ............................................................................................................................ 3-164

3.22.6 Settings ........................................................................................................................ 3-164

3.23 Trip Logic ................................................................................................... 3-165


3.23.1 General Application ...................................................................................................... 3-165

3.23.2 Function Description .................................................................................................... 3-165

3.23.3 I/O Signals ................................................................................................................... 3-165

3.23.4 Logic ............................................................................................................................ 3-166

3.23.5 Settings ........................................................................................................................ 3-167

3.24 VT Circuit Supervision.............................................................................. 3-168

PCS-902 Line Distance Relay 3-e


Date: 2011-07-06
3 Operation Theory

3.24.1 General Application ...................................................................................................... 3-168

3.24.2 Function Description .................................................................................................... 3-168

3.24.3 Function Block Diagram ............................................................................................... 3-169

3.24.4 I/O Signals ................................................................................................................... 3-169

3.24.5 Logic ............................................................................................................................ 3-169

3.24.6 Settings ........................................................................................................................ 3-170

3.25 CT Circuit Supervision ............................................................................. 3-170


3.25.1 General Application ...................................................................................................... 3-170

3.25.2 Function Description .................................................................................................... 3-170

3.25.3 Function Block Diagram ............................................................................................... 3-170

3.25.4 I/O Signals ................................................................................................................... 3-170

3.25.5 Logic ............................................................................................................................ 3-171

3.26 Faulty Phase Selection ............................................................................. 3-171


3.26.1 Variation of Operating Voltage (Faulty Phase Selection Element 1) ............................ 3-171

3.26.2 I0 and I2A (Faulty Phase Selection Element 2) ............................................................ 3-172

3.27 Fault Location ........................................................................................... 3-173


3.27.1 Application.................................................................................................................... 3-173

3.27.2 Function Description .................................................................................................... 3-173

3.27.3 Mutual Compensation .................................................................................................. 3-173

3.27.4 I/O Signals ................................................................................................................... 3-176

List of Figures
Figure 3.3-1 Logic diagram of CB position supervision.........................................................3-4

Figure 3.3-2 Logic diagram of trip&closing circuit supervision ............................................3-5

Figure 3.4-1 Flow chart of protection program .......................................................................3-9

Figure 3.4-2 Logic diagram of fault detector .........................................................................3-10

Figure 3.5-1 Protected reach of distance protection for each zone ....................................3-12

Figure 3.5-2 Operating time of single-phase fault (50Hz, SIR=1) .........................................3-13

Figure 3.5-3 Operating time of two-phase fault (50Hz, SIR=1) .............................................3-14

Figure 3.5-4 Operating time of three-phase fault (50Hz, SIR=1) ..........................................3-14

3-f PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Figure 3.5-5 Operating time of single-phase fault (50Hz, SIR=30) .......................................3-15

Figure 3.5-6 Operating time of two-phase fault (50Hz, SIR=30) ...........................................3-15

Figure 3.5-7 Operating time of three-phase fault (50Hz, SIR=30) ........................................3-16

Figure 3.5-8 Operation characteristic for forward fault ........................................................3-17

Figure 3.5-9 Operation characteristic for reverse fault ........................................................3-18

Figure 3.5-10 Logic diagram of DPFC distance protection ..................................................3-19

Figure 3.5-11 Phase-to-ground operation characteristic for forward fault .........................3-20

Figure 3.5-12 Phase-to-phase operation characteristic for forward fault ...........................3-21

Figure 3.5-13 Operation characteristic for reverse fault ......................................................3-23

Figure 3.5-14 Steady-state characteristic of three-phase short-circuit fault ......................3-23

Figure 3.5-15 Operation characteristic of three-phase close up short-circuit fault ...........3-24

Figure 3.5-16 Shift impedance characteristic of zone 1 and zone 2 ....................................3-25

Figure 3.5-17 Operation characteristic of reverse Z4 distance protection .........................3-26

Figure 3.5-18 Operation characteristic of blinder .................................................................3-27

Figure 3.5-19 Logic diagram of enabling distance protection (Mho) ..................................3-28

Figure 3.5-20 Logic diagram of distance protection (Mho zone 1) ......................................3-29

Figure 3.5-21 Logic diagram of distance protection (Mho zone 2) ......................................3-30

Figure 3.5-22 Logic diagram of distance protection (Mho zone 3) ......................................3-31

Figure 3.5-23 Logic diagram of distance protection (Mho zone 4) ......................................3-32

Figure 3.5-24 Quadrilateral forward distance element characteristics ...............................3-36

Figure 3.5-25 Zone 4 reverse quadrilateral distance element characteristic ......................3-36

Figure 3.5-26 Logic diagram of enabling distance protection (Quad) .................................3-38

Figure 3.5-27 Logic diagram of distance protection (Quad zone 1) ....................................3-38

Figure 3.5-28 Logic diagram of distance protection (Quad zone 2) ....................................3-39

Figure 3.5-29 Logic diagram of distance protection (Quad zone 3) ....................................3-40

Figure 3.5-30 Logic diagram of distance protection (Quad zone 4) ....................................3-41

Figure 3.5-31 Protected zone of pilot distance protection ...................................................3-45

Figure 3.5-32 Pilot reverse weak infeed element ..................................................................3-45

Figure 3.5-33 Logic diagram of pilot distance zone (Quad characteristic) .........................3-46

Figure 3.5-34 Logic diagram of pilot distance zone (Mho characteristic) ...........................3-46

PCS-902 Line Distance Relay 3-g


Date: 2011-07-06
3 Operation Theory

Figure 3.5-35 Logic diagram of power swing detection .......................................................3-48

Figure 3.5-36 Logic diagram of PSBR ....................................................................................3-52

Figure 3.5-37 Logic diagram of enabling distance SOTF protection ...................................3-54

Figure 3.5-38 Logic diagram of distance SOTF protection ..................................................3-55

Figure 3.6-1 Application of dedicated channel......................................................................3-59

Figure 3.6-2 Application of multiplex channel.......................................................................3-59

Figure 3.6-3 Schematic diagram of communication channel time ......................................3-61

Figure 3.6-4 Logic diagram of receiving signal n .................................................................3-63

Figure 3.7-1 Enabling/disabling logic of pilot distance protection......................................3-65

Figure 3.7-2 Logic diagram of receiving signal.....................................................................3-65

Figure 3.7-3 Zone extension ...................................................................................................3-66

Figure 3.7-4 Simple schematic of PUTT ................................................................................3-67

Figure 3.7-5 Logic diagram of pilot distance protection (PUTT)..........................................3-67

Figure 3.7-6 Simple schematic of POTT ................................................................................3-68

Figure 3.7-7 Logic diagram of pilot distance protection (POTT) .........................................3-68

Figure 3.7-8 Simple schematic of system fault .....................................................................3-69

Figure 3.7-9 Simple schematic of blocking ...........................................................................3-69

Figure 3.7-10 Logic diagram of pilot distance protection (Blocking) ..................................3-70

Figure 3.7-11 Logic diagram of pilot distance protection (Unblocking) ..............................3-70

Figure 3.7-12 Current reversal ................................................................................................3-71

Figure 3.7-13 Logic diagram of current reversal blocking ...................................................3-72

Figure 3.7-14 Line fault description .......................................................................................3-72

Figure 3.7-15 Weak infeed logic during pickup .....................................................................3-73

Figure 3.7-16 Weak infeed logic without pickup ...................................................................3-73

Figure 3.7-17 Simplified CB Echo logic for POTT .................................................................3-74

Figure 3.8-1 Enabling/disabling logic of pilot directional earth-fault protection ...............3-77

Figure 3.8-2 Logic diagram of receiving signal.....................................................................3-78

Figure 3.8-3 Forward/reverse direction of zero-sequence power........................................3-78

Figure 3.8-4 Simple schematic of DEF (permissive scheme) ..............................................3-79

Figure 3.8-5 Logic diagram of DEF (permissive scheme) ....................................................3-79

3-h PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Figure 3.8-6 Simple schematic of blocking ...........................................................................3-80

Figure 3.8-7 Logic diagram of DEF (Blocking scheme) ........................................................3-81

Figure 3.8-8 Logic diagram for unblocking ...........................................................................3-82

Figure 3.9-1 Line fault description .........................................................................................3-84

Figure 3.9-2 Vector diagram of current and voltage .............................................................3-86

Figure 3.9-3 Vector diagram of zero-sequence power ..........................................................3-88

Figure 3.10-1 Logic diagram of phase overcurrent protection ............................................3-94

Figure 3.11-1 Logic diagram of earth fault protection ........................................................3-101

Figure 3.12-1 Logic diagram of overcurrent protection for VT circuit failure...................3-106

Figure 3.13-1 Logic diagram of residual current SOTF protection ....................................3-108

Figure 3.14-1 Logic diagram of stage x of overvoltage protection .................................... 3-112

Figure 3.14-2 Blocking logic of undervoltage protection ................................................... 3-118

Figure 3.14-3 Logic diagram of stage x of undervoltage protection ................................. 3-118

Figure 3.15-1 Logic diagram of stage x of overfrequency protection ...............................3-122

Figure 3.15-2 Logic diagram of stage x of underfrequency protection .............................3-125

Figure 3.16-1 Logic diagram of breaker failure protection.................................................3-128

Figure 3.17-1 Characteristic curve of the thermal overload model ...................................3-131

Figure 3.17-2 Logic diagram of thermal overload protection ............................................3-132

Figure 3.18-1 3/2 breakers arrangement ..............................................................................3-133

Figure 3.18-2 Logic diagram of stub overcurrent protection .............................................3-134

Figure 3.19-1 Pole discrepancy ............................................................................................3-136

Figure 3.19-2 Logic diagram of pole discrepancy protection ............................................3-137

Figure 3.20-1 Relationship between reference voltage and synchronous voltage ..........3-138

Figure 3.20-2 Voltage connection for single busbar arrangement ....................................3-139

Figure 3.20-3 Voltage connection for single busbar arrangement ....................................3-139

Figure 3.20-4 Voltage connection for double busbars arrangement .................................3-140

Figure 3.20-5 Voltage selection for double busbars arrangement ....................................3-140

Figure 3.20-6 Voltage connection for one and a half breakers arrangement....................3-141

Figure 3.20-7 Voltage selection for one and a half breakers arrangement .......................3-142

Figure 3.20-8 Voltage selection for one and a half breakers arrangement .......................3-143

PCS-902 Line Distance Relay 3-i


Date: 2011-07-06
3 Operation Theory

Figure 3.20-9 Synchronism check ........................................................................................3-145

Figure 3.20-10 Dead charge check logic..............................................................................3-146

Figure 3.20-11 Synchrocheck logic ......................................................................................3-146

Figure 3.21-1 Logic diagram of AR ready ............................................................................3-152

Figure 3.21-2 Single-phase tripping initiating AR ...............................................................3-153

Figure 3.21-3 Three-phase tripping initiating AR ................................................................3-154

Figure 3.21-4 1-pole AR initiation .........................................................................................3-154

Figure 3.21-5 3-pole AR initiation .........................................................................................3-155

Figure 3.21-6 One-shot AR ....................................................................................................3-155

Figure 3.21-7 Extra time delay and blocking logic of AR ...................................................3-156

Figure 3.21-8 Reclosing output logic ...................................................................................3-157

Figure 3.21-9 Reclosing failure.............................................................................................3-157

Figure 3.21-10 Single-phase transient fault.........................................................................3-160

Figure 3.21-11 Single-phase permanent fault ([79.N_Rcls]=2) ...........................................3-161

Figure 3.22-1 Logic diagram of transfer trip........................................................................3-164

Figure 3.23-1 Simplified tripping logic (part 1) ....................................................................3-166

Figure 3.23-2 Simplified tripping logic (part 2) ....................................................................3-166

Figure 3.23-3 Simplified tripping logic (part 3) ....................................................................3-167

Figure 3.23-4 Simplified tripping logic (part 4) ....................................................................3-167

Figure 3.24-1 Logic of VT circuit supervision .....................................................................3-169

Figure 3.25-1 Logic diagram of CT circuit failure ...............................................................3-171

Figure 3.26-1 The region of faulty phase selection ............................................................3-172

Figure 3.27-1 Equivalent sequence network .......................................................................3-174

List of Tables
Table 3.1-1 System parameters ................................................................................................3-1

Table 3.2-1 Line parameters ......................................................................................................3-2

Table 3.3-1 Configurable I/O signals of CB position supervision ..........................................3-3

Table 3.3-2 Internal I/O signals of CB position supervision ...................................................3-4

Table 3.3-3 Internal settings of CB position supervision .......................................................3-5

3-j PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Table 3.4-1 Configurable I/O signals of fault detector ..........................................................3-10

Table 3.4-2 Internal I/O signals of fault detector ...................................................................3-10

Table 3.4-3 Settings of fault detector .....................................................................................3-10

Table 3.5-1 Configurable I/O signals of DPFC distance protection .....................................3-19

Table 3.5-2 Settings of DPFC distance protection ................................................................3-19

Table 3.5-3 Configurable I/O signals of distance protection (Mho) .....................................3-27

Table 3.5-4 Internal I/O signals of distance protection (Mho) ..............................................3-28

Table 3.5-5 Settings of distance protection (Mho) ................................................................3-32

Table 3.5-6 Internal settings of distance protection (Mho) ...................................................3-35

Table 3.5-7 Configurable I/O signals of distance protection (Quad) ...................................3-37

Table 3.5-8 Internal I/O signals of distance protection (Quad).............................................3-37

Table 3.5-9 Settings of distance protection (Quad) ..............................................................3-41

Table 3.5-10 Internal settings of distance protection (Quad) ...............................................3-44

Table 3.5-11 Settings of pilot distance zone ..........................................................................3-47

Table 3.5-12 Configurable I/O signals of power swing detection ........................................3-47

Table 3.5-13 Internal I/O signals of power swing detection .................................................3-48

Table 3.5-14 Settings of power swing detection ...................................................................3-48

Table 3.5-15 Internal I/O signals of PSBR ..............................................................................3-51

Table 3.5-16 Settings of PSBR ................................................................................................3-52

Table 3.5-17 Configurable I/O signals of distance SOTF protection ...................................3-54

Table 3.5-18 Settings of distance SOTF protection ..............................................................3-56

Table 3.5-19 Internal settings of distance SOTF protection .................................................3-58

Table 3.6-1 Configurable I/O signals of pilot channel ...........................................................3-62

Table 3.6-2 Internal I/O signals of pilot channel ....................................................................3-63

Table 3.6-3 Settings of pilot channel ......................................................................................3-64

Table 3.7-1 Configurable I/O signals of pilot distance protection .......................................3-75

Table 3.7-2 Settings of pilot distance protection ..................................................................3-75

Table 3.7-3 Internal settings of pilot distance protection .....................................................3-76

Table 3.8-1 Configurable I/O signals of pilot directional earth-fault protection .................3-83

Table 3.8-2 Settings of pilot directional earth-fault protection ............................................3-83

PCS-902 Line Distance Relay 3-k


Date: 2011-07-06
3 Operation Theory

Table 3.8-3 Internal settings of pilot distance protection .....................................................3-84

Table 3.9-1 Direction description ...........................................................................................3-87

Table 3.9-2 Internal I/O signals of current direction..............................................................3-89

Table 3.9-3 Settings of current direction ...............................................................................3-90

Table 3.10-1 Inverse-time curve parameters..........................................................................3-92

Table 3.10-2 Configurable I/O signals of phase overcurrent protection .............................3-93

Table 3.10-3 Internal I/O signals of phase overcurrent protection ......................................3-93

Table 3.10-4 Settings of phase overcurrent protection ........................................................3-94

Table 3.11-1 Inverse-time curve parameters ..........................................................................3-99

Table 3.11-2 Configurable I/O signals of earth fault protection .........................................3-100

Table 3.11-3 Internal I/O signals of earth fault protection ..................................................3-100

Table 3.11-4 Settings of earth fault protection ....................................................................3-102

Table 3.12-1 Configurable I/O signals of overcurrent protection for VT circuit failure ....3-105

Table 3.12-2 Settings of overcurrent protection for VT circuit failure ...............................3-106

Table 3.13-1 Configurable I/O signals of residual SOTF protection ..................................3-107

Table 3.13-2 Settings of residual current SOTF protection ................................................3-108

Table 3.14-1 Inverse-time curve parameters........................................................................ 3-110

Table 3.14-2 Configurable I/O signals of overvoltage protection ...................................... 3-111

Table 3.14-3 Internal I/O signals of overvoltage protection................................................ 3-112

Table 3.14-4 Settings of overvoltage protection ................................................................. 3-112

Table 3.14-5 Inverse-time curve parameters of phase undervoltage protection .............. 3-116

Table 3.14-6 Configurable I/O signals of undervoltage protection .................................... 3-117

Table 3.14-7 Internal I/O signals of undervoltage protection ............................................. 3-117

Table 3.14-8 Settings of undervoltage protection ............................................................... 3-119

Table 3.15-1 Configurable I/O signals of overfrequency protection ..................................3-121

Table 3.15-2 Internal I/O signals of overfrequency protection ...........................................3-121

Table 3.15-3 Settings of overfrequency protection .............................................................3-122

Table 3.15-4 Configurable I/O signals of underfrequency protection ...............................3-124

Table 3.15-5 Internal I/O signals of underfrequency protection ........................................3-124

Table 3.15-6 Settings of overfrequency protection .............................................................3-125

3-l PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Table 3.16-1 Configurable I/O signals of breaker failure protection ..................................3-127

Table 3.16-2 Internal I/O signals of breaker failure protection ...........................................3-128

Table 3.16-3 Settings of breaker failure protection .............................................................3-129

Table 3.17-1 Configurable I/O signals of thermal overload protection..............................3-131

Table 3.17-2 Internal I/O signals of thermal overload protection .......................................3-132

Table 3.17-3 Settings of thermal overload protection.........................................................3-132

Table 3.18-1 Configurable I/O signals of stub overcurrent protection ..............................3-134

Table 3.18-2 Settings of stub overcurrent protection .........................................................3-134

Table 3.19-1 Configurable I/O signals of pole discrepancy protection .............................3-135

Table 3.19-2 Internal I/O signals of pole discrepancy protection ......................................3-136

Table 3.19-3 Settings of pole discrepancy protection ........................................................3-137

Table 3.20-1 Internal I/O signals of synchrocheck ..............................................................3-143

Table 3.20-2 Settings of synchrocheck ................................................................................3-146

Table 3.21-1 Configurable I/O signals of auto-reclosing ....................................................3-150

Table 3.21-2 Internal I/O signals of auto-reclosing .............................................................3-150

Table 3.21-3 Reclosing number ............................................................................................3-159

Table 3.21-4 Settings of auto-reclosing ...............................................................................3-161

Table 3.22-1 Configurable I/O signals of transfer trip .........................................................3-164

Table 3.22-2 Internal I/O signals of transfer trip ..................................................................3-164

Table 3.22-3 Settings of Transfer trip ...................................................................................3-164

Table 3.23-1 Internal I/O signals of trip logic .......................................................................3-165

Table 3.23-2 Settings of trip logic .........................................................................................3-167

Table 3.24-1 Configurable I/O signals of VT circuit supervision .......................................3-169

Table 3.24-2 Internal I/O signals of VT circuit supervision .................................................3-169

Table 3.24-3 VTS Settings .....................................................................................................3-170

Table 3.25-1 Configurable I/O signals of CT circuit supervision .......................................3-170

Table 3.25-2 Internal I/O signals of CT circuit supervision ................................................3-171

Table 3.26-1 Relation between ΔUOΦMAX and faulty phase .............................................3-172

Table 3.27-1 Internal I/O signals of fault location ................................................................3-176

PCS-902 Line Distance Relay 3-m


Date: 2011-07-06
3 Operation Theory

3-n PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.1 System Parameters


3.1.1 General Application

The device performs various protection functions by respective algorithms with the information
(currents and voltages) acquired from primary system through current transformer and voltage
transformer, so it is important to configure analog input channels correctly.

Further to correct configuration of analog input channels, other protected system information, such
as the parameters of voltage transformer and current transformer are also required.

3.1.2 Function Description

The device generally considers transmission line as its protected object, current flows from busbar
to line is considered as the forward direction.

3.1.3 Settings

Table 3.1-1 System parameters

No. Name Range Step Unit Remark


1 Active_Grp 1~10 1 Active setting group
2 Opt_SysFreq 50 or 60 Hz System frequency
3 PrimaryEquip_ID ID of primary equipment
4 U1n 33~65500 1 kV Primary rated value of VT (phase to phase)
5 I1n 0~6000 1 A Primary rated value of CT
6 U2n 80~220 1 V Secondary rated value of VT (phase to phase)
7 I2n 1 or 5 A Secondary rated value of CT

3.2 Line Parameters


3.2.1 General Application

When the device equips with line protection functions, line parameters of protected line are
required, especially for fault location, precise line parameters are the basic criterion for accurate
fault location.

3.2.2 Function Description

Line parameters mainly include positive-sequence reactance, positive-sequence resistance,


zero-sequence reactance, zero-sequence resistance, mutual zero-sequence reactance, mutual
zero-sequence resistance and line length.

The positive-sequence reactance, zero-sequence reactance, positive-sequence resistance and


zero-sequence resistance are the reactance and resistance value of the whole line. In general, the
device locates the fault through calculating the impedance value from the location of the device to
fault point.

PCS-902 Line Distance Relay 3-1


Date: 2011-07-06
3 Operation Theory

3.2.3 Settings

Table 3.2-1 Line parameters

No. Name Range Step Unit Remark


Positive-sequence reactance of the whole
1 X1L (0.000~2Unn)/In 0.001 ohm
line (secondary value)
Positive-sequence resistance of the whole
2 R1L (0.000~2Unn)/In 0.001 ohm
line (secondary value)
Zero-sequence reactance of the whole line
3 X0L (0.000~2Unn)/In 0.001 ohm
(secondary value)
Zero-sequence resistance of the whole line
4 R0L (0.000~2Unn)/In 0.010 ohm
(secondary value)
Zero-sequence mutual reactance
5 X0M (0.000~2Unn)/In 0.001 ohm
(secondary value)
Zero-sequence mutual resistance of the
6 R0M (0.000~2Unn)/In 0.01 ohm
whole line (secondary value)
7 LineLength 0.00~655.35 0.01 km Total length of the whole line
Phase angle of line positive-sequence
8 phi1_Reach 45.00~89.00 0.01 Deg
impedance
Phase angle of line zero-sequence
9 phi0_Reach 45.00~89.00 0.01 Deg
impedance
10 K0 0.000~4.000 0.001 Zero-sequence compensation factor

3.3 Circuit Breaker Position Supervision


3.3.1 General Application

The status of circuit breaker (CB) position is applied for protection and control functions in this
device, such as, SOTF protection, auto-reclose and VT circuit supervision, etc. The status of CB
position can be applied as input signals for other features configured by user.

3.3.2 Function Description

The signal reflecting CB position is acquired via opto-coupler with settable delay pickup and
dropoff, and forms digital signal used by protection functions. CB position can reflect the status of
each phase by means of phase-segregated inputs.

In order to prevent that wrong status of CB position is input into the device via binary input,
appropriate monitor method is used to check the rationality of the binary input. When the binary
input of CB open position is detected, the status of CB position will be thought as incorrect and an
alarm [Alm_52b] will be issued if there is current detected in the line.

Together with the status of circuit breaker and the information of external circuit, this function can
be used to supervise control circuit of circuit breaker.

3.3.3 Function Block Diagram

1. For phase-segregated circuit breaker

3-2 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

CB Position Supervision

52b_PhA Alm_52b

52b_PhB

52b_PhC

2. For non-phase segregated circuit breaker

CB Position Supervision

52b Alm_52b

3. Trip&closing circuit supervision (TCCS)

TCCS

52a TCCS.Alm

52b

TCCS.Input

TCCS will be disabled automatically when it is used for phase-segregated circuit breaker.

3.3.4 I/O Signals

Table 3.3-1 Configurable I/O signals of CB position supervision

No. Input Signal Description


1 52b_PhA Normally closed contact of A-phase of circuit breaker
2 52b_PhB Normally closed contact of B-phase of circuit breaker
3 52b_PhC Normally closed contact of C-phase of circuit breaker
4 52b Normally closed contact of three-phase of circuit breaker
5 52a Normally open contact of three-phase of circuit breaker
6 TCCS.Input Control circuit failure
No. Output Signal Description
1 Alm_52b CB position is abnormal
2 TCCS.Alm Control circuit of circuit breaker is abnormal

PCS-902 Line Distance Relay 3-3


Date: 2011-07-06
3 Operation Theory

Table 3.3-2 Internal I/O signals of CB position supervision

No. Input Signal Description


1 I3P Three-phase current input

3.3.5 Logic

BI 52b_PhA t1_52b_A t2_52b_A &


>=1
52b_A_CB

BI 52b_PhB t1_52b_B t2_52b_B &


>=1
52b_B_CB

BI 52b_PhC t1_52b_C t2_52b_C &


>=1
52b_C_CB

EN [En_3PhCB] &

BI 52b t1_52b_3Ph t2_52b_3Ph

SIG [52b_PhA] &


&

SIG [52b_PhB] & &

>=1
SIG [52b_PhC] &

& &
>=1 10s 10s Alm_52b
SIG Ia>0.06In

&

SIG Ib>0.06In

&

SIG Ic>0.06In

Figure 3.3-1 Logic diagram of CB position supervision

3-4 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

BI [52a] [t1_52a_3Ph] [t2_52a_3Ph] >=1


>=1
BI [52b] [t1_52b_3Ph] [t2_52b_3Ph] [TCCS.t_DPU] [TCCS.t_DDO] TCCS.Alm

BI [TCCS.Input] [t1_TCCS_3Ph] [t2_TCCS_3Ph]

Figure 3.3-2 Logic diagram of trip&closing circuit supervision

Where:

1. t1_52b_A, t1_52b_B, t1_52b_C are pickup delay time of A, B, C-phase CB open position
input signal respectively. They are configurable and default value is 5ms.

2. t2_52b_A, t2_52b_B, t2_52b_C are dropoff delay time of A, B, C-phase CB open position
input signal respectively. They are configurable and default value is 5ms.

3. t1_52b_3Ph is pickup delay time of three-phase CB open position input signal. It is


configurable and default value is 5ms.

4. t2_52b_3Ph is dropoff delay time of three-phase CB open position input signal. It is


configurable and default value is 5ms.

5. t1_52a_3Ph is pickup delay time of three-phase CB closed position input signal. It is


configurable and default value is 5ms.

6. t2_52a_3Ph is dropoff delay time of three-phase CB closed position input signal. It is


configurable and default value is 5ms.

7. TCCS.t_DPU is pickup delay time of control circuit failure alarm. Default value is 500ms.

8. TCCS.t_DDO is dropoff delay time of control circuit failure alarm. Default value is 500ms.

9. I_Line is threshold value used to determine whether line is on-load or no-load. Default value
0.06In.

3.3.6 Settings

Table 3.3-3 Internal settings of CB position supervision

No. Name Default Value Unit Remark


1 TCCS.t_DPU 0.5 s Pickup delay time of control circuit failure alarm
2 TCCS.t_DDO 0.5 s Dropoff delay time of control circuit failure alarm
This setting is used to determine whether CB position
is determined by phase-segregated auxiliary contact
or three-phase auxiliary contact
3 En_3PhCB 0
0: phase-segregated contact ([52b_PhA], [52b_PhB],
[52b_PhC])
1: three-phase contact ([52b])

PCS-902 Line Distance Relay 3-5


Date: 2011-07-06
3 Operation Theory

3.4 Fault Detector (FD)


3.4.1 Application

The device has one DSP module with fault detector DSP and protection DSP for fault detector and
protection calculation respectively. Protection DSP with protection fault detector element is
responsible for calculation of protection elements, and fault detector DSP is responsible to
determine fault appearance on the protected power system. Fault detector in fault detector DSP
picks up to provide positive supply to output relays. The output relays can only operate when both
the fault detector in fault detector DSP and a protection element operate simultaneously.
Otherwise, the output relays would not operate. An alarm message will be issued with blocking
outputs if a protection element operates while the fault detector does not operate.

3.4.2 Fault Detector in Fault Detector DSP

Main part of FD is DPFC current detector element that detects the change of phase-to-phase
power frequency current, and residual current fault detector element that calculates the vector
sum of 3 phase currents as supplementary. They are continuously calculating the analog input
signals.

The FD pickup condition in this device includes:

1. Pickup condition 1: DPFC current is greater than the setting value

2. Pickup condition 2: Residual current is greater than the setting value

3. Pickup condition 3: Phase voltage or phase-to-phase voltage is greater than the setting value

4. Pickup condition 4: Circuit breaker position discrepancy

Pickup condition 3 and 4 are only available when respective protection elements are enabled.

If any of the above conditions is complied, the FD will operate to activate the output circuit
providing DC power supply to the output relays.

3.4.2.1 Fault Detector Based on DPFC Current (pickup condition 1)

DPFC phase-to-phase current is obtained by subtracting the phase-to-phase current from that of a
cycle before.

I(k) is the sampling value at a point.

I(k-24) is the value of a sampling point before a cycle, 24 is the sampling points in one cycle.

3-6 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

200

100

-100

-200
0 20 40 60 80 100 120
Original Current
100

50

-50

-100
0 20 40 60 80 100 120
DPFC current

From above figures, it is concluded that DPFC can reflect the sudden change of current at the
initial stage of a fault and has a perfect performance of fault detection.

It is used to determine whether this pickup condition is met according to Equation 3.4-1.

For multi-phase short-circuit fault, the DPFC phase-to-phase current has high sensitivity to ensure
the pickup of protection device. For usual single phase to earth fault, it also has sufficient
sensitivity to pick up except the earth fault with very large fault resistance. Under this condition the
DPFC current is relative small, however, residual current is also used to judge pickup condition
(pickup condition 2).

This element adopts adaptive floating threshold varied with the change of load current
continuously. The change of load current is small and steadily under normal or power swing
condition, the adaptive floating threshold with the ΔISet is higher than the change of current under
these conditions and hence maintains the element stability.

The criterion is:

ΔIΦΦMAX>1.25ΔITh+ΔISet Equation 3.4-1

Where:

ΔIΦΦMAX: The maximum half-wave integration value of phase-to-phase current (ΦΦ=AB, BC, CA)

ΔISet: The fixed threshold value (i.e. the setting [FD.DPFC.I_Set])

ΔITh: The floating threshold value

The coefficient, 1.25, is an empirical value which ensures the threshold always higher than the
unbalance output value of the system.

If operating condition is met, DPFC current element will pickup and trigger FD to provide DC power
supply for output relays, the FD operation signal will maintain 7 seconds after DPFC current
element drops off.

PCS-902 Line Distance Relay 3-7


Date: 2011-07-06
3 Operation Theory

3.4.2.2 Fault Detector Based on Residual Current (pickup condition 2)

This pickup condition will be met when 3I0 is greater than the setting [FD.ROC.3I0_Set].

Where:

3I0: residual current calculates from the vector sum of Ia, Ib and Ic

When residual current FD element operates and lasts for longer than 10 seconds, an alarm
[Alm_PersistI0] will be issued.

If operating condition is met, the residual current FD element will pickup and trigger FD to provide
DC power supply for output relay, and pickup signal will be kept for 7 seconds after the residual
current FD element drops off.

3.4.2.3 Fault Detector Based on Overvoltage (pickup condition 3)

Overvoltage fault detector will be automatically effective when overvoltage protection is enabled.

If the logic setting [59Px.Opt_1P/3P] is set as “1” (x=1 or 2), i.e. the protective device adopts
1-out-of-3 mode, when any phase voltage is greater than the setting [59Px.U_Set] (x=1 or 2), the
overvoltage fault detector element will pickup and trigger FD to provide DC power supply for
output relays, the FD operation signal will maintain 7 seconds after overvoltage fault detector
element drops off.

If the logic setting [59Px.Opt_1P/3P] is set as “0” (x=1 or 2), i.e. the protective device adopts
3-out-of-3 mode, when all three phase voltages are greater than the setting [59Px.U_Set] (x=1 or
2), the overvoltage fault detector element will pickup and trigger FD to provide DC power supply
for output relays, the FD operation signal will maintain 7 seconds after overvoltage fault detector
element drops off.

3.4.2.4 Fault Detector Based on Circuit Breaker Position Discrepancy (pickup condition 4)

When pole discrepancy protection is enabled, i.e. the logic setting [62PD.En] is set as “1”, and if
three phases of circuit breaker are not in the same status, pole discrepancy FD element will
operate to provide DC power supply for output relays, and pickup signal will maintain 7 seconds
after pole discrepancy FD element drops out.

3.4.3 Protection Fault Detector in Protection Calculation DSP

The protection device is running either of the two programs: one is “Regular program” for normal
state, and the other is “Fault calculation program” after protection fault detector picks up.

Under the normal state, the protection device will perform the following tasks:

1. Calculate analog quantity

2. Read binary input

3. Hardware self-check

4. Circuit breaker position supervision

5. Analog quantity input supervision

3-8 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

6. Channel supervision

Once the protection fault detector element in protection calculation DSP picks up, the protection
device will switch to fault calculation program, for example the calculation of distance protection,
and to determine logic. If the fault is within the protected zone, the protection device will send
tripping command.

The protection program flow chart is shown as Figure 3.4-1.

Main program

Sampling program

No Yes
Pickup?

Regular program Fault calculation program

Figure 3.4-1 Flow chart of protection program

The protection FD pickup conditions are the same as the FD in fault detector DSP as shown below.
The operation criteria for the conditions are also the same as that in fault detector DSP. Please
refer to section 3.4.2 for details.

1. Pickup condition 1: DPFC current is greater than the setting value

2. Pickup condition 2: Residual current is greater than the setting value

3. Pickup condition 3: Phase voltage or phase-to-phase voltage is greater than the setting value

4. Pickup condition 4: Circuit breaker position discrepancy

When any pickup condition mentioned above is met, the protection device will go to fault
calculation state.

Pickup condition 3 and 4 are not common fault detector elements, only used for respective
protection element. Please refer to section 3.14.1 and section 3.19 for details.

PCS-902 Line Distance Relay 3-9


Date: 2011-07-06
3 Operation Theory

3.4.4 Function Block Diagram

FD

FD.Pkp

3.4.5 I/O Signals

Table 3.4-1 Configurable I/O signals of fault detector

No. Output Signal Description


1 FD.Pkp The device picks up

Table 3.4-2 Internal I/O signals of fault detector

No. Input Signal Description


1 I3P Three-phase current input
No. Output Signal Description
1 FD.DPFC.Pkp DPFC current fault detector element operates.
2 FD.ROC.Pkp Residual current fault detector element operates.

3.4.6 Logic

SIG Ia Calculate DPFC phase-to-phase ΔIab>[FD.DPFC.I_Set]


current >=1
SIG Ib △Iab=△(Ia-Ib) ΔIbc>[FD.DPFC.I_Set] FD.DPFC.Pkp
△Ibc=△(Ib-Ic)
SIG Ic △Ica=△(Ic-Ia) ΔIca>[FD.DPFC.I_Set] >=1
0s 7s FD.Pkp

3I0>[FD.ROC.3I0_Set]
FD.ROC.Pkp
Calculate zero-sequence current
3I0=Ia+Ib+Ic

Figure 3.4-2 Logic diagram of fault detector

3.4.7 Settings

Table 3.4-3 Settings of fault detector

No. Name Range Step Unit Remark


Current setting of DPFC current fault
1 FD.DPFC.I_Set (0.050~30.000)×In 0.001 A
detector element
Current setting of residual current fault
2 FD.ROC.3I0_Set (0.050~30.000)×In 0.001 A
detector element

3-10 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.5 Distance Protection


3.5.1 General Application

When a fault happens on a power system, distance protection will trip circuit breaker to isolate the
fault from power system with its specific time delay if the fault is within the protected zone of
distance protection.

3.5.2 Function Description

The device comprises 3 forward zones, 1 reverse zone and 1 pilot zone. For each independent
distance element zone, full scheme design provides continuous measurement of impedance
separately in three independent phase-to-phase measuring loops as well as in three independent
phase-to-ground measuring loops. Selection of zone characteristic between mho and quadrilateral
is available. Distance protection includes:

1. DPFC distance protection

It is independent fast protection providing extremely fast speed to clear close up fault
especially on long line and thus improves system stability.

2. Mho phase-to-phase distance protection

Zone1~3: forward direction

Zone 4: reverse direction including origin

3. Mho phase-to-ground distance protection

Zone1~3: forward direction

Zone 4: reverse direction including origin

4. Quadrilateral phase-to-phase distance protection

Zone1~3: forward direction

Zone 4: reverse direction

5. Quadrilateral phase-to-ground distance protection

Zone1~3: forward direction

Zone 4: reverse direction

6. Pilot distance protection

The pilot zone is for PUTT, POTT and blocking scheme. The forward direction element is for
sending signal for POTT and tripping upon receiving permissive signal for both PUTT and
POTT scheme. The forward direction element for blocking scheme is used to stop sending
blocking signal. The reverse direction element is only for POTT scheme with weak infeed
condition.

7. Blinder

PCS-902 Line Distance Relay 3-11


Date: 2011-07-06
3 Operation Theory

It is used to prevent distance protection with Mho characteristic from undesired trip due to
load encroachment under heavy load condition especially for long lines.

8. Power swing detection (PSD)

9. Power swing blocking releasing (PSBR)

For power swing with external fault, distance protection is always blocked, but for power
swing with internal fault, PSBR will operate to release the blocking for distance protection.

10. SOTF distance protection

For manual closing or automatic closing on to a fault, zone 2 or 3 of distance protection will
accelerate to trip.

When VT circuit fails, VT circuit supervision logic will output a blocking signal to block all distance
protection except DPFC distance protection. The operating threshold will be increased to 1.5UN to
enhance stability.

Distance protection can select line VT or bus VT for protection algorithm by a setting
[VTS.En_Line_VT]. When no VT is provided, logic setting [VTS.En_Out_VT] should be set as “1”,
all distance protection will be blocked automatically. The coordination among zones of distance
protection is shown in the following figure.

Z4

M P N
EM A B C D EN

Z1、DZ

Z2

Z3

Figure 3.5-1 Protected reach of distance protection for each zone

Where:

Z1: forward direction zone 1

Z2: forward direction zone 2

Z3: forward direction zone 3

Z4: reverse direction zone 4

DZ: DPFC distance protection

The choice of impedance reach is as follow. (only for reference)

The zone 1 impedance reach setting should be set to cover as much the protected line as possible
but not to respond faults beyond the protected line. The accuracy of the relay distance elements is

3-12 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

+/- 2.5% in general applications, however, the error could be much larger due to errors of current
transformer, voltage transformer and inaccuracies of line parameter from which the relay settings
are calculated. It is recommended the zone 1 reach is set to 80%~85% of the protected line in
consideration the aforesaid errors and safety margin to prevent instantaneously tripping for faults
on adjacent lines. The remaining 20% of the protected line relies on the zone 2 distance elements.
With the pilot scheme distance protection, fast fault clearance could also be achieved for end zone
faults at both ends of the protected line.

The general rule for zone 2 impedance reach setting is set to cover the protected line plus 20% of
the adjacent line. However, the coverage of adjacent line should be extended in the presence of
additional infeed at the remote end of the protected line to ensure 20% coverage of adjacent line.
This assures the fast operation of zone 2 distance element for faults at the remote end of the
protected line since the fault is well within zone 2 reach. This is important for pilot protection as the
impedance reach of pilot zone is the same as that of zone 2 distance element. In a parallel line
situation, a fault cleared sequentially on a line may cause current reversal in the healthy line. If the
pilot zone settings are set to cover 50% of adjacent line and the POTT or Blocking scheme is used,
the current reversal in the healthy line could cause relay mal-operation. Therefore, current reversal
logic is required and explained in section 3.7.2.6.

The Z3 distance element acts as backup protection for protected line and adjacent line but not to
over the zone 2 setting of adjacent line. The zone 3 impedance reach is generally 2 times zone 1
reach, i.e. 160% of protected line.

35

30

25
Operating Time (ms)

20

15

10

0
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Fault Location (% of relay setting)

Figure 3.5-2 Operating time of single-phase fault (50Hz, SIR=1)

PCS-902 Line Distance Relay 3-13


Date: 2011-07-06
3 Operation Theory

35

30

25
Operating Time (ms)

20

15

10

0
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Fault Location (% of relay setting)

Figure 3.5-3 Operating time of two-phase fault (50Hz, SIR=1)

35

30

25
Operating Time (ms)

20

15

10

0
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Fault Location (% of relay setting)

Figure 3.5-4 Operating time of three-phase fault (50Hz, SIR=1)

3-14 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

33

32

31
Operating Time (ms)

30

29

28

27

26
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Fault Location (% of relay setting)

Figure 3.5-5 Operating time of single-phase fault (50Hz, SIR=30)

45
40
35
30
Operating Time (ms)

25
20
15
10
5
0
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Fault Location (% of relay setting)

Figure 3.5-6 Operating time of two-phase fault (50Hz, SIR=30)

PCS-902 Line Distance Relay 3-15


Date: 2011-07-06
3 Operation Theory

33

32

31
Operating Time (ms)

30

29

28

27
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Fault Location (% of relay setting)

Figure 3.5-7 Operating time of three-phase fault (50Hz, SIR=30)

3.5.3 DPFC Distance Protection

The power system is normally treated as a balanced symmetrical three-phase network. When a
fault occurs in the power system, by applying the principle of superposition, the load current and
voltage can be calculated in the system prior to the fault and the pure fault component can be
calculated by fault current or voltage subtracted by pre-fault load current or voltage. DPFC
distance protection concerns change of current and voltage at power frequency, therefore, DPFC
distance protection is not influenced by load current.

As an independent fast protection, DPFC distance protection is mainly used to clear close up fault
of long line quickly, its protected range can set as 80%~85% of the whole line.

Since DPFC distance protection only reflects fault component and is not influenced by current
change due to load variation and power swing, power swing blocking (PSB) is this not required.
Moreover, there is no transient overreaching due to infeed current from the remote power supply
because it is not influenced by load current.

DPFC distance protection may not overreach, and its protected zone will be inverse-proportion
reduced with system impedance behind it, i.e. the protected zone will be less than setting if the
system impedance is greater. The protected zone will be close to setting value if the system
impedance is smaller. Therefore, DPFC distance protection is usually used for long transmission
line with large power source and it is recommended to disable DPFC distance protection for short
line or the line with weak power source.

3-16 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.5.3.1 Impedance Characteristic

ZZD

M F N
Z
EM EN
∆I

ZS ZK

jX

Zzd
Zk

Φ
R
Zs+Zk
-Zs

Figure 3.5-8 Operation characteristic for forward fault

Where:

ZZD: the setting of DPFC distance protection

ZS: total impedance between local system and device location

ZK: measurement impedance

Φ: positive-sequence sensitive angle, i.e. [phi1_Reach]

Figure 3.5-8 shows the operation characteristic of DPFC distance protection on R-X plane when a
fault occurs in forward direction, which is the circle with the –Zs as the center and the│Zs+Zzd│ as
the radius. When measured impedance Zk is in the circle, DPFC distance protection will operate.
DPFC distance protection has a larger capability of enduring fault resistance than distance
protection using positive-sequence as polarized voltage.

PCS-902 Line Distance Relay 3-17


Date: 2011-07-06
3 Operation Theory

ZZD

F M N
Z
EM EN
∆I
ZK
Z′S

jX

Z's

Zzd

Φ R

-Zk

Figure 3.5-9 Operation characteristic for reverse fault

Z'S:total impedance between remote system and protective device location

Figure 3.5-9 shows the operation characteristic of the DPFC distance element on R-X plane when
a fault occurs in reverse direction, which is the circle with the Z′S as the center and the│Z′S-Zzd│as
the radius. The region of operation is in the quadrant 1 but the measured impedance -Zk is always
in the quadrant 3, the DPFC distance protection will not operate.

The DPFC distance protection can be enabled or disabled by logic setting and binary input.

3.5.3.2 Function Block Diagram

21D

21D.En_DPFC 21D.Op_DPFC

21D.Blk_DPFC

3-18 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.5.3.3 I/O Signals

Table 3.5-1 Configurable I/O signals of DPFC distance protection

No. Input Signal Description


1 21D.En_DPFC DPFC distance protection enabling input, it can be a binary input or a logic link.
2 21D.Blk_DPFC DPFC distance protection blocking input, such as a function blocking binary input.
No. Output Signal Description
1 21D.Op_DPFC DPFC distance protection operates.

3.5.3.4 Logic

EN [21D.En_DPFC] &

SIG 21D.Blk_DPFC >=1

EN [VTS.En_Out_VT]

SIG Manual closing signal


>=1
SIG 3-pole reclosing signal

SET [21D.Z_DPFC]< 0.05Ω/In

SET ZΦ<[21D.Z_DPFC] &


>=1 &
SIG UP<0.85Un & 21D.Op_DPFC

SET ZΦΦ<[21D.Z_DPFC] &

SIG UPP<0.85Unn

SIG PD signal

Figure 3.5-10 Logic diagram of DPFC distance protection

Note!

PD signal only blocks DPFC distance element of corresponding phase (i.e. broken phase),
and healthy phases (operation phases) are not affected.

3.5.3.5 Settings

Table 3.5-2 Settings of DPFC distance protection

No. Name Range Step Unit Remark


Impedance setting of DPFC distance
1 21D.Z_DPFC (0.000~2Unn)/In 0.001 ohm
protection
Enabling/disabling DPFC distance
protection
2 21D.En_DPFC 0 or 1
0: disable
1: enable

PCS-902 Line Distance Relay 3-19


Date: 2011-07-06
3 Operation Theory

3.5.4 Mho Distance Protection

3.5.4.1 Impedance Characteristic

1. Zone 1, 2 and 3 of phase-to-ground distance element

ZZD

M F N
Z IN
EM EN
I

ZS ZK

jX

ZZD

ZK

Φ
R

-2ZS/3

Figure 3.5-11 Phase-to-ground operation characteristic for forward fault

Where:

ZZD: the setting of distance protection

ZS: total impedance between local system and protective device location

ZK: measurement impedance

Φ: positive-sequence sensitive angle, i.e. [phi1_Reach]

Phase-to-neutral positive sequence voltage is used as polarized signal for phase-to-ground


distance protection.

For zone 1 and zone 2:

Operation voltage:

Polarized voltage:

3-20 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

In short line, phase shift θ1 could be applied to the polarized voltage to improve the performance
against high resistance fault. The device provides an angle-shift setting, [ZG.phi_Shift], to set
value of θ1 among 0°, 15°and 30°. Their impedance shift characteristics towards quadrant 1 are
respectively shown as the impedance circle A, B and C in Figure 3.5-16.

For zone 3:

Operation voltage:

Polarized voltage:

UPΦ uses phase positive-sequence voltage as polarized voltage. For earth fault, positive-sequence
voltage is mainly formed from healthy phases, basically retaining the phase of the
positive-sequence voltage before fault.

Phase comparison equation is:

The operation characteristic is shown in Figure 3.5-5. Operation characteristic of ZK on R-X plane
is a circle with line connecting ends of ZZD and -2ZS/3 as the diameter. The origin is enclosed in the
circle.

2. Zone 1, 2 and 3 of phase-to-phase distance element

jX

ZZD

ZK

Φ
R

-ZS/2

Figure 3.5-12 Phase-to-phase operation characteristic for forward fault

Phase-to-phase positive sequence voltage is used as polarized signal for phase-to-phase


distance protection.

For zone 1 and zone 2:

PCS-902 Line Distance Relay 3-21


Date: 2011-07-06
3 Operation Theory

Operation voltage:

Polarized voltage:

Phase shift θ2 could be applied to polarized voltage of zones 1 and 2 just like θ1 in
phase-to-ground distance element. It is also used for improving performance against high
resistance fault in short line. The device provides an angle-shift setting, [ZP.phi_Shift], to set value
of θ2 among 0°, 15° and 30°. Their impedance shift characteristics towards quadrant 1 are
respectively shown as the impedance circle A, B and C in Figure 3.5-16.

For zone 3:

Operation voltage:

Polarized voltage:

Phase-to-phase positive-sequence voltage is applied as the polarized voltage of this element.

Phase comparison equation is:

The operation characteristic of phase-to-phase distance element is shown in Figure 3.5-12.


Operation characteristic of ZK on R-X plane is a circle with line connecting ends of ZZD and -ZS/2 as
the diameter. The origin is enclosed in the circle.

Figure 3.5-13 shows operation characteristic of measured impedance -ZK on R-X plane when an
asymmetric reverse fault occurs. This characteristic is a circle with line connecting ends of ZZD and
Z'S as the diameter. It will operate only when -ZK is in the circle. Therefore, directionality of the
distanced protection is achieved.

ZZD

F M N
Z
EM EN

ZK
Z′S

3-22 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

jX

Z'S

ZZD

Φ
R

-ZK

Figure 3.5-13 Operation characteristic for reverse fault

Z'S: total impedance between remote system and protective device location

jX

ZZD

ZK

Φ
R

Figure 3.5-14 Steady-state characteristic of three-phase short-circuit fault

Phase-to-phase distance protection is also used for three-phase short-circuit fault. The operation
characteristic is shown in Figure 3.5-14. Operation characteristic of ZK on R-X plane is a circle with
setting impedance ZZD as the diameter.

PCS-902 Line Distance Relay 3-23


Date: 2011-07-06
3 Operation Theory

jX

ZZD

ZK

Φ
R

C
-ZS B
A

Figure 3.5-15 Operation characteristic of three-phase close up short-circuit fault

Where:

ZZD: the setting of distance protection (zone x)

ZS: total impedance between local system and protective device location

ZK: measured impedance

Φ: positive-sequence characteristic angle, i.e. [phi1_Reach]

As shown in Figure 3.5-15, the characteristic of the distance protection for a three-phase fault on a
system is an impedance circle cross the origin, and there is a voltage dead zone around the origin.
In order to eliminate the dead zone of the distance protection for a close up three-phase fault
memorized positive-sequence voltage is adopted as polarized voltage when the
positive-sequence voltage drops down to 15%Un or below.

The transient (during process of memory) operation characteristic is shown as the impedance
circle A in the above figure. The circle takes ZZD and -ZZS as diameter and thus the origin is within
the impedance circle. When three-phase fault happens in reverse direction, its transient
characteristic is shown in figure 3.5-7, i.e. the distance protection has a clearly defined
directionality and no dead zone during the process of memory.

For zone 1, zone 2 and zone 3 of the phase-to-phase distance protection, if distance protection
operates with memorized polarizing voltage, this means a close up forward fault. When the
memory fades out, the operation characteristic will be reverse offset a little to enclose the origin as
impedance circle B shown in Figure 3.5-15 to ensure keeping operating of distance protection until
the fault being cleared. If distance protection does not operate with memorized polarizing voltage,
it will be a close up reverse fault. When the memory fades out, the operation characteristic will be
forward offset not to enclose the origin as impedance circle C shown in Figure 3.5-15, and the
distance protection will not mal-operate even if voltage is zero.

The distance protection with such design thoroughly eliminates the dead zone when three-phase

3-24 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

close up fault occurs. It also has favorable directivity and will not operate for a reverse three-phase
fault at busbar.

When receiving manual closing signal or 3-pole reclosing signal, the operation characteristic of
phase to phase distance protection will always enclose the origin of impedance, with no dead zone,
i.e. the reverse offset impedance circle B shown in Figure 3.5-15.

jX

B: 15° C: 30°
ZZD
A: 0°
D

-ZS

Figure 3.5-16 Shift impedance characteristic of zone 1 and zone 2

The impedance characteristic of phase-to-ground distance protection is the circle with line
connecting ends of ZZD and -2ZS/3 as the diameter and that of phase-to-phase distance is the
circle with line connecting ends of ZZD and -ZS/2 as the diameter.

In order to prevent the transient overreach caused by the infeed power supply from the remote
end, the zero-sequence reactance line D is added. These measures have enhanced the capacity
against fault resistance when using distance protection in short lines.

3. Zone 4

ZZDR ZZDF

F M N
I Z
EM EN

ZK

PCS-902 Line Distance Relay 3-25


Date: 2011-07-06
3 Operation Theory

jX

ZZDF

Φ
R

ZK

ZZDR

Figure 3.5-17 Operation characteristic of reverse Z4 distance protection

Where:

ZZDF: impedance setting of zone 4 in forward direction, i.e. [21M.Z4.Z_Fwd]

ZZDR: impedance setting of zone 4 in reverse direction, i.e. [21M.Z4.Z_Rev]

Φ: positive-sequence characteristic angle, i.e. [phi1_Reach]

ZK: measurement impedance

When a fault occurs on the rear busbar, reverse distance element is provided to clear it with
definite time delay and is taken as backup protection for reverse busbar fault. Its operation
characteristic is shown in Figure 3.5-17.

4. Blinder

The blinder characteristic for all zones shown in Figure 3.5-18 can be used to restrict the reach of
a distance relay on a long line or during heavy load conditions. The distance relay will be allowed
to trip only when both blinders are operated (i.e., the apparent impedance must be between the
two characteristics).

3-26 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

jX

B ZZD A

Φ
R

RZD RZD

Figure 3.5-18 Operation characteristic of blinder

In order to ensure distance protection reach not to encroach into load impendence, the
phase-to-phase and phase-to-ground blinders are used. As shown above, the characteristic angle
of the blinder is the same as line positive sequence characteristic angle Φ, this makes the
protected zones covering same fault resistance. RZD is the setting [21M.R_Blinder]. The operation
region is between line A and line B. The logic setting [21M.En_Blinder] can decide whether the
blinder is enabled or not.

3.5.4.2 Function Block Diagram

21M

21M.En 21M.Z1.Op

21M.Blk 21M.Z2.Op

21M.Z3.Op

21M.Z4.Op

3.5.4.3 I/O Signals

Table 3.5-3 Configurable I/O signals of distance protection (Mho)

No. Input Signal Description


1 21M.En Distance protection enabling input, it can be a binary input or a logic link.
2 21M.Blk Distance protection blocking input, such as a function blocking binary input.
No. Output Signal Description
1 21M.Z1.Op Zone 1 of distance protection operates
2 21M.Z2.Op Zone 2 of distance protection operates
3 21M.Z3.Op Zone 3 of distance protection operates
4 21M.Z4.Op zone 4 of distance protection operates

PCS-902 Line Distance Relay 3-27


Date: 2011-07-06
3 Operation Theory

Table 3.5-4 Internal I/O signals of distance protection (Mho)

No. Input Signal Description


1 21M.ZG1.In_En Zone 1 of phase-to-ground distance protection enabling input, default value is “1”
2 21M.ZG1.In_Blk Zone 1 of phase-to-ground distance protection blocking input, default value is “0”
3 21M.ZP1.In_En Zone 1 of phase-to-phase distance protection enabling input, default value is “1”
4 21M.ZP1.In_Blk Zone 1 of phase-to-phase distance protection blocking input, default value is “0”
5 21M.ZG2.In_En Zone 2 of phase-to-ground distance protection enabling input, default value is “1”
6 21M.ZG2.In_Blk Zone 2 of phase-to-ground distance protection blocking input, default value is “0”
7 21M.ZP2.In_En Zone 2 of phase-to-phase distance protection enabling input, default value is “1”
8 21M.ZP2.In_Blk Zone 2 of phase-to-phase distance protection blocking input, default value is “0”
9 21M.ZG3.In_En Zone 3 of phase-to-ground distance protection enabling input, default value is “1”
10 21M.ZG3.In_Blk Zone 3 of phase-to-ground distance protection blocking input, default value is “0”
11 21M.ZP3.In_En Zone 3 of phase-to-phase distance protection enabling input, default value is “1”
12 21M.ZP3.In_Blk Zone 3 of phase-to-phase distance protection blocking input, default value is “0”
13 21M.ZG4.In_En Zone 4 of phase-to-ground distance protection enabling input, default value is “1”
14 21M.ZG4.In_Blk Zone 4 of phase-to-ground distance protection blocking input, default value is “0”
15 21M.ZP4.In_En Zone 4 of phase-to-phase distance protection enabling input, default value is “1”
16 21M.ZP4.In_Blk Zone 4 of phase-to-phase distance protection blocking input, default value is “0”

3.5.4.4 Logic

SIG 21M.En &


&
SIG 21M.Blk 21M.Enable

SIG VTS.Alm >=1

EN [VTS.En_Out_VT]

Figure 3.5-19 Logic diagram of enabling distance protection (Mho)

3-28 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

SIG 21M.Enable
&
SIG 21M.ZG1.In_En & 21M.ZG1.Enable

SIG 21M.ZG1.In_Blk
&
SIG 21M.ZP1.In_En & 21M.ZP1.Enable

SIG 21M.ZP1.In_Blk

SIG 21M.Z1.Rls_PSBR
&
SIG 21M.ZG1.Enable & [21M.ZG1.t_Op] 0 21M.ZG1.Op

EN [21M.ZG1.En]

SIG Flag.21M.ZG1.Z (PG) &


Flag.21M.R_Blinder (PG)
>=1
SIG &

SET 3I0>[FD.ROC.3I0_Set]
>=1
SIG Flag.21M.ZP1.Z (PP) & 21M.Z1.Flg_PSBR

SIG Flag.21M.R_Blinder (PP)


&
SIG 21M.ZP1.Enable & [21M.ZP1.t_Op] 0 21M.ZP1.Op

EN [21M.ZP1.En]

SIG 21M.ZG1.Op >=1


21M.Z1.Op
SIG 21M.ZP1.Op

Figure 3.5-20 Logic diagram of distance protection (Mho zone 1)

Where:

Flag.21M.ZG1.Z (PG) means that measured impedance by zone 1 of phase-to-ground distance


protection is within the range determined by the setting [21M.ZG1.Z_Set].

Flag.21M.R_Blinder (PG) means that measured impedance by zone 1 of phase-to-ground


distance protection is within the range determined by the setting [21M.R_Blinder].

Flag.21M.ZP1.Z (PP) means that measured impedance by zone 1 of phase-to-phase distance


protection is within the range determined by the setting [21M.ZP1.Z_Set].

Flag.21M.R_Blinder (PP) means that measured impedance by zone 1 of phase-to-phase distance


protection is within the range determined by the setting [21M.R_Blinder].

PCS-902 Line Distance Relay 3-29


Date: 2011-07-06
3 Operation Theory

SIG 21M.Enable
&
SIG 21M.ZG2.In_En & 21M.ZG2.Enable

SIG 21M.ZG2.In_Blk
&
SIG 21M.ZP2.In_En & 21M.ZP2.Enable

SIG 21M.ZP2.In_Blk

SIG 21M.Z2.In_En_ShortDly &


&
SIG 21M.Z2.In_Blk_ShortDly 21M.Z2.Enable_ShortDly

EN [21M.Z2.En_ShortDly]

SIG 21M.ZP2.Enable_ShortDly &


[21M.ZG2.t_ShortDly] 0
SIG 21M.Z2.Rls_PSBR
>=1
SIG 21M.ZG2.Enable & & 21M.ZG2.Op
[21M.ZG2.t_Op] 0
EN [21M.ZG2.En]
>=1
SIG Flag.21M.ZG2.Z (PG) & >=1
21M.Z2.Flg_PSBR
SIG Flag.21M.R_Blinder (PG) &

SET 3I0>[FD.ROC.3I0_Set]

SIG Flag.21M.ZP2.Z (PP) &

SIG Flag.21M.R_Blinder (PP) &


[21M.ZP2.t_Op] 0
SIG 21M.ZP2.Enable &
>=1
& 21M.ZP2.Op
EN [21M.ZP2.En]
[21M.ZP2.t_ShortDly] 0
SIG 21M.Z2.Enable_ShortDly

SIG 21M.ZG2.Op >=1


21M.Z2.Op
SIG 21M.ZP2.Op

Figure 3.5-21 Logic diagram of distance protection (Mho zone 2)

Where:

Flag.21M.ZG2.Z (PG) means that measured impedance by zone 2 of phase-to-ground distance


protection is within the range determined by the setting [21M.ZG2.Z_Set].

Flag.21M.R_Blinder (PG) means that measured impedance by zone 2 of phase-to-ground


distance protection is within the range determined by the setting [21M.R_Blinder].

Flag.21M.ZP2.Z (PP) means that measured impedance by zone 2 of phase-to-phase distance


protection is within the range determined by the setting [21M.ZP2.Z_Set].

Flag.21M.R_Blinder (PP) means that measured impedance by zone 2 of phase-to-phase distance


protection is within the range determined by the setting [21M.R_Blinder].

3-30 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

SIG 21M.Enable
&
SIG 21M.ZG3.In_En & 21M.ZG3.Enable

SIG 21M.ZG3.In_Blk
&
SIG 21M.ZP3.In_En & 21M.ZP3.Enable

SIG 21M.ZP3.In_Blk

SIG 21M.Z3.In_En_ShortDly &


&
SIG 21M.Z3.In_Blk_ShortDly 21M.Z3.Enable_ShortDly

EN [21M.Z3.En_ShortDly]

SIG 21M.Z3.Enable_ShortDly &


[21M.ZG3.t_ShortDly] 0 >=1
21M.ZG3.Op
SIG 21M.Z3.Rls_PSBR

SIG 21M.ZG3.Enable & &


[21M.ZG3.t_Op] 0
EN [21M.ZG3.En]

SIG Flag.21M.ZG3.Z (PG) &


>=1
SIG Flag.21M.R_Blinder (PG) 21M.Z3.Flg_PSBR

SIG Flag.21M.ZP3.Z (PP) &


&
SIG Flag.21M.R_Blinder (PP)

SIG 21M.ZP3.Enable & [21M.ZP3.t_Op] 0 >=1


21M.ZP3.Op
EN [21M.ZP3.En] &
[21M.ZP3.t_ShortDly] 0
SIG 21M.ZP3.Enable_ShortDly

SIG 21M.ZG3.Op >=1


21M.Z3.Op
SIG 21M.ZP3.Op

Figure 3.5-22 Logic diagram of distance protection (Mho zone 3)

Where:

Flag.21M.ZG3.Z (PG) means that measured impedance by zone 3 of phase-to-ground distance


protection is within the range determined by the setting [21M.ZG3.Z_Set].

Flag.21M.R_Blinder (PG) means that measured impedance by zone 3 of phase-to-ground


distance protection is within the range determined by the setting [21M.R_Blinder].

Flag.21M.ZP3.Z (PP) means that measured impedance by zone 3 of phase-to-phase distance


protection is within the range determined by the setting [21M.ZP3.Z_Set].

Flag.21M.R_Blinder (PP) means that measured impedance by zone 3 of phase-to-phase distance


protection is within the range determined by the setting [21M.R_Blinder].

PCS-902 Line Distance Relay 3-31


Date: 2011-07-06
3 Operation Theory

SIG 21M.Enable
&
SIG 21M.ZG4.In_En & 21M.ZG4.Enable

SIG 21M.Zp4.In_Blk
&
SIG 21M.ZP4.In_En & 21M.ZP4.Enable

SIG 21M.ZP4.In_Blk

SIG 21M.ZG4.Enable &


&
EN [21M.ZG4.En] [21M.ZG4.t_Op] 0 21M.ZG4.Op

SET 3I0>[FD.ROC.3I0_Set] &


>=1
SIG Flag.21M.Z4.Z (PG) 21M.Z4.Flg_PSBR

SIG Flag.21M.Z4.Z (PP) &


[21M.ZP4.t_Op] 0 21M.ZP4.Op

SIG 21M.ZP4.Enable &

EN [21M.ZP4.En]

SIG 21M.ZG4.Op >=1


21M.Z4.Op
SIG 21M.ZP4.Op

Figure 3.5-23 Logic diagram of distance protection (Mho zone 4)

Where:

Flag.21M.Z4.Z (PG) means that measured impedance by zone 4 of phase-to-ground distance


protection is within the range determined by the settings [21M.Z4.Z_Fwd] and [21M.Z4.Z_Rev].

Flag.21M.Z4.Z (PP) means that measured impedance by zone 4 of phase-to-phase distance


protection is within the range determined by the settings [21M.Z4.Z_Fwd] and [21M.Z4.Z_Rev].

3.5.4.5 Settings

Table 3.5-5 Settings of distance protection (Mho)

No. Name Range Step Unit Remark


Phase shift of zone 1, 2 of
1 21M.ZG.phi_Shift 0, 15 or 30 Deg
phase-to-ground distance protection
Phase shift of zone 1, 2 of
2 21M.ZP.phi_Shift 0, 15 or 30 Deg
phase-to-phase distance protection
Impedance setting of zone 1 of
3 21M.ZG1.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-ground distance protection
Time delay of zone 1 of
4 21M.ZG1.t_Op 0.000~10.000 0.001 s
phase-to-ground distance protection

3-32 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Enabling/disabling zone 1 of
phase-to-ground distance protection
5 21M.ZG1.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-ground
zone 1 of distance protection operation
6 21M.ZG1.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 1 of
7 21M.ZP1.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-phase distance protection
Time delay of zone 1 of
8 21M.ZP1.t_Op 0.000~10.000 0.001 s
phase-to-phase distance protection
Enabling/disabling zone 1 of
phase-to-phase distance protection
9 21M.ZP1.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-phase
zone 1 of distance protection operation
10 21M.ZP1.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 2 of
11 21M.ZG2.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-ground distance protection
Time delay of zone 2 of
12 21M.ZG2.t_Op 0.000~10.000 0.001 s
phase-to-ground distance protection
Enabling/disabling zone 2 of
phase-to-ground distance protection
13 21M.ZG2.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-ground
zone 2 of distance protection operation
14 21M.ZG2.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 2 of
15 21M.ZP2.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-phase distance protection
Time delay of zone 2 of
16 21M.ZP2.t_Op 0.000~10.000 0.001 s
phase-to-phase distance protection
Enabling/disabling zone 2 of
phase-to-phase distance protection
17 21M.ZP2.En 0 or 1
0: disable
1: enable
18 21M.ZP2.En_BlkAR 0 or 1 Enabling/disabling phase-to-phase

PCS-902 Line Distance Relay 3-33


Date: 2011-07-06
3 Operation Theory

zone 2 of distance protection operation


to block AR
0: disable
1: enable
Impedance setting of zone 3 of
19 21M.ZG3.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-ground distance protection
Time delay of zone 3 of
20 21M.ZG3.t_Op 0.000~10.000 0.001 s
phase-to-ground distance protection
Enabling/disabling zone 3 of
phase-to-ground distance protection
21 21M.ZG3.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-ground
zone 3 of distance protection operation
22 21M.ZG3.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 3 of
23 21M.ZP3.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-phase distance protection
Time delay of zone 3 of
24 21M.ZP3.t_Op 0.000~10.000 0.001 s
phase-to-phase distance protection
Enabling/disabling zone 3 of
phase-to-phase distance protection
25 21M.ZP3.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-phase
zone 3 of distance protection operation
26 21M.ZP3.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 4 of
27 21M.Z4.Z_Fwd (0.000~2Unn)/In 0.001 ohm
distance protection in forward direction
Impedance setting of zone 4 of
28 21M.Z4.Z_Rev (0.000~2Unn)/In 0.001 ohm
distance protection in reverse direction
Time delay of zone 4 of distance
29 21M.Z4.t_Op 0.000~10.000 0.001 s
protection
Enabling/disabling zone 4 of
phase-to-ground distance protection
30 21M.ZG4.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-ground
zone 4 of distance protection operation
31 21M.ZG4.En_BlkAR 0 or 1
to block AR
0: disable

3-34 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

1: enable
Enabling/disabling zone 4 of
phase-to-phase distance protection
32 21M.ZP4.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-phase
zone 4 of distance protection operation
33 21M.ZP4.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Resistive impedance reach of distance
34 21M.R_Blinder (0.000~2Unn)/In 0.001 ohm
element
Enabling/disabling blinder element
35 21M.En_Blinder 0 or 1 0: disable
1: enable

Table 3.5-6 Internal settings of distance protection (Mho)

No. Name Default Value Unit Remark


Short time delay of zone 2 of phase-to-ground
1 21M.ZG2.t_ShortDly 0.025 s
distance protection
Short time delay of zone 2 of phase-to-phase
2 21M.ZP2.t_ShortDly 0.025 s
distance protection
Fixed accelerate zone 2 of distance protection
3 21M.Z2. En_ShortDly 0 0: disable
1: enable
Short time delay of zone 3 of phase-to-ground
4 21M.ZG3.t_ShortDly 0.025 s
distance protection
Short time delay of zone 3 of phase-to-phase
5 21M.ZP3.t_ShortDly 0.025 s
distance protection
Fixed accelerate zone 3 of distance protection
6 21M.Z3.En_ShortDly 0 0: disable
1: enable

3.5.5 Quadrilateral Distance Element

3.5.5.1 Impedance Characteristic

Features available with quadrilateral distance protection are shown as follows.

1. Three forward zones phase-to-ground distance protection

2. One reverse zone phase-to-ground distance protection

3. Three forward zones phase-to-phase distance protection

4. One reverse zone phase-to-phase distance protection

5. Power swing blocking releasing, respectively enable or disable for each zone

PCS-902 Line Distance Relay 3-35


Date: 2011-07-06
3 Operation Theory

6. Pilot zone distance protection

Quadrilateral distance protection will be disabled when VT circuit fails.

Quadrilateral forward distance element characteristic for zone 1, 2 and 3 is shown as follows:

jX

ZZD
θ

α φ
φ

β R
O RZD

Figure 3.5-24 Quadrilateral forward distance element characteristics

Where:

ZZD: impedance setting.

RZD: resistive setting range.

φ: line positive-sequence characteristic angle.

α: the angle of directional line in the second quadrant, fixed at 15 °.

β: the angle of directional line in the fourth quadrant, fixed at 15 °.

θ: downward angle of reactance line.

When a fault occurs on the busbar at the back, reverse distance element zone 4 is provided to
clear it with definite time delay and is used as backup protection for reverse busbar fault.

jX
C
RZD β O
R
φ φ
α

B
θ
ZZD A

Figure 3.5-25 Zone 4 reverse quadrilateral distance element characteristic

3-36 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Where:

ZZD: impedance setting of zone 4 in reverse direction

RZD: resistance setting of zone 4 in reverse direction

φ: positive-sequence characteristic angle,

α: the angle of directional line, fixed at 15°

β: the angle of directional line, fixed at 15°

θ: tilted angle of the reactance line AB, fixed at 12°

3.5.5.2 Function Block Diagram

21Q

21Q.En 21Q.Z1.Op

21Q.Blk 21Q.Z2.Op

21Q.Z3.Op

21Q.Z4.Op

3.5.5.3 I/O Signals

Table 3.5-7 Configurable I/O signals of distance protection (Quad)

No. Input Signal Description


1 21Q.En Distance protection enabling input, it can be a binary input or a logic link.
2 21Q.Blk Distance protection blocking input, such as a function blocking binary input.
No. Output Signal Description
1 21Q.Z1.Op Zone 1 of distance protection operates
2 21Q.Z2.Op Zone 2 of distance protection operates
3 21Q.Z3.Op Zone 3 of distance protection operates
4 21Q.Z4.Op zone 4 of distance protection operates

Table 3.5-8 Internal I/O signals of distance protection (Quad)

No. Input Signal Description


1 21Q.ZG1.In_En Zone 1 of phase-to-ground distance protection enabling input, default value is “1”
2 21Q.ZG1.In_Blk Zone 1 of phase-to-ground distance protection blocking input, default value is “0”
3 21Q.ZP1.In_En Zone 1 of phase-to-phase distance protection enabling input, default value is “1”
4 21Q.ZP1.In_Blk Zone 1 of phase-to-phase distance protection blocking input, default value is “0”
5 21Q.ZG2.In_En Zone 2 of phase-to-ground distance protection enabling input, default value is “1”
6 21Q.ZG2.In_Blk Zone 2 of phase-to-ground distance protection blocking input, default value is “0”
7 21Q.ZP2.In_En Zone 2 of phase-to-phase distance protection enabling input, default value is “1”
8 21Q.ZP2.In_Blk Zone 2 of phase-to-phase distance protection blocking input, default value is “0”
9 21Q.ZG3.In_En Zone 3 of phase-to-ground distance protection enabling input, default value is “1”

PCS-902 Line Distance Relay 3-37


Date: 2011-07-06
3 Operation Theory

10 21Q.ZG3.In_Blk Zone 3 of phase-to-ground distance protection blocking input, default value is “0”
11 21Q.ZP3.In_En Zone 3 of phase-to-phase distance protection enabling input, default value is “1”
12 21Q.ZP3.In_Blk Zone 3 of phase-to-phase distance protection blocking input, default value is “0”
13 21Q.ZG4.In_En Zone 4 of phase-to-ground distance protection enabling input, default value is “1”
14 21Q.ZG4.In_Blk Zone 4 of phase-to-ground distance protection blocking input, default value is “0”
15 21Q.ZP4.In_En Zone 4 of phase-to-phase distance protection enabling input, default value is “1”
16 21Q.ZP4.In_Blk Zone 4 of phase-to-phase distance protection blocking input, default value is “0”

3.5.5.4 Logic

SIG 21Q.En &


&
SIG 21Q.Blk 21Q.Enable

SIG VTS.Alm >=1

EN [VTS.En_Out_VT]

Figure 3.5-26 Logic diagram of enabling distance protection (Quad)

SIG 21Q.Enable

EN [21Q.ZG1.En]
&
& 21Q.ZG1.Enable
SIG 21Q.ZG1.In_En

SIG 21Q.ZG1.In_Blk

EN [21Q.ZP1.En]
&
& 21Q.ZP1.Enable
SIG 21Q>ZP1.In_En

SIG 21Q.ZP1.In_Blk
&
SIG 21Q.ZG1.Enable & [21Q.ZG1.t_Op] 0 21Q.ZG1.Op

SIG Flag.21Q.ZG1
>=1
SIG 21Q.Z1.Rls_PSBR 21Q.Z1.Flg_PSBR

SIG 21Q.ZP1.Enable &


&
SIG Flag.21Q.ZP1 [21Q.ZP1.t_Op] 0 21Q.ZP1.Op

SIG 21Q.ZG1.Op >=1


21Q.Z1.Op
SIG 21Q.ZP1.Op

Figure 3.5-27 Logic diagram of distance protection (Quad zone 1)

Where:

Flag.21Q.ZG1 means that measured impedance by zone 1 of phase-to-ground distance protection

3-38 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

is within the range determined by the settings [21Q.ZG1.Z_Set] and [21Q.ZG1.R_Set].

Flag.21Q.ZP1 means that measured impedance by zone 1 of phase-to-phase distance protection


is within the range determined by the settings [21Q.ZP1.Z_Set] and [21Q.ZP1.R_Set].

SIG 21Q.Enable

EN [21Q.ZG2.En]
&
& 21Q.ZG2.Enable
SIG 21Q.ZG2.In_En

SIG 21Q.ZG2.In_Blk

EN [21Q.ZP2.En]
&
& 21Q.ZP2.Enable
SIG 21Q.ZP2.In_En

SIG 21Q.ZP2.In_Blk

SIG 21Q.Z2.In_En_ShortDly &


&
SIG 21Q.Z2.In_Blk_ShortDly 21Q.Z2.Enable_ShortDly

EN [21Q.Z2.En_ShortDly]

SIG 21Q.Z2.Enable_ShortDly &


& [21Q.ZG2.t_ShortDly] 0 >=1
SIG 21Q.ZG2.Enable & 21Q.ZG2.Op

[21Q.ZG2.t_Op] 0
SIG Flag.21Q.ZG2
>=1
SIG 21Q.Z2.Rls_PSBR 21Q.Z2.Flg_PSBR

SIG 21Q.ZP2.Enable & &


& [21Q.ZP2.t_ShortDly] 0 >=1
SIG Flag.21Q.ZP2 21Q.ZP2.Op

[21Q.ZP2.t_Op] 0
SIG 21Q.ZG2.Op >=1
21Q.Z2.Op
SIG 21Q.ZP2.Op

Figure 3.5-28 Logic diagram of distance protection (Quad zone 2)

Where:

Flag.21Q.ZG2 means that measured impedance by zone 2 of phase-to-ground distance protection


is within the range determined by the settings [21Q.ZG2.Z_Set] and [21Q.ZG2.R_Set].

Flag.21Q.ZP2 means that measured impedance by zone 2 of phase-to-phase distance protection


is within the range determined by the settings [21Q.ZP2.Z_Set] and [21Q.ZP2.R_Set].

PCS-902 Line Distance Relay 3-39


Date: 2011-07-06
3 Operation Theory

SIG 21Q.Enable

EN [21Q.ZG3.En]
&
& 21Q.ZG3.Enable
SIG 21Q.ZG3.In_En

SIG 21Q.ZG3.In_Blk

EN [21Q.ZP3.En]
&
& 21Q.ZP3.Enable
SIG 21Q.ZP3.In_En

SIG 21Q.ZP3.In_Blk

SIG 21Q.Z3.In_En_ShortDly &


&
SIG 21Q.Z3.In_Blk_ShortDly 21Q.Z3.Enable_ShortDly

EN [21Q.Z3.En_ShortDly]

SIG 21Q.Z3.Enable_ShortDly &


& [21Q.ZG3.t_ShortDly] 0 >=1
SIG 21Q.ZG3.Enable & 21Q.ZG3.Op

[21Q.ZG3.t_Op] 0
SIG Flag.21Q.ZG3
>=1
SIG 21Q.Z3.Rls_PSBR 21Q.Z2.Flg_PSBR

SIG 21Q.ZP3.Enable & &


& [21Q.ZP3.t_ShortDly] 0 >=1
SIG Flag.21Q.ZP3 21Q.ZP3.Op

[21Q.ZP3.t_Op] 0
SIG 21Q.ZG3.Op >=1
21Q.Z3.Op
SIG 21Q.ZP3.Op

Figure 3.5-29 Logic diagram of distance protection (Quad zone 3)

Where:

Flag.21Q.ZG3 means that measured impedance by zone 3 of phase-to-ground distance protection


is within the range determined by the settings [21Q.ZG3.Z_Set] and [21Q.ZG3.R_Set].

Flag.21Q.ZP3 means that measured impedance by zone 3 of phase-to-phase distance protection


is within the range determined by the settings [21Q.ZP3.Z_Set] and [21Q.ZP3.R_Set].

3-40 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

SIG 21Q.Enable

EN [21Q.ZG4.En]
&
& 21Q.ZG4.Enable
SIG 21Q.ZG4.In_En

SIG 21Q.ZG4.In_Blk

EN [21Q.ZP4.En]
&
& 21Q.ZP4.Enable
SIG 21Q.ZP4.In_En

SIG 21Q.ZP4.In_Blk
&
SIG 21Q.ZG4.Enable & [21Q.ZG4.t_Op] 0 21Q.ZG4.Op

SIG Flag.21Q.ZG4
>=1
SIG 21Q.Z4.Rls_PSBR 21Q.Z4.Flg_PSBR

SIG 21Q.ZP4.Enable &


&
SIG Flag.21Q.ZP4 [21Q.ZP4.t_Op] 0 21Q.ZP4.Op

SIG 21Q.ZG4.Op >=1


21Q.Z4.Op
SIG 21Q.ZP4.Op

Figure 3.5-30 Logic diagram of distance protection (Quad zone 4)

Where:

Flag.21Q.ZG4 means that measured impedance by zone 4 of phase-to-ground distance protection


is within the range determined by the settings [21Q.ZG4.Z_Set] and [21Q.ZG4.R_Set].

Flag.21Q.ZP4 means that measured impedance by zone 4 of phase-to-phase distance protection


is within the range determined by the settings [21Q.ZP4.Z_Set] and [21Q.ZP4.R_Set].

3.5.5.5 Settings

Table 3.5-9 Settings of distance protection (Quad)

No. Name Range Step Unit Remark


Real component of zero-sequence
1 21Q.Real_K0 -2.000~2.000 0.001
compensation coefficient
Imaginary component of
2 21Q.Imag_K0 -2.000~2.000 0.001 zero-sequence compensation
coefficient
Impedance setting of zone 1 of
3 21Q.ZG1.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-ground distance protection
Resistance setting of zone 1 of
4 21Q.ZG1.R_Set (0.000~2Unn)/In 0.001 ohm
phase-to-ground distance protection

PCS-902 Line Distance Relay 3-41


Date: 2011-07-06
3 Operation Theory

Time delay of zone 1 of


5 21Q.ZG1.t_Op 0.000~10.000 0.001 s
phase-to-ground distance protection
Enabling/disabling zone 1 of
phase-to-ground distance protection
6 21Q.ZG1.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-ground
zone 1 of distance protection operation
7 21Q.ZG1.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 1 of
8 21Q.ZP1.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-phase distance protection
Resistance setting of zone 1 of
9 21Q.ZP1.R_Set (0.000~2Unn)/In 0.001 ohm
phase-to-phase distance protection
Time delay of zone 1 of
10 21Q.ZP1.t_Op 0.000~10.000 0.001 s
phase-to-phase distance protection
Enabling/disabling zone 1 of
phase-to-phase distance protection
11 21Q.ZP1.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-phase
zone 1 of distance protection operation
12 21Q.ZP1.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 2 of
13 21Q.ZG2.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-ground distance protection
Resistance setting of zone 2 of
14 21Q.ZG2.R_Set (0.000~2Unn)/In 0.001 ohm
phase-to-ground distance protection
Time delay of zone 2 of
15 21Q.ZG2.t_Op 0.000~10.000 0.001 s
phase-to-ground distance protection
Enabling/disabling zone 2 of
phase-to-ground distance protection
16 21Q.ZG2.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-ground
zone 2 of distance protection operation
17 21Q.ZG2.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 2 of
18 21Q.ZP2.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-phase distance protection
19 21Q.ZP2.R_Set (0.000~2Unn)/In 0.001 ohm Resistance setting of zone 2 of

3-42 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

phase-to-phase distance protection


Time delay of zone 2 of
20 21Q.ZP2.t_Op 0.000~10.000 0.001 s
phase-to-phase distance protection
Enabling/disabling zone 2 of
phase-to-phase distance protection
21 21Q.ZP2.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-phase
zone 2 of distance protection operation
22 21Q.ZP2.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 3 of
23 21Q.ZG3.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-ground distance protection
Resistance setting of zone 3 of
24 21Q.ZG3.R_Set (0.000~2Unn)/In 0.001 ohm
phase-to-ground distance protection
Time delay of zone 3 of
25 21Q.ZG3.t_Op 0.000~10.000 0.001 s
phase-to-ground distance protection
Enabling/disabling zone 3 of
phase-to-ground distance protection
26 21Q.ZG3.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-ground
zone 3 of distance protection operation
27 21Q.ZG3.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 3 of
28 21Q.ZP3.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-phase distance protection
Resistance setting of zone 3 of
29 21Q.ZP3.R_Set (0.000~2Unn)/In 0.001 ohm
phase-to-phase distance protection
Time delay of zone 3 of
30 21Q.ZP3.t_Op 0.000~10.000 0.001 s
phase-to-phase distance protection
Enabling/disabling zone 3 of
phase-to-phase distance protection
31 21Q.ZP3.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-phase
zone 3 of distance protection operation
32 21Q.ZP3.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 3 of
33 21Q.ZG4.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-ground distance protection

PCS-902 Line Distance Relay 3-43


Date: 2011-07-06
3 Operation Theory

Resistance setting of zone 3 of


34 21Q.ZG4.R_Set (0.000~2Unn)/In 0.001 ohm
phase-to-ground distance protection
Time delay of zone 4 of
35 21Q.ZG4.t_Op 0.000~10.000 0.001 s
phase-to-ground distance protection
Enabling/disabling zone 4 of
phase-to-ground distance protection
36 21Q.ZG4.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-ground
zone 4 of distance protection operation
37 21Q.ZG4.En_BlkAR 0 or 1 to block AR
0: disable
1: enable
Impedance setting of zone 3 of
38 21Q.ZP4.Z_Set (0.000~2Unn)/In 0.001 ohm
phase-to-phase distance protection
Resistance setting of zone 3 of
39 21Q.ZP4.R_Set (0.000~2Unn)/In 0.001 ohm
phase-to-phase distance protection
Time delay of zone 4 of
40 21Q.ZP4.t_Op 0.000~10.000 0.001 s
phase-to-phase distance protection
Enabling/disabling zone 4 of
phase-to-phase distance protection
41 21Q.ZP4.En 0 or 1
0: disable
1: enable
Enabling/disabling phase-to-phase
zone 4 of distance protection operation
42 21Q.ZP4.En_BlkAR 0 or 1 to block AR
0: disable
1: enable

Table 3.5-10 Internal settings of distance protection (Quad)

No. Name Default Value Unit Remark


Short time delay of zone 2 of phase-to-ground
1 21Q.ZG2.t_ShortDly 0.025 s
distance protection
Short time delay of zone 2 of phase-to-phase
2 21Q.ZP2.t_ShortDly 0.025 s
distance protection
Fixed accelerate zone 2 of distance protection
3 21Q.Z2. En_ShortDly 0 0: disable
1: enable
Short time delay of zone 3 of phase-to-ground
4 21Q.ZG3.t_ShortDly 0.025 s
distance protection
Short time delay of zone 3 of phase-to-phase
5 21Q.ZP3.t_ShortDly 0.025 s
distance protection
Fixed accelerate zone 3 of distance protection
6 21Q.Z3.En_ShortDly 0
0: disable

3-44 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

1: enable

3.5.6 Pilot Distance Zone

3.5.6.1 Impedance Characteristic

An independent pilot zone distance protection is used for PUTT and POTT scheme. There is also
a reverse pilot distance element available as an option for application of POTT on weak power
source system.

Pilot.Z_Set_B Pilot.Z_Rev_B

M N
EM A B C D

Pilot.Z_Rev_A Pilot.Z_Set_A

Figure 3.5-31 Protected zone of pilot distance protection

The operation characteristic of pilot zone is same as that of zone 2, including mho and
quadrilateral characteristic.

When an internal fault occurs, distance protection at weak source end may not operate due to
small fault current. Thus, a reverse distance element is provided to coordinate with the
independent pilot distance protection to implement weak infeed logic, ensure pilot distance
protection can operate to send signal or trip in the weak end. The operation characteristic is shown
in Figure 3.5-32. The reverse weak infeed distance element is forward offset with 1/4 of the
reverse setting to enclose the origin.

Operation characteristics of pilot reverse weak infeed element distance are shown as below.

jX
jX
B
β 21Q.Z_Rev/4
21M.Z_Rev/4

Φ
21Q.R_Rev o R
α
R φ φ

C
θ
21M.Z_Rev 21Q.Z_Rev
A

Figure 3.5-32 Pilot reverse weak infeed element

PCS-902 Line Distance Relay 3-45


Date: 2011-07-06
3 Operation Theory

Where:

Φ: positive-sequence characteristic angle, i.e. [phi1_Reach]

α: the angle of directional line, fixed at 15°

β: the angle of directional line, fixed at 15°

θ: tilted angle of the reactance line AC, fixed at 12°

3.5.6.2 Logic

SIG Enable zone &


&
SIG 21Q.Pilot.Rls_PSBR ZPilotP

SET Flag.21Q.Pilot.Z (PG) >=1


Flag_Z_PilotP
SET Flag.21Q.Pilot.Z (PP)

Figure 3.5-33 Logic diagram of pilot distance zone (Quad characteristic)

SIG Enable zone &


&
SIG 21M.Pilot.Rls_PSBR ZPilotP

SET Flag.21M.Pilot.Z (PG) >=1


&
SET Flag.21M.Pilot.Z (PG) Flag_Z_PilotP

SET |ZΦ|<[21M. R_Blinder]

Figure 3.5-34 Logic diagram of pilot distance zone (Mho characteristic)

Where:

Flag.21Q.Pilot.Z (PG) means that measured impedance by phase-to-ground distance element is


within the range determined by the setting [21Q.Pilot.Z_Set]. (Quad characteristic)

Flag.21Q.Pilot.Z (PP) means that measured impedance by phase-to-phase distance element is


within the range determined by the setting [21Q.Pilot.Z_Set]. (Quad characteristic)

Flag.21M.Pilot.Z (PG) means that measured impedance by phase-to-ground distance element is


within the range determined by the setting [21M.Pilot.Z_Set]. (Mho characteristic)

Flag.21M.Pilot.Z (PP) means that measured impedance by phase-to-phase distance element is


within the range determined by the setting [21M.Pilot.Z_Set]. (Mho characteristic)

3-46 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.5.6.3 Settings

Table 3.5-11 Settings of pilot distance zone

No. Name Range Step Unit Remark


Impedance setting of pilot distance
1 21M.Pilot.Z_Set (0.000~2Unn)/In 0.001 ohm
protection (Mho characteristic)
Impedance setting of pilot distance
2 21Q.Pilot.Z_Set (0.000~2Unn)/In 0.001 ohm
protection (Quad characteristic)
Impedance setting of pilot distance
3 21M.Pilot.Z_Rev (0.000~2Unn)/In 0.001 ohm protection in reverse direction (Mho
characteristic)
Impedance setting of pilot distance
4 21Q.Pilot.Z_Rev (0.000~2Unn)/In 0.001 ohm protection in reverse direction (Quad
characteristic)
Impedance setting of pilot distance
5 21Q.Pilot.R_Set (0.000~2Unn)/In 0.001 ohm
protection (Quad characteristic only)
Impedance setting of pilot distance
6 21Q.Pilot.R_Rev (0.000~2Unn)/In 0.001 ohm protection in reverse direction (Quad
characteristic only)

3.5.7 Power Swing Detection

Power swing is generally a dynamic process when power system is disturbed. When power swing
occurs, the angle between the generators in parallel operation, the frequency of the system, the
voltage on the bus, the current and power of the branch lines are all fluctuating. Power swing may
destroy the normal operation of power systems and even damage electrical equipment, causing
the system to collapse.

3.5.7.1 Function Block Diagram

68

68.In_En 68.St

68.Blk

3.5.7.2 I/O Signals

Table 3.5-12 Configurable I/O signals of power swing detection

No. Input Signal Description


1 68.In_En Power swing detection enabling input, it can be a binary input or a logic link.
2 68.Blk Power swing detection blocking input, such as a function blocking binary input.

PCS-902 Line Distance Relay 3-47


Date: 2011-07-06
3 Operation Theory

No. Output Signal Description


1 68.St Power swing detection takes into effect.

Table 3.5-13 Internal I/O signals of power swing detection

No. Input Signal Description


1 21.St Any element of distance protection picks up.
2 FD.ROC.Pkp Residual current FD element operates.
3 52b Circuit breaker is in closed position.
4 52a Circuit breaker is in open position.

3.5.7.3 Logic

EN 68.En &

SIG 68.In_En
&
&
SIG 68.Blk &
t1 t2 &
SIG I1>[Y.I_PSBR] & 68.St

SIG 21.St

SIG FD.ROC_FD &


>=1
SIG 3 CB Closed

SIG 3 CB open
>=1
SIG Unblocking for SF

SIG Unblocking for PDF

Figure 3.5-35 Logic diagram of power swing detection

Y: 21M or 21Q

3.5.7.4 Settings

Table 3.5-14 Settings of power swing detection

No. Name Range Step Unit Remark


Enabling/disabling power swing detection
1 68.En 0 or 1 0: disable
1: enable

3.5.8 Power Swing Blocking Releasing

When power swing occurs on the power system, the impedance measured by the distance
measuring element may vary from the load impedance area into the operating zone of the
distance element. The distance measuring element may operate due to the power swing occurs in
many points of interconnected power systems. To keep the stability of whole power system,

3-48 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

tripping due to operation of the distance measuring element during a power swing is generally not
allowed. Our distance protection adopts power swing blocking releasing to avoid maloperation
resulting from power swing. In another word, distance protection is blocked all along under the
normal condition and power swing when the respective logic settings are enabled. Only when fault
(internal fault or power swing with internal fault) is detected, power swing blocking for distance
protection is released by PSBR element.

Power swing blocking for distance element will be released if any of the following PSBR elements
operates. Each distance zone elements has respective setting for selection this function.

 Fault detector PSBR element (FD PSBR)

 Unsymmetrical fault PSBR element (UF PSBR)

 Symmetrical fault PSBR element (SF PSBR)

1. Fault detector PSBR element

If any of the following condition is matched, FD PSBR will operate for 160ms.

1) Positive sequence current is lower than the setting [I_PSBR] before general fault detector
element operates.

2) Positive sequence current is higher than the setting [I_PSBR] before general fault detector
element operates, but the duration is less than 10ms.

2. Unsymmetrical fault PSBR element

The operation criterion:

I0+I2>m×I1

The “m”, an empirical value, is internal fixed coefficient which can ensure UF PSBR operation
during power swing with internal unsymmetrical fault, while no operation during power swing or
power swing with external fault.

This decision mainly utilizes the "discrepancy" that there is no negative-sequence or


zero-sequence current during power swing, and there are negative-sequence and zero-sequence
currents in case of asymmetric fault. In addition, value of m is used to differentiate internal
asymmetric fault and external asymmetric fault in case of power swing.

 In case of power swing or both power swing and external fault, asymmetric fault discriminating
element will not operate and distance protection will be blocked:

In case of power swing but no fault, I0 and I2 are near zero, but I1 is very large. Asymmetric fault
discriminating element will not operate.

In case of both power swing and external fault, if center of power swing is in scope of protection,
both phase-to-phase and grounding impedance relays may operate. At this time, selection of
value of m is used to ensure no operation of asymmetric fault discriminating element, blocking of
distance protection, and no incorrect operation without selectivity. If power swing center is not on
this line, distance protection will not operate incorrectly without selectivity due to power swing.

PCS-902 Line Distance Relay 3-49


Date: 2011-07-06
3 Operation Theory

 In case of internal asymmetric fault, asymmetric fault discriminating element operates and
distance protection will be release to clear internal fault:

In case of both power swing and internal fault, if at the instant of short circuit, system electric
potential angle is not laid out, asymmetric fault discriminating element will operate at once. If at the
instant of short circuit, system electric potential angle is laid out, asymmetric fault discriminating
element will operate when system angle gradually decreases, or local side tripping may be
activated after immediate operation of opposite side asymmetric fault discriminating element and
releasing of distance protection tripping. In case of normal internal asymmetric phase-to-phase or
grounding fault in the system, relatively large zero-sequence or negative-sequence component will
exist. At this time, the above equation is true and distance protection will be released.

3. Symmetrical fault PSBR element

If a three-phase fault occurs and FD PSBR is invalid (160ms after FD operates), neither FD PSBR
nor UF PSBR will be able to release the distance protection. Thus, SF PSBR is provided for this
case specially. This detection is based on measuring the voltage at power swing center, during
power swing, U1cosΦ will constantly change periodically.

UOS=U1×COSΦ

Where:

Φ: the angle between positive sequence voltage and current

U1: the positive sequence voltage

As shown in the figure below, assume system connection impedance angle of 90°, current vector
will be perpendicular to the line connecting EM and EN, and have the same phase as power swing
center voltage. During normal operation of system or power swing, U1cosΦ just reflects
positive-sequence voltage of power swing center. In case of 3-phase short circuit, U1cosΦ is
voltage drop on arc resistor, transition resistance is arc resistance, and voltage drop on arc resistor
is less than 5%UN. In actual system, line impedance angle is not 90°. Through compensation of
angle Φ, power swing center voltage can be measured accurately. After compensation, power
swing center voltage is U1cos(Φ+90o-ΦL), where ΦL is line impedance angle.

I
EM U EN
UOS

During power swing, power swing center voltage U1cosΦ has the following characteristics: When
electric potential phase angle difference between power supplies at two sides is 180o, U1cosΦ=0
and change rate dU1cosΦ/dt is the maximum. When this phase angle difference is near 0o, power
swing center voltage change rate dU1cosΦ/dt is the minimum. During short circuit, U1cosΦ
remains unchanged and dU1cosΦ/dt=0. However, in early stage of short circuit when normal state

3-50 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

enters short circuit state, dU1cosΦ/dt is very large. Therefore, use of dU1cosΦ/dt solely to
differentiate power swing and short circuit is not complete.

For these reasons, the method to release distance protection on condition that power swing center
voltage U1cosΦ is less than a setting and after a short delay can be used as symmetric fault
discriminating element. This element can accurately differentiate power swing and 3-phase short
circuit fault, and constitute a complete power swing blocking scheme with other elements. The
element to open distance protection if U1cosΦ is less than a certain setting and after a delay is
easy to realize and has short delay, and can trip fault more quickly and accurately trip 3-phase
short circuit fault during power swing.

The criterion of SF PSBR element comprises the following two parts:

 when -0.03UN<UOS<0.08UN, the SF PSBR element will operate after 150ms.

 when -0.1UN<UOS<0.25UN, the SF PSBR element will operate after 500ms.

The second criterion is a backup of the first criterion allowing longer monitoring period of voltage
variation.

3.5.8.1 I/O Signals

Table 3.5-15 Internal I/O signals of PSBR

No. Input Signal Description


1 21M.En_PSBR Enabling power swing blocking releasing (Mho characteristic)
2 21Q.En_PSBR Enabling power swing blocking releasing (Quad characteristic)
3 21M.Blk_PSBR Blocking power swing blocking releasing (Mho characteristic)
4 21Q.Blk_PSBR Blocking power swing blocking releasing (Quad characteristic)
No. Output Signal Description
1 21M.Z1.En_PSBR PSBR operates to release zone 1 (Mho characteristic)
2 21Q.Z1.En_PSBR PSBR operates to release zone 1 (Quad characteristic)
3 21M.Z2.En_PSBR PSBR operates to release zone 2 (Mho characteristic)
4 21Q.Z2.En_PSBR PSBR operates to release zone 2 (Quad characteristic)
5 21M.Z3.En_PSBR PSBR operates to release zone 3 (Mho characteristic)
6 21Q.Z3.En_PSBR PSBR operates to release zone 3 (Quad characteristic)
7 21M.Z4.En_PSBR PSBR operates to release zone 4 (Mho characteristic)
8 21Q.Z4.En_PSBR PSBR operates to release zone 4 (Quad characteristic)
9 21M.Pilot.En_PSBR PSBR operates to release pilot distance protection (Mho characteristic)
10 21Q.Pilot.En_PSBR PSBR operates to release pilot distance protection (Quad characteristic)

PCS-902 Line Distance Relay 3-51


Date: 2011-07-06
3 Operation Theory

3.5.8.2 Logic

SIG Y.En_PSBR &


Y.Enable_PSBR
SIG Y.Blk_PSBR

SIG Y.Enable

SIG Y.Enable_PSBR &


&
EN [Y.Zx .En_PSBR] Y.Zx.Rls_PSBR

Unsymmetrical |I0|+|I2|>
>=1
OTH >=1
>=1
OTH symmetrical |U1cosΦ|< t 0ms &

SET I1>[Y.I_PSBR] 10ms 0ms &


0 160ms
SIG FD.Pkp

SIG Zx.Flg_PSBR

Figure 3.5-36 Logic diagram of PSBR

Y: 21M or 21Q

x: 1, 2, 3, 4 or pilot

3.5.8.3 Settings

Table 3.5-16 Settings of PSBR

No. Name Range Step Unit Remark


Current setting for power swing
1 21M.I_PSBR (0.050~30.000)×In 0.001 A
blocking (Mho characteristic)
Current setting for power swing
2 21Q.I_PSBR (0.050~30.000)×In 0.001 A
blocking (Quad characteristic)
Enabling/disabling zone 1 of distance
protection controlled by PSBR (Mho
3 21M.Z1.En_PSBR 0 or 1 characteristic)
0: disable
1: enable
Enabling/disabling zone 1 of distance
protection controlled by PSBR (Quad
4 21Q.Z1.En_PSBR 0 or 1 characteristic)
0: disable
1: enable
Enabling/disabling zone 2 of distance
protection controlled by PSBR (Mho
5 21M.Z2.En_PSBR 0 or 1 characteristic)
0: disable
1: enable

3-52 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Enabling/disabling zone 2 of distance


protection controlled by PSBR (Quad
6 21Q.Z2.En_PSBR 0 or 1 characteristic)
0: disable
1: enable
Enabling/disabling zone 3 of distance
protection controlled by PSBR (Mho
7 21M.Z3.En_PSBR 0 or 1 characteristic)
0: disable
1: enable
Enabling/disabling zone 3 of distance
protection controlled by PSBR (Quad
8 21Q.Z3.En_PSBR 0 or 1 characteristic)
0: disable
1: enable
Enabling/disabling zone 4 of distance
protection controlled by PSBR (Mho
9 21M.Z4.En_PSBR 0 or 1 characteristic)
0: disable
1: enable
Enabling/disabling zone 4 of distance
protection controlled by PSBR (Quad
10 21Q.Z4.En_PSBR 0 or 1 characteristic)
0: disable
1: enable
Enabling/disabling pilot distance
zone controlled by PSBR (Mho
11 21M.Pilot.En_PSBR 0 or 1 characteristic)
0: disable
1: enable
Enabling/disabling pilot distance
zone controlled by PSBR (Quad
12 21Q.Pilot.En_PSBR 0 or 1 characteristic)
0: disable
1: enable

3.5.9 Distance SOTF Protection

When the circuit breaker is closed manually or automatically, it is possible to switch on to a fault.
This is especially critical if the line in the remote station is grounded, since the distance protection
would not clear the fault until overreach zones (Z2 and/or zone 3) time delays have elapsed. In this
situation, however, the fastest possible clearance is required.

The SOTF (switch onto fault) protection is a complementary function to the distance protection.
With distance SOTF protection, a fast trip is achieved for a fault on the whole line, when the line is

PCS-902 Line Distance Relay 3-53


Date: 2011-07-06
3 Operation Theory

being energized. It shall be responsive to all types of faults anywhere within the protected line.

3.5.9.1 Function Block Diagram

68

21SOTF.In_En 21SOTF.Op

21SOTF.Blk 21SOTF.Op_PDF

3.5.9.2 I/O Signals

Table 3.5-17 Configurable I/O signals of distance SOTF protection

No. Input Signal Description


1 21SOTF.En Distance SOTF protection enabling input, it can be a binary input or a logic link.
2 21SOTF.Blk Distance SOTF protection blocking input, such as a function blocking binary input.
No. Output Signal Description
Accelerate distance protection to trip when manual closing or auto-reclosing to
1 21SOTF.Op
fault
Accelerate distance protection to trip when another fault happened under pole
2 21SOTF.Op_PDF
discrepancy conditions

3.5.9.3 Logic

SIG 21SOTF.In_En &


&
SIG 21SOTF.Blk 21SOTF.Enable

EN [21SOTF.En]

Figure 3.5-37 Logic diagram of enabling distance SOTF protection

3-54 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

SIG 21SOTF.Enable

EN [21SOTF.En_ManCls]
&
& [21SOTF.t_ManCls] 0
SIG Manual closing signal

EN [21SOTF.Z2.En_ManCls] &

SIG Y.Z2.Flg_PSBR

EN [21SOTF.Z3.En_ManCls] & >=1

SIG Y.Z3.Flg_PSBR

EN [21SOTF.Z4.En_ManCls] &

SIG Y.Z4.Flg_PSBR
& >=1
EN [21SOTF.En_3PAR] & [21SOTF.t_3PAR] 0 21SOTF.Op

SIG 3-pole reclosing signal

EN [21SOTF.Z2.En_3PAR] &

SIG Y.Z2.Flg_PSBR

EN [21SOTF.Z3.En_3PAR] & >=1


>=1
SIG Y.Z3.Flg_PSBR

EN [21SOTF.Z4.En_3PAR] &

SIG Y.Z4.Flg_PSBR

EN [21SOTF.Z2.En_PSBR]
&
SIG Y.Z2.Flg_PSBR

SIG Y.Z2.Rls_PSBR
>=1

EN [21SOTF.Z3.En_PSBR]
&
SIG Y.Z3.Flg_PSBR
&
SIG Y.Z3.Rls_PSBR [21SOTF.t_1PAR] 0

EN [21SOTF.En_1PAR]
&
SIG PD signal

SIG Y.Z2.Rls_PSBR

SIG 21SOTF.Enable &


[21SOTF.t_PDF] 0 21SOTF.Op_PDF
EN [21SOTF.En_PDF]
&
SIG Y.Z2.Rls_PSBR &

SIG PD signal

Figure 3.5-38 Logic diagram of distance SOTF protection

Y: 21M or 21Q

Distance SOTF protection can be enabled or disabled by logic setting [21SOTF.En] and can be

PCS-902 Line Distance Relay 3-55


Date: 2011-07-06
3 Operation Theory

optional enabled by logic settings (setting table No. 2, 7, 15 & 17) independently for several cases,
including manual closing, 3-pole reclosing, 1-pole reclosing and pole discrepancy conditions.

Distance protection for SOTF will operate to trip three-phase circuit breaker when closing manually.
Controlled by the logic settings, zone 2, 3 and 4 of distance protection can be determined whether
is accelerated to operate.

Zone 2, 3 and 4 of distance element for SOTF with or without PSBR logic will operate to trip circuit
breaker if the logic setting [21SOTF.Z2.En_3PAR], [21SOTF.Z3.En_3PAR] and
[21SOTF.Z4.En_3PAR] are set as “0” or “1” respectively when 3-pole auto-reclosing.

Zone 2 of distance element for SOTF with PSBR logic will operate to trip three-phase circuit
breaker when 1-pole or 3-pole auto-reclosing if both the logic setting [21SOTF.Z2.En_3PAR] and
[21SOTF.Z3.En_3PAR] are set as “0”.

For single-phase permanent fault, distance SOTF protection for 1-pole reclosing onto the faulty
phase will trip three-phase circuit breaker.

Under pole discrepancy condition after single-phase tripping, distance SOTF protection will
accelerate to operate if another fault happens to the healthy phase.

SOTF protection is automatically enabled after circuit breaker opened for 50 ms and automatically
disabled after circuit breaker closed for 400ms.

3.5.9.4 Settings

Table 3.5-18 Settings of distance SOTF protection

No. Name Range Step Unit Remark


Enabling/disabling distance SOTF
protection
1 21SOTF.En 0 or 1
0: disable
1: enable
Enabling/disabling zone 2 of
distance SOTF protection for
2 21SOTF.Z2.En_ManCls 0 or 1 manual closing
1: enable
0: disable
Enabling/disabling zone 3 of
distance SOTF protection for
3 21SOTF.Z3.En_ManCls 0 or 1 manual closing
1: enable
0: disable
Enabling/disabling zone 4 of
distance SOTF protection for
4 21SOTF.Z4.En_ManCls 0 or 1 manual closing
1: enable
0: disable
5 21SOTF.Z2.En_3PAR 0 or 1 Enabling/disabling zone 2 of

3-56 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

distance SOTF protection for


3-pole reclosing
1: enable
0: disable
Enabling/disabling zone 3 of
distance SOTF protection for
6 21SOTF.Z3.En_3PAR 0 or 1 3-pole reclosing
1: enable
0: disable
Enabling/disabling zone 4 of
distance SOTF protection for
7 21SOTF.Z4.En_3PAR 0 or 1 3-pole reclosing
1: enable
0: disable
Enabling/disabling zone 2
controlled by PSB of distance
SOTF protection for 3-pole
8 21SOTF.Z2.En_PSBR 0 or 1
reclosing
1: enable
0: disable
Enabling/disabling zone 3
controlled by PSB of distance
SOTF protection for 3-pole
9 21SOTF.Z3.En_PSBR 0 or 1
reclosing
1: enable
0: disable
Enabling/disabling zone 4
controlled by PSB of distance
SOTF protection for 3-pole
10 21SOTF.Z4.En_PSBR 0 or 1
reclosing
1: enable
0: disable
Enabling/disabling distance SOTF
protection under pole discrepancy
11 21SOTF.En_PDF 0 or 1 conditions
1: enable
0: disable
Time delay of distance protection
12 21SOTF.t_PDF 0.000~10.000 0.001 s operating under pole discrepancy
conditions
Option of manual SOTF mode
0: initiated by input signal of
13 SOTF.Opt_Mode_ManCls 0, 1 or 2
manual closing
1: initiated by CB position

PCS-902 Line Distance Relay 3-57


Date: 2011-07-06
3 Operation Theory

2: initiated by either input signal of


manual closing or CB position

Table 3.5-19 Internal settings of distance SOTF protection

No. Name Default Value Unit Remark


Enabling/disabling distance SOTF protection for
manual closing
1 21SOTF. En_ManCls 1
0: disable
1: enable
Time delay of distance protection accelerating to
2 21SOTF.t_ManCls 0.025 s
trip when manual closing
Enabling/disabling distance SOTF protection for
3-pole reclosing
3 21SOTF.En_3PAR 1
0: disable
1: enable
Time delay of distance protection accelerating to
4 21SOTF.t_3PAR 0.025 s
trip when 3-pole reclosing
Enabling/disabling distance SOTF protection for
1-pole reclosing
5 21SOTF.En_1PAR 1
0: disable
1: enable
Time delay of distance protection accelerating to
6 21SOTF.t_1PAR 0.025 s
trip when 1-pole reclosing

3.6 Optical Pilot Channel (Option)


3.6.1 General Application

When fibre optical channel is available between the devices at both ends, the devices have an
optional module to transmit permissive signal or blocking signal (subject to the scheme selected),
transfer signal and transfer trip via the fibre ports of the module. The communication rate can be
64 kbit/s or 2048kbit/s via optional dedicated optical fibre channel or multiplex channel.

3.6.2 Function Description

12 digital bits are integrated in each frame of transmission message for various applications. Each
received message frame via fibre optical channel will pass through security check to ensure the
integrity of the message consistently.

The last four digital bits of the 12 have been assigned for pilot scheme protection. The
communication channel can be configured as single channel mode or as dual channels mode.
(FOx, x can be 1 or 2) according to the optical pilot channel module selected.

3.6.2.1 Channel Interface

The modules can communicate in two modes via multiplexer or dedicated optical fibre.
Communication through dedicated fibre is usually recommended unless the received power does

3-58 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

not meet with the requirement.

Channel of 64 kbit/s or 2048kbit/s via dedicated fibre is shown in Figure 3.6-1 Two fibre cores of
optical cable are dedicated to pilot scheme protection.

TX RX
PCS-9XX 64kbit/s or 2048kbit/s PCS-9XX
RX TX

Figure 3.6-1 Application of dedicated channel

Channel of 64 kbit/s or 2048kbit/s via multiplexer is shown in Figure 3.6-2.

Pig Tail Coaxial cable Communicate


TX 64kbit/s or
SDH Device net
MUX-2M
PCS-9XX or MUX-64
2048kbit/s
RX E1Interface
Pig Tail

Figure 3.6-2 Application of multiplex channel

3.6.2.2 Communication Clock

Valid messages exchange is key factor for digital pilot scheme protection.

The device transmits and receives messages based on respective clocks, which are called
transmit clock (i.e. clock TX) and receive clock (i.e. clock RX) respectively. Clock RX is fixed to be
extracted from message frame, which can ensure no slip frame and no error message received.
Clock TX has two options:

1. Use internal crystal clock, which is called internal clock. (master clock)

2. Use external clock. (slave clock)

Depend on the clock used by the device at both ends, there are three modes.

1. Master-master mode

Both ends use internal clock.

2. Slave-slave mode

Both ends use external clock.

3. Master-slave mode

One of them uses internal clock, the other uses external clock

The logic setting [FOx.En_IntClock] is used in pilot scheme protection to select the communication
clock. The internal clock is enabled automatically when the logic setting [FOx.En_IntClock] is set
as “1”. Contrarily, the external clock is enabled automatically when the logic setting
[FOx.En_IntClock] is set to “0”.

If the device uses multiplex PCM channel, logic setting [FOx.En_IntClock] at both ends should be

PCS-902 Line Distance Relay 3-59


Date: 2011-07-06
3 Operation Theory

set as “0” (Mode 2). If the device uses dedicated optical fibre channel, clock Mode 1 and Mode 3
can be used. Mode 1 is recommended in considering simplification to user, i.e. logic setting
[FOx.En_IntClock] at both ends should be set as “1”.

3.6.2.3 Identity Code

In order to ensure reliability of the device when digital communication channel is applied, settings
[FOx.LocID] and [FOx.RmtID] are provided as identity code to distinguish uniquely the device at
remote end using same channel.

Under normal conditions, the identity code of the device at local end should be different with that at
remote end. In addition, it is recommended that the identity code of all devices, i.e., the setting
[FOx.LocID], should be unique in the power grid. The setting range is from 0 to 65535. Only for
loop test, they are set as the same.

The setting [FOx.LocID] of the device at an end should be the same as the setting [FOx.RmtID] of
the device at opposite end and the greater [FOx.LocID] between the two ends is chosen as a
master end for sampling synchronism, the smaller [FOx.LocID] is slave end. If the setting
[FOx.LocID] is set the same as [FOx.RmtID], that implies the device in loopback testing state.

The setting [FOx.LocID] is packaged in the message frame and transmitted to the remote end.
When the [FOx.LocID] of the device at remote end is received by local device is same to the
setting [FOx.RmtID] of local device, the message received from the remote end is valid, and
protection information involved in message is read. When these settings are not matched, the
message is considered as invalid and protection information involved in message is ignored,
corresponding alarms will be issued.

3.6.2.4 Channel Statistics

The device has the function of on-line channel monitoring and channel statistics. It can produce
channel statistic report automatically at 9:00 every day and the report can be printed for operator
to check the channel quality. The monitoring contents of channel status are shown as follows, and
they can be viewed by the menu “Main Menu→Test→Prot Ch Count→Chx Counter”.

1. FOx.Start_Time (starting time)

It shows the starting time of the channel status statistics of the device at local end.

2. FOx.RmtID (ID code of the remote end)

It shows the ID information received by the device at local end now.

3. FOx.t_ChDly (propagation delay of channel x)

It shows the calculated communication channel time delay of the device at local end now (unit: us).
The calculation is based on the assumption of same channel path for to and from remote end. The
device measures propagation delay of communication channel based on the below principle.

Side S transmits a frame of message to side M, and meanwhile records the transmitting time “tss”
on the basis of clock on side S. When side M receives the message, it will record receiving time
“tmr” of the message with its own clock, and return a frame of message to side S at next fixed

3-60 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

transmitting time, meanwhile data of “tms-tmr” is included in the frame of message. Side S will
receive the message from side M at the time “tsr” and obtain the data of “tms-tmr”.

Therefore, the propagation delay of the channel “Td” is obtained through calculation:

(t sr  t ss )  (t ms  t mr )
Td 
2

T1

tss tsr "S"

tmr tms "M"


Td T2

Figure 3.6-3 Schematic diagram of communication channel time

4. FOx. Alm (channel x is abnormal)

5. FOx.Alm_NoValFram (no valid data frame of channel x is received)

6. FOx. Alm_CRC (rate of error code of channel x is larger than 40 error codes per second)

7. FOx.N_CRCFail (total number of error frame of channel x)

It shows the total number of the error frames of the device at local end from starting time of
channel statistics until now. Error frame means that this frame fails in CRC check.

8. FOx.N_FramErr (total number of abnormal messages of channel x)

It shows the total number of abnormal messages of the device at local end from starting time of
channel statistics until now.

9. FOx.N_FramLoss (total number of lost frames of channel x)

It shows the total number of the lost frames of the device at local end from starting time of channel
statistics until now.

10. FOx.N_RmtAbnor (total number of abnormal messages from the remote end of channel x)

It shows the total number of abnormal messages received from the remote end from starting time
of channel statistics until now.

11. FOx.t_CRCFailSec (seconds of serious error frames of channel x)

It shows the total number of serious error frame seconds of the device at local end from starting

PCS-902 Line Distance Relay 3-61


Date: 2011-07-06
3 Operation Theory

time of the channel statistics until now.

12. FOx.N_LossSyn (desynchronizing times of channel x)

It shows the total number of desynchronizing of the device at local end from starting time of
channel statistics until now.

3.6.3 Function Block Diagram

FOx

FOx.Send1 FOx.Recv1

FOx.Send2 FOx.Recv2

FOx.Send3 FOx.Recv3

FOx.Send4 FOx.Recv4

FOx.Send5 FOx.Recv5

FOx.Send6 FOx.Recv6

FOx.Send7 FOx.Recv7

FOx.Send8 FOx.Recv8

FOx.Alm

FOx.Alm_ID

3.6.4 I/O Signals

Table 3.6-1 Configurable I/O signals of pilot channel

No. Input Signal Description


1 FOx.Send1 Sending signal 1 of channel x
2 FOx.Send2 Sending signal 2 of channel x
3 FOx.Send3 Sending signal 3 of channel x
4 FOx.Send4 Sending signal 4 of channel x
5 FOx.Send5 Sending signal 5 of channel x
6 FOx.Send6 Sending signal 6 of channel x
7 FOx.Send7 Sending signal 7 of channel x
8 FOx.Send8 Sending signal 8 of channel x
No. Output Signal Description
1 FOx.Recv1 Receiving signal 1 of channel x
2 FOx.Recv2 Receiving signal 2 of channel x
3 FOx.Recv3 Receiving signal 3 of channel x
4 FOx.Recv4 Receiving signal 4 of channel x
5 FOx.Recv5 Receiving signal 5 of channel x
6 FOx.Recv6 Receiving signal 6 of channel x
7 FOx.Recv7 Receiving signal 7 of channel x

3-62 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

8 FOx.Recv8 Receiving signal 8 of channel x


9 FOx.Alm Channel x is abnormal
Received ID from the remote end is not as same as the setting [FO1.RmtID] of the
10 FOx.Alm_ID
device in local end

Table 3.6-2 Internal I/O signals of pilot channel

No. Input Signal Description


1 FOx.Send9 Sending signal 9 of channel x
2 FOx.Send10 Sending signal 10 of channel x
3 FOx.Send11 Sending signal 11 of channel x
4 FOx.Send12 Sending signal 12 of channel x
No. Output Signal Description
1 FOx.Recv9 Receiving signal 9 of channel x
2 FOx.Recv10 Receiving signal 10 of channel x
3 FOx.Recv11 Receiving signal 11 of channel x
4 FOx.Recv12 Receiving signal 12 of channel x
5 FOx.RmtID ID information received from the remote end by the device at local end now
Calculated propagation delay of communication channel of the device at local
6 FOx.t_ChDly
end now
7 FOx.Alm_NoValFram No valid frame of channel x is received
8 FOx.Alm_CRC Rate of error code of channel x is larger than 40 error codes per second
9 FOx.N_CRCFail Total number of error frame of channel x
10 FOx.N_FramErr Total number of abnormal messages of channel x
11 FOx.N_FramLoss Total number of lost frames of channel x
12 FOx.N_RmtAbnor Total number of abnormal messages from the remote end of channel x
13 FOx.t_CRCFailSec Seconds of serious error frames of channel x
14 FOx.Alm_Connect Optical fibre of channel x is connected wrongly
15 FOx.N_LossSyn Total number of loss synchronization of channel x

3.6.5 Logic

SIG Receiving transfer signal n from remote side &


FOx.Recvn
SIG FOx.Alm >=1

SIG FOx.Alm_ID

Figure 3.6-4 Logic diagram of receiving signal n

Where:

n can be 1~12

PCS-902 Line Distance Relay 3-63


Date: 2011-07-06
3 Operation Theory

3.6.6 Settings

Table 3.6-3 Settings of pilot channel

No. Name Range Step Unit Remark

1 FOx.LocID 0-65535 1 Identity code of the device at local end

2 FOx.RmtID 0-65535 1 Identity code of the device at remote end

Option of internal clock or external clock


3 FOx.En_IntClock 0 or 1 0: external clock
1: internal clock

3.7 Pilot Distance Protection


3.7.1 General Application

The instant distance protection with underreaching setting is impossible to isolate the fault at
remote end of the line, while distance protection with overreaching setting needs a time delay to
grade with downstream protection to maintain discrimination. Pilot distance protection that
exchanges distance protection information at both ends of the line can remove the fault within this
line quickly, and will not operate for external fault.

Pilot distance protection requires communication channel to exchange protection information at


both ends. The channel may be dedicated or multiplexed channel through optical fiber or any other
communication media. Pilot distance protection has schemes of permissive underreaching
transfer trip (PUTT), permissive overreaching transfer trip (POTT) and blocking.

3.7.2 Function Description

Pilot distance protection determines whether it will send the signal to the remote end according to
the discrimination result of the distance element or direction element. Pilot distance protection can
be divided into permissive scheme and blocking scheme according to whether the signal sent is
used to permit tripping or block tripping. For permissive scheme, it can be divided into
overreaching mode or underreaching mode according to the setting of distance element and
scheme selected, furthermore, it will provide the unblocking scheme as auxiliary function. For
overreaching mode, current reversal logic and weak infeed logic are available for parallel line
operation and weak power source situation respectively.

Pilot distance protection with permissive scheme receives permissive signal from the remote end,
so as to combine with local discrimination condition to accelerate tripping, so it has high security.

Blocking scheme will operate with a short time delay [85.t_DPU_Blocking1] if forward pilot zone
element operates and not receiving blocking signal before the short time delay expired.

Pilot distance protection can be enabled or disabled by input signals, logic setting and blocking
signal, as shown in Figure 3.7-1.

3-64 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

SIG 85.Z.En1
&
SIG 85.Z.En2

EN [85.Z.En]
&
Enable 85.Z
SIG 85.Z.Blk

Figure 3.7-1 Enabling/disabling logic of pilot distance protection

Pilot distance protection receives and sends signals via pilot channel, and the logic of receiving
signal is shown in Figure 3.7-2.

SET 85.Blocking &


>=1
Valid_Recv1

SIG 85.Recv1 &


>=1
SIG 85.Abnor_Ch1

SIG Unblocking1 Valid


&
EN [85.PUTT] >=1

EN [85.POTT]

Figure 3.7-2 Logic diagram of receiving signal

Pilot distance protection has the following application modes:

3.7.2.1 Zone Extension

When pilot scheme protection is out of service due to pilot channel failure or no pilot scheme
protection is provided. The fault outside zone 1 only can be cleared by zone 2 with a time delay. It
can not ensure that all faults within protected line are cleared instantaneously. As a supplement of
pilot scheme protection, zone extension can clear the fault within the whole line instantaneously.
Different with pilot distance protection, zone extension can also operate for external close up fault
in parallel line, but power supply can be restored by AR. So zone extension should be blocked
when AR is out of service and is not ready.

In order to prevent too many lines from disconnecting with system due to zone extension operate
when the circuit breaker is closed into permanent fault, zone extension should be blocked when
AR operates. For temporary fault, the line can be into service again after AR operates successfully.
For permanent fault in either local line or parallel line, distance protection with a time delay will
operate.

PCS-902 Line Distance Relay 3-65


Date: 2011-07-06
3 Operation Theory

SIG 85.ZX.En1
&
SIG 85.ZX.En2

EN 85.ZX.En

SIG 85.ZX.Blk1 >=1 &


[85.t_DPU_ZX] 0ms 85.Op_ZX
SIG 85.ZX.Blk2

SIG 79.Ready &

SIG Zpilot

Figure 3.7-3 Zone extension

Zone extension uses the setting of pilot zone (ZPilot), and its operation characteristic can be Mho
or Quad.

3.7.2.2 Permissive Underreaching Transfer Trip (PUTT)

Distance elements zone 1 (Z1) with underreaching setting and pilot zone (ZPilot) with
overreaching setting are used for this scheme. Z1 element will send permissive signal to the
remote end and release tripping after Z1 time delay expired. After receiving permissive signal with
ZPilot element pickup, a tripping signal will be released.

The signal transmission element for PUTT is set according to underreaching mode, so current
reversal need not be considered.

For PUTT, there may be a dead zone under weak power source condition. If the fault occurs
outside Z1 zone at strong power source side, Z1 at weak power supply side may not operate to trip
and transmit permissive signal, and pilot distance protection will not operate. Therefore, the
system fault can only be removed by Z2 at strong power source side with time delay.

ZPilot
Z2

Z1
M
EM A Fault B EN

Z1 N

Z2
ZPilot

3-66 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Relay A Relay B
Z1 Z1

& &
ZPilot >=1 85.Op_Z 85.Op_Z & ZPilot

WI WI

Figure 3.7-4 Simple schematic of PUTT

Pilot distance protection always adopts pilot channel 1, and the logic of PUTT is shown in Figure
3.7-5.

SIG 21M/21Q.Z1.Op 0ms 100ms >=1


&
SIG 85.ExTrp 0ms 150ms Send1

SET 85.PUTT &

SIG Enable 85.Z &


&
SIG FD.Pkp 8ms 0ms 85.Op_Z

SIG Valid_Recv1

SIG ZPilot >=1

OTH WI

Figure 3.7-5 Logic diagram of pilot distance protection (PUTT)

3.7.2.3 Permissive Overreaching Transfer Trip (POTT)

Pilot zone (ZPilot) distance element with an overreaching setting as zone 2 distance element is
used for POTT scheme if selected. ZPilot will send permissive signal to remote end once it picks
up and release tripping signal upon receiving permissive signal from the remote end.

When POTT is applied on parallel lines arrangement and the ZPilot setting covers 50% of the
parallel line, there may be a problem under current reversal condition, settings for current reversal
condition should be considered, please refer to section 3.7.2.6 for details.

Under weak power source condition, the problem of dead zone at weak power source end is
eliminated by the weak infeed logic, please refers to section 3.7.2.7 for details.

PCS-902 Line Distance Relay 3-67


Date: 2011-07-06
3 Operation Theory

ZPilot
Z2

Zpilot_Rev
M
EM A Fault B EN

N
Zpilot_Rev Z2
ZPilot

Relay A Relay B
& &
ZPilot >=1 85.Op_Z 85.Op_Z >=1 ZPilot

WI WI

Figure 3.7-6 Simple schematic of POTT

OTH Zpilot

SIG 85.ExTrp 0ms 150ms

& >=1
OTH CB open position &
200ms 0ms
SIG Valid_Recv1 &
Send1

SIG ZPilot & &


>=1 &
SIG Enable 85.Z t1 t2

OTH WI &
& 85.Op_Z
SIG FD.Pkp 8ms 0ms

SET [85.POTT]

Figure 3.7-7 Logic diagram of pilot distance protection (POTT)

Where:

t1: pickup time delay of current reversal, the setting [85.t_DPU_CR1]

t2: dropoff time delay of current reversal, the setting [85.t_DDO_CR1]

3.7.2.4 Blocking

Permissive scheme has high security, but it relies on pilot channel seriously. Pilot distance
protection will not operate when there is an internal fault with abnormal channel. Blocking scheme
could be considered as an alternative.

3-68 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Blocking scheme takes use of pilot distance element Zpilot operation to terminate sending of
blocking signal. Blocking signal will be sent once fault detector picks up without pilot zone Zpilot
operation. Pilot distance protection will operate with a short time delay if pilot distance element
operates and not receiving blocking signal after timer expired.

The setting of pilot zone element Zpilot in Blocking scheme is overreaching, so current reversal
condition should be considered. However, the short time delay of pilot distance protection has an
enough margin for current reversal, that this problem has been resolved.

The short time delay must consider channel delay and with a certain margin to set. As shown in
Figure 3.7-8, an external fault happens to line MN. The fault is behind the device at M side, for
blocking scheme, the device at M side will send blocking signal to the device at N side. If channel
delay is too long, the device at side N has operated before receiving blocking signal. Hence, the
time delay of pilot distance protection adopted in blocking scheme should be set according to
channel delay.

Blocking signal
M N
EM Fault A B EN

Figure 3.7-8 Simple schematic of system fault

For blocking scheme, pilot distance protection will operate when there is an internal fault with
abnormal channel, however, it is possible that pilot distance protection issue an undesired trip
when there is an external fault with abnormal channel.

ZPilot

Zpilot_Rev
M
EM A Fault B EN

N
Zpilot_Rev
ZPilot

Relay A Relay B
FD.Pkp & & FD.Pkp

Zpilot & & Zpilot


[85.t_DPU_Blocking1] 85.Op_Z 85.Op_Z [85.t_DPU_Blocking1]

Figure 3.7-9 Simple schematic of blocking

PCS-902 Line Distance Relay 3-69


Date: 2011-07-06
3 Operation Theory

SIG Zpilot

SIG 85.ExTrp 0ms 150ms

& >=1
SIG CB open position &
200ms 0ms
SIG Valid_Recv1
&
Send1
&
SIG FWD_ZPilot >=1

SIG WI
&
SIG FD.Pkp [85.t_DPU_Blocking1] 85.Op_Z

SET 85.Blocking &

SIG Enable 85.Z

Figure 3.7-10 Logic diagram of pilot distance protection (Blocking)

Current reversal logic is only used for permissive scheme. For blocking scheme, the time delay of
pilot distance protection has enough margin for current reversal, so current reversal need not be
considered.

3.7.2.5 Unblocking

Permissive scheme will trip only when it receives permissive signal from the remote end. However,
it may not receive permissive signal from the remote end when pilot channel fails. For this case,
pilot distance protection can adopt unblocking scheme. Under normal conditions, the signaling
equipment works in the pilot frequency, and when the device operates to send permissive signal,
the signaling equipment will be switched to high frequency. While pilot channel is blocked, the
signaling equipment will receive neither pilot frequency signal nor high frequency signal. The
signaling equipment will provide a contact to the device as unblocking signal. When the device
receives unblocking signal from the signaling equipment, it will recognize channel failure, and
unblocking signal will be taken as permissive signal temporarily.

The unblocking function can only be used together with PUTT and POTT.

SIG [85.En_Unblocking1] &


SIG 85.Unblocking1 &

[85.t_Unblocking1] 0ms

SIG Detecting multi-phase fault >=1

EN [85.Opt_PilotCh1]
&
Unblocking1 Valid
SIG Pilot distance forward element

Figure 3.7-11 Logic diagram of pilot distance protection (Unblocking)

3-70 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.7.2.6 Current Reversal

When there is a fault in one of the parallel lines, the direction of the fault current may change
during the sequence tripping of the circuit breaker at both ends as shown in Figure 3.7-12: When a
fault occurs on line C–D near breaker D, the fault current through line A-B to D will flow from A to B.
When breaker D is tripped, but breaker C is not tripped, the fault current in line A-B will then flow
from B to A. This process is the current reversal.

M N M N
Strong Weak
A B A B
source source
EM EN EM EN

C D C D

Direction of fault current Direction of fault current


flow before CB‘D’open flow after CB‘D’open

Figure 3.7-12 Current reversal

As shown above, the device A judges a forward fault while the device B judges a reverse fault
before break D is tripped. However, the device A judges a reverse fault while the device B judges a
forward fault after breaker D is tripped. There is a competition between pickup and drop off of pilot
zones in the device A and the device B when the fault measured by the device A changes from
forward direction into reverse direction and vice versa for the device B. There may be
maloperation for the device in line A-B if the forward direction of the device B has operated but the
forward direction of the device A drops off slightly slower or the forward direction of the device B
has operated but the forward direction information of the device A is still received due to the
channel delay (the permissive signal is received).

In general, the following two methods shall be adopted to solve the problem of current reversal:

1. The fault shall be measured by means of the reverse element of the device B. Once the
reverse element of the device B operates, the send signals and the tripping circuit will be
blocked for a period of time after a short time delay. This method can effectively solve the
problem of competition between the device A and the device B, but there shall be a
precondition. The reverse element of the device B must be in cooperation with the forward
element of the device A, i.e. in case of a fault in adjacent lines, if the forward element of the
device A operates, and the reverse element of the device B must also operate. Once the
bilateral cooperation fails, the anticipated function cannot be achieved. In addition, the
blocking time for sending signals and the tripping circuit after the reverse element of the
device B operates shall be set in combination with the channel time delay.

2. Considering the pickup and drop off time difference of distance elements and the channel time
delay between the device A and the device B, the maloperation due to current reversal shall
be eliminated by setting the time delay. The reverse direction element of the device is not
required for this method, the channel time delay and the tripping time of adjacent breaker
shall be taken into account comprehensively.

This protection device adopts the second method to eliminate the maloperation due to current
reversal.

PCS-902 Line Distance Relay 3-71


Date: 2011-07-06
3 Operation Theory

SIG Pilot forward zone start condition &


t1 t2 Current reversal blocking
SIG Signal received conditon

Figure 3.7-13 Logic diagram of current reversal blocking

t1: [85.t_DPU_CR1]

t2: [85.t_DDO_CR1]

Referring to above figure, when signal from the remote end is received without pilot forward zone
pickup, the current reversal blocking logic is enabled after t1 delay.

The time delay of t1 [85.t_DPU_CR1] shall be set the shortest possible but allowing sufficient time
for pilot forward zone pickup, generally set as 25ms.

Once the current reversal logic is enabled, the healthy line device B transfer tripping is blocked.
The logic will be disabled by either the dropoff of signal or the pickup of pilot forward zone. A time
delay t2 [85.t_DDO_CR1] is required to avoid maloperation for the case that the pilot forward zone
(or forward element of pilot directional earth-fault protection) of device B picks up before the signal
from device A drops off. Considering the channel propagation delay and the pickup and drop-off
time difference of pilot forward zone (or pilot directional earth-fault element) with margin, t2 is
generally set between 25ms ~ 40ms.

Because the time delay of pilot distance protection has an enough margin to current reversal,
current reversal blocking only used for permissive scheme not blocking scheme.

3.7.2.7 Weak Infeed

In case of a fault in line at one end of which there is a weak power source, the fault current
supplied to the fault point from the weak power source is very small or even nil, and the
conventional distance element could not operate. The weak infeed logic combines the protection
information from the strong power source end and the electric feature of the local end to cope with
the case.

ZPilot

Z1 Zpilot_Rev
M
EM A Fault B EN

Z1 N
Zpilot_Rev

ZPilot

Load

Figure 3.7-14 Line fault description

The device has options for weak infeed echo only or weak infeed echo with weak infeed tripping.
The weak infeed logic can be applied together with unblocking logic for PUTT and POTT.

3-72 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

When the weak infeed logic is enabled, distance forward and reverse element and direction
element of directional earth-fault protection do not operate with the voltage lower than the setting
[85.U_UV_WI] after the device picks up, upon receiving signal from remote end, the weak infeed
logic will echo the signal back to remote end for 200ms if the weak infeed echo is enabled, the
weak infeed end will echo signal and release tripping according to the logic.

ZPilot_Rev at weak source end must coordinate with ZPilot_Set of the remote end. The coverage
of ZPilot_Rev must exceed that of ZPilot_Set of the remote end. ZPilot_Rev only activates in the
protection calculation when the weak infeed logic is enabled. In case of the weak infeed logic not
enabled, the setting coordination is not required.

If the device does not pick up, and the weak infeed logic is enabled, upon receiving signal from
remote end with the voltage lower than the setting [85.U_UV_WI], the weak infeed logic will echo
back to remote end for 200ms. When either weak infeed echo or weak infeed tripping is enabled,
then the weak infeed logic is deemed to be enabled. During the device picking up, the weak infeed
logic is shown in Figure 3.7-15.

SIG Valid_Recv1

SIG Pilot DEF forward direction >=1

SIG Pilot DEF reverse direction


&
SIG Pilot distance forward direction >=1 &
Forward direction (WI)
SIG Pilot distance reverse direction

EN [85.En_WI]

SET Up<[85.U_UV_WI] >=1 200ms 0ms &

SET Upp<[85.U_UV_WI]

Figure 3.7-15 Weak infeed logic during pickup

If the device does not pick up, the weak infeed logic is shown as the following figure:

SIG Signal receive condition &


&
EN [85.En_WI] WI echo

SET Up<[85.U_UV_WI] >=1


200ms 0ms &
SET Upp<[85.U_UV_WI]

Figure 3.7-16 Weak infeed logic without pickup

For permissive scheme, the signal receive condition means that the permissive signal is received
or the unblocking signal is valid.

PCS-902 Line Distance Relay 3-73


Date: 2011-07-06
3 Operation Theory

3.7.2.8 CB Echo

A feature is also provided which enables fast tripping to be maintained along the whole length of
the protected line, even when one terminal is open. The device will initiate sending a pulse of
200ms permissive signal when signal receive condition is met during CB is in open position.

SIG FD.Pkp &


&
SIG CB open position 200ms 0ms &
Send permissive signal
SIG Valid_Recv1 &

EN 85.POTT

Figure 3.7-17 Simplified CB Echo logic for POTT

CB Echo logic is only applied to permissive overreach mode not underreach mode, and it is
processed without the device pickup. This logic will be terminated immediately once the device
picks up.

3.7.3 Function Block Diagram

85

85.Z.En1 85.Op_Z

85.Z.En2 85.Send1

85.Z.Blk 85.SendB

85.Abnor_Ch1 85.SendC

85.Rcv1 85.Op_ZX

85.RcvB

85.RcvC

85.ExTrp

85.Unblocking1

85.ZX.En1

85.ZX.En2

85.ZX.Blk1

85.ZX.Blk2

79.Ready

3-74 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.7.4 I/O Signals

Table 3.7-1 Configurable I/O signals of pilot distance protection

No. Input Signal Description


1 85.Z_En1 Pilot distance protection enabling input 1, it can be a binary input or a logic link.
2 85.Z_En2 Pilot distance protection enabling input 2, it can be a binary input or a logic link.
3 85.Z_Blk Pilot distance protection blocking input, such as a function blocking binary input.
4 85.Abnor_Ch1 Input signal of indicating that pilot channel 1 is abnormal
Input signal of receiving permissive signal via channel No.1, or input signal of
5 85.Rcv1 receiving permissive signal of A-phase via channel No.1 (only for
phase-segregated command scheme)
Input signal of receiving permissive signal of B-phase via channel No.1 (only for
6 85.RcvB
phase-segregated command scheme)
Input signal of receiving permissive signal of C-phase via channel No.1 (only for
7 85.RcvC
phase-segregated command scheme)
8 85.ExTrp Input signal of initiating sending permissive signal from external tripping signal
9 85.Unblocking1 Unblocking signal 1
10 85.ZX_En1 Zone Extension enabling input 1, it can be a binary input or a logic link.
11 85.ZX_En2 Zone Extension enabling input 2, it can be a binary input or a logic link.
12 85.ZX_Blk1 Zone Extension blocking input 1, such as a function blocking binary input.
13 85.ZX_Blk2 Zone Extension blocking input 2, such as a function blocking binary input.
14 79.Ready AR has been ready for reclosing cycle.
No. Output Signal Description
1 85.Op_Z Pilot distance protection operates.
Output signal of sending permissive signal 1 or sending A-phase permissive
2 85.Send1
signal (only for phase-segregated command scheme)
Output signal of sending B-phase permissive signal (only for phase-segregated
3 85.SendB
command scheme)
Output signal of sending C-phase permissive signal (only for phase-segregated
4 85.SendB
command scheme)
5 85.Op_ZX Zone extension protection operates.

3.7.5 Settings

Table 3.7-2 Settings of pilot distance protection

No. Name Range Step Unit Remark


Option of pilot scheme
0: POTT
1 85.Opt_PilotMode 0~2 1
1: PUTT
2: Blocking
Option of phase-segregated
signal scheme or three-phase
2 85.Opt_Ch_PhSeg 0 or 1
signal scheme
0: three-phase signal scheme

PCS-902 Line Distance Relay 3-75


Date: 2011-07-06
3 Operation Theory

1: phase-segregated signal
scheme
Enabling/disabling weak infeed
scheme
3 85.En_WI 0 or 1
0: disable
1: enable
Undervoltage setting of weak
4 85.U_UV_WI 0~0.8Un 0.001 V
infeed logic
Enabling/disabling pilot
distance protection
5 85.Z.En 0 or 1
0: disable
1: enable
Enabling/disabling unblocking
scheme
6 85.En_Unblocking1 0 or 1
0: disable
1: enable
Time delay for blocking
7 85.t_DPU_Blocking1 0.000~1.000 0.001 s scheme of pilot distance
protection operation
Time delay dropoff for current
8 85.t_DDO_CR1 0.000~1.000 0.001 s
reversal logic
Time delay pickup for current
9 85.t_DPU_CR1 0.000~1.000 0.001 s
reversal logic
Enabling/disabling zone
extension protection
10 85.ZX.En 0 or 1
0: disable
1: enable
Pickup time delay for zone
11 85.t_DPU_ZX 0.000~10.000 0.001 s
extension protection operation

Table 3.7-3 Internal settings of pilot distance protection

No. Name Default Value Unit Remark


Pickup time delay of unblocking scheme for pilot
1 85.t_Unblocking1 0.1 s
channel 1
Option of PLC channel for pilot channel 1
2 85.Opt_PilotCh1 1 0: phase-to-phase channel
1: phase-to-ground channel

3.8 Pilot Directional Earth-fault Protection


3.8.1 General Application

Directional earth fault protection needs to coordinate with downstream protection with definite or
inverse time delay so it cannot clear an internal fault quickly. Pilot directional earth-fault protection
takes use of directional earth fault elements on both ends, it can detect high resistance fault and

3-76 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

maintain high-speed operation.

Pilot protection requires communication channel to exchange the protection information at both
ends. The channel may be dedicated or multiplexed channel through optical fiber or any other
communication media.

Pilot directional earth-fault protection can be used independently, for example, no distance
protection is equipped with the device but fast operation is required for the whole line, or it is used
as backup protection of pilot distance protection to enhance the sensitivity for an earth fault with
high fault resistance.

3.8.2 Function Description

Sending permissive signal (or terminating sending signal) to the opposite end is controlled by
forward direction element. Current reversal logic is available for parallel line operation and CB
echo logic is provided once pilot directional earth fault protection is enabled. Current reversal logic
is only used for permissive scheme. For blocking scheme, current reversal need not be considered
because there is a settable time delay in pilot directional earth-fault protection.

Pilot directional earth-fault protection can be enabled or disabled by input signals, logic setting and
blocking signal, as shown in Figure 3.8-1.

SIG 85.DEF.En1
&
SIG 85.DEF.En2

EN [85.DEF.En]
&
Enable 85.DEF
SIG 85.DEF.Blk

Figure 3.8-1 Enabling/disabling logic of pilot directional earth-fault protection

Pilot directional earth-fault protection comprises permissive scheme and blocking scheme. It can
share pilot channel 1 ([85.DEF.En_IndepCh]=0) with pilot distance protection, or uses independent
pilot channel 2 ([85.DEF.En_IndepCh]=1) by setting logic setting [85.DEF.En_IndepCh]. For
underreach mode, pilot directional earth-fault always adopts independent pilot channel 2. The
logic of receiving signal is shown in Figure 3.8-2.

PCS-902 Line Distance Relay 3-77


Date: 2011-07-06
3 Operation Theory

SET 85.Blocking &


>=1
SIG 85.Recv1

&

SIG 85.Abnor_Ch1

SIG Unblocking1 Valid


&
SET 85.PUTT >=1 >=1
Valid_Recv_DEF
EN [85.DEF.En_IndepCh]

SET 85.Blocking & &


>=1

SIG 85.Recv2 &

SIG 85.Abnor_Ch2

SIG Unblocking2 Valid

Figure 3.8-2 Logic diagram of receiving signal

SIG FWD_ROC &


85.FWD_DEF_Pilot
SIG 3I0>[85.DEF.3I0_Set]

SIG REV_ROC &


85.REV_DEF_Pilot
SIG FD.ROC.Pkp

Figure 3.8-3 Forward/reverse direction of zero-sequence power

FWD_ROC: The forward direction of zero-sequence power.

REV_ROC: The reverse direction of zero-sequence power.

3.8.2.1 Permissive Transfer Trip (PTT)

Pilot protection with permissive scheme receives permissive signal from the device of remote end,
so as to combine with local discrimination condition to accelerate tripping, so it has high security.

Operation of forward directional earth fault element is used to send permissive signal to the
remote end when the protection is enabled and will release tripping signal upon receiving
permissive signal from the remote end with further guarded by no operation of reverse directional
earth fault element. This ensures the security of the protection.

The following figure shows the schematic of permissive transfer trip.

3-78 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

FWD_DEF_Pilot

Rev_DEF_Pilot
M
EM A Fault B EN

N
Rev_DEF_Pilot

FWD_DEF_Pilot

Relay A
FWD_DEF_Pilot & &
85.DEF.t_DPU 85.Op_DEF 85.Op_DEF 85.DEF.t_DPU
FWD_DEF_Pilot
Relay B

Figure 3.8-4 Simple schematic of DEF (permissive scheme)

For blocking scheme, pilot directional earth-fault protection will operate when there is an internal
fault with abnormal channel, however, it is possible that pilot directional earth-fault protection issue
an undesired trip when there is an external fault with abnormal channel.

SIG [85.ExTrp] 0ms 150ms

& >=1
SIG CB open position &
200ms 0ms
SIG Valid_Recv_DEF
&
SIG FD.Pkp 85.Send_DEF

SIG FWD_DEF_Pilot &

SIG REV_DEF_Pilot
&
&
SIG Valid_Recv_DEF t1 t2

&
SIG FD.Pkp

SET 85.PUTT >=1

SET 85.POTT
&

SIG Enable 85.DEF &


& 85.Op_DEF
[85.DEF.t_DPU] >=1

&

EN 85.DEF.En_IndepCh

Figure 3.8-5 Logic diagram of DEF (permissive scheme)

PCS-902 Line Distance Relay 3-79


Date: 2011-07-06
3 Operation Theory

t1: pickup time delay of current reversal

t2: dropoff time delay of current reversal

When adopting independent pilot channel 2, settings of t1 [85.t_DPU_CR2] and t2


[85.t_DDO_CR2] should be considered individually from channel 1.

When sharing pilot channel 1 with pilot distance protection, t1 and t2 are the settings
[85.t_DPU_CR1] and [85.t_DDO_CR1] respectively.

3.8.2.2 Blocking

Permissive scheme has high security, but it relies on pilot channel seriously. Pilot directional
earth-fault protection will not operate when there is an internal fault with abnormal channel.
Blocking scheme could be considered as an alternative.

Blocking scheme sends blocking signal when fault detector picks up if and zero-sequence forward
element does not operate or both zero-sequence forward element and zero-sequence reverse
element do not operate. Pilot directional earth-fault protection will operate if forward directional
zero-sequence overcurrent element operates and not receiving blocking signal.

FWD_DEF_Pilot

Rev_DEF_Pilot
M
EM A Fault B EN

N
Rev_DEF_Pilot

FWD_DEF_Pilot

Relay B
Relay A
Pkp_FD_Prot Pkp_FD_Prot

& &
REV_DEF_Pilot & & REV_DEF_Pilot

FWD_DEF_Pilot FWD_DEF_Pilot

& &
& 85.Op_DEF 85.Op_DEF &
[t_DEF_PilotP] [t_DEF_PilotP]

Figure 3.8-6 Simple schematic of blocking

3-80 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

SIG 85.TRIPOUT >=1

SIG 85.ExTrp 0ms 150ms


>=1
SIG CB open position &
Send_DEF
SIG Valid_Recv_DEF
&
SIG FWD_DEF_Pilot &

SIG REV_DEF_Pilot
&
SIG FD.Pkp [85.DEF.t_DPU] 85.Op_DEF

SET 85.Blocking &

SIG Enable 85.DEF

Figure 3.8-7 Logic diagram of DEF (Blocking scheme)

When DEF shares pilot channel 1 with pilot distance protection, time delay of pilot directional
earth-fault protection will change from the setting [85.DEF.t_DPU] to the setting
[85.t_DPU_Blocking1].

Because the time delay of pilot directional earth-fault protection has enough margin for current
reversal, so blocking scheme should not consider the current reversal condition.

3.8.2.3 Unblocking

Permissive scheme will operate only when it receives permissive signal from the remote end.
However, it may not receive permissive signal from the remote end when pilot channel fails. For
this case, pilot directional earth-fault protection can adopt unblocking scheme. Under normal
conditions, the signaling equipment works in the pilot frequency, and when the device operates to
send permissive signal, the signaling equipment will be switched to high frequency. While the
channel is blocked, the signaling equipment will receive neither pilot frequency signal nor high
frequency signal. The signaling equipment will provide a contact to the device as unblocking signal.
When the device receives unblocking signal from the signaling equipment, it will recognize
channel failure, and unblocking signal will be taken as permissive signal temporarily.

The unblocking scheme can only be used together with permissive scheme.

PCS-902 Line Distance Relay 3-81


Date: 2011-07-06
3 Operation Theory

EN [85.En_Unblocking2] &

BI 85.Unblocking2 &

[85.t_Unblocking2] 0ms

SIG Selection of multi-phase >=1

EN [85.Opt_PilotCh2]
&
Unblocking2 Valid
SIG Pilot DEF forward detection

Figure 3.8-8 Logic diagram for unblocking

3.8.2.4 Current Reversal

The reach of directional earth-fault protection is difficult to define. There may have problem for
pilot direction earth-fault protection applied on parallel line arrangement due to current reversal
phenomenon. Current reversal blocking logic using time delay method is adopted in the device. It
is the same logic as pilot distance protection. Please refer to section 3.7.2.6 for details. The only
difference is that different signal receive terminal is used if independent channel is selected.

3.8.2.5 CB Echo

It is the same logic as pilot distance protection. Please refer to section 3.7.2.8 for details. The only
difference is that different signal receive terminal is used if independent channel is selected.

3.8.3 Function Block Diagram

85

85.DEF.En1 85.Op_DEF

85.DEF.En2 85.DEF_BlkAR

85.DEF.Blk 85.Send1

85.Abnor_Ch1 85.Send2

85.Abnor_Ch2

85.Rcv1

85.Rcv2

85.ExTrp

85.Unblocking1

85.Unblocking2

3-82 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.8.4 I/O Signals

Table 3.8-1 Configurable I/O signals of pilot directional earth-fault protection

No. Input Signal Description


Pilot directional earth-fault protection enabling input 1, it can be a binary input or a
1 85.DEF.En1
logic link.
Pilot directional earth-fault protection enabling input 2, it can be a binary input or a
2 85.DEF.En2
logic link.
Pilot directional earth-fault protection blocking input, such as a function blocking
3 85.DEF.Blk
binary input.
4 85.Abnor_Ch1 Input signal of indicating that pilot channel 1 is abnormal
5 85.Abnor_Ch2 Input signal of indicating that pilot channel 2 is abnormal
6 85.Rcv1 Input signal of receiving permissive signal via channel 1
7 85.Rcv2 Input signal of receiving permissive signal via channel 2
8 85.ExTrp Input signal of initiating sending permissive signal from external tripping signal
9 85.Unblocking1 Unblocking signal 1
10 85.Unblocking2 Unblocking signal 2
No. Output Signal Description
1 85.Op_DEF Pilot directional earth-fault protection operates.
2 85.DEF_BlkAR Pilot directional earth-fault protection operates to block AR.
Output signal of sending permissive signal 1 when pilot directional earth-fault
3 85.Send1
protection sharing pilot channel 1 with pilot distance protection
Output signal of sending permissive signal 2 only for pilot directional earth-fault
4 85.Send2
protection adopting independent pilot channel 2

3.8.5 Settings

Table 3.8-2 Settings of pilot directional earth-fault protection

No. Name Range Step Unit Remark


Enabling/disabling pilot directional
earth-fault protection
1 85.DEF.En 0 or 1
0: disable
1: enable
Enabling/disabling pilot directional
earth-fault protection operate to
block AR
2 85.DEF.En_BlkAR 0 or 1 0: selective phase tripping and not
blocking AR
1: three-phase tripping and blocking
AR
Enabling/disabling independent
channel for pilot directional
3 85.DEF_En_IndepCh 0 or 1
earth-fault protection
0: pilot directional earth-fault

PCS-902 Line Distance Relay 3-83


Date: 2011-07-06
3 Operation Theory

protection sharing same channel


with pilot distance protection
1: pilot directional earth-fault
adopting independent pilot channel
Enabling/disabling unblocking
scheme for pilot DEF via pilot
4 85.En_Unblocking2 0 or 1 channel 2
0: disable
1: enable
Current setting of pilot directional
5 85.DEF.3I0_Set (0.050~30.000)×In 0.001 A
earth-fault protection
Time delay of pilot directional
6 85.DEF.t_DPU 0.001~10.000 0.001 s
earth-fault protection
Time delay pickup for current
reversal logic when pilot directional
7 85.t_DPU_CR2 0.000~1.000 0.001 s
earth-fault protection adopts
independent pilot channel 2
Time delay dropoff for current
reversal logic when pilot directional
8 85.t_DDO_CR2 0.000~1.000 0.001 s
earth-fault protection adopts
independent pilot channel 2

Table 3.8-3 Internal settings of pilot distance protection

No. Name Default Value Unit Remark


Pickup time delay of unblocking scheme for pilot
1 85.t_Unblocking2 0.2 s
channel 2
Option of PLC channel for pilot channel 2
2 85.Opt_PilotCh2 1 0: phase-to-phase channel
1: phase-to-ground channel

3.9 Current Direction


3.9.1 General Application

Overcurrent protection is widely used in the power system as backup protection, but in some
cases, the direction of current is necessary to aid to complete the selective tripping. As shown
below:

L M N
EM C D A B EN
Fault

Figure 3.9-1 Line fault description

3-84 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

When line LM has an earth fault, the fault currents flowing through the relay A and the relay D are
of similar magnitude in most cases. It is desirable that the fault is isolated from the power system
by tripping the circuit breaker C and circuit breaker D. Hence, the overcurrent protection of relay A
and relay D require to associate with current direction to fulfill selective tripping.

Directional earth fault protection has a time delay due to coordinate with that of downstream so it
cannot clear the fault quickly. Pilot directional earth-fault protection, which is fulfilled by directional
earth fault element on both ends, it can maintain fast operation and achieve high sensitivity to
detect high resistance fault.

3.9.2 Function Description

The module computes direction of phase current and phase-to-phase current, zero-sequence
current and negative-sequence current.

The direction of phase current and phase-to-phase current equips with an under-voltage direction
function to ensure that phase or phase-to-phase overcurrent protection has explicit directionality
when the polarized voltage is too low for close up fault.

The direction of zero-sequence current and negative-sequence current direction equips with an
impedance compensation function to ensure that zero-sequence or negative-sequence
overcurrent protection has explicit directionality when the zero-sequence voltage or the
negative-sequence voltage is too low.

3.9.2.1 Phase/Phase-to-phase Current Direction

By setting the characteristic angle [RCA_OC] to determine the most sensitive forward angle of
phase current and phase-to-phase current, power value is calculated using phase current with
phase polarized voltage or phase-to-phase current with phase-to-phase polarized voltage to
determine the direction of phase current or phase-to-phase current respectively in forward
direction or reverse direction. When the power value is zero, neither forward direction nor reverse
direction is considered. As shown below:

PCS-902 Line Distance Relay 3-85


Date: 2011-07-06
3 Operation Theory

jX
U

φ
θ I

R
O

Forward direction

Reverse direction

Figure 3.9-2 Vector diagram of current and voltage

Where:

φ is the setting [RCA_OC]

θ is the phase angle between polarized voltage and current

The power value is calculated as below:

P=U×[I×COS(θ-φ)]

1. If P>0, the current direction polarized by U is forward direction

2. If P<0, the current direction polarized by U is reverse direction

From above diagram can be seen, when θ=φ, P reaches to the maximum value. It is considered
as the most sensitive forward direction. Hence, φ is called as sensitivity angle of phase
overcurrent protection.

1. Polarized voltage of phase or phase-to-phase current direction

In the event of asymmetrical fault, because phase or phase-to-phase voltage may decrease to
very low voltage whereas positive-sequence voltage does not, the polarized voltage of phase or
phase-to-phase current direction uses positive-sequence voltage to avoid wrong direction due to
too low polarized voltage. Therefore, using positive-sequence voltage as polarized voltage can
ensure that the direction determination has no dead zone for asymmetrical fault. For symmetric
fault, if positive-sequence voltage decreases to 15%Un, the device uses memorized
positive-sequence voltage as polarized voltage, the memorized positive-sequence voltage is 1.5
cycles pre-fault positive-sequence voltage.

2. Phase or phase-to-phase current direction under normal polarized voltage condition

When using normal polarized voltage to calculate phase and phase-to-phase current direction,

3-86 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

there are total twelve direction determination algorithm including forward direction and reverse
direction.

Table 3.9-1 Direction description

Direction Polarized Voltage Current


Forward direction U1a Ia
Phase A
Reverse direction U1a Ia
Forward direction U1b Ib
Phase B
Reverse direction U1b Ib
Forward direction U1c Ic
Phase C
Reverse direction U1c Ic
Forward direction U1ab Iab
Phase AB
Reverse direction U1ab Iab
Forward direction U1bc Ibc
Phase BC
Reverse direction U1bc Ibc
Forward direction U1ca Ica
Phase CA
Reverse direction U1ca Ica

3. Phase or phase-to-phase current direction for under-voltage conditions

When the symmetrical fault occurs on a power system, positive-sequence voltage may reduce to
less than 0.15Un, the device will switch to phase or phase-to-phase current direction for
under-voltage condition. The 1.5 cycle pre-fault positive-sequence voltage is used as polarized
voltage with reverse threshold to ensure stable direction decision when three-phase voltage goes
to approximately zero due to close up fault.

At first, the threshold is forward offset before direction is determined, and the threshold will be
reversed offset after direction is determined.

3.9.2.2 Zero-sequence/Negative-sequence Current Direction

By setting the characteristic angle [RCA_ROC] and [RCA_NegOC] to determine the most
sensitive forward angle of zero-sequence current and negative-sequence current, power value is
calculated using zero-sequence current with zero-sequence voltage or negative-sequence current
with negative-sequence voltage to determine the direction of zero-sequence current and
negative-sequence current respectively in forward direction or reverse direction.

When the power value is between 0 and -0.1In, neither forward direction nor reverse direction is
considered.

PCS-902 Line Distance Relay 3-87


Date: 2011-07-06
3 Operation Theory

jX 3U0

θ-180°

-3I0
φ

R
O

3I0
θ Reverse direction

Forward direction

Figure 3.9-3 Vector diagram of zero-sequence power

Vector diagram of negative-sequence power is similar to that of zero-sequence power.

Where:

φ is the setting [RCA_ROC] or the setting [RCA_NegOC]

θ is the phase angle between zero/negative-sequence voltage and zero/negative-sequence


current

3I0: calculated zero-sequence current by vector sum of Ia, Ib and Ic

The power value is calculated as below:

P=U×[I×COS(θ-φ)]

 If P>0, the direction of zero /negative-sequence current is reverse direction

 If P<-0.1InVA, the direction of zero /negative-sequence current is forward direction

1. The direction of zero-sequence current

Calculating the power value using zero-sequence current (3I0) and zero-sequence voltage (3U0)
to determine the direction of zero-sequence current

According to the equation:

The zero-sequence current and the zero-sequence voltage can be gained by calculation

3-88 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Zero-sequence power is: P=3U0×[3I0×COS(θ-φ)]

2. The direction of negative-sequence current

Calculating the power value using negative-sequence current (3I2) and negative-sequence
voltage (3U2) to determine the direction of negative-sequence current

According to the equation:

The negative-sequence current and the negative-sequence voltage can be gained by calculation

Negative-sequence power is: P=3U2×[3I2×COS(θ-φ)]

3. The direction of zero-sequence/negative-sequence current with impedance compensation

When zero-sequence impedance or negative-sequence impedance behind the device is very


small, if the fault in forward direction happens, the measured zero-sequence voltage or
negative-sequence voltage by the device may be relatively small to determine correct direction. In
order to solve this problem, compensated zero-sequence voltage and negative-sequence voltage
are used for power calculation.

The compensation formula is as follows:

is the setting [Z0_Comp], which cannot exceed the total zero-sequence impedance of

the protected line

is the setting [Z2_Comp], which cannot exceed the total negative-sequence impedance

of the protected line

3.9.3 I/O Signals

Table 3.9-2 Internal I/O signals of current direction

No. Output Signal Description


1 FWD_ROC The forward direction of zero-sequence power
2 REV_ROC The reverse direction of zero-sequence power
3 FWD_NegOC The forward direction of negative-sequence power
4 REV_NegOC The reverse direction of negative-sequence power
5 Forward DIR A, B, C The forward direction of phase current

PCS-902 Line Distance Relay 3-89


Date: 2011-07-06
3 Operation Theory

6 Reverse DIR A, B, C The reverse direction of phase current


7 Forward DIR AB, BC, CA The forward direction of phase-to-phase current
8 Reverse DIR AB, BC, CA The reverse direction of phase-to-phase current

3.9.4 Settings

Table 3.9-3 Settings of current direction

No. Name Range Step Unit Remark


The characteristic angle of directional
1 RCA_OC 45.00~89.00 0.01 Deg
phase overcurrent element
The characteristic angle of directional earth
2 RCA_ROC 45.00~89.00 0.01 Deg
fault element
The characteristic angle of directional
3 RCA_NegOC 45.00~89.00 0.01 Deg
negative-sequence overcurrent element
The compensated zero-sequence
4 Z0_Comp (0.000~2Unn)/In 0.001 ohm
impedance
The compensated negative-sequence
5 Z2_Comp (0.000~2Unn)/In 0.001 ohm
impedance

3.10 Phase Overcurrent Protection


3.10.1 General Application

When a fault occurs in power system, usually the fault current would be very large and phase
overcurrent protection operates monitoring fault current is then adopted to avoid further damage to
protected equipment. Directional element can be selected to improve the sensitivity and selectivity
of the protection. For application on feeder-transformer circuits, second harmonic can also be
selected to block phase overcurrent protection to avoid the effect of inrush current on the
protection.

3.10.2 Function Description

Phase overcurrent protection has following functions:

1. Four-stage phase overcurrent protection with independent logic, current and time delay
settings.

2. All stages can be selected as definite-time or inverse-time characteristic. The inverse-time


characteristic is selectable among IEC and ANSI/IEEE standard inverse-time characteristics,
and a user-defined inverse-time curve is available for stage 1 of phase overcurrent protection.

3. Direction control element can be selected to control each stage phase overcurrent protection
with three options: no direction, forward direction and reverse direction.

4. Second harmonic can be selected to block each stage of phase overcurrent protection.

3.10.2.1 Overview

Phase overcurrent protection consists of following three elements:

3-90 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

1. Overcurrent element: each stage is independent overcurrent element.

2. Direction control element: one direction control element shared by all overcurrent elements,
and each overcurrent element can individually select protection direction.

3. Harmonic blocking element: one harmonic blocking element shared by all overcurrent
elements and each phase overcurrent element can individually enable the output signal from
harmonic element as a blocking input.

3.10.2.2 Overcurrent Element

The operation criterion for each stage of overcurrent element is:

Ip> [50/51Px.I_Set] Equation 3.10-1

Where:

Ip is measured phase current.

[50/51Px.I_Set] is the current setting of stage x (x=1, 2, 3, or 4) of overcurrent element.

3.10.2.3 Direction Control Element

Please refer to section 3.9 for details.

3.10.2.4 Harmonic Blocking Element

When phase overcurrent protection is used to protect feeder transformer circuits harmonic
blocking function can be selected for each stage of phase overcurrent element by configuring logic
setting [50/51Px.En_Hm2] (x=1, 2, 3 or 4) to prevent maloperation due to inrush current.

When the percentage of second harmonic component to fundamental component of any phase
current is greater than the setting [50/51P.K_Hm2], harmonic blocking element operates to block
stage x overcurrent element if corresponding logic setting [50/51Px.En_Hm2] enabled.

Operation criterion:

Equation 3.10-2

Where:

is second harmonic of phase current

is fundamental component of phase current.

[50/51P.K_Hm2] is harmonic blocking coefficient.

If fundamental component of any phase current is lower than the minimum operating current
(0.1In), then harmonic calculation is not carried out and harmonic blocking element does not
operate.

PCS-902 Line Distance Relay 3-91


Date: 2011-07-06
3 Operation Theory

3.10.2.5 Characteristic Curve

All stages can be selected as definite-time or inverse-time characteristic, inverse-time operating


characteristic is as follows.

Where:

Iset is current setting [50/51Px.I_Set].

Tp is time multiplier setting [50/51Px.TMS].

α is a constant.

K is a constant.

C is a constant.

I is measured phase current from line CT

The user can select the operating characteristic from various inverse-time characteristic curves by
setting [50/51Px.Opt_Curve], and parameters of available characteristics for selection are shown
in the following table.

Table 3.10-1 Inverse-time curve parameters

51Px.Opt_Curve Time Characteristic K α C


0 Definite time
1 IEC Normal inverse 0.14 0.02 0
2 IEC Very inverse 13.5 1.0 0
3 IEC Extremely inverse 80.0 2.0 0
4 IEC Short-time inverse 0.05 0.04 0
5 IEC Long-time inverse 120.0 1.0 0
6 ANSI Extremely inverse 28.2 2.0 0.1217
7 ANSI Very inverse 19.61 2.0 0.491
8 ANSI Inverse 0.0086 0.02 0.0185
9 ANSI Moderately inverse 0.0515 0.02 0.114
10 ANSI Long-time extremely inverse 64.07 2.0 0.25
11 ANSI Long-time very inverse 28.55 2.0 0.712
12 ANSI Long-time inverse 0.086 0.02 0.185
13 Programmable user-defined

If all available curves do not comply with user application, user may set [50/51Px.Opt_Curve] as
“13” to customize the inverse-time curve characteristic with constants α, K and C. (only stage 1)

When inverse-time characteristic is selected, if calculated operating time is less than setting
[50/51Px.tmin], then the operating time of the protection changes to the value of setting

3-92 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

[50/51Px.tmin] automatically.

Define-time or inverse-time phase overcurrent protection drops off instantaneously after fault
current disappears.

3.10.3 Function Block Diagram

50/51Px

50/51Px.En1 50/51Px.St

50/51Px.En2 50/51Px.Op

50/51Px.Blk

3.10.4 I/O Signals

Table 3.10-2 Configurable I/O signals of phase overcurrent protection

No. Input Signal Description


Stage x of phase overcurrent protection enabling input 1, it can be a binary input
1 50/51Px.En1
or a logic link.
Stage x of phase overcurrent protection enabling input 2, it can be a binary input
2 50/51Px.En2
or a logic link.
Stage x of phase overcurrent protection blocking input, such as a function
3 50/51Px.Blk
blocking binary input.
No. Output Signal Description
1 50/51P1.Op Stage 1 of phase overcurrent protection operates.
2 50/51P2.Op Stage 2 of phase overcurrent protection operates.
3 50/51 P3.Op Stage 3 of phase overcurrent protection operates.
4 50/51P4.Op Stage 4 of phase overcurrent protection operates.
5 50/51P1.St Stage 1 of phase overcurrent protection starts.
6 50/51P2.St Stage 2 of phase overcurrent protection starts.
7 50/51P3.St Stage 3 of phase overcurrent protection starts.
8 50/51P4.St Stage 4 of phase overcurrent protection starts.

Table 3.10-3 Internal I/O signals of phase overcurrent protection

No. Input Signal Description


1 I3P Three-phase current input
2 U3P Three-phase voltage input

PCS-902 Line Distance Relay 3-93


Date: 2011-07-06
3 Operation Theory

3.10.5 Logic

EN [50/51Px.En]
&
SIG [50/51Px.En1]

SIG [50/51Px.En2]

SIG [50/51Px.Blk]

SET Ia>[50/51Px.I_Set]
>=1
SET Ib>[50/51Px.I_Set]

SET Ic>[50/51Px.I_Set]

SET [50/51Px.Opt_Dir]=1 &


& &
[50/51Px.St]
SIG Forward DIR

SET [50/51Px.Opt_Dir]=2 &


Timer
SIG Reverse DIR
>=1 t
[50/51Px.Op]
t
SET [50/51Px.Opt_Dir]=0

SIG I3P 2nd Hm Detect &

SET [50/51Px.En_Hm2]

Figure 3.10-1 Logic diagram of phase overcurrent protection

Where:

x=1, 2, 3, 4

3.10.6 Settings

Table 3.10-4 Settings of phase overcurrent protection

No. Name Range Step Unit Remark


Setting of second harmonic
1 50/51P.k_Hm2 0.000~1.000 0.001 component for blocking phase
overcurrent elements
Current setting for stage 1 of phase
2 50/51P1.I_Set (0.050~30.000)×In 0.001 A
overcurrent protection
Time delay for stage 1 of phase
3 50/51P1.t_Op 0.000~20.000 0.001 s
overcurrent protection
Enabling/disabling stage 1 of phase
overcurrent protection
4 50/51P1.En 0 or 1
0: disable
1: enable
Direction option for stage 1 of phase
5 50/51P1.Opt_Dir 0, 1 or 2
overcurrent protection

3-94 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

0: no direction
1: forward direction
2: reverse direction
Enabling/disabling second harmonic
blocking for stage 1 of phase
6 50/51P1.En_Hm2 0 or 1 overcurrent protection
0: disable
1: enable
Option of characteristic curve for
7 50/51P1.Opt_Curve 0~13 1 stage 1 of phase overcurrent
protection
Time multiplier setting for stage 1 of
8 50/51P1.TMS 0.010~200.000 0.001 inverse-time phase overcurrent
protection
Minimum operating time for stage 1 of
9 50/51P1.tmin 0.000~20.000 0.001 s inverse-time phase overcurrent
protection
Constant “α” for stage 1 of
customized inverse-time
10 50/51P1.Alpha 0.010~5.000 0.001
characteristic phase overcurrent
protection
Constant “C” for stage 1 of
customized inverse-time
11 50/51P1.C 0.000~200.000 0.001
characteristic phase overcurrent
protection
Constant “K” for stage 1 of
customized inverse-time
12 50/51P1.K 0.050~20.000 0.001
characteristic phase overcurrent
protection
Current setting for stage 2 of phase
13 50/51P2.I_Set (0.050~30.000)×In 0.001 A
overcurrent protection
Time delay for stage 2 of phase
14 50/51P2.t_Op 0.000~20.000 0.001 s
overcurrent protection
Enabling/disabling stage 2 of phase
overcurrent protection
15 50/51P2.En 0 or 1
0: disable
1: enable
Direction option for stage 2 of phase
overcurrent protection
16 50/51P2.Opt_Dir 0, 1 or 2 0: no direction
1: forward direction
2: reverse direction
Enabling/disabling second harmonic
17 50/51P2.En_Hm2 0 or 1
blocking for stage 2 of phase

PCS-902 Line Distance Relay 3-95


Date: 2011-07-06
3 Operation Theory

overcurrent protection
0: disable
1: enable
Option of characteristic curve for
18 50/51P2.Opt_Curve 0~12 stage 2 of phase overcurrent
protection
Time multiplier setting for stage 2 of
19 50/51P2.TMS 0.010~200.000 0.001 inverse-time phase overcurrent
protection.
Minimum operating time for stage 2 of
20 50/51P2.tmin 0.000~20.000 0.001 s inverse-time phase overcurrent
protection
Current setting for stage 3 of phase
21 50/51P3.I_Set (0.050~30.000)×In 0.001 A
overcurrent protection
Time delay for stage 3 of phase
22 50/51P3.t_Op 0.000~20.000 0.001 s
overcurrent protection
Enabling/disabling stage 3 of phase
overcurrent protection
23 50/51P3.En 0 or 1
0: disable
1: enable
Direction option for stage 3 of phase
overcurrent protection
24 50/51P3.Opt_Dir 0, 1 or 2 0: no direction
1: forward direction
2: reverse direction
Enabling/disabling second harmonic
blocking for stage 3 of phase
25 50/51P3.En_Hm2 0 or 1 overcurrent protection
0: disable
1: enable
Option of characteristic curve for
26 50/51P3.Opt_Curve 0~12 stage 3 of phase overcurrent
protection
Time multiplier setting for stage 3 of
27 50/51P3.TMS 0.010~200.000 0.001 inverse-time phase overcurrent
protection.
Minimum operating time for stage 3 of
28 50/51P3.tmin 0.000~20.000 0.001 s inverse-time phase overcurrent
protection
Current setting for stage 4 of phase
29 50/51P4.I_Set (0.050~30.000)×In 0.001 A
overcurrent protection
Time delay for stage 4 of phase
30 50/51P4.t_Op 0.000~20.000 0.001 s
overcurrent protection
31 50/51P4.En 0 or 1 Enabling/disabling stage 4 of phase

3-96 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

overcurrent protection
0: disable
1: enable
Direction option for stage 4 of phase
overcurrent protection
32 50/51P4.Opt_Dir 0, 1 or 2 0: no direction
1: forward direction
2: reverse direction
Enabling/disabling second harmonic
blocking for stage 4 of phase
33 50/51P4.En_Hm2 0 or 1 overcurrent protection
0: disable
1: enable
Option of characteristic curve for
34 50/51P4.Opt_Curve 0~12 stage 4 of phase overcurrent
protection
Time multiplier setting for stage 4 of
35 50/51P4.TMS 0.010~200.000 0.001 inverse-time phase overcurrent
protection.
Minimum operating time for stage 4 of
36 50/51P4.tmin 0.000~20.000 0.001 s inverse-time phase overcurrent
protection

3.11 Earth Fault Protection


3.11.1 General Application

During normal operation of power system, there is trace residual current, whereas a fault current
flows to earth will result in greater residual current. Therefore, residual current is adopted for the
calculation of earth fault protection.

In order to improve the selectivity of earth fault protection in power grid with multiple power
sources, directional element can be selected to control earth fault protection. For application on
line-transformer unit, second harmonic also can be selected to block earth fault protection to avoid
the effect of sympathetic current on the protection.

3.11.2 Function Description

Earth fault protection has following functions:

1. Four-stage earth fault protection with independent logic, current and time delay settings.

2. All stages can be selected as definite-time or inverse-time characteristic. The inverse-time


characteristic is selectable, among IEC and ANSI/IEEE standard inverse-time characteristics,
and a user-defined inverse-time curve is available for stage 1 of earth fault protection.

3. Directional element can be selected to control each stage of earth fault protection with three
options: no direction, forward direction and reverse direction.

PCS-902 Line Distance Relay 3-97


Date: 2011-07-06
3 Operation Theory

4. Second harmonic can be selected to block each stage of earth fault protection.

3.11.2.1 Overview

Earth fault protection consists of following three elements:

1. Overcurrent element: each stage equipped with one independent overcurrent element.

2. Directional control element: one direction control element shared by all overcurrent elements,
and each overcurrent element can individually select protection direction.

3. Harmonic blocking element: one harmonic blocking element shared by all overcurrent
elements and each overcurrent element can individually enable the output signal of harmonic
blocking element as a blocking input.

3.11.2.2 Directional Earth-fault Element

The operation criterion for each stage of earth fault protection is:

3I0>[50/51Gx.3I0_Set] Equation 3.11-1

Where:

3I0 is the calculated residual current.

[50/51Gx.3I0_Set] is the current setting of stage x (x=1, 2, 3, or 4) of earth fault protection.

3.11.2.3 Direction Control Element

Please refer to section 3.9 for details.

3.11.2.4 Harmonic Blocking Element

In order to prevent effects of inrush current on earth fault protection, harmonic blocking function
can be selected for each stage of earth fault element by configuring logic setting
[50/51Gx.En_Hm2] (x=1, 2, 3 or 4).

When the percentage of second harmonic component to fundamental component of residual


current is greater than the setting [50/51G.K_Hm2], harmonic blocking element operates to block
stage x of earth fault protection if corresponding logic setting [50/51Gx.En_Hm2] is enabled

Operation criterion:

Equation 3.11-2

Where:

is second harmonic of residual current

is fundamental component of residual current.

[50/51G.K_Hm2] is harmonic blocking coefficient.

3-98 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

If fundamental component of residual current is lower than the minimum operating current (0.1In)
then harmonic calculation is not carried out and harmonic blocking element does not operate.

3.11.2.5 Characteristic Curve

All 4 stages earth fault protection can be selected as definite-time or inverse-time characteristic,
and inverse-time operating time curve is as follows.

Equation 3.11-3

Where:

Iset is residual current setting [50/51Gx.3I0_Set].

Tp is time multiplier setting [50/51Gx.TMS].

K is a constant

C is a constant.

α is a constant.

3I0 is the calculated residual current.

The user can select the operating characteristic from various inverse-time characteristic curves by
setting [50/51Gx.Opt_Curve], and parameters of available characteristics for selection are shown
in the following table.

Table 3.11-1 Inverse-time curve parameters

51Gx.Opt_Curve Time Characteristic K α C


0 Definite time
1 IEC Normal inverse 0.14 0.02 0
2 IEC Very inverse 13.5 1.0 0
3 IEC Extremely inverse 80.0 2.0 0
4 IEC Short-time inverse 0.05 0.04 0
5 IEC Long-time inverse 120.0 1.0 0
6 ANSI Extremely inverse 28.2 2.0 0.1217
7 ANSI Very inverse 19.61 2.0 0.491
8 ANSI Inverse 0.0086 0.02 0.0185
9 ANSI Moderately inverse 0.0515 0.02 0.114
10 ANSI Long-time extremely inverse 64.07 2.0 0.25
11 ANSI Long-time very inverse 28.55 2.0 0.712
12 ANSI Long-time inverse 0.086 0.02 0.185
13 Programmable User-defined

If all available curves do not comply with user application, user may set [51Gx.Opt_Curve] as “13”

PCS-902 Line Distance Relay 3-99


Date: 2011-07-06
3 Operation Theory

to customize the inverse-time curve characteristic, and constants K, α and C with configuration
tool software. (only stage 1)

When inverse-time characteristic is selected, if calculated operating time is less than setting
[50/51Gx.tmin], then the operating time of the protection changes to the value of setting
[50/51Gx.tmin] automatically.

Define-time or inverse-time directional earth-fault protection drops off instantaneously after fault
current disappears.

3.11.3 Function Block Diagram

50/51Gx

50/51Gx.En1 50/51Gx.St

50/51Gx.En2 50/51Gx.Op

50/51Gx.Blk

3.11.4 I/O Signals

Table 3.11-2 Configurable I/O signals of earth fault protection

No. Input Signal Description


Stage x of earth fault protection enabling input 1, it can be a binary input or a logic
1 50/51Gx.En1
link.
Stage x of earth fault protection enabling input 2, it can be a binary input or a logic
2 50/51Gx.En2
link.
Stage x of earth fault protection blocking input, such as a function blocking binary
3 50/51Gx.Blk
input.
No. Output Signal Description
1 50/51G1.Op Stage 1 of earth fault protection operates.
2 50/51G2.Op Stage 2 of earth fault protection operates.
3 50/51 G3.Op Stage 3 of earth fault protection operates.
4 50/51G4.Op Stage 4 of earth fault protection operates
5 50/51G1.St Stage 1 of earth fault protection starts.
6 50/51G2.St Stage 2 of earth fault protection starts.
7 50/51G3.St Stage 3 of earth fault protection starts.
8 50/51G4.St Stage 4 of earth fault protection starts.

Table 3.11-3 Internal I/O signals of earth fault protection

No. Input Signal Description


1 I3P Three-phase current input
2 U3P Three-phase voltage input

3-100 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.11.5 Logic

EN [50/51Gx.En]

SIG [50/51Gx.En1]
&
SIG [50/51Gx.En2]

SIG [50/51Gx.Blk]

SET 3I0>[50/51Gx.3I0_Set]

EN [50/51Gx.En_Abnor_Blk] >=1 &


&
& [50/51Gx.St]
SIG No abnormal conditions

>=1 Timer
>=1 t
[50/51Gx.Op]
t

SET [50/51Gx.Opt_Dir]=1 &

SIG Forward DIR

SET [50/51Gx.Opt_Dir]=2 &

SIG Reverse DIR


>=1

SET [50/51Gx.Opt_Dir]=0

SIG CTS.Alm &

EN [50/51Gx.En_CTS_Blk]

SIG I3P 2nd Hm Detect &

SET [50/51Gx.En_Hm2]

Figure 3.11-1 Logic diagram of earth fault protection

Where:

x=1, 2, 3, 4

Abnormal condition 1: when the system is under pole disagreement condition, for 1-pole AR, earth
fault protection will operate. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “1”, the stage x of
earth fault protection will be blocked. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “0”,
earth fault protection is not controlled by direction element.

Abnormal condition 2: When manually closing circuit breaker, three phases of the circuit breaker
maybe not operate simultaneously, and SOTF protection should operate. If the logic setting
[50/51Gx.En_Abnor_Blk] is set as “1”, the stage x of earth fault protection will be blocked. If the
logic setting [50/51Gx.En_Abnor_Blk] is set as “0”, earth fault protection is not controlled by
direction element.

Abnormal condition 3: VT circuit failure. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “1”,
the stage x of earth fault protection will be blocked. If the logic setting [50/51Gx.En_Abnor_Blk] is
set as “0”, earth fault protection is not controlled by direction element.

PCS-902 Line Distance Relay 3-101


Date: 2011-07-06
3 Operation Theory

3.11.6 Settings

Table 3.11-4 Settings of earth fault protection

No. Name Range Step Unit Remark


Setting of second harmonic
1 50/51G.K_Hm2 0.000~1.000 0.001 component for blocking earth fault
elements
Current setting for stage 1 of earth
2 50/51G1.3I0_Set (0.050~30.000)×In 0.001 A
fault protection
Time delay for stage 1 of earth fault
3 50/51G1.t_Op 0.000~20.000 0.001 s
protection
Enabling/disabling stage 1 of earth
fault protection
4 50/51G1.En 0 or 1
0: disable
1: enable
Direction option for stage 1 of earth
fault protection
5 50/51G1.Opt_Dir 0, 1 or 2 0: no direction
1: forward direction
2: reverse direction
Enabling/disabling second
harmonic blocking for stage 1 of
6 50/51G1.En_Hm2 0 or 1 earth fault protection
0: disable
1: enable
Enabling/disabling blocking for
stage 1 of earth fault protection
7 50/51G1.En_Abnor_Blk 0 or 1 under abnormal conditions
0: disable
1: enable
Enabling/disabling blocking for
stage 1 of earth fault protection
8 50/51G1.En_CTS_Blk 0 or 1 under CT failure conditions
0: disable
1: enable
Option of characteristic curve for
9 50/51G1.Opt_Curve 0~13 1
stage 1 of earth fault protection
Time multiplier setting for stage 1 of
10 50/51G1.TMS 0.010~200.000 0.001
inverse-time earth fault protection
Minimum operating time for stage 1
11 50/51G1.tmin 0.050~200.000 0.001 s
of inverse-time earth fault protection
Constant “α” for stage 1 of
12 50/51G1.Alpha 0.010~5.000 0.001 customized inverse-time
characteristic earth fault protection

3-102 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Constant “C” for stage 1 of


13 50/51G1.C 0.000~20.000 0.001 customized inverse-time
characteristic earth fault protection
Constant “K” for stage 1 of
14 50/51G1.K 0.050~20.000 0.001 customized inverse-time
characteristic earth fault protection
Current setting for stage 2 of earth
15 50/51G2.3I0_Set (0.050~30.000)×In 0.001 A
fault protection
Time delay for stage 2 of earth fault
16 50/51G2.t_Op 0.000~20.000 0.001 s
protection
Enabling/disabling stage 2 of earth
fault protection
17 50/51G2.En 0 or 1
0: disable
1: enable
Direction option for stage 2 of earth
fault protection
18 50/51G2.Opt_Dir 0, 1 or 2 0: no direction
1: forward direction
2: reverse direction
Enabling/disabling second
harmonic blocking for stage 2 of
19 50/51G2.En_Hm2 0 or 1 earth fault protection
0: disable
1: enable
Enabling/disabling blocking for
stage 2 of earth fault protection
20 50/51G2.En_Abnor_Blk 0 or 1 under abnormal conditions
0: disable
1: enable
Enabling/disabling blocking for
stage 2 of earth fault protection
21 50/51G2.En_CTS_Blk 0 or 1 under CT failure conditions
0: disable
1: enable
Option of characteristic curve for
22 50/51G2.Opt_Curve 0~12
stage 2 of earth fault protection
Time multiplier setting for stage 2 of
23 50/51G2.TMS 0.010~200.000 0.001
inverse-time earth fault protection
Minimum operating time for stage 2
24 50/51G2.tmin 0.050~200.000 0.001 s
of inverse-time earth fault protection
Current setting for stage 3 of earth
25 50/51G3.3I0_Set (0.050~30.000)×In 0.001 A
fault protection
Time delay for stage 3 of earth fault
26 50/51G3.t_Op 0.000~20.000 0.001 s
protection

PCS-902 Line Distance Relay 3-103


Date: 2011-07-06
3 Operation Theory

Enabling/disabling stage 3 of earth


fault protection
27 50/51G3.En 0, 1 or 2
0: disable
1: enable
Direction option for stage 3 of earth
fault protection
28 50/51G3.Opt_Dir 0 or 1 0: no direction
1: forward direction
2: reverse direction
Enabling/disabling second
harmonic blocking for stage 3 of
29 50/51G3.En_Hm2 0 or 1 earth fault protection
0: disable
1: enable
Enabling/disabling blocking for
stage 3 of earth fault protection
30 50/51G3.En_Abnor_Blk 0 or 1 under abnormal conditions
0: disable
1: enable
Enabling/disabling blocking for
stage 3 of earth fault protection
31 50/51G3.En_CTS_Blk 0 or 1 under CT failure conditions
0: disable
1: enable
Option of characteristic curve for
32 50/51G3.Opt_Curve 0~12
stage 3 of earth fault protection
Time multiplier setting for stage 3 of
33 50/51G3.TMS 0.010~200.000 0.001
inverse-time earth fault protection
Minimum operating time for stage 3
34 50/51G3.tmin 0.050~200.000 0.001 s
of inverse-time earth fault protection
Current setting for stage 4 of earth
35 50/51G4.3I0_Set (0.050~30.000)×In 0.001 A
fault protection
Time delay for stage 4 of earth fault
36 50/51G4.t_Op 0.000~20.000 0.001 s
protection
Enabling/disabling stage 4 of earth
fault protection
37 50/51G4.En 0, 1 or 2
0: disable
1: enable
Direction option for stage 4 of earth
fault protection
38 50/51G4.Opt_Dir 0 or 1 0: no direction
1: forward direction
2: reverse direction
39 50/51G4.En_Hm2 0 or 1 Enabling/disabling second

3-104 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

harmonic blocking for stage 4 of


earth fault protection
0: disable
1: enable
Enabling/disabling blocking for
stage 4 of earth fault protection
40 50/51G4.En_Abnor_Blk 0 or 1 under abnormal conditions
0: disable
1: enable
Enabling/disabling blocking for
stage 4 of earth fault protection
41 50/51G4.En_CTS_Blk 0 or 1 under CT failure conditions
0: disable
1: enable
Option of characteristic curve for
42 50/51G4.Opt_Curve 0~12
stage 4 of earth fault protection
Time multiplier setting for stage 4 of
43 50/51G4.TMS 0.010~200.000 0.001
inverse-time earth fault protection
Minimum operating time for stage 4
44 50/51G4.tmin 0.050~200.000 0.001 s
of inverse-time earth fault protection

3.12 Overcurrent Protection for VT Circuit Failure


3.12.1 General Application

When protection VT circuit fails, distance protection will be disabled. As a substitute, phase overcurrent
protection and ground overcurrent protection will be enabled automatically, if selected, as backup
protection of distance protection.

3.12.2 Function Block Diagram

51PVT/51GVT

51PVT.Op

51GVT.Op

3.12.3 I/O Signals

Table 3.12-1 Configurable I/O signals of overcurrent protection for VT circuit failure

No. Output Signal Description


1 51PVT.Op Phase overcurrent protection for VT circuit failure operates.

PCS-902 Line Distance Relay 3-105


Date: 2011-07-06
3 Operation Theory

2 51GVT.Op Ground overcurrent protection for VT circuit failure operates.

3.12.4 Logic

SET 3I0>[51GVT.3I0_Set]
&
EN [51GVT.En] [51GVT.t_Op] 0ms 51GVT.Op

SIG FD.Pkp_ROC &

SIG VTS.Alm &


[51PVT.t_Op] 0ms 51PVT.Op
SET Max(Ia, Ib, Ic)>[51PVT.I_Set] &

EN [51PVT.En]

Figure 3.12-1 Logic diagram of overcurrent protection for VT circuit failure

3.12.5 Settings

Table 3.12-2 Settings of overcurrent protection for VT circuit failure

No. Name Range Step Unit Remark


Current setting of ground overcurrent
1 51GVT.3I0_Set (0.050~30.000)×In 0.001 A
protection when VT circuit failure
Time delay of ground overcurrent
2 51GVT.t_Op 0.000~10.000 0.001 s
protection when VT circuit failure
Enabling/disabling ground
overcurrent protection when VT circuit
3 51GVT.En 0 or 1 failure
0: disable
1: enable
Current setting of phase overcurrent
4 51PVT.I_Set (0.050~30.000)×In 0.001 A
protection when VT circuit failure
Time delay of phase overcurrent
5 51PVT.t_Op 0.000~10.000 0.001 s
protection when VT circuit failure
Enabling/disabling phase overcurrent
protection when VT circuit failure
6 51PVT.En 0 or 1
0: disable
1: enable

3.13 Residual Current SOTF Protection


3.13.1 General Application

When the circuit breaker is closed manually or automatically, it is possible to switch on to an


existing fault. This is especially critical if the line in the remote station is grounded, since earth fault
protection would not clear the fault until their time delays had elapsed. In this situation, however,

3-106 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

the fastest possible clearance is desired.

Residual current SOTF (switch onto fault) protection is a complementary function to earth fault
protection. With residual current SOTF protection, a fast trip is achieved for a fault on the line,
when the line is being energized. It shall be responsive to all types of earth faults anywhere within
the protected line, and it shall be enabled for a period of 400ms when the circuit is energized either
manually or via an auto-reclosing system.

3.13.2 Function Description

Residual current SOTF protection will operate to trip three-phase circuit breaker with a time delay
of 60ms when 1-pole auto-reclosing.

Residual current SOTF protection will operate to trip three-phase circuit breaker with a time delay of
100ms when 3-pole auto-reclosing or closing manually.

3.13.3 Function Block Diagram

50SOTF

50SOTF.En 50SOTF.Op

50SOTF.Blk

3.13.4 I/O Signals

Table 3.13-1 Configurable I/O signals of residual SOTF protection

No. Input Signal Description


Residual current SOTF protection enabling input, it can be a binary input or a logic
1 50SOTF.En
link.
Residual current SOTF protection blocking input, such as a function blocking
2 50SOTF.Blk
binary input.
No. Output Signal Description
1 50SOTF.Op Residual current SOTF protection operates.

PCS-902 Line Distance Relay 3-107


Date: 2011-07-06
3 Operation Theory

3.13.5 Logic

SIG 3-pole AR signal >=1


&
SIG Manual closing signal 100ms 0ms

SET 3I0>[50SOTF.3I0_Set] & >=1


50SOTF.Op
SIG 50SOTF.En &
& &
SIG 50SOTF.Blk 60ms 0ms

EN [50SOTF.En_3I0]

SIG FD.Pkp_ROC

SIG 1-pole AR signal

Figure 3.13-1 Logic diagram of residual current SOTF protection

3.13.6 Settings

Table 3.13-2 Settings of residual current SOTF protection

No. Name Range Step Unit Remark


Current setting of residual current
1 50SOTF.3I0_Set (0.050~30.000)×In 0.001 A
SOTF protection
Enabling/disabling residual current
SOTF protection
2 50SOTF.En_3I0 0 or 1
0: disable
1: enable

3.14 Voltage Protection


Voltage protection has the function of protecting device against undervoltage and overvoltage.
Both operational states are unfavorable as overvoltage may cause insulation breakdown while
undervoltage may cause stability problem. Each voltage protection function has two individual
stages with respective time delay. These voltage protection functions can be switched on or off
separately. Selectable definite-time characteristic and multiple inverse-time characteristics are
available.

3.14.1 Overvoltage Protection

3.14.1.1 General Application

Abnormal high voltages often occur e.g. in low loaded, long distance transmission lines, in
islanded systems when generator voltage regulation fails, or load rejection of a generator. Even if
compensation reactors are provided to avoid line overvoltage by compensation of the line
capacitance and thus reduction of the overvoltage, the overvoltage will endanger the insulation if
the reactors fail. The line must be de-energized within a very short time.

The overvoltage protection in this device detects the phase voltages Ua, Ub and Uc or the

3-108 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

phase-to-phase voltages Uab, Ubc and Uca with an option of any phase or all phases operation
for output. The overvoltage protection can be used for tripping purpose as well as to initiate
transfer trip, which selectable controlled by local circuit breaker.

3.14.1.2 Function Description

Phase overvoltage protection has following functions:

1. Two-stage phase overvoltage protection with independent logic, voltage and time delay
settings.

2. Stage 1 and stage 2 can be selected as definite-time or inverse-time characteristic. The

inverse-time characteristic is selectable, among IEC and ANSI/IEEE standard inverse-time

characteristics.

3. Phase voltage or phase-to-phase voltage can be selected for protection calculation.

4. “1-out-of-3” or “3-out-of-3” logic can be selected for protection criterion. (1-out-of-3 means any

of three phase voltages, 3-out-of-3 means all three phase voltages)

1. Operation Criterion

Users can select phase voltage or phase-to-phase voltage for the protection calculation. If setting
[59Px.Opt_Up/Upp] is set to “0”, phase voltage criterion is selected and if [59Px.Opt_Up/Upp] is
set to “1”, phase-to-phase voltage criterion is selected.

When phase voltage or phase-to-phase voltage is greater than any enabled stage voltage setting,
the stage protection picks up and operates after delay, which will drop off instantaneously when
fault voltage disappears.

 Phase voltage criterion

Two operation criteria of definite-time overvoltage protection are shown as follows, which of them
is applied depending on the logic setting [59Px.Opt_1P/3P].

UΦ_max>[ 59Px.U_Set] Equation 3.14-1

or

Ua>[59Px.U_Set] & Ub>[59Px.U_Set] & Uc>[59Px.U_Set] Equation 3.14-2

Where:

UΦ_max is the maximum value among three phase-voltage.

Ua, Ub, Uc are three phase voltages.

[59Px.U_Set] is the setting of stage x (x=1 or 2) overvoltage protection.

When [59Px.Opt_1P/3P] is set as “0”, “1-out-of-3” logic (Equation 3.14-1) is selected as operation
criterion, and when set as “1”, “3-out-of-3” logic (Equation 3.14-2) is selected.

PCS-902 Line Distance Relay 3-109


Date: 2011-07-06
3 Operation Theory

 Phase-to-phase voltage criterion

Two operation criteria of definite-time overvoltage protection are shown as follows, which of them
is applied depending on the logic setting [59Px.Opt_1P/3P].

UΦΦ_max>[ 59Px.U_Set] Equation 3.14-3

or

Uab>[59Px.U_Set] & Ubc>[59Px.U_Set] & Uca>[59Px.U_Set] Equation 3.14-4

[59Px.U_Set] is the setting of stage x (x =1 or 2) overvoltage protection.

When [59Px.Opt_1P/3P] is set as “0”, “1-out-of-3” logic (Equation 3.14-3) is selected as operation
criterion, and when set as “1”, “3-out-of-3” logic (Equation 3.14-4) is selected.

2. Characteristic Curve

Phase overvoltage protection stage 1 and stage 2 can be selected as definite-time or inverse-time
characteristic, and inverse-time operating time curve is as follows.

Where:

Uset is the voltage setting [59Px.U_Set] (x=1 or 2).

Tp is time multiplier setting [59Px.Opt_TMS].

K is a constant.

C is a constant.

α is a constant.

U is the measured voltage

For stage 1 and stage 2 of overvoltage protection, operating characteristic can be chosen from
definite-time characteristic and 12 inverse-time characteristics by setting the logic setting
[59Px.Opt_Curve] (x=1~12). The parameters of each characteristic are listed in the following table.

Table 3.14-1 Inverse-time curve parameters

51Px.Opt_Curve Time Characteristic K α C

0 Definite time

1 IEC Normal inverse 0.14 0.02 0

2 IEC Very inverse 13.5 1.0 0

3 IEC Extremely inverse 80.0 2.0 0

3-110 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

51Px.Opt_Curve Time Characteristic K α C

4 IEC Short-time inverse 0.05 0.04 0

5 IEC Long-time inverse 120.0 1.0 0

6 ANSI Extremely inverse 28.2 2.0 0.1217

7 ANSI Very inverse 19.61 2.0 0.491

8 ANSI Inverse 0.0086 0.02 0.0185

9 ANSI Moderately inverse 0.0515 0.02 0.114

10 ANSI Long-time extremely inverse 64.07 2.0 0.25

11 ANSI Long-time very inverse 28.55 2.0 0.712

12 ANSI Long-time inverse 0.086 0.02 0.185

When inverse-time characteristic is selected, if calculated operating time is less than setting
[59Px.tmin], then the operating time changes to the value of setting [59Px.tmin] automatically.

Define-time or inverse-time phase overvoltage protection drops off instantaneously when


measured voltage is lower than reset voltage.

3.14.1.3 Function Block Diagram

59Px

59Px.En1 59Px.St

59Px.En2 59Px.Op

59Px.Blk 59Px.InitTT

3.14.1.4 I/O Signals

Table 3.14-2 Configurable I/O signals of overvoltage protection

No. Input Signal Description


Stage x of overvoltage protection enabling input 1, it can be a binary input or a
1 59Px.En1
logic link.
Stage x of overvoltage protection enabling input 2, it can be a binary input or a
2 59Px.En2
logic link.
Stage x of overvoltage protection blocking input, such as a function blocking
3 59Px.Blk
binary input.
No. Output Signal Description
1 59P1.Op Stage 1 of overvoltage protection operates.
2 59P2.Op Stage 2 of overvoltage protection operates

PCS-902 Line Distance Relay 3-111


Date: 2011-07-06
3 Operation Theory

3 59P1.St Stage 1 of overvoltage protection starts.


4 59P2.St Stage 2 of overvoltage protection starts.
5 59P1.Op_InitTT Stage 1 of overvoltage protection operates to initiate transfer trip.
6 59P2.Op_InitTT Stage 2 of overvoltage protection operates to initiate transfer trip.

Table 3.14-3 Internal I/O signals of overvoltage protection

No. Input Signal Description


1 U3P Three-phase voltage input

3.14.1.5 Logic

EN [59Px.En_Alm]

EN [59Px.En]

[59Px.Opt_Up/Upp] Timer
EN & & t
>=1 t
&
SET UA>[59Px.U_Set] & &
>=1 [59Px.Alm]
&

SET UAB>[59Px.U_Set] &


[59Px.Op]
Timer
& & t
>=1 t
SET UB>[59Px.U_Set]

&

SET UBC>[59Px.U_Set]
>=1
Timer
& & t
&
>=1 t
SET UC>[59Px.U_Set]

&

SET UCA>[59Px.U_Set]
&
EN [59Px.Opt_1P/3P] >=1
[59Px.Op_InitTT]
BI [52b_PhA]
&
BI [52b_PhB]
&

BI [52b_PhC]

EN [59Px.En_52b_TT]

EN [59Px.En_TT]

Figure 3.14-1 Logic diagram of stage x of overvoltage protection

Where:

x=1, 2

3.14.1.6 Settings

Table 3.14-4 Settings of overvoltage protection

No. Name Range Step Unit Remark


Voltage setting for stage 1 of overvoltage
1 59P1.U_Set Un~2Unn 0.001 V
protection
Time delay for stage 1 of overvoltage
2 59P1.t_Op 0.000~30.000 0.001 s
protection

3-112 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Enabling/disabling stage 1 of overvoltage


protection
3 59P1.En 0 or 1
0: disable
1: enable
Option of 1-out-of-3 mode or 3-out-of-3
mode
4 59P1.Opt_1P/3P 0 or 1
0: 3-out-of-3 mode
1: 1-out-of-3 mode
Option of phase-to-phase voltage or phase
voltage
5 59P1.Opt_Up/Upp 0 or 1
0: phase voltage
1: phase-to-phase voltage
Enabling/disabling stage 1 of overvoltage
protection for alarm purpose
6 59P1.En_Alm 0 or 1
0: disable
1: enable
Enabling/disabling transfer trip controlled
by CB open position for stage 1 of
7 59P1.En_52b_TT 0 or 1 overvoltage protection
0: disable
1: enable
Enabling/disabling stage 1 of overvoltage
protection operate to initiate transfer trip
8 59P1.En_TT 0 or 1
0: disable
1: enable
Option of characteristic curve for stage 1 of
9 59P1.Opt_Curve 0~13
overvoltage protection
Time multiplier setting for stage 1 of
10 59P1.Opt_TMS 0.010~200.000 0.001
inverse-time overvoltage protection
Minimum delay for stage 1 of inverse-time
11 59P1.tmin 0.050~20.000 0.001 s
overvoltage protection
Voltage setting for stage 2 of overvoltage
12 59P2.U_Set Un~2Unn 0.001 V
protection
Time delay for stage 2 of overvoltage
13 59P2.t_Op 0.000~30.000 0.001 s
protection
Enabling/disabling stage 2 of overvoltage
protection
14 59P2.En 0 or 1
0: disable
1: enable
Option of 1-out-of-3 mode or 3-out-of-3
mode
15 59P2.Opt_1P/3P 0 or 1
0: 3-out-of-3 mode
1: 1-out-of-3 mode
16 59P2.Opt_Up/Upp 0 or 1 Option of phase-to-phase voltage or phase

PCS-902 Line Distance Relay 3-113


Date: 2011-07-06
3 Operation Theory

voltage
0: phase voltage
1: phase-to-phase voltage
Enabling/disabling stage 2 of overvoltage
protection for alarm purpose
17 59P2.En_Alm 0 or 1
0: disable
1: enable
Enabling/disabling transfer trip controlled
by CB open position for stage 2 of
18 59P2.En_52b_TT 0 or 1 overvoltage protection
0: disable
1: enable
Enabling/disabling stage 2 of overvoltage
protection operate to initiate transfer trip
19 59P2.En_TT 0 or 1
0: disable
1: enable
Option of characteristic curve for stage 2 of
20 59P2.Opt_Curve 0~12
overvoltage protection
Time multiplier setting for stage 2 of
21 59P2.Opt_TMS 0.010~200.000 0.001
inverse-time overvoltage protection
Minimum delay for stage 2 of inverse-time
22 59P2.tmin 0.050~20.000 0.001 s
overvoltage protection

3.14.2 Undervoltage Protection

3.14.2.1 General Application

The undervoltage protection can be applied to trip when fault occurs in a system. Two stages of
undervoltage protection are available measuring phase voltages UA, UB and UC or phase-to-phase
voltages UAB, UBC and UCA. The protection output can be selected for either any phase or all
phases operation. The undervoltage protection is normally used as decoupling system rather than
load shedding.

3.14.2.2 Function Description

Phase undervoltage protection has following functions:

1. Two-stage phase undervoltage protection with independent logic, voltage and time delay
settings.

2. Stage 1 and stage 2 can be selected as definite-time or inverse-time characteristic. The


inverse-time characteristic is selectable, among IEC and ANSI/IEEE standard inverse-time
characteristics.

3. Phase voltage or phase-to-phase voltage can be selected for protection calculation.

4. “1-out-of-3” or “3-out-of-3” logic can be selected for protection criterion. (1-out-of-3 means any
of three phase voltages, 3-out-of-3 means all three phase voltages)

3-114 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

1. Operation Criterion

Users can select phase voltage or phase-to-phase voltage for the protection calculation. If setting
[27Px.Opt_Up/Upp] is set to “0”, phase voltage criterion is selected and if [27Px.Opt_Up/Upp] is
set to “1”, phase-to-phase voltage criterion is selected.

When phase voltage or phase-to-phase voltage is less than any enabled stage voltage setting, the
stage protection picks up and operates after delay, which will drop off instantaneously when fault
voltage disappears.

 Phase voltage criterion

Two operation criteria of definite-time undervoltage protection are shown as follows, which of them
is applied depending on the logic setting [27Px.Opt_1P/3P].

UΦ_min<[ 27Px.U_Set] Equation 3.14-5

or

Ua<[ 27Px.U_Set] & Ub<[27Px.U_Set] & Uc<[27Px.U_Set] Equation 3.14-6

Where:

UΦ_min is the minimum value among three phase voltages.

Ua, Ub and Uc are three phase voltages.

[27Px.U_Set] is the setting of stage x (x=1 or 2) undervoltage protection.

When [27Px.Opt_1P/3P] is set as “0”, “1-out-of-3” logic (Equation 3.14-5) is selected as operation
criterion, and when set as “1”, “3-out-of-3” logic (Equation 3.14-6) is selected.

 Phase-to-phase voltage criterion

Two operation criteria of definite-time undervoltage protection are shown as follows, which of them
is applied depending on the logic setting [27Px.Opt_Up/Upp].

UΦΦ_min<[ 27Px.U_Set] Equation 3.14-7

or

Uab<[27Px.U_Set] & Ubc<[27Px.U_Set] & Uca<[27Px.U_Set] Equation 3.14-8

Where:

UΦΦ_min is the minimum value among three phase-to-phase voltages.

Uab, Ubc and Uca are three phase-to-phase voltages.

[27Px.U_Set] is the setting of stage x (x =1 or 2) undervoltage protection.

When the setting [27Px.Opt_1P/3P] is set as “0”, “1-out-of-3” logic (Equation 3.14-7) is selected as
operation criterion, and when it is set as “1”, “3-out-of-3” logic (Equation 3.14-8) is selected.

2. Characteristic Curve

Undervoltage protection stage 1 and stage 2 can be selected as definite-time or inverse-time

PCS-902 Line Distance Relay 3-115


Date: 2011-07-06
3 Operation Theory

characteristic, and inverse-time operating time curve is as follows.

Where:

Uset is the setting [27Px.U_Set] (x=1 or 2).

Tp is time multiplier setting [27Px.Opt_TMS].

K is a constant.

C is a constant.

α is a constant.

U is the measured voltage

For stage 1 and stage 2 of undervoltage protection, operating characteristic can be chosen from
definite-time characteristic and twelve inverse-time characteristics by setting the logic setting
[27Px.Opt_Curve] (x=1~12). The parameters of each characteristic are listed in the following table.

Table 3.14-5 Inverse-time curve parameters of phase undervoltage protection

27Px.Opt_Curve Time Characteristic K α C

0 Definite time

1 IEC Normal inverse 0.14 0.02 0

2 IEC Very inverse 13.5 1.0 0

3 IEC Extremely inverse 80.0 2.0 0

4 IEC Short-time inverse 0.05 0.04 0

5 IEC Long-time inverse 120.0 1.0 0

6 ANSI Extremely inverse 28.2 2.0 0.1217

7 ANSI Very inverse 19.61 2.0 0.491

8 ANSI Inverse 0.0086 0.02 0.0185

9 ANSI Moderately inverse 0.0515 0.02 0.114

10 ANSI Long-time extremely inverse 64.07 2.0 0.25

11 ANSI Long-time very inverse 28.55 2.0 0.712

12 ANSI Long-time inverse 0.086 0.02 0.185

When inverse-time characteristic is selected, if calculated operating time is less than setting

3-116 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

[27Px.tmin], then the operating time changes to the value of setting [27Px.tmin] automatically.

Define-time or inverse-time phase under voltage protection drops off instantaneously when
measured voltage is higher than reset voltage.

3.14.2.3 Function Block Diagram

27Px

27Px.En1 27Px.St

27Px.En2 27Px.Op

27Px.Blk 27Px.InitTT

3.14.2.4 I/O Signals

Table 3.14-6 Configurable I/O signals of undervoltage protection

No. Input Signal Description


Stage x of undervoltage protection enabling input 1, it can be a binary input or a
1 27Px.En1
logic link.
Stage x of undervoltage protection enabling input 2, it can be a binary input or a
2 27Px.En2
logic link.
Stage x of undervoltage protection blocking input, such as a function blocking
3 27Px.Blk
binary input.
No. Output Signal Description
1 27P1.Op Stage 1 of undervoltage protection operates.
2 27P2.Op Stage 2 of undervoltage protection operates
3 27P1.St Stage 1 of undervoltage protection starts.
4 27P2.St Stage 2 of undervoltage protection starts.
5 27P1.Op_InitTT Stage 1 of undervoltage protection operates to initiate transfer trip.
6 27P2.Op_InitTT Stage 2 of undervoltage protection operates to initiate transfer trip.

Table 3.14-7 Internal I/O signals of undervoltage protection

No. Input Signal Description


1 U3P Three-phase voltage input

3.14.2.5 Logic

When FD element reflecting current operates, including DPFC current element and residual
current element, the undervoltage protection is released for operation.

When any of the following conditions is fulfilled, the undervoltage protection will be blocked.

1. VT signal fails;if the voltage comes from busbar VT, the voltage will restore to the normal
immediately after the fault being cleared away. However, if the voltage comes from line VT,
the voltage will drop to zero immediately after the fault is cleared. The undervoltage protection

PCS-902 Line Distance Relay 3-117


Date: 2011-07-06
3 Operation Theory

will be continuously in operation, thus an auxiliary current criterion is provided to solve it.
(Input 1)

2. Any phase is out of service, i.e. Up<0.01Un and IP<0.06In. (Input 2)

3. Binary input of blocking undervoltage is energized, such as normally closed contact of line
disconnector. (Input 3)

4. Any phase of circuit breaker is open (binary input of normal close contact of breaker is
energized) and the corresponding phase current is smaller than 0.06In. (Input 4)

SIG Input 1 20ms 100ms

SIG Input 2 >=1


Block UV
SIG Input 3

SIG Input 4

Figure 3.14-2 Blocking logic of undervoltage protection

EN [27Px.En_Alm]

EN [27Px.En]

SIG Block UV

SET [27Px.Opt_Up/Upp] & & Timer


t
>=1 &
t
SET UA<[27Px.U_Set] &

&
&
SET UAB<[27Px.U_Set] [27Px.Op]

& & Timer


t
>=1
t
SET UB<[27Px.U_Set] &
[27Px.Alm]
&

SET UBC<[27Px.U_Set]
>=1
& & Timer
t
>=1
t
SET UC<[27Px.U_Set]

&
>=1
&
SET UCA<[27Px.U_Set]

SET [27Px.Opt_Up/Upp]

Figure 3.14-3 Logic diagram of stage x of undervoltage protection

Where:

x=1, 2

3-118 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.14.2.6 Settings

Table 3.14-8 Settings of undervoltage protection

No. Name Range Step Unit Remark


Voltage setting for stage 1 of undervoltage
1 27P1.U_Set 0~Unn 0.001 V
protection
Time delay for stage 1 of undervoltage
2 27P1.t_Op 0.000~30.000 0.001 s
protection
Enabling/disabling stage 1 of undervoltage
protection
3 27P1.En 0 or 1
0: disable
1: enable
Option of 1-out-of-3 mode or 3-out-of-3
mode
4 27P1.Opt_1P/3P 0 or 1
0: 3-out-of-3 mode
1: 1-out-of-3 mode
Option of voltage criterion adopting
phase-to-phase voltage or phase voltage
5 27P1.Opt_Up/Upp 0 or 1
0: phase voltage
1: phase-to-phase voltage
Enabling/disabling stage 1 of undervoltage
protection operate to alarm
6 27P1.En_Alm 0 or 1
0: disable
1: enable
Option of characteristic curve for stage 1
7 27P1.Opt_Curve 0~13 1
of undervoltage protection
Time multiplier setting for stage 1 of
8 27P1.Opt_TMS 0.010~200.000 0.001
inverse-time undervoltage protection
Minimum delay for stage 1 of inverse-time
9 27P1.tmin 0.050~20.000 0.001 s
undervoltage protection
Voltage setting for stage 2 of undervoltage
10 27P2.U_Set 0~Unn 0.001 V
protection
Time delay for stage 2 of undervoltage
11 27P2.t_Op 0.000~30.000 0.001 s
protection
Enabling/disabling stage 2 of undervoltage
protection
12 27P2.En 0 or 1
0: disable
1: enable
Option of 1-out-of-3 mode or 3-out-of-3
mode
13 27P2.Opt_1P/3P 0 or 1
0: 3-out-of-3 mode
1: 1-out-of-3 mode
Option of voltage criterion adopting
14 27P2.Opt_Up/Upp 0 or 1
phase-to-phase voltage or phase voltage

PCS-902 Line Distance Relay 3-119


Date: 2011-07-06
3 Operation Theory

0: phase voltage
1: phase-to-phase voltage
Enabling/disabling stage 2 of undervoltage
protection operate to alarm
15 27P2.En_Alm 0 or 1
0: disable
1: enable
Option of characteristic curve for stage 2
16 27P2.Opt_Curve 0~12 1
of undervoltage protection
Time multiplier setting for stage 2 of
17 27P2.Opt_TMS 0.010~200.000 0.001
inverse-time undervoltage protection
Minimum delay for stage 2 of inverse-time
18 27P2.tmin 0.050~20.000 0.001 s
undervoltage protection

3.15 Frequency Protection


3.15.1 Overfrequency Protection

3.15.1.1 General Application

In the power system, when the increase in frequency is caused by the excess active power,
according to the rise value of system frequency, overfrequency protection will automatically
remove a part of generator-transformer unit from the power plant so as to re-balance between
active power output of power system and the load.

3.15.1.2 Function Description

Overfrequency protection consists of the four stages (stage 1 to stage 4). When system frequency
reaches to 50.5Hz, overfrequency protection will put into service. If system frequency continually
increases and is greater than the setting [81O1.f_Set], stage 1 of overfrequency protection will
operate to remove a part of generator-transformer unit with the time delay [81O1.t_Op]. After that,
overfrequency protection will drop out if system frequency restore below 50.5Hz. By contrast,
system frequency still increases after stage 1 of overfrequency protection operates, stage 2 and 3
will operate in succession until system frequency restore below 50.5Hz when corresponding
operating conditions is met.

However, stage 4, as a special stage, will operate with the time delay [81O4.t_Op] if system
frequency is greater than the setting [81O4.f_Set].

In order to prevent overfrequency protection from undesired trip due to some abnormal conditions,
such as, load infeed, higher harmonic, VT circuit failure and so on. Overfrequency protection will
be blocked by the following conditions.

1. Under voltage condition

When positive-sequence voltage is smaller than 0.15Un, overfrequency protection will be blocked

2. Frequency abnormality condition

When f<40Hz or f>65Hz, overfrequency protection will be blocked

3-120 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.15.1.3 Function Block Diagram

81Ox

81Ox.En1 81Ox.St

81Ox.En2 81Ox.Op

81Ox.Blk

3.15.1.4 I/O Signals

Table 3.15-1 Configurable I/O signals of overfrequency protection

No. Input Signal Description


Stage x of overfrequency protection enabling input 1, it can be a binary input or a
1 81Ox.En1
logic link.
Stage x of overfrequency protection enabling input 2, it can be a binary input or a
2 81Ox.En2
logic link.
Stage x of overfrequency protection blocking input, such as a function blocking
3 81Ox.Blk
binary input.
No. Output Signal Description
1 80O1.Op Stage 1 of overfrequency protection operates.
2 80O2.Op Stage 2 of overfrequency protection operates.
3 80O3.Op Stage 3 of overfrequency protection operates.
4 80O4.Op Stage 4 of overfrequency protection operates.
5 80O1.St Stage 1 of overfrequency protection starts.
6 80O2.St Stage 2 of overfrequency protection starts.
7 80O3.St Stage 3 of overfrequency protection starts.
8 80O4.St Stage 4 of overfrequency protection starts.

Table 3.15-2 Internal I/O signals of overfrequency protection

No. Input Signal Description


1 U3P Three-phase voltage input

PCS-902 Line Distance Relay 3-121


Date: 2011-07-06
3 Operation Theory

3.15.1.5 Logic

EN [81Ox.En]
&
SIG 81Ox.En1 Enable 81Ox

SIG 81Ox.En2

SIG 81Ox.Blk
>=1
OTH U1<0.15Un Block 81Ox

SIG f<40Hz or f>65Hz

SIG Enable 81Ox &

SIG Block 81Ox &

SIG f>50.5Hz 50ms 0ms 81Ox.St


&
SET f>[81Ox.f_Set] [81Ux.t_Op] 0ms 81Ox.Op

EN [81Ox.En]

Figure 3.15-1 Logic diagram of stage x of overfrequency protection

3.15.1.6 Settings

Table 3.15-3 Settings of overfrequency protection

No. Name Range Step Unit Remark


Frequency setting for stage 1 of overfrequency
1 81O1.f_Set 50.00~65.00 0.01 Hz
protection
Time delay for stage 1 of overfrequency
2 81O1.t_Op 0.000~100.000 0.001 s
protection
Frequency setting for stage 2 of overfrequency
3 81O2.f_Set 50.00~65.00 0.01 Hz
protection
Time delay for stage 2 of overfrequency
4 81O2.t_Op 0.000~100.000 0.001 s
protection
Frequency setting for stage 3 of overfrequency
5 81O3.f_Set 50.00~65.00 0.01 Hz
protection
Time delay for stage 3 of overfrequency
6 81O3.t_Op 0.000~100.000 0.001 s
protection
Frequency setting for stage 4 of overfrequency
7 81O4.f_Set 50.00~65.00 0.01 Hz
protection
Time delay for stage 4 of overfrequency
8 81O4.t_Op 0.000~100.000 0.001 s
protection
Enabling/disabling stage 1 of overfrequency
protection
9 81O1.En 0 or 1
0: disable
1: enable

3-122 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Enabling/disabling stage 2 of overfrequency


protection
10 81O2.En 0 or 1
0: disable
1: enable
Enabling/disabling stage 3 of overfrequency
protection
11 81O3.En 0 or 1
0: disable
1: enable
Enabling/disabling stage 4 of overfrequency
protection
12 81O4.En 0 or 1
0: disable
1: enable

3.15.2 Underfrequency Protection

3.15.2.1 General Application

In the power system, when the decrease in frequency is caused by the shortfall of active power
due to the increase of active-power load, according to the reduction value of system frequency,
underfrequency protection will automatically remove a part of load so as to re-balance between
system power supply and the load.

3.15.2.2 Function Description

Underfrequency protection consists of the four stages (stage 1 to stage 4). When system
frequency reaches to 49.5Hz, underfrequency protection will put into service. If system frequency
continually decreases and is smaller than the setting [81U1.f_Set], stage 1 of under-frequency
protection will operate to remove a part of load with the time delay [81U1.t_Op]. After that,
under-frequency protection will drop out if system frequency restore above 49.5Hz. By contrast,
system frequency still decreases after stage 1 of underfrequency protection operates, stage 2 and
3 will operate in succession until system frequency restore above 49.5Hz when corresponding
operating conditions is met.

However, stage 4, as a special stage, will operate with the time delay [81U4.t_Op] if system
frequency is smaller than the setting [81U4.f_Set].

In order to prevent under-frequency protection from undesired trip due to some abnormal
conditions, such as, load infeed, higher harmonic, VT circuit failure and so on. Underfrequency
protection will be blocked by the following conditions.

1. Undervoltage condition

When positive-sequence voltage is smaller than 0.15Un, underfrequency protection will be


blocked

2. Frequency slip condition

When -df/dt is greater the setting [81U.df/dt_Blk], underfrequency protection will be blocked. After
system frequency restore above 49.5Hz, the blocking will be released automatically.

PCS-902 Line Distance Relay 3-123


Date: 2011-07-06
3 Operation Theory

3. Frequency abnormality condition

When f<40Hz or f>65Hz, underfrequency protection will be blocked

3.15.2.3 Function Block Diagram

81Ux

81Ux.En1 81Ux.St

81Ux.En2 81Ux.Op

81Ux.Blk

3.15.2.4 I/O Signals

Table 3.15-4 Configurable I/O signals of underfrequency protection

No. Input Signal Description


Stage x of underfrequency protection enabling input 1, it can be a binary input or a
1 81Ux.En1
logic link.
Stage x of underfrequency protection enabling input 2, it can be a binary input or a
2 81Ux.En2
logic link.
Stage x of underfrequency protection blocking input, such as a function blocking
3 81Ux.Blk
binary input.
No. Output Signal Description
1 80U1.Op Stage 1 of underfrequency protection operates.
2 80U2.Op Stage 2 of underfrequency protection operates.
3 80U3.Op Stage 3 of underfrequency protection operates.
4 80U4.Op Stage 4 of underfrequency protection operates.
5 80U1.St Stage 1 of underfrequency protection starts.
6 80U2.St Stage 2 of underfrequency protection starts.
7 80U3.St Stage 3 of underfrequency protection starts.
8 80U4.St Stage 4 of underfrequency protection starts.

Table 3.15-5 Internal I/O signals of underfrequency protection

No. Input Signal Description


1 U3P Three-phase voltage input

3-124 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.15.2.5 Logic

EN [81Ux.En]
&
SIG 81Ux.En1 Enable 81Ux

SIG 81Ux.En2

SIG 81Ux.Blk >=1


Block 81Ux
OTH U1<0.15Un
>=1
SET -df/dt>[81U.df/dt_Blk]

SIG f<40Hz or f>65Hz

SIG Enable 81Ux &

SIG Block 81Ux &

SIG f<49.5Hz 50ms 0ms 81Ux.St


&
SET f<[81Ux.f_Set] [81Ux.t_Op] 0ms 81Ux.Op

EN [81Ux.En]

Figure 3.15-2 Logic diagram of stage x of underfrequency protection

3.15.2.6 Settings

Table 3.15-6 Settings of overfrequency protection

No. Name Range Step Unit Remark


Frequency setting for stage 1 of
1 81U1.f_Set 40.00~50.00 0.01 Hz
underfrequency protection
Time delay for stage 1 of underfrequency
2 81U1.t_Op 0.000~100.000 0.001 s
protection
Frequency setting for stage 2 of
3 81U2.f_Set 40.00~50.00 0.01 Hz
underfrequency protection
Time delay for stage 2 of underfrequency
4 81U2.t_Op 0.000~100.000 0.001 s
protection
Frequency setting for stage 3 of
5 81U3.f_Set 40.00~50.00 0.01 Hz
underfrequency protection
Time delay for stage 3 of underfrequency
6 81U3.t_Op 0.000~100.000 0.001 s
protection
Frequency setting for stage 4 of
7 81U4.f_Set 40.00~50.00 0.01 Hz
underfrequency protection
Time delay for stage 4 of underfrequency
8 81U4.t_Op 0.000~100.000 0.001 s
protection
Rate of frequency change for blocking
9 81U.df/dt_Blk 0.20~20.00 0.01 Hz/s
underfrequency protection
10 81U1.En 0 or 1 Enabling/disabling stage 1 of underfrequency

PCS-902 Line Distance Relay 3-125


Date: 2011-07-06
3 Operation Theory

protection
0: disable
1: enable
Enabling/disabling stage 2 of underfrequency
protection
11 81U2.En 0 or 1
0: disable
1: enable
Enabling/disabling stage 3 of underfrequency
protection
12 81U3.En 0 or 1
0: disable
1: enable
Enabling/disabling stage 4 of underfrequency
protection
13 81U4.En 0 or 1
0: disable
1: enable

3.16 Breaker Failure Protection


3.16.1 General Application

Duplicated protection configurations are usually adopted for EHV power system, but the primary
equipment, circuit breaker, is not duplicated. Breaker failure protection is adopted to cater circuit
breaker tripping failure.

Breaker failure protection issues a back-up trip command to trip adjacent circuit breakers in case
of a tripping failure of the circuit breaker, and clears the fault as requested by the device. To utilize
the protection information of faulty equipment and the electrical information of failure circuit
breaker to constitute the criterion of breaker failure protection, it can ensure that the adjacent
circuit breakers of failure circuit breaker are tripped with a shorter time delay, so that the affected
area is minimized, and ensure stable operation of the entire power grid to prevent generators,
transformers and other components from seriously damaged.

3.16.2 Function Description

The instantaneous re-tripping function, after receiving tripping signal from other device and the
corresponding phase overcurrent element operating, is available and provides phase-segregated
binary output contact, which can ensure the circuit breaker is still tripped in case the secondary
circuit between the device and the circuit breaker is abnormal, to avoid undesired tripping of
breaker failure protection and the expansion of the affected area. Instantaneous re-tripping
function does not block AR.

When both the phase-segregated tripping contact from line protection and the corresponding
phase overcurrent element operate, or both the three-phase tripping contact and any phase
overcurrent element operate, breaker failure protection will send three-phase tripping command to
trip local circuit breaker after time delay of [50BF.t1_Op] and trip all adjacent circuit breakers after
time delay of [50BF.t2_Op].

3-126 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

When the protection element except undervoltage element within this device operates and issues
tripping signal, breaker failure protection will also be initiated.

Taking into account that the faulty current is too small for generator or transformer fault, the
sensitivity of phase current element may not meet the requirements, zero-sequence current
criterion and negative-sequence current criterion are provided in addition to the phase overcurrent
element for breaker failure protection initiated by input signal [50BF.ExTrp3P_GT] from generator
and transformer protection. They can be enabled or disabled by logic settings [50BF.En_3I0_3P]
and [50BF.En_I2_3P] respectively.

For some special fault (for example, mechanical protection or overvoltage protection operating),
maybe faulty current is very small and current criterion of breaker failure protection is not met, in
order to make breaker failure protection can also operate under the above situation, an input
signal [50BF.ExTrp_WOI] is equipped to initiate breaker failure protection, once the input signal is
energized, normally closed auxiliary contact of circuit breaker is chosen in addition to breaker
failure current check to trigger breaker failure timer. The device takes current as priority with CB
auxiliary contact (52b) as an option criterion for breaker failure check.

3.16.3 Function Block Diagram

50BF

50BF.ExTrp3P_L 50BF.Op_ReTrpA

50BF.ExTrp3P_GT 50BF.Op_ReTrpB

50BF.Op_ReTrpC

50BF.Op_ReTrp3P

50BF.Op_t1

50BF.Op_t2

3.16.4 I/O Signals

Table 3.16-1 Configurable I/O signals of breaker failure protection

No. Input Signal Description


1 50BF.ExTrp3P_L Input signal of three-phase tripping contact from line protection
Input signal of three-phase tripping contact from generator or transformer
2 50BF.ExTrp3P_GT
protection
No. Output Signal Description
1 50BF.Op_ReTrpA Breaker failure protection operates to re-trip phase-A circuit breaker
2 50BF.Op_ReTrpB Breaker failure protection operates to re-trip phase-B circuit breaker
3 50BF.Op_ReTrpC Breaker failure protection operates to re-trip phase-C circuit breaker
4 50BF.Op_ReTrp3P Breaker failure protection operates to re-trip three-phase circuit breaker
5 50BF.Op_t1 Stage 1 breaker failure protection operates
6 50BF.Op_t2 Stage 2 breaker failure protection operates

PCS-902 Line Distance Relay 3-127


Date: 2011-07-06
3 Operation Theory

Table 3.16-2 Internal I/O signals of breaker failure protection

No. Input Signal Description


1 50BF.ExTrpA Input signal of phase-A tripping contact from external device
2 50BF.ExTrpB Input signal of phase-B tripping contact from external device
3 50BF.ExTrpC Input signal of phase-C tripping contact from external device
Input signal of three-phase tripping contact from external device. Once it is
4 50BF.ExTrp_WOI energized, normally closed auxiliary contact of circuit breaker is chosen in
addition to breaker failure current check to trigger breaker failure timers.

3.16.5 Logic

EN [50BF.En] &

EN [50BF.En_ReTrip]

EN [50BF.En_3I0_1P] >=1

SET 3I0>[50BF.3I0_Set]

SIG BFI_A >=1 & &


>=1 [50.BF.t_Retrp] 0ms [50BF.Op_ReTrpA]
BI [50BF.ExTrpA]

SET IA>[50BF.I_Set]

SIG BFI_B >=1 & &


>=1 [50.BF.t_Retrp] 0ms [50BF.Op_ReTrpB]
BI [50BF.ExTrpB]

SET IB>[50BF.I_Set]

SIG BFI_C >=1 & &


>=1 [50.BF.t_Retrp] 0ms [50BF.Op_ReTrpC]
BI [50BF.ExTrpC] >=1

SET IC>[50BF.I_Set] >=1

SIG BFI_3P >=1


&
BI [50BF.ExTrp3P_L] & [50BF.Op_ReTrp3P]
>=1
BI [50BF.ExTrp3P_GT] >=1

BI [50BF.ExTrp_WOI]
&
EN [En_ROC_3P_BFP] &
>=1
>=1
SET 3I0>[50BF.3I0_Set]
&
EN [50BF.En_I2_3P] &

SET I2>[50BF.I2_Set]
& [50BF.t1_Op] 0ms [50BF.Op_t1]
EN [50BF.En_CB_Ctrl] &
[50BF.t2_Op] 0ms [50BF.Op_t2]
BI [52b_PhA]
&
BI [52b_PhB]

BI [52b_PhC]

EN [50BF.En]

Figure 3.16-1 Logic diagram of breaker failure protection

3-128 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.16.6 Settings

Table 3.16-3 Settings of breaker failure protection

No. Name Range Step Unit Remark


Current setting of phase current
1 50BF.I_Set (0.050~30.000 )×In 0.001 A
criterion for BFP
Current setting of zero-sequence
2 50BF.3I0_Set (0.050~30.000 )×In 0.001 A
current criterion for BFP
Current setting of
3 50BF.I2_Set (0.050~30.000 )×In 0.001 A negative-sequence current
criterion for BFP
4 50BF.t_ReTrp 0.000~10.000 0.001 s Time delay of re-tripping for BFP

5 50BF.t1_Op 0.000~10.000 0.001 s Time delay of stage 1 for BFP

6 50BF.t2_Op 0.000~10.000 0.001 s Time delay of stage 2 for BFP


Enabling/disabling breaker failure
protection
7 50BF.En 0 or 1
0: disable
1: enable
Enabling/disabling re-trip function
for BFP
8 50BF.En_ReTrip 0 or 1
0: disable
1: enable
Enabling/disabling zero-sequence
current criterion for BFP initiated by
9 50BF.En_3I0_1P 0 or 1 single-phase tripping contact
0: disable
1: enable
Enabling/disabling zero-sequence
current criterion for BFP initiated by
10 50BF.En_3I0_3P 0 or 1 three-phase tripping contact
0: disable
1: enable
Enabling/disabling
negative-sequence current criterion
for BFP initiated by three-phase
11 50BF.En_I2_3P 0 or 1
tripping contact
0: disable
1: enable
Enabling/disabling breaker failure
protection can be initiated by
normally closed contact of circuit
12 50BF.En_CB_Ctrl 0 or 1
breaker
0: disable
1: enable

3.17 Thermal Overload Protection


3.17.1 General Application

During overload operation of a transmission line (specially for cable), great current results in

PCS-902 Line Distance Relay 3-129


Date: 2011-07-06
3 Operation Theory

greater heat to lead temperature increase and if the temperature reaches too high values the
equipment might be damaged.

Thermal overload protection estimates the internal heat content (temperature) continuously. This
estimation is made by using a thermal model with two time constants, which is based on current
measurement.

When the temperature increases to the alarm value, the protection issues alarm signals to remind
the operator for attention, and if the temperature continues to increase to the trip value, the
protection sends trip command to disconnect the protected line.

3.17.2 Function Description

Thermal overload protection has following functions:

 Thermal time characteristic adopting IEC 60255-8

 Two stages for alarm purpose and two stages for trip purpose

 Thermal accumulation can be cleared by external input signal

The device provides a thermal overload model which is based on the IEC60255-8 standard. The
thermal overload formulas are shown as below.

1. Criterion of cooling start characteristic:

I2
T    ln 2
I  (k  I B ) 2

2. Criterion of hot start characteristic:

I 2  I p2
T    ln
I 2  (k  I B ) 2

Where:

T = Time to operate (in seconds)

 = Thermal time constant of the equipment to be protected, the setting [49.Tau]


IB = Full load current rating, the setting [49.Ib_Set]

I = The RMS value of the largest phase current

IP = Steady state pre-loading before application of the overload

k = Factor associated to the thermal state formula, the setting [49.K]

ln = Natural logarithm

The characteristic curve of thermal overload model is shown in Figure 3.17-1.

3-130 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

t Refer to IEC60255-8

Ip
P=—
IB

P = 0.0
P = 0.6
P = 0.8
P = 0.9

kIB I

Figure 3.17-1 Characteristic curve of the thermal overload model

The hot start characteristic is adopted in the device. The calculation is carried out at zero of Ip, so
users need not to set the value of Ip.

Tripping outputs of the protection is controlled by current, even if the thermal accumulation value is
greater than the setting for tripping, the protection drops off instantaneously when current
disappears. Alarm outputs of the protection is not controlled by current, and only if the thermal
accumulation value is greater than the setting for alarm, alarm output contacts, which can be
connected to block the auto-reclosure, will operate.

3.17.3 Function Block Diagram

49

49.Clr 49.St

49.En 49-1.Alm

49.Blk 49-1.Op

49-2.Alm

49-2.Op

3.17.4 I/O Signals

Table 3.17-1 Configurable I/O signals of thermal overload protection

No. Input Signal Description


1 49.Clr Input signal of clear thermal accumulation value
Thermal overload protection enabling input, it can be a binary input or a logic
2 49.En
link.
Thermal overload protection blocking input, such as a function blocking binary
3 49.Blk
input.
No. Output Signal Description

PCS-902 Line Distance Relay 3-131


Date: 2011-07-06
3 Operation Theory

1 49.St Thermal overload protection starts.


2 49-1.Op Stage 1 of thermal overload protection operates to trip.
3 49-2.Op Stage 2 of thermal overload protection operates to trip.
4 49-1.Alm Stage 1 of thermal overload protection operates to alarm.
5 49-2.Alm Stage 2 of thermal overload protection operates to alarm.

Table 3.17-2 Internal I/O signals of thermal overload protection

No. Input Signal Description


1 I3P Three-phase current input

3.17.5 Logic

SIG [49.Blk] &

SIG [49.En]
&
SIG [49.I3P] 49.St

SET [49.Ib_Set]
& Timer
t
49-x.Op
t
EN [49-x.En_Trp]

& Timer
t
49-x.Alm
t
EN [49-x.En_Alm]

BI [49.Clr]

Figure 3.17-2 Logic diagram of thermal overload protection

Where:

x can be 1 or 2

3.17.6 Settings

Table 3.17-3 Settings of thermal overload protection

No. Name Range Step Unit Remark


The factor setting for stage 1 of
thermal overload protection which
1 49-1.K 1.000~3.000 0.001 %
is associated to the thermal state
formula
The factor setting for stage 2 of
thermal overload protection which
2 49-2.K 1.000~3.000 0.001 %
is associated to the thermal state
formula
The reference current setting of the
3 49.Ib_Set (0.050~30.000 )×In 0.001 A
thermal overload protection
4 49.Tau 0.100~100.000 0.001 min The time constant setting of the

3-132 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

IDMT overload protection


Enabling/disabling stage 1 of
thermal overload protection for
5 49-1.En_Alm 0 or 1 alarm purpose
0: disable
1: enable
Enabling/disabling stage 1 of
thermal overload protection for trip
6 49-1.En_Trp 0 or 1 purpose
0: disable
1: enable
Enabling/disabling stage 2 of
thermal overload protection for
7 49-2.En_Alm 0 or 1 alarm purpose
0: disable
1: enable
Enabling/disabling stage 2 of
thermal overload protection for trip
8 49-2.En_Trp 0 or 1 purpose
0: disable
1: enable

3.18 Stub Overcurrent Protection


3.18.1 General Application

Stub overcurrent protection is mainly designed for one and a half breakers arrangement. When
line disconnector is open and transmission line is put into maintenance, line VT is no voltage.
Distance protection is disabled, and stub overcurrent protection is enabled. It is used to protect
stub section among for two circuit breakers and line disconnector. Usually, stub overcurrent
protection is enabled automatically by normally closed auxiliary contact of line disconnector.

CT1 CT2

Bus Bus

To the device

Line Line

Figure 3.18-1 3/2 breakers arrangement

PCS-902 Line Distance Relay 3-133


Date: 2011-07-06
3 Operation Theory

3.18.2 Function Block Diagram

50STB

50STB.In_En 50STB.Op

50STB.Blk

3.18.3 I/O Signals

Table 3.18-1 Configurable I/O signals of stub overcurrent protection

No. Input Signal Description


1 50STB.In_En Stub overcurrent protection enabling input, it can be a binary input or a logic link.
Stub overcurrent protection blocking input, such as a function blocking binary
2 50STB.Blk
input.
No. Output Signal Description
1 50STB.Op Stub overcurrent protection operates.

3.18.4 Logic

Only one stage is available to stub overcurrent protection. Based on calculating summation
current from dual CTs, the logic scheme of stub overcurrent protection is shown as Figure 3.18-2.

SIG 50STB.In_En &


&
SIG 50STB.Blk &
[50STB.t_Op] 50STB.Op
SET Ia>[50STB.I_Set]
>=1
SET Ib>[50STB.I_Set]

SET Ic>[50STB.I_Set]

EN [50STB.En]

Figure 3.18-2 Logic diagram of stub overcurrent protection

3.18.5 Settings

Table 3.18-2 Settings of stub overcurrent protection

No. Name Range Step Unit Remark


Current setting of stub overcurrent
1 50STB.I_Set (0.050~30.000)×In 0.001 A
protection
Time delay of stub overcurrent
2 50STB.t_Op 0.000~10.000 0.001 s
protection

3-134 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Enabling/disabling stub overcurrent


protection
3 50STB.En 0 or 1
1: enable
0: disable

3.19 Pole Discrepancy Protection


3.19.1 General Application

The pole discrepancy of circuit breaker may occur during operation of a breaker with segregated
operating gears for the three phases. The reason could be an interruption in the tripping/closing
circuits, or mechanical failure. A pole discrepancy can only be tolerated for a limited period. When
there is loading, zero-sequence or negative-sequence current will be generated in the power
system, which will result in overheat of the generator or the motor. With the load current increasing,
overcurrent elements based on zero-sequence current or negative-sequence current may operate.
Pole discrepancy protection is required to operate before the operation of these overcurrent
elements.

3.19.2 Function Description

Pole discrepancy protection determines three-phase breaker pole discrepancy condition by its
phase segregated CB auxiliary contacts. In order to improve the reliability of pole discrepancy
protection, the asymmetrical current component can be selected as addition criteria when needed.

3.19.3 Function Block Diagram

62PD

62PD.En1 62PD.Op

62PD.En2

62PD.Blk

3.19.4 I/O Signals

Table 3.19-1 Configurable I/O signals of pole discrepancy protection

No. Input Signal Description


Pole discrepancy protection enabling input 1, it can be a binary input or a logic
1 62PD.En1
link.
Pole discrepancy protection enabling input 2, it can be a binary input or a logic
2 62PD.En2
link.
Pole discrepancy protection blocking input, such as a function blocking binary
3 62PD.Blk
input.
No. Output Signal Description
1 62PD.Op Pole discrepancy protection operates to trip

PCS-902 Line Distance Relay 3-135


Date: 2011-07-06
3 Operation Theory

Table 3.19-2 Internal I/O signals of pole discrepancy protection

No. Input Signal Description


1 I3P Three-phase current input
2 62PD.In_PD Pole discrepancy binary input

3.19.5 Logic

Pole discrepancy protection can be initiated by two methods.

1. Initiation method 1

It uses combination of circuit breaker normally closed and normally open auxiliary contacts to
initiate pole discrepancy protection, i.e. the binary input [62PD.In_PD] and its connection is shown
as below.

DC+
52b_PhA 52a_PhA

52b_PhB 52a_PhB
Binary input
52b_PhC 52a_PhC 62PD.In_PD

Figure 3.19-1 Pole discrepancy

Where:

52b_PhA: normally closed CB auxiliary contact of phase A

52b_PhB: normally closed CB auxiliary contact of phase B

52b_PhC: normally closed CB auxiliary contact of phase C

52a_PhA: normally open CB auxiliary contact of phase A

52a_PhB: normally open CB auxiliary contact of phase B

52a_PhC: normally open CB auxiliary contact of phase C

2. Initiation method 2

Phase-segregated circuit breaker auxiliary contacts are connected to the device. When the state
of three phase-segregated circuit breaker auxiliary contacts are inconsistent, pole discrepancy
protection will be started and initiate output after a time delay [62PD.t_Op].

Pole discrepancy protection can be blocked by external input signal [62PD.Blk]. In general, this
input signal is usually from the output of 1-pole AR initiation, so as to prevent pole discrepancy
protection from operation during 1-pole AR initiation.

3-136 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

SIG 62PD.En1 &

SIG 62PD.En2

BI [62PD.Blk]
& &
EN [62PD.En] [62PD.t_Op] 0ms 62PD.Op

BI [62PD.In_PD]

EN [62PD.En_3I0/I2_Ctrl] >=1
SET 3I0>[62PD.3I0_Set] >=1

SET I2>[62PD.I2_Set]

Figure 3.19-2 Logic diagram of pole discrepancy protection

3.19.6 Settings

Table 3.19-3 Settings of pole discrepancy protection

No. Name Range Step Unit Remark


Current setting of residual current
1 62PD.3I0_Set (0.050~30.000 )×In 0.001 A criterion for pole discrepancy
protection
Current setting of
2 62PD.I2_Set (0.050~30.000 )×In 0.001 A negative-sequence current criterion
for pole discrepancy protection
Time delay of pole discrepancy
3 62PD.t_Op 0.000~10.000 0.001 s
protection
Enabling/disabling pole
discrepancy protection
4 62PD.En 0 or 1
0: disable
1: enable
Enabling/disabling residual
current criterion and
negative-sequence current criterion
5 62PD.En_3I0/I2_Ctrl 0 or 1
for pole discrepancy protection
0: disable
1: enable

3.20 Synchrocheck
3.20.1 General Application

The purpose of synchrocheck is to ensure two systems are synchronism before they are going to
be connected.

When two asynchronous systems are connected together, due to phase difference between the
two systems, larger impact will be led to the system during closing. Thus auto-reclosing and
manual closing are applied with the synchrocheck to avoid this situation and maintain the system
stability. The synchrocheck includes synchronism check and dead charge check.

PCS-902 Line Distance Relay 3-137


Date: 2011-07-06
3 Operation Theory

3.20.2 Function Description

The synchronism check function measures the conditions across the circuit breaker and compares
them with the corresponding settings. The output is only given if all measured quantities are
simultaneously within their set limits.

The dead charge check function measures the amplitude of line voltage and bus voltage at both
sides of the circuit breaker, and then compare them with the live check setting [25.U_Lv] and the
dead check setting [25.U_Dd]. The output is only given when the measured quantities comply with
the criteria.

Synchrocheck in this device can be used for auto-reclosing and manual closing for both
single-breaker and dual-breakers. Details are described in the following sections.

When used for the synchrocheck of single-breaker, comparative relationship between reference
voltage (UL) and incoming voltage (UB) for synchronism is as follows.

UL
UB

Figure 3.20-1 Relationship between reference voltage and synchronous voltage

3.20.2.1 Single Busbar Arrangement

Voltage selection function is not required for this busbar arrangement, the connection of the
voltage signals and respective VT MCB auxiliary contacts to the device is shown in the Figure
3.20-2 and Figure 3.20-3.

1. Three-phase bus voltage used for protection

3-138 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

VTS.En_Line_VT=0 Bus

 Ua
UL1 Ub CB

Uc
MCB_VT_UL1

UB1

MCB_VT_UB1
Line

Figure 3.20-2 Voltage connection for single busbar arrangement

2. Three-phase line voltage used for protection

VTS.En_Line_VT=1 Bus

UB1 CB

MCB_VT_UB1

 Ua
UL1 Ub
Uc
MCB_VT_UL1 Line

Figure 3.20-3 Voltage connection for single busbar arrangement

In the figures, the setting [VTS.En_Line_VT] is used to determine protection voltage signals (Ua,
Ub, Uc) from line VT or bus VT according to the condition.

PCS-902 Line Distance Relay 3-139


Date: 2011-07-06
3 Operation Theory

3.20.2.2 Double Busbars Arrangement

Bus2

Bus1

B1D B2D
UB1
MCB_VT_UB1

UB2
MCB_VT_UB2

UB1D_Clsd
UB1D_Open  CB

UB2D_Clsd
UB2D_Open 
 Ua

UL1 Ub
Line
Uc
MCB_VT_UL1

Figure 3.20-4 Voltage connection for double busbars arrangement

For double busbars arrangement, selection of appropriate voltage signals from Bus 1 and Bus 2
for synchronizing are required. Line VT signal is taken as reference to check synchronizing with
the voltage after voltage selection function. Selection approach is as follows.

For the disconnector positions, the normally open (NO) and normally closed (NC) contacts of the
disconnector for bus 1 and bus 2 are required to determine the disconnector open and closed
positions. The voltage selection logic is as follows.

BI UB1D_Clsd &
UB1_SEL
BI UB1D_Open
Voltage
Selection Logic
BI UB2D_Clsd &
UB2_SEL
BI UB2D_Open

&
Invalid_SEL

UB1 UB

UB2

Figure 3.20-5 Voltage selection for double busbars arrangement

3-140 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

After acquiring the disconnector open and closed positions of double busbars, use the following
logic to acquire the feeder voltage of double busbars.

DS2 CLOSED DS2 OPEN


DS1 CLOSED Keep original value Voltage from Bus 1 VT (UB1_Sel=1)
DS1 OPEN Voltage from Bus 2 VT (UB2_Sel=1) Keep original value

DS1 is disconnector of Bus 1

DS2 is disconnector of Bus 2

If voltage selection is invalid (Invalid_SEL=1), keep original selection and without switchover.

3.20.2.3 One and A Half Breakers Arrangement

For one and a half breakers arrangement, selection of appropriate voltage signals among Line1
VT, Line2 VT and Bus 2 VT as reference voltage to check synchronizing with Bus 1 voltage signal
for closing breaker at Bus 1 side.

Bus1

UB1
MCB_VT_UB1

UB1D_Clsd
UB1D_Open  B1D

 Ua Line 1
UL1 Ub
Uc
MCB_VT_UL1
L1D
UL1D_Clsd
UL1D_Open  Line 2
UL2
MCB_VT_UL2

UL2D_Clsd
UL2D_Open 

L2D
UB2D_Clsd
UB2D_Open

UB2
MCB_VT_UB2

B2D

Bus2

Figure 3.20-6 Voltage connection for one and a half breakers arrangement

PCS-902 Line Distance Relay 3-141


Date: 2011-07-06
3 Operation Theory

For the circuit breaker at bus side (take bus breaker of bus 1 as an example), the device acquires
the disconnector open and closed positions of two feeders and bus 2. The voltage selection logic
is as follows.

BI UL1D_Clsd &
UL1_SEL
BI UL1D_Open
&
BI UL2D_Clsd & UL2_SEL

BI UL2D_Open
&
BI UB2D_Clsd & UB2_SEL

BI UB2D_Open
&
Invalid_SEL

UL1 UL

UL2

UB2

Figure 3.20-7 Voltage selection for one and a half breakers arrangement

For the tie breaker, the device acquires the disconnector open and closed positions of two feeders
and two busbars. Either Line 1 VT or Bus 1 VT signal is selected as reference voltage to check
synchronizing with the selected voltage between Line 2 VT and Bus 2 VT. The voltage selection
logic is as follows.

3-142 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

BI UL1D_Clsd &
UL1_SEL
BI UL1D_Open
&
BI UB1D_Clsd & UB1_SEL

BI UB1D_Open
&

UL1 UL

UB1

BI UL2D_Clsd &
UL2_SEL
BI UL2D_Open
&
BI UB2D_Clsd & UB2_SEL

BI UB2D_Open
>=1
& Invalid_SEL

UL2 UB

UB2

Figure 3.20-8 Voltage selection for one and a half breakers arrangement

When the voltage selection fails (including VT circuit failure and MCB failure), the device will issue
the corresponding failure signal. If the voltage selection is invalid (Invalid_SEL=1), keep original
selection and without switchover.

In order to simplify description, one of the two voltages used in the synchrocheck (synchronism check
and dead charge check) which obtained after voltage selection function is regarded as line voltage,
and another is bus voltage.

3.20.3 I/O Signals

Table 3.20-1 Internal I/O signals of synchrocheck

No. Input Signal Description


1 25.Blk_Chk Input signal of blocking synchrocheck function for AR.
Input signal of blocking synchronism check for AR. If the value is “1”, the output of
2 25.Blk_SynChk
synchronism check is “0”.
3 25.Blk_DdChk Input signal of blocking dead charge check for AR.
Input signal of starting synchronism check, usually it was starting signal of AR
4 25.Start_Chk
from auto-reclosing module.
No. Output Signal Description
1 UL1_Sel To select voltage of Line 1

PCS-902 Line Distance Relay 3-143


Date: 2011-07-06
3 Operation Theory

2 UL2_Sel To select voltage of Line 2


3 UB1_Sel To select voltage of Bus 1
4 UB2_Sel To select voltage of Bus 2
5 Invalid_Sel Voltage selection is invalid.
To indicate that frequency difference condition for synchronism check of AR is
6 25.Ok_fDiff
met, frequency difference between UB and UL is smaller than [25.f_Diff].
To indicate that voltage difference condition for synchronism check of AR is met,
7 25.Ok_UDiff
voltage difference between UB and UL is smaller than [25.U_Diff]
To indicate phase difference condition for synchronism check of AR is met, phase
8 25.Ok_phiDiff
difference between UB and UL is smaller than [25.phi_Diff].
9 25.Ok_DdL_DdB Dead line and dead bus condition is met
10 25.Ok_DdL_LvB Dead line and live bus condition is met
11 25.Ok_LvL_DdB Live line and dead bus condition is met
12 25.Chk_LvL Line voltage is greater than the voltage setting [25.U_Lv]
13 25.Chk_DdL Line voltage is smaller than the voltage setting [25.U_Dd]
14 25.Chk_LvB Bus voltage is greater than the voltage setting [25.U_Lv]
15 25.Chk_DdB Bus voltage is smaller than the voltage setting [25.U_Dd]
16 25.Ok_DdChk To indicate that dead charge check condition of AR is met
17 25.Ok_ChkChk To indicate that synchronism check condition of AR is met
18 25.Ok_Chk To indicate that synchrocheck condition of AR is met
19 25.VTS_Alm_UB Synchronism voltage circuit is abnormal (UB)
20 25.VTS_Alm_UL Synchronism voltage circuit is abnormal (UL)
21 f_Prot Frequency of the voltage used by protection calculation
22 f_Syn Frequency of the voltage used by synchrocheck
23 u_Diff Voltage difference for synchronism check
24 f_Diff Frequency difference for synchronism check
25 phi_Diff Phase difference for synchronism check

3.20.4 Logic

These logic diagrams give the introduction to the working principles of the synchronism check and
dead charge check.

3.20.4.1 Synchronism Check Logic

The frequency difference, voltage difference, and phase difference of voltages from both sides of
the circuit breaker are calculated in the device, they are used as input conditions of the
synchronism check.

When the synchronism check function is enabled and the voltages of both ends meets the
requirements of the voltage difference, phase difference, and frequency difference, and there is no
synchronism check blocking signal, it is regarded that the synchronism check conditions are met.

3-144 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

SIG 25.Blk_Chk >=1


&
SIG 25.Blk_SynChk

EN [25.En_SynChk]

SIG 25.Start_Chk

SIG UB>[25.U_Lv]
& &
OTH UL>[25.U_Lv] 50ms 0ms & [25.t_SynChk] 0ms 25.Ok_SynChk

OTH 25.Ok_UDiff

OTH 25.Ok_phiDiff

OTH 25.Ok_fDiff

Figure 3.20-9 Synchronism check

3.20.4.2 Dead Charge Check Logic

The dead charge check conditions have three types, namely, live-bus and dead-line check,
dead-bus and live-line check and dead-bus and dead-line check. The above three modes can be
enabled and disabled by the corresponding logic settings. The device can calculate the measured
bus voltage and line voltage at both sides of the circuit breaker and compare them with the
settings [25.U_Lv] and [25.U_Dd]. When the voltage is higher than [25.U_Lv], the bus/line is
regarded as live. When the voltage is lower than [25.U_Dd], the bus/line is regarded as dead.

PCS-902 Line Distance Relay 3-145


Date: 2011-07-06
3 Operation Theory

SIG 25.Blk_Chk >=1


&
SIG 25.Blk_DdChk &
>=1 [25.t_DdChk] 0ms 25.Ok_DdChk
SIG 25.Start_Chk

EN [25.En_DdL_DdB] &
25.Ok_DdL_DdB

EN [25.En_DdL_LvB] &
25.Ok_DdL_LvB

EN [25.En_LvL_DdB] &
25.Ok_LvL_DdB
OTH UL>[25.U_Lv]

OTH UL<[25.U_Dd]

OTH UB>[25.U_Lv]

OTH UB<[25.U_Dd]

SIG 25.Alm_VTS_UB >=1

SIG 25.Alm_VTS_UL

Figure 3.20-10 Dead charge check logic

3.20.4.3 Synchrocheck Logic

SIG 25.Ok_SynChk
>=1
EN 25.En_NoChk 25.Ok_Chk

SIG 25.Ok_DdChk

Figure 3.20-11 Synchrocheck logic

This device comprises two synchrocheck modules, correspond to circuit breaker 1 and circuit
breaker 2 respectively.

3.20.5 Settings

Table 3.20-2 Settings of synchrocheck

No. Name Range Step Unit Remark


Voltage selecting mode of line.
0: A-phase voltage
1 25.Opt_Source_UL 0~5 1 1: B-phase voltage
2: C-phase voltage
3: AB-phase voltage

3-146 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

4: BC-phase voltage
5: CA-phase voltage
Voltage selecting mode of bus.
0: A-phase voltage
1: B-phase voltage
2 25.Opt_Source_UB 0~5 1 2: C-phase voltage
3: AB-phase voltage
4: BC-phase voltage
5: CA-phase voltage

3 25.U_Dd 0.05Un~0.8Un 0.001 V Voltage threshold of dead check

4 25.U_Lv 0.5Un~Un 0.001 V Voltage threshold of live check

Compensation coefficient for


5 25.K_Usyn 0.20-5.00
synchronous voltage
Phase difference limit of
6 25.phi_Diff 0~ 89 1 Deg
synchronism check for AR
Compensation for phase
7 25.phi_Comp 0~359 1 Deg difference between two
synchronous voltages
Frequency difference limit of
8 25.f_Diff 0.02~1.00 0.01 Hz
synchronism check for AR
Voltage difference limit of
9 25.U_Diff 0.02Un~0.8Un V
synchronism check for AR
Time delay to confirm dead check
10 25.t_DeadChk 0.010~25.000 s
condition
Time delay to confirm
11 25.t_SynChk 0.010~25.000 s
synchronism check condition
Enabling/disabling frequency
difference check
12 25.En_fDiffChk 0 or 1
0: disable
1: enable
Enabling/disabling synchronism
check
13 25.En_SynChk 0 or 1
0: disable
1: enable
Enabling/disabling dead line and
dead bus (DLDB) check
14 25.En_DdL_DdB 0 or 1
0: disable
1: enable
Enabling/disabling dead line and
live bus (DLLB) check
15 25.En_DdL_LvB 0 or 1
0: disable
1: enable
16 25.En_LvL_DdB 0 or 1 Enabling/disabling live line and

PCS-902 Line Distance Relay 3-147


Date: 2011-07-06
3 Operation Theory

dead bus (LLDB) check


0: disable
1: enable
Enabling/disabling AR without any
check
17 25.En_NoChk 0 or 1
0: disable
1: enable

3.21 Automatic Reclosure


3.21.1 General Application

To maintain the integrity of the overall electrical transmission system, the device is installed on the
transmission system to isolate faulted segments during system disturbances. Faults caused by
lightning, wind, or tree branches could be transient in nature and may disappear once the circuit is
de-energized. According to statistics, for overhead transmission line, 80%~90% of the faults on
overhead lines are the transient faults. Auto-reclosing systems are installed to restore the faulted
section of the transmission system once the fault is extinguished (providing it is a transient fault).
For certain transmission systems, auto-reclosure is used to improve system stability by restoring
critical transmission paths as soon as possible.

Besides overhead lines, other equipment failure, such as cables, busbar, transformer fault and so
on, are generally permanent fault, and auto-reclosing is not initiated after faulty feeder is tripped.
For some mixed circuits, such as overhead line with a transformer unit, hybrid transmission lines,
etc., it is required to ensure that auto-reclosing is only initiated for faults overhead line section, or
make a choice according to the situation.

3.21.2 Function Description

This auto-reclosing logic can be used with either integrated device or external device. When the
auto-reclosure is used with integrated device, the internal protection logic can initiate AR,
moreover, a tripping contact from external device can be connected to the device via opto-coupler
input to initiate integrated AR function.

When external auto-reclosure is used, the device can output some configurable output to initiate
external AR, such as, contact of initiating AR, phase-segregated tripping contact, single-phase
tripping contact, three-phase tripping contact and contact of blocking AR. According to
requirement, these contacts can be selectively connected to external auto-reclosure device to
initiate AR.

For phase-segregated circuit breaker, AR mode can be 1-pole AR for single-phase fault and
3-pole AR for multi-phase fault, or always 3-pole AR for any kinds of fault according to system
requirement. For persistent fault or multi-shot AR number preset value is reached, the device will
send final tripping command. The device will provide appropriate tripping command based on
faulty phase selection if adopting 1-pole AR.

AR can be enabled or disabled by logic setting or external signal via binary input. When AR is
enabled, the device will output contact [79.On], otherwise, output contact [79.Off]. After some

3-148 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

reclosing conditions, such as, CB position, CB pressure and so on, is satisfied, the device will
output contact [79.Ready].

According to requirement, the device can be set as one-shot or multi-shot AR. When adopting
multi-shot AR, the AR mode of first time reclosing can be set as 1-pole AR, 3-pole AR or 1/3-pole
AR. The rest AR mode is only 3-pole AR and its number is determined by the maximum 3-pole
reclosing number.

For one-shot AR or first reclosing of multi-shot AR, AR mode can be selected by logic setting
[79.En_1PAR], [79.En_3PAR] and [79.En_1P/3PAR] or external signal via binary inputs. When
3-pole or 1/3-pole AR mode is selected, the following three types of check modes can be selected:
dead charge check, synchronism check and no check.

3.21.3 Function Block Diagram

79

79.In_En 79.On

79.Blk 79.Off

79.Ready

79.AR_Blkd

79.Active

79.Inprog

79.Inprog_1P

79.Inprog_3PS2

79.WaitToSlave

79.AR_Out

79.Prep_Trp1P

79.Prep_Trp3P

79.Fail_Rcls

79.Fail_Chk

79.Mode_1PAR

79.Mode_3PAR

79.Mode_1/3PAR

PCS-902 Line Distance Relay 3-149


Date: 2011-07-06
3 Operation Theory

3.21.4 I/O Signals

Table 3.21-1 Configurable I/O signals of auto-reclosing

No. Input Signal Description


Input signal of enabling AR. If the logic setting [79.En_ExtCtrl] is set as “1”, AR will
1 79.In_En
be controlled to enable by external input signal.
Input signal of disabling AR. If the logic setting [79.En_ExtCtrl] is set as “1”, AR
2 79.Blk
will be controlled to disable by external input signal.
No. Output Signal Description
1 79.On AR is enabled.
2 79.Off AR is disabled.
3 79.Ready AR has been ready for reclosing cycle.
4 79.AR_Blkd AR is blocked.
5 79.Active AR logic is active.
6 79.Inprog AR cycle is in progress.
7 79.Inprog_1P The first 1-pole AR cycle is in progress.
8 79.Inprog_3PS2 The first 3-pole AR cycle is in progress.
Waiting signal of AR which will be sent to slave AR (when reclosing multiple circuit
9 79.WaitToSlave
breakers)

10 79.AR_Out Auto-reclosing signal

11 79.Prep_Trp1P Single-phase circuit breaker will be tripped once the device operates.
12 79.Prep_Trp3P Three-phase circuit breaker will be tripped once the device operates.
13 79.Fail_Rcls Auto-reclosing fails.
14 79.Fail_Chk Synchrocheck of AR fails.
15 79.Mode_1PAR Output signal of 1-pole AR mode
16 79.Mode_3PAR Output signal of 3-pole AR mode
17 79.Mode_1/3PAR Output signal of 1/3-pole AR mode

Table 3.21-2 Internal I/O signals of auto-reclosing

No. Input Signal Description


Input signal of selecting 1-pole AR mode of corresponding circuit
1 79.Sel_1PAR
breaker
Input signal of selecting 3-pole AR mode of corresponding circuit
2 79.Sel_3PAR
breaker
Input signal of selecting 1/3-pole AR mode of corresponding circuit
3 79.Sel_1P/3PAR
breaker
4 79.Trp Input signal of single-phase tripping from line protection to initiate AR
5 79.Trp3P Input signal of three-phase tripping from line protection to initiate AR
6 79.TrpA Input signal of A-phase tripping from line protection to initiate AR
7 79.TrpB Input signal of B-phase tripping from line protection to initiate AR
8 79.TrpC Input signal of C-phase tripping from line protection to initiate AR
Input signal of indicating that the circuit breaker has enough energy
9 79.CB_Healthy
to perform closing function

3-150 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Input signal of blocking reclosing, usually it is connected with manual


10 79.LockOut closing contact or tripping contact of breaker failure protection,
transformer protection and busbar differential protection, etc.
11 79.PLC_Lost Input signal of indicating the alarm signal that signal channel is lost
Input signal of waiting for reclosing permissive signal from master
12 79.WaitMaster
AR (when reclosing multiple circuit breakers)
Input signal of blocking AR which will be latched and only can be
13 79.BlkOn
released by input signal [79.Rls_BlkOn]
14 79.Rls_BlkOn Releasing command of blocking signal of auto-reclosure [79.BlkOn]
No. Output Signal Description
1 79.N_Total_Rcls Total Recorded number of all reclosing attempts
2 79.N_Total_Rcls 1-pole Shot 1 Recorded number of first 1-pole reclosing attempts
3 79.N_Total_Rcls 3-pole Shot 1 Recorded number of first 3-pole reclosing attempts
4 79.N_Total_Rcls 3-pole Shot 2 Recorded number of second 3-pole reclosing attempts
5 79.N_Total_Rcls 3-pole Shot 3 Recorded number of third 3-pole reclosing attempts
6 79.N_Total_Rcls 3-pole Shot 4 Recorded number of fourth 3-pole reclosing attempts

3.21.5 Logic

3.21.5.1 AR Ready

For the first reclosing of multi-shot AR, AR mode can be 1-pole AR or 3-pole AR, however, the
selection is valid only to the first reclosing, after that it can only be 3-pole AR.

When logic setting [79.SetOpt] is set as “1”, AR mode is determined by logic settings. When logic
setting [79.SetOpt] is set as “0”, AR mode is determined by external signal via binary inputs.

An auto-reclosure must be ready to operate before performing reclosing. The output signal
[79.Ready] means that the auto-reclosure can perform at least one time of reclosing function, i.e.,
breaker open-close-open.

When the device is energized or after the settings are modified, the following conditions must be
met before the reclaim time begins:

1. AR function is enabled.

2. The circuit breaker is ready, such as, normal storage energy and no low pressure signal.

3. The duration of the circuit breaker in closed position before fault occurrence is not less than
the setting [79.t_CBClsd].

4. There is no block signal of auto-reclosing.

After the auto-reclosure operates, the auto-reclosure must reset, i.e., [79.Active]=0, in addition to
the above conditions for reclosing again.

The logic of AR ready is shown in Figure 3.21-1.

PCS-902 Line Distance Relay 3-151


Date: 2011-07-06
3 Operation Theory

SIG CB closed position [79.t_CBClsd] 100ms


& >=1
SIG 79.Active >=1

OTH Any tripping signal


&
79.Ready
BI [79.CB_Healthy] 0ms [79.t_CBReady] &

SIG 79.LockOut 0ms [79.t_DDO_BlkAR] 79.AR_Blkd

>=1
EN [79.En] &

EN [79.En_ExtCtrl]
>=1
79.On

&
SIG 79.In_En &

SIG 79.Blk

Figure 3.21-1 Logic diagram of AR ready

The input signal [79.CB_Healthy] must be energized before auto-reclosure gets ready. Because
most circuit breakers can finish one complete process: open-closed-open, it is necessary that
circuit breaker has enough energy before reclosing. When the time delay of AR is exhausted, AR
will be blocked if the input signal [79.CB_Healthy] is still not energized within time delay
[79.t_CBReady]. If this function is not required, the input signal [79.CB_Healthy] can be not to
configure, and its state will be thought as “1” by default.

When the input signal [79.LockOut] is energized, auto-reclosure will be blocked immediately. After
this input signal is de-energized, the blocking condition will disappear with a time delay
[79.t_DDO_BlkAR].

When the internal blocking condition of AR is met (such as, zone 3 of distance protection operates,
the device operates for multi-phase fault, three-phase fault and so on.) The blocking flag of AR will
be also controlled by the internal blocking condition of AR. When the blocking flag of AR is valid,
auto-reclosure will be blocked immediately. After the blocking flag of AR is invalid, the blocking for
AR will disappear with a time delay [79.t_DDO_BlkAR].

AR will be blocked immediately once the blocking condition of AR appears, but the blocking
condition of AR will drop off with a time delay [79.t_DDO_BlkAR] after blocking signal disappears

When any protection element operates to trip, the device will output a signal [79.Active] until AR
drop off (Reset Command). Any tripping signal can be from external protection device or internal
protection element.

AR function can be enabled by internal logic settings of AR mode or external signal via binary
inputs in addition to internal logic setting [79.En]. When logic setting [79.En_ExtCtrl] is set as “1”,
AR enable are determined by external signal via binary inputs and logic settings. When logic
setting [79.En_ExtCtrl] set as “0”, AR enable are determined only by logic settings.

For one-shot reclosing, if 1-pole AR mode is selected, auto-reclosure will reset when there is

3-152 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

three-phase tripping signal or input signal of multi-phase open position.

3.21.5.2 AR Initiation

AR mode can be selected by external signal via binary inputs or internal logic settings. If the logic
setting [79.SetOpt] set as “1”, AR mode is determined by the internal logic settings. If the logic
settings [79.SetOpt] set as “0”, AR mode is determined by the external inputs.

1. AR initiated by tripping signal of line protection

AR can be initiated by tripping signal of line protection, and the tripping signal may be from internal
trip signal or external trip signal.

When selecting 1-pole AR or 1/3-pole AR, line single-phase fault will trigger 1-pole AR. When AR
is ready to reclosing (“79.Ready”=1) and the single-phase tripping command is received, this
single-phase tripping command will be kept in the device, and 1-pole AR will be initiated after the
single-phase tripping command drops off. The single-phase tripping command kept in the device
will be cleared after the completion of auto-reclosing sequence (Reset Command). Its logic is
shown in Figure 3.21-2.

SIG Reset Command &


>=1

SIG Single-phase Trip

&
SIG 79.Ready
&
1-pole AR Initiation
SIG 79.Sel_1PAR >=1

SIG 79.Sel_1P/3PAR

Figure 3.21-2 Single-phase tripping initiating AR

When selecting 3-pole AR or 1/3-pole AR, three-phase tripping will trigger 3-pole AR. When AR is
ready to reclosing (“79.Ready”=1) and the three-phase tripping command is received, this
three-phase tripping command will be kept in the device, and 3-pole AR will be initiated after the
three-phase tripping command drops off. The three-phase tripping command kept in the device will
be cleared after the completion of auto-reclosing sequence. (Reset Command) Its logic is shown
in Figure 3.21-3.

PCS-902 Line Distance Relay 3-153


Date: 2011-07-06
3 Operation Theory

SIG Reset Command &


>=1

SIG Three-phase Trip

&
SIG 79.Ready
&
3-pole AR Initiation
SIG 79.Sel_3PAR >=1

SIG 79.Sel_1P/3PAR

Figure 3.21-3 Three-phase tripping initiating AR

2. AR initiated by CB state

A logic setting [79.En_CBInit] is available for selection that AR is initiated by CB state. Under
normal conditions, when AR is ready to reclosing (“79.Ready”=1), AR will be initiated if circuit
breaker is open and corresponding phase current is nil. AR initiated by CB state can be divided
into initiating 1-pole AR and 3-pole AR, their logics are shown in Figure 3.21-4 and Figure 3.21-5
respectively. Usually normally closed contact of circuit breaker is used to reflect CB state.

SIG Reset Command

SIG Phase A open


>=1
SIG Phase B open
&
SIG Phase C open & &
& &
1-pole AR Initiation

EN [79.En_CBInit]

SIG 79.Ready

SIG 79.Sel_1PAR >=1

SIG 79.Sel_1P/3PAR

Figure 3.21-4 1-pole AR initiation

3-154 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

SIG Reset Command &


SIG Phase A open
&
& 3-pole AR Initiation
SIG Phase B open

SIG Phase C open

EN [79.En_CBInit] &

SIG 79.Ready

EN [79.Sel_1PAR] >=1

EN [79.Sel_1P/3PAR]

Figure 3.21-5 3-pole AR initiation

3.21.5.3 AR Reclosing

After AR is initiated, the device will output the initiating contact of AR. For 1-pole AR, in order to
prevent pole discrepancy protection from maloperation under pole discrepancy conditions, the
contact of “1-pole AR initiation” can be used to block pole discrepancy protection.

When the dead time delay of AR expires after AR is initiated, as for 1-pole AR, the result of
synchronism check will not be judged, and reclosing command will be output directly. As far as the
3-pole AR, if the synchronism check is enabled, the release of reclosing command shall be subject
to the result of synchronism check. After the dead time delay of AR expires, if the synchronism
check is still unsuccessful within the time delay [79.t_wait_Chk], the signal of synchronism check
failure (79.Fail_Syn) will be output and the AR will be blocked. If 3-pole AR with no-check is
enabled, the condition of synchronism check success (79.Ok_Chk) will always be established.
And the signal of synchronism check success (79.Ok_Chk) from the synchronism check logic can
be applied by auto-reclosing function inside the device or external auto-reclosure device.

>=1
79.Inprog

79.Inprog_1P

79.Inprog_3P

SIG 1-pole AR Initiation [79.t_Dd_1PS1] 0ms

>=1
SIG 3-pole AR Initiation [79.t_Dd_3PS1] 0ms & AR Pulse

&
[79.t_Wait_Chk] 0ms 79.Fail_Chk
SIG 79.Ok_Chk

Figure 3.21-6 One-shot AR

PCS-902 Line Distance Relay 3-155


Date: 2011-07-06
3 Operation Theory

When there is a fault on an overhead line, the concerned circuit breakers will be tripped normally.
After fault is cleared, the tripping command will drop off immediately. In case the circuit breaker is
in failure, etc., and the tripping signal of the circuit breaker maintains and in excess of the time
delay [79.t_PersistTrp], AR will be blocked, as shown in the following figure.

In case pilot protection adopting permissive scheme, when the communication channel is
abnormal, pilot protection will be disabled. In the process of channel abnormality, an internal fault
occurs on the transmission line, backup protection at both ends of line will operate to trip the circuit
breaker of each end. The operation time of backup protection at both ends of the line is possibly
non-accordant, whilst the time delay of AR needs to consider the arc-extinguishing and insulation
recovery ability for transient fault, so the time delay of AR shall be considered comprehensively
according to the operation time of the device at both ends. When the communication channel of
main protection is abnormal (input signal [79.PLC_Lost] is energized), and the logic setting
[79.En_AddDly] is set as “1”, then the dead time delay of AR shall be equal to the original dead
time delay of AR plus the extra time delay [79.t_AddDly], so as to ensure the recovery of insulation
intensity of fault point when reclosing after transient fault. This extra time delay [t_ExtendDly] is
only valid for the first shot AR.

SIG Single-phase Trip >=1


[79.t_PersistTrp] 0ms 79.AR_Blkd
SIG Three-phase Trip

>=1

&

BI [79.PLC_Lost]
&

SIG 79.Active
&
Extend AR time
EN [79.En_AddDly]

Figure 3.21-7 Extra time delay and blocking logic of AR

Reclosing pulse length may be set through the setting [79.t_DDO_AR]. For the circuit breaker
without anti-pump interlock, a logic setting [79.En_CutPulse] is available to control the reclosing
pulse. When this function is enabled, if the device operates to trip during reclosing, the reclosing
pulse will drop off immediately, so as to prevent multi-shot reclosing onto fault. After the reclosing
command is issued, AR will drop off with time delay [79.t_Reclaim], and can carry out next
reclosing.

3-156 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

SIG AR Pulse 0ms 50ms >=1


79.AR_Out
0ms [79.t_DDO_AR]

SIG Single-phase Trip >=1


&
SIG Three-phase Trip &

EN [79.En_CutPulse]

Figure 3.21-8 Reclosing output logic

3.21.5.4 Reclosing Failure

For transient fault, the fault will be cleared after the device operates to trip. After the reclosing
command is issued, AR will drop off after time delay [79.t_Reclaim], and can carry out next
reclosing. When the reclosing is unsuccessful or the reclosing condition is not met after AR
initiated, the reclosing will be considered as unsuccessful, including the following cases.

1. For one-shot AR, if the tripping command is received again within reclaim time after the
reclosing pulse is issued, the reclosing shall be considered as unsuccessful.

2. For multi-shot AR, if the reclosing times are equal to the setting value of AR number and the
tripping command is received again after the last reclosing pulse is issued, the reclosing shall
be considered as unsuccessful.

3. The logic setting [79.En_FailCheck] is available to judge whether the reclosing is successful
by CB state, when it is set as “1”. If CB is still in open position with a time delay [79.t_Fail] after
the reclosing pulse is issued, the reclosing shall be considered as unsuccessful. For this case,
the device will issue a signal (79.Fail_Rcls) to indicate that the reclosing is unsuccessful, and
this signal will drop off after (Reset Command). AR will be blocked if the reclosing shall be
considered as unsuccessful.

SIG Any tripping command &


0ms 200ms >=1
SIG Last shot is made 79.Fail_Rcls

>=1

SIG AR Pulse
&
[79.t_Fail] 0ms &
SIG CB closed

EN [79.En_FailCheck]

Figure 3.21-9 Reclosing failure

After unsuccessful AR is confirmed, AR will be blocked. AR will not enter into the ready state
unless the circuit breaker position drops off , and can only begin to enter into the ready state again
after the circuit breaker is closed.

PCS-902 Line Distance Relay 3-157


Date: 2011-07-06
3 Operation Theory

3.21.5.5 Reclosing Numbers Control

The device may be set up into one-shot or multi-shot AR. Through the setting [79.N_Rcls], the
maximum number of reclosing attempts may be set up to 4 times. Generally, only one-shot AR is
selected. Some corresponding settings may be hidden if one-shot AR is selected.

1. 1-pole AR

[79.N_Rcls]=1 means one-shot reclosing. For one-shot 1-pole AR mode, 1-pole AR will be initiated
only for single-phase fault and respective faulty phase selected, otherwise, AR will be blocked. For
single-phase transient fault on the line, line protection device will operate to trip and 1-pole AR is
initiated. After the dead time delay for 1-pole AR is expired, the device will send reclosing pulse,
and then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the next
reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed,
and the device will output the signal of reclosing failure [79.Fail_Rcls].

[79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 1-pole AR mode, the first
reclosing is 1-pole AR, and the subsequent reclosing can only be 3-pole AR. For single-phase
transient fault on the line, line protection device will operate to trip and then 1-pole AR is initiated.
After the dead time delay of the first reclosing is expired, the device will send reclosing pulse, and
then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the next
reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed,
and then 3-pole AR is initiated. At this time, the time delay applies the setting [79.t_Dd_3PS2].
After the time delay is expired, if the reclosing condition is met, the device will send reclosing pulse.
The sequence is repeated until the reclosing is successful or the maximum permit reclosing
number [79.N_Rcls] is reached. If the first fault is multi-phase fault, the device operates to trip
three-phase and initiate 3-pole AR. At this time, the time delay applies the setting [79.t_Dd_3PS1].
For the possible reclosing times of 3-pole AR in 1-pole AR mode, please refer to Table 3.21-3.

2. 3-pole AR

[79.N_Rcls]=1 means one-shot reclosing. For one-shot 3-pole AR mode, line protection device will
operate to trip when a transient fault occurs on the line and 3-pole AR will be initiated. After the
dead time delay for 3-pole AR is expired, the device will send reclosing pulse, and then the
auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the next reclosing. For
permanent fault, the device will operate to trip again after the reclosing is performed, and the
device will output the signal of reclosing failure [79.Fail_Rcls].

[79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 3-pole AR mode, line
protection device will operate to trip when a transient fault occurs on the line and 3-pole AR will be
initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing
pulse, and then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the
next reclosing. For permanent fault, the device will operate to trip again after the reclosing is
performed, and then 3-pole AR is initiated after the tripping contact drops off. After the time delay
for AR is expired, the device will send reclosing pulse. The sequence is repeated until the
reclosing is successful or the maximum permit reclosing number [79.N_Rcls] is reached.

3. 1/3-pole AR

3-158 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

[79.N_Rcls]=1 means one-shot reclosing. For one-shot 1/3-pole AR mode, line protection device
will operate to trip when a transient fault occurs on the line and 1-pole AR will be initiated for
single-phase fault and 3-pole AR will be initiated for multi-phase fault. After respective dead time
delay for AR is expired, the device will send reclosing pulse, and then the auto-reclosure will drop
off after the time delay [79.t_Reclaim] to ready for the next reclosing. For permanent fault, the
device will operate to trip again after the reclosing is performed, and the device will output the
signal of reclosing failure [79.Fail_Rcls].

[79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 1/3-pole AR mode, line
protection device will operate to trip when a transient fault occurs on the line and AR will be
initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing
pulse, and then the auto-reclosure will drop off after the time delay [79.t_Reclaim] to ready for the
next reclosing. For permanent fault, the device will operate to trip again after the reclosing is
performed, and then 3-pole AR is initiated after the tripping contact drops off. After the time delay
for AR is expired, the device will send reclosing pulse. The sequence is repeated until the
reclosing is successful or the maximum permit reclosing number [79.N_Rcls] is reached. For the
possible reclosing times of 3-pole AR in 1/3-pole AR mode, please refer to Table 3.21-3.

The table below shows the number of reclose attempts with respect to the settings and AR modes.

Table 3.21-3 Reclosing number

1-pole AR 3-pole AR 1/3-pole AR


Setting Value
N-1AR N-3AR N-1AR N-3AR N-1AR N-3AR
1 1 0 0 1 1 1
2 1 1 0 2 1 2
3 1 2 0 3 1 3
4 1 3 0 4 1 4

N-1AR: the reclosing number of 1-pole AR

N-3AR: the reclosing number of 3-pole AR

4. Coordination between dual auto-reclosures

Duplicated protection configurations are normally applied for UHV lines. If reclosing function is
integrated within line protections, the auto-reclosing function can be enabled in any or both of the
line protections without coordination.

If both sets of reclosing functions are enabled, when one of them first recloses onto a permanent
fault, the other will block the reclosing pulse according to the latest condition of the faulty phase.
For one-shot AR mode, if the current is detected in the faulty phase, AR will be blocked
immediately to prevent the circuit breaker from repetitive reclosing. For multi-shot AR mode, if the
current is detected in the faulty phase, the current reclosing pulse will be blocked and go into the
next reclosing pulse logic automatically. If the maximum permitted reclosing number [79.N_Rcls] is
reached, the auto-reclosure will drop off after the time delay [79.t_Reclaim].

For one-shot or multi-shot AR, there is a corresponding reclosing counter at each stage. After
reclosing pulse is sent, the corresponding reclosing counter will plus 1 and the reclosing counter

PCS-902 Line Distance Relay 3-159


Date: 2011-07-06
3 Operation Theory

may be cleared by the submenu “Clear Counter”. If the circuit breaker is reclosed by other
devices during AR initiation, the auto-reclosure will go into the next reclosing pulse logic.

3.21.5.6 AR Time Sequence Diagram

The following two examples indicate typical time sequence of AR process for transient fault and
permanent fault respectively.

Signal

Fault

Trip

CB 52b
Open
79.t_Reclaim [79.t_Reclaim]

79.Active

79.Inprog [79.t_Dd_1PS1]

79.Inprog_1P [79.t_Dd_1PS1]

79.Ok_Chk

AR Out [79.t_DDO_AR]

79.Perm_Trp3P

79.Fail_Rcls

Time

Figure 3.21-10 Single-phase transient fault

3-160 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Signal

Fault

Trip

Open Open
52b

79.t_Reclaim [79.t_Reclaim]

79.Active

79.Inprog

79.Inprog_1P [79.t_Dd_1PS1]

79.Inprog_3PS2 [79.t_Dd_3PS2]

79.Ok_Chk

AR Out [79.t_DDO_AR] [79.t_DDO_AR]

79.Perm_Trp3P

79.Fail_Rcls 200ms

Time

Figure 3.21-11 Single-phase permanent fault ([79.N_Rcls]=2)

3.21.6 Settings

Table 3.21-4 Settings of auto-reclosing

No. Name Range Step Unit Remark

1 79.N_Rcls 1~4 1 Maximum number of reclosing attempts

2 79.t_Dd_1PS1 0.000~600.000 0.001 s Dead time of first shot 1-pole reclosing

3 79.t_Dd_3PS1 0.000~600.000 0.001 s Dead time of first shot 3-pole reclosing

Dead time of second shot 3-pole


4 79.t_Dd_3PS2 0.000~600.000 0.001 s
reclosing

5 79.t_Dd_3PS3 0.000~600.000 0.001 s Dead time of third shot 3-pole reclosing

Dead time of fourth shot 3-pole


6 79.t_Dd_3PS4 0.000~600.000 0.001 s
reclosing
Time delay of circuit breaker in closed
7 79.t_CBClsd 0.000~600.000 0.001 s
position before reclosing
Time delay to wait for CB healthy, and
begin to timing when the input signal
8 79.t_CBReady 0.000~600.000 0.001 s
[79.CB_Healthy] is de-energized and if
it is not energized within this time delay,

PCS-902 Line Distance Relay 3-161


Date: 2011-07-06
3 Operation Theory

AR will be blocked.
Maximum wait time for synchronism
9 79.t_WaitChk 0.000~600.000 0.001 s
check
Time delay allow for CB status change
10 79.t_Fail 0.000~600.000 0.001 s
to conform reclosing successful

11 79.t_DDO_AR 0.000~600.000 0.001 s Pulse width of AR closing signal

12 79.t_Reclaim 0.000~600.000 0.001 s Reclaim time of AR

Time delay of excessive trip signal to


13 79.t_PersistTrp 0.000~600.000 0.001 s
block auto-reclosing
Drop-off time delay of blocking AR,
when blocking signal for AR
14 79.t_DDO_BlkAR 0.000~600.000 0.001 s
disappears, AR blocking condition
drops off after this time delay

15 79.t_AddDly 0.000~600.000 0.001 s Additional time delay for auto-reclosing

Maximum wait time for reclosing


16 79.t_WaitMaster 0.000~600.000 0.001 s
permissive signal from master AR
Time delay of discriminating another
fault, and begin to times after 1-pole AR
initiated, 3-pole AR will be initiated if
17 79.t_SecFault 0.000~600.000 0.001 s
another fault happens during this time
delay. AR will be blocked if another fault
happens after that.
Enabling/disabling auto-reclosing
blocked when a fault occurs under pole
18 79.En_PDF_Blk 0 or 1 disagreement condition
0: disable
1: enable
Enabling/disabling auto-reclosing with
an additional dead time delay
19 79.En_AddDly 0 or 1
0: disable
1: enable
Enabling/disabling adjust the length of
reclosing pulse
20 79.En_CutPulse 0 or 1
0: disable
1: enable
Enabling/disabling confirm whether AR
is successful by checking CB state
21 79.En_FailCheck 0 or 1
0: disable
1: enable
Enabling/disabling auto-reclosing
22 79.En 0 or 1 0: disable
1: enable

3-162 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

Enabling/disabling AR by external input


signal besides logic setting [79.En]
23 79.En_ExtCtrl 0 or 1
0: only logic setting
1: logic setting and external input signal
Enabling/disabling AR be initiated by
open state of circuit breaker
24 79.En_CBInit 0 or 1
0: disable
1: enable
Option of AR priority
0:None (single-breaker arrangement)
1:High (master AR of multi-breaker
25 79.Opt_Priority 0, 1 or 2
arrangement)
2 : Low (slave AR of multi-breaker
arrangement)
Control option of AR mode
1: select AR mode by internal logic
26 79.SetOpt 0 or 1 settings
0: select AR mode by external input
signals
Enabling/disabling 1-pole AR mode
27 79.En_1PAR 0 or 1 0: disable
1: enable
Enabling/disabling 3-pole AR mode
28 79.En_3PAR 0 or 1 0: disable
1: enable
Enabling/disabling 1/3-pole AR mode
29 79.En_1P/3PAR 0 or 1 0: disable
1: enable

3.22 Transfer Trip


3.22.1 General Application

This function module provides a binary input [TT.Init] for receiving transfer trip from the remote end.
This feature ensures simultaneous tripping at both ends.

3.22.2 Function Description

Transfer trip can be controlled by local fault detector by logic settings [TT.En_FD_Ctrl]. In addition,
the binary input [TT.Init] is always supervised, and the device will issue an alarm [TT.Alm] and
block transfer trip once the binary input is energized for longer than 4s and drop off after resumed
to normal with a time delay of 10s.

PCS-902 Line Distance Relay 3-163


Date: 2011-07-06
3 Operation Theory

3.22.3 Function Block Diagram

TT

TT.Init TT.Alm

TT.Op

3.22.4 I/O Signals

Table 3.22-1 Configurable I/O signals of transfer trip

No. Input Signal Description


1 TT.Init Input signal of initiating transfer trip after receiving transfer trip
No. Output Signal Description
1 TT.Alm Input signal of receiving transfer trip is abnormal
2 TT.Op Transfer trip operates

Table 3.22-2 Internal I/O signals of transfer trip

No. Input Signal Description


1 FD.Pkp The device picks up

3.22.5 Logic

BI [TT.Init] 4s 10s TT.Alm

SIG TT.Alm &


TT.Op
EN [TT.En_FD_Ctrl] >=1

OTH FD.Pkp

BI [TT.Init]

Figure 3.22-1 Logic diagram of transfer trip

3.22.6 Settings

Table 3.22-3 Settings of Transfer trip

No. Name Range Step Unit Remark


1 TT.t_Op 0.000~10.000 0.001 s Time delay of transfer trip
Transfer trip controlled by local fault detector
element
2 TT.En_FD_Ctrl 0 or 1 0: not controlled by local fault detector
element
1: controlled by local fault detector element

3-164 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.23 Trip Logic


3.23.1 General Application

For any enabled protection tripping elements, their operation signal will convert to appropriate
tripping signals through trip logics and then trigger output contacts by configuration.

3.23.2 Function Description

This module gathers signals from phase selection and protection tripping elements and then
converts the operation signal from protection tripping elements to appropriate tripping signals.
The device can implement phase-segregated tripping or three-phase tripping, and may output the
contact of blocking AR and the contact of initiating breaker failure protection.

3.23.3 I/O Signals

Table 3.23-1 Internal I/O signals of trip logic

No. Input Signal Description


All operation signals of various line protection tripping elements, such
1 Line tripping element
as distance protection, overcurrent protection, etc.
The result of fault phase selection. If multi-phase is selected,
2 Phase selection element
three-phase breakers will be tripped.
All protection tripping elements concerned with breaker, such as pole
3 Breaker tripping element
discrepancy protection, etc.
4 Three-phase tripping element Three-phase tripping signal for any fault conditions
5 Initiating BFP element Tripping element to initiate BFP
No. Output Signal Description
1 TrpA Tripping A-phase circuit breaker
2 TrpB Tripping B-phase circuit breaker
3 TrpC Tripping C-phase circuit breaker
4 Trp Tripping any phase circuit breaker
5 3PTrp Tripping three-phase circuit breaker
Protection tripping signal of A-phase configured to initiate BFP, BFI
6 BFI_A
signal shall be reset immediately after tripping signal drops off.
Protection tripping signal of B-phase configured to initiate BFP, BFI
7 BFI_B
signal shall be reset immediately after tripping signal drops off.
Protection tripping signal of C-phase configured to initiate BFP, BFI
8 BFI_ C
signal shall be reset immediately after tripping signal drops off.
Protection tripping signal of three-phase configured to initiate BFP, BFI
9 BFI_3P
signal shall be reset immediately after tripping signal drops off.
10 Trp3P_PSFail Initiating three-phase tripping due to failure in fault phase selection

PCS-902 Line Distance Relay 3-165


Date: 2011-07-06
3 Operation Theory

3.23.4 Logic

SIG Fault phase selection (phase A) &


>=1
Trip Phase A

SIG Fault phase selection (phase B) &


>=1
Trip Phase B

SIG Fault phase selection (phase C) &


Faulty phase selection (three-phase) >=1
SIG & Trip Phase C

>=1
Trip any phase

&
Trip three-phase
SIG Line tripping element

>=1
&
200ms 0ms Trp3P_PSFail

Figure 3.23-1 Simplified tripping logic (part 1)

Reset A-phase tripping command


SIG Trip phase A [t_Dwell_Trp] &
A-phase tripping command is confirmed
SET Ia<0.06In

Reset B-phase tripping command


SIG Trip phase B [t_Dwell_Trp] &
B-phase tripping command is confirmed
SET Ib<0.06In

Reset C-phase tripping command


SIG Trip phase C [t_Dwell_Trp] &
C-phase tripping command is confirmed
SET Ic<0.06In

Reset three-phase tripping command


SIG Trip three-phase [t_Dwell_Trp] &
Three-phase tripping command is confirmed
SET Max(Ia, Ib, Ic)<0.06In

Figure 3.23-2 Simplified tripping logic (part 2)

3-166 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

SIG Breaker tripping element [t_Dwell_Trp] &

SIG No current

SIG Three-phase tripping command >=1 >=1


& Trip three-phase
EN [En_3PTrp]

SIG Tripping command


>=1
Trip A-phase
SIG A-phase tripping command

>=1
Trip B-phase
SIG B-phase tripping command

>=1
Trip C-phase
SIG C-phase tripping command

Figure 3.23-3 Simplified tripping logic (part 3)

SIG Initiating BFP &


BFI_A
SIG Trip phase A

&
BFI_B
SIG Trip phase B

&
BFI_C
SIG Trip phase C

&
BFI_3P
SIG Trip command

Figure 3.23-4 Simplified tripping logic (part 4)

3.23.5 Settings

Table 3.23-2 Settings of trip logic

No. Name Range Step Unit Remark


Enabling/disabling auto-reclosing blocked
when multi-phase fault happens
1 En_MPF_Blk_AR 0 or 1
0: disable
1: enable
Enabling/disabling auto-reclosing blocked
2 En_3PF_Blk_AR 0 or 1 when three-phase fault happens
0: disable

PCS-902 Line Distance Relay 3-167


Date: 2011-07-06
3 Operation Theory

1: enable
Enabling/disabling auto-reclosing blocked
when faulty phase selection fails
3 En_PhSF_Blk_AR 0 or 1
0: disable
1: enable
Enabling/disabling three-phase tripping mode
for any fault conditions
4 En_3PTrp 0 or 1
0: disable
1: enable
The dwell time of tripping command, empirical
value is 0.04
5 t_Dwell_Trp 0.000~10.000 0.001 s The tripping contact shall drop off under
conditions of no current or protection tripping
element drop-off.

3.24 VT Circuit Supervision


3.24.1 General Application

The purpose of VT circuit supervision is to detect whether VT circuit is normal. Because some
protection functions, such as distance protection, under-voltage protection and so on, will be
influenced by VT circuit failure, these protection functions should be disabled when VT circuit fails.

VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit fault,
poor contact of VT circuit, VT maintenance and so on. The device can detect them and issue an
alarm signal to block relevant protection functions. However, the alarm of VT circuit failure should
not be issued when the following cases happen.

1. Line VT is used as protection VT and the protected line is out of service.

2. Only current protection functions are enabled and VT is not connected to the device.

3.24.2 Function Description

VT circuit supervision can detect failure of single-phase, two-phase and three-phase on protection
VT, supervision for synchronism VT circuit of auto-reclosing is also available. Under normal
condition, the device continuously supervises input voltage from VT, VT circuit failure signal will be
activated if residual voltage exceeds the threshold value or positive-sequence voltage is lower
than the threshold value. If the device is under pickup state due to system fault or other
abnormality, VT circuit supervision will be disabled.

Under normal conditions, the device detect residual voltage greater than 8% of Unn to determine
single-phase or two-phase VT circuit failure, and detect three times positive-sequence voltage less
than Unn to determine three-phase VT circuit failure. Upon detecting abnormality on VT circuit, an
alarm will comes up after 1.25s and drop off with a time delay of 10s after VT circuit restored to
normal.

VT (secondary circuit) MCB auxiliary contact as a binary input can be connected to the binary
input circuit of the device. If MCB is open (i.e. [VTS.MCB_VT] is energized), the device will

3-168 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

consider the VT circuit is not in a good condition and issues an alarm without a time delay. If the
auxiliary contact is not connected to the device, VT circuit supervision will be issued with time
delay as mentioned in previous paragraph.

When VT is not connected into the device, the alarm will be not issued if the logic setting
[VTS.En_Out_VT] is set as “1”. However, the alarm is still issued if the binary input [VTS.MCB_VT]
is energized, no matter that the logic setting [VTS.En_Out_VT] is set as “1” or “0”.

3.24.3 Function Block Diagram

VTS

VTS.Alm

3.24.4 I/O Signals

Table 3.24-1 Configurable I/O signals of VT circuit supervision

No. Output Signal Description


1 VTS.Alm Alarm signal to indicate VT circuit fails

Table 3.24-2 Internal I/O signals of VT circuit supervision

No. Input Signal Description


1 VTS.MCB_VT Binary input for VT MCB auxiliary contact

3.24.5 Logic

OTH 3U0>0.08Unn
>=1
OTH 3U1<Unn & &
>=1 1.25s 10s
EN [VTS.En_Line_VT] &

OTH 52b_3P

EN [VTS.En_Out_VT]
>=1

BI [VTS.MCB_VT]
&
VTS.Alm
EN [VTS.En]

Figure 3.24-1 Logic of VT circuit supervision

Unn: rated phase-to-phase voltage

PCS-902 Line Distance Relay 3-169


Date: 2011-07-06
3 Operation Theory

3.24.6 Settings

Table 3.24-3 VTS Settings

No. Name Range Step Unit Remark


No voltage used for protection calculation
1: enable
1 VTS.En_Out_VT 0 or 1 0: disable
In general, when VT is not connected to the
device, this logic setting should be set as “1”
Voltage selection for protection calculation from
busbar VT or line VT
2 VTS.En_Line_VT 0 or 1
1: line VT
0: busbar VT
Alarm function of VT circuit supervision
3 VTS.En 0 or 1 1: enable
0: disable

3.25 CT Circuit Supervision


3.25.1 General Application

The purpose of the CT circuit supervision is to detect any abnormality on CT secondary circuit.

3.25.2 Function Description

Under normal conditions, CT secondary signal is continuously supervised by detecting the


residual current and voltage. If residual current is larger than 10%In whereas residual voltage is
less than 3V, an error in CT circuit is considered, the concerned protection functions are blocked
and an alarm is issued with a time delay of 10s and drop off with a time delay of 10s after CT
circuit is restored to normal condition.

3.25.3 Function Block Diagram

CTS

CTS.En CTS.Alm

CTS.Blk

3.25.4 I/O Signals

Table 3.25-1 Configurable I/O signals of CT circuit supervision

No. Input Signal Description


1 CTS.En CT circuit supervision enabling input, it can be a binary input or a logic link.
2 CTS.Blk CT circuit supervision blocking input, such as a function blocking binary input.

3-170 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

No. Output Signal Description


1 CTS.Alm Alarm signal to indicate CT circuit fails

Table 3.25-2 Internal I/O signals of CT circuit supervision

No. Input Signal Description


1 U3P Three-phase voltage input
2 I3P Three-phase current input

3.25.5 Logic

OTH 3I0>0.1In &


10s 10s CTS.Alm
OTH 3U0<3V

Figure 3.25-1 Logic diagram of CT circuit failure

3.26 Faulty Phase Selection


Fault phase selection logic can be implemented by the following methods:

1. Detecting the variation of operating voltage

2. Detecting the phase difference between I0 and I2A

The logic makes the device ideal for single-phase tripping applications.

3.26.1 Variation of Operating Voltage (Faulty Phase Selection Element 1)

1. Variation of phase operating voltage

1) Phase A: ΔUOPA

2) Phase B: ΔUOPB

3) Phase C: ΔUOPC

2. Variation of phase-to-phase operating voltage

1) Phase AB: ΔUOPAB

2) Phase BC: ΔUOPBC

3) Phase CA: ΔUOPCA

ΔUOΦMAX=Max(ΔUOPA, ΔUOPB, ΔUOPC)

ΔUOΦΦMAX=Max(ΔUOPAB, ΔUOPBC, ΔUOPCA)

If ΔUOΦMAX is several times higher than the variation of operating voltages of other two phases, the
single-phase fault is ensured, otherwise, the multi-phase fault is ensured.

PCS-902 Line Distance Relay 3-171


Date: 2011-07-06
3 Operation Theory

Table 3.26-1 Relation between ΔUOΦMAX and faulty phase

ΔUOΦMAX or ΔUOΦΦMAX Fault phase

ΔUOPA Phase A

ΔUOPB Phase B

ΔUOPC Phase C

ΔUOPAB Phase AB

ΔUOPBC Phase BC

ΔUOPCA Phase CA

3.26.2 I0 and I2A (Faulty Phase Selection Element 2)

The phase selection algorithm uses the angle relation between I0 and I2A of the device. As shown
in Figure 3.26-1, there are three faulty phase selection regions.

Region A
60° -60°

Region B Region C

180°

Figure 3.26-1 The region of faulty phase selection

Depended on the phase relation between I0 and I2A, the faulty phase can be determined.

1. -60º<Arg(I0/I2A)<60º, region A is selected, possible faulty phase is phase A or phase BC.

2. 60º<Arg(I0/I2A)<180º, region B is selected, possible faulty phase is phase B or phase CA.

3. 180º<Arg(I0/I2A)<300º, region C is selected, possible faulty phase is phase C or phase AB.

For single-phase earth fault, I0 and I2 of faulty phase are in-phase and its distance element
operates.

For phase to phase to earth fault, I0 and I2 of non-faulty phase are in-phase but its distance
element does not operate.

3-172 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

3.27 Fault Location


3.27.1 Application

The main objective of line protection is fast, selective and reliable operation for faults on a
protected line section. Besides this, information on distance to fault is very important for those
involved in operation and maintenance. Reliable information on the fault location greatly
decreases the outage of the protected lines and increases the total availability of a power system.
This fault location function cannot be used for the transmission line with series compensation.

3.27.2 Function Description

The fault location is an essential function to various line protection devices, after selecting faulty
phase, it measures and indicates the distance to the fault with high accuracy. Thus, the fault can
be quickly located for repairs. The calculation algorithm considers the effect of load currents,
double-end infeed and additional fault resistance. Both double-end fault location and single-end
fault location are available in line differential relay, but only single-end fault location is provided in
other relays.

The calculation equation is:

Where:

Dist: The distance of fault location according to the Zcalc

Zcalc: The impedance value calculated from the location of protection device to fault point

Zl: The impedance value of the whole line + mutual impedance

Length: The input length of transmission line

3.27.3 Mutual Compensation

When an earth fault occurred on a line of parallel lines arrangement, a distance relay at one end of
the faulty line will tend to underreach whilst the distance relay at the other end will tend to
overreach. Usually the degree of underreach or overreach is acceptable, however, for cases
where precise fault location is required for long lines with high mutual coupling, mutual
compensation is then required to improve the distance measurement. Practically, the mutual effect
between the parallel lines is insignificant to positive and negative sequence and thus the mutual
compensation is only for zero sequence

PCS-902 Line Distance Relay 3-173


Date: 2011-07-06
3 Operation Theory

A Ia B

ZM
k

C Ic D
kZL (1-k)ZL
ZS

ZL

The principle in the application of mutual compensation is shown as follows with the aid of
following sequence network diagram figure . The diagram indicates a parallel lines arrangement
with an earth fault at location k on line CD.

The equivalent sequence network for an earth fault on a parallel lines arrangement with single
source is shown as below.

Ia1 ZL1
ZS1
kZL1 (1-k)ZL1
Ic1

Ia2 ZL2
ZS2
kZL2 (1-k)ZL2
Ic2

Ia0 ZL0

ZS0
Z0M
kZL0 (1-k)ZL0
Ic0

Figure 3.27-1 Equivalent sequence network

The device at location C without mutual compensation will have voltage URC and current IRC
measured as shown in the expression

URC is the voltage of the device at location C.

If the line is fully transposed, ZL1=ZL2, Then

3-174 PCS-902 Line Distance Relay


Date: 2011-07-06
3 Operation Theory

The impedance presented to the device is:

For an earth fault, ,

With the mutual compensation enabled,

(Actual distance of the fault)

The residual current from the parallel line should be added to the device. It should be connected to
terminal 08 and star point of the parallel line CT connected to terminal 07 as shown in the following
figure. Please note the connection diagram and the terminal numbers are for reference only. The
final connection terminals are subject to the device configuration at site.

PCS-902 Line Distance Relay 3-175


Date: 2011-07-06
3 Operation Theory

P2 S2 P2 S2

P1 S1 P1 S1

02 01 02 01

04 03 04 03

06 05 06 05

08 07 08 07

3.27.4 I/O Signals

Table 3.27-1 Internal I/O signals of fault location

No. Input Signal Description


1 U3P Three-phase voltage input
2 I3P Three-phase current input
3 FPS_Fault Faulty phase selection
4 FD.Pkp The device picks up
No. Output Signal Description
1 Fault_Location The result of fault location
2 Faulty_Phase The selected faulty phase
3 Fault_Phase_Curr Maximum faulty current
4 Fault_Resid_Curr Maximum residual current

3-176 PCS-902 Line Distance Relay


Date: 2011-07-06
4 Supervision

4 Supervision

Table of Contents
4 Supervision ...................................................................................... 4-a
4.1 Overview .......................................................................................................... 4-1
4.2 Supervision Alarms ......................................................................................... 4-1
4.3 Relay Self-supervision.................................................................................... 4-5
4.3.1 Relay Hardware Monitoring................................................................................................ 4-5

4.3.2 Fault Detector Monitoring ................................................................................................... 4-5

4.3.3 Check Tripping Output Circuit ............................................................................................ 4-5

4.3.4 Check Setting..................................................................................................................... 4-5

4.4 AC Input Monitoring ........................................................................................ 4-5


4.4.1 Voltage/current Drift Monitoring and Auto-adjustment ........................................................ 4-5

4.4.2 Sampling Monitoring .......................................................................................................... 4-6

4.5 Secondary Circuit Monitoring ........................................................................ 4-6


4.5.1 Opto-coupler Power Supervision ....................................................................................... 4-6

4.5.2 Circuit Breaker Supervision................................................................................................ 4-6

4.5.3 Synchronism Voltage Circuit Failure Supervision ............................................................... 4-6

Table of Tables
Table 4.2-1 Alarm description and handling suggestion ........................................................4-1

PCS-902 Line Distance Relay 4-a


Date: 2011-07-06
4 Supervision

4-b PCS-902 Line Distance Relay


Date: 2011-07-06
4 Supervision

4.1 Overview
Protection system is in quiescent state under normal conditions, and it is required to respond
promptly for faults occurred on power system. When equipment is in energizing process before the
LED “HEALTHY” is on, the equipment need to be checked to ensure no abnormality. Therefore,
the automatic supervision function, which checks the health of the protection system when startup
and during normal operation, plays an important role.

The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.

In case a defect is detected during initialization when DC power supply is provided to the
equipment, the equipment will be blocked with indication and alarm of relay out of service. It is
suggested a trial recovery of the equipment by re-energization. Please contact supplier if the
equipment is still failure.

When a failure is detected by the automatic supervision, it is followed by a LCD message, LED
indication and alarm contact outputs. The failure alarm is also recorded in event recording report
and can be printed If required.

4.2 Supervision Alarms


Hardware circuit and operation status of the equipment are self-supervised continuously. If any
abnormal condition is detected, information or report will be displayed and a corresponding alarm
will be issued.

A minor abnormality may block a certain number of protections functions while the other functions
can still work. However, if severe hardware failure or abnormality are detected, all protection
functions will be blocked and the LED “HEALTHY” will be extinguished and blocking output
contacts BO_FAIL will be given. The protective device then can not work normally and
maintenance is required to eliminate the failure. All the alarm signals and the corresponding
handling suggestions are listed below.

Note!

If the protective device is blocked or alarm signal is sent during operation, please do find
out its reason with the help of self-diagnostic record. If the reason can not be found at site,
please notify the factory NR. Please Do not simply press button “TARGET RESET” on the
protection panel or re-energize on the device.

Table 4.2-1 Alarm description and handling suggestion

No. Item Alarm description Handing suggestion


The signal is issued with other specific alarm
1 Fail_Device The device fails. signals, and please refer to the handeling
suggestion other specific alarm signals.
2 Alm_Device The device is abnormal. The signal is issued with other specific alarm

PCS-902 Line Distance Relay 4-1


Date: 2011-07-06
4 Supervision

signals, and please refer to the handeling


suggestion other specific alarm signals.
No special treatment is needed, and disable
The device is in the
3 Alm_CommTest the communication test function after the
communication test mode.
completion of the test.
Please reset setting values according to the
range described in the instruction manual,
Set value of any setting is out then re-power or reboot the equipment and
4 Alm_Setting_OvRange
of scope. the alarm message will disappear and the
equipment will restore to normal operation
state.
1. Go to the menu “Information→Borad
Info”, check the abnormality information.
Mismatch between the 2. For the abnormality board, if the board
configuration of plug-in is not used, then remove, and if the board is
5 Alm_BoardConfig modules and the designing used, then check whether the board is
drawing of an applied-specific installed properly and work normally.
project. 3. After the abnormality is removed,
re-power or reboot the device and the device
will restore to normal operation state.
Driving circuits of binary Please re-insert the corresponding binary
output relays of BO plug-in output module and re-power the equipment
6 Bxx.Alm_Output
module in slot xx are after the completion of insertion, and the
damaged. device will restore to normal operation state.
The error is found during
Please inform the manufacture or the agent
7 Alm_Settings_MON MON module checking
for repair.
settings of device.
Users may pay no attention to the alarm
signal in the project commissioning stage,
but it is needed to download the latest
package file (including correct version
The error is found during
checksum file) provided by R&D engineer to
checking the version of
8 Alm_Version make the alarm signal disappear. Then users
software downloaded to the
get the correct software version. It is not
device.
allowed that the alarm signal is issued on the
device already has been put into service. the
devices having being put into service so
that the alarm signal disappears.
Please check the settings mentioned in the
After config file is updated, prompt message on the LCD, and go to the
settings of the file and menu “Settings” and select
9 Fail_SettingItem_Chgd
settings saved on the device “Confirm_Settings” item to comfirm
are not matched. settings. Then, the device will restore to
normal operation stage.

4-2 PCS-902 Line Distance Relay


Date: 2011-07-06
4 Supervision

Please check the value of setting


[Active_Grp] and binary input of indiating
The active group set by
active group, and make them matched. Then
settingsin device and that set
10 Alm_BI_SettingGrp the “ALARM” LED will be extinguished and
by binary input are not
the corresponding alarm message will
matched
disappear and the device will restore to
normal operation state.
Error is found during Please inform the manufacture or the agent
11 Fail_Memory
checking memory data. for repair.
1. Check CT ratio settings of each side of
transformer to be set in proper range, and if
need, please reset those settings and reboot
or re-power the device.
2. Check overexcitation settings to be set
Error is found during
12 Fail_Settings reasonable, and if need, please reset those
checking settings.
settings and reboot or re-power the device.
3. After above two steps, abnormality may
disappear. Otherwise, a hardware failue
probably ocurrs and please inform the
manufacture or the agent.
Chips are damaged and please inform the
13 Fail_DSP DSP chip is damaged. manufacture or the agent replacing the
module.
1. check whether the binary input module
is connected to the power supply.
2. check whether the voltage of power
The power supply of BI supply is in the required range.
14 Bxx.Alm_OptoDC plug-in module in slot xx is 3. After the voltage for binary input module
abnormal. restores to normal range, the “ALARM” LED
will be extinguished and the corresponding
alarm message will disappear and the device
will restore to normal operation state.
Please inform configuration engineers to
Software configuation is
15 Fail_Config check and confirm visualization functions of
incorrect.
the device
1. Please make the device out of service.
2. Then check if the analog input modules
AC current and voltage and wiring connectors connected to those
16 Fail_Sample
samplings are abnormal. modules are installed at the position.
3. Re-power the device and the device will
restore to normal operation state.
Please check secondary values and
Fault detector element
17 Alm_PersistFD protection settings. If settings are not set
operates for longer than 10s.
reasonable to make fault detectors pick up,

PCS-902 Line Distance Relay 4-3


Date: 2011-07-06
4 Supervision

please reset settings, and then the alarm


message will disappear and the device will
restore to normal operation state.
Please check secondary values and
protection settings. If settings are not set
Neutral current element reasonable to make fault detectors pick up,
18 Alm_PersistI0
operates for longer than 10s. please reset settings, and then the alarm
message will disappear and the device will
restore to normal operation state.
Please check the corresponding VT
secondary circuit. After the abnormality is
19 VTS.Alm Protection VT circuit fails. eliminated, “ALARM” LED will go off
automatically and device returns to normal
operation state.
Please check the corresponding CT
secondary circuit. After the abnormality is
CT circuit of corresponding
20 CTS.Alm eliminated, “ALARM” LED will go off
circuit breaker fails.
automatically and device returns to normal
operation state.
The auxiliary normally closed Please check the auxiliary contact of CB.
contact (52b) of After the abnormality is eliminated, “ALARM”
21 Alm_52b
corresponding circuit breaker LED will go off automatically and the device
is abnormal. returns to normal operation state.
Thess alarms may be issued for electric
transformer applied projects. If alarms are
The quality factor of sample
22 Fail_SV_QF issued, please check working state of
values is abnormal.
merging units and the connection between
merging units and the protection device.
After maintenance is finished, please
de-energized the binary input
The device is in maintenance
23 Alm_Maintenance [BI_Maintenance] and then the alarm will
state.
disappear and the device restore to normal
operation state.

1. check whether the selected clock


synchronization mode matches the clock
synchronization source;

Time synchronization 2. check whether the wiring connection


24 Alm_TimeSync between the equipment and the clock
abnormality alarm.
synchronization source is correct

3. check whether the setting for selecting


clock synchronization (i.e. [Opt_TimeSync])
is set correctly. If there is no clock

4-4 PCS-902 Line Distance Relay


Date: 2011-07-06
4 Supervision

synchronization, please set the setting


[Opt_TimeSync] as ”No TimeSync”.

4. After the abnormality is removed, the


“ALARM” LED will be extinguished and the
corresponding alarm message will disappear
and the device will restore to normal
operation state.
Please check the corresponding binary input
Input signal of receiving secondary circuit. After the abnormality is
25 TT.Alm transfer trip is energized for eliminated, “ALARM” LED will go off
longer than 4s. automatically and device returns to normal
operation state with a time delay of 10s.

4.3 Relay Self-supervision

4.3.1 Relay Hardware Monitoring


All chips on DSP module are monitored to ensure whether they are damaged or having errors. If
any one of them is detected damaged or having error, the alarm signal [Fail_DSP] is issued with
the device being blocked.

4.3.2 Fault Detector Monitoring


When neutral current fault detector picks up and lasts for longer than 10 seconds, an alarm
[Alm_PersistI0] will be issued without the device blocked.

When any fault detector picks up for longer than 10s, an alarm will be issued [Alm_PersistFD]
without the device blocked.

4.3.3 Check Binary Output Circuit


Chips controlling the output relays in the output circuit are continually monitored. If any error or
damage is detected in these chips, alarm [Bxx.Alm_Output] will be given.

4.3.4 Check Setting


This relay has 10 setting groups, only one Setting group could be activiated (is active) at a time.
The settings of active setting group are checked to ensure they are reasonable. If settings are
checked to be unreasonable or out of setting scopes, a corresponding alarm signal will be issued,
and protective device is also blocked.

4.4 AC Input Monitoring


4.4.1 Voltage/current Drift Monitoring and Auto-adjustment
Zero point of voltage and current may drift due to variation of temperature or other environment
factors. The equipment continually traces the drift and adjust it to normal value automatically.

PCS-902 Line Distance Relay 4-5


Date: 2011-07-06
4 Supervision

4.4.2 Sampling Monitoring


AC current and voltage samplings of protection DSP and fault detector DSP are monitored and if
the samples of protection DSP and fault detector DSP are detected to be wrong or inconsistent
between them, the alarm signal [Fail_Sample] will be issued and the device will be blocked.

4.5 Secondary Circuit Monitoring


4.5.1 Opto-coupler Power Supervision
Positive power supply of opto-coupler is continually monitored. If an error or damage has occurred,
an alarm [Bxx.Alm_OptoDC] will be issued.

4.5.2 Circuit Breaker Supervision


If 52b of three phases are energized ,which indicates circuit breaker is open and there is no
current detected in the line, the line will be considered to be out of service. SOTF protection will be
enabled after 50ms.

If 52b of three phases are energized that indicates circuit breaker is open but there is still current
detected in the line (the measured current is greater than a settable threshold value) or
three-phase circuit breaker is in pole disagreement, an alarm signal [Alm_52b] will be issued after
10 seconds.

4.5.3 Synchronism Voltage Circuit Failure Supervision


If synchronism voltage from line VT or busbar VT is used for auto-reclosing with synchronism or
dead line or busbar check, the synchronism voltage is monitored.

If the circuit breaker is in closed state (52b of three phases are de-energized), but the synchronism
voltage is lower than the setting [25.U_Lv], it means that synchronism voltage circuit fails and an
alarm [VTS.Alm_UB] or [VTS.Alm_UL] will be issued with a time delay of 10s.

If auto-reclosing is disabled, or the logic setting [25.En_NoChk] is set as “1”, synchronism voltage
is not required and synchronism voltage circuit failure supervision will be disabled.

When synchronism voltage circuit failure is detected, function of synchronism check and dead
check in auto-reclosing logic will be disabled.

After synchronism voltage reverted to normal condition, the alarm will be reset automatically with a
time delay of 10s.

4-6 PCS-902 Line Distance Relay


Date: 2011-07-06
5 Meaurement and Recording

5 Meaurement and Recording

Table of Contents
5 Meaurement and Recording............................................................ 5-a
5.1 Measurement ................................................................................................... 5-1
5.2 Recording ........................................................................................................ 5-4
5.2.1 Overview ............................................................................................................................ 5-4

5.2.2 Event Recording ................................................................................................................ 5-4

5.2.3 Disturbance Recording ...................................................................................................... 5-5

5.2.4 Present Recording ............................................................................................................. 5-6

PCS-902 Line Distance Relay 5-a


Date: 2011-03-21
5 Meaurement and Recording

5-b PCS-902 Line Distance Relay


Date: 2011-03-21
5 Meaurement and Recording

5.1 Measurement
PCS-902 performs continuous measurement of the analogue input quantities. The device samples
24 points per cycle and calculates the RMS value in each interval and updated the LCD display in
every 0.5 second. The measurement data can be displayed on the LCD of the relay front panel or
on the local/remote PC via software tool. Navigate the menu to view the sampling value through
LCD screen.

This device can be used for one or two circuit breaker configuration. If it is used for two circuit
breakers configuration, some corresponding metering will be suffixed by CBn (n is the number of
the CB and it can be 1 and 2).

1. RMS Values

Access path: Press key “▲” to enter main menu firstly. Select the item “Measurements “ and
press key “ENT” to enter, and then select submenu “Measurements1” (from protection DSP) or
“Measurements2” (from fault detector DSP). Press key “ENT” to display corresponding
measurement values as below on the LCD.

 Magnitude of three-phase protection voltage Ua, Ub, Uc (i.e. UL1)

 Magnitude of synchronism voltage (UB1, UB2 and UL2)

Please refer to “Function Description in Synchronism Check” about the definitions of UL1, UB1,
UL2 and UB2.

 Manitude of calculated residual voltage (3U0)

 Magnitude of phase current Ia, Ib, Ic (it represents the current of line, for two circuit breakers
configuration, such as one and a half breakers arrangement, it is equal to the summation of
corresponding phase currents of two circuit breakers)

 Magnitude of calculated residual current 3I0 (For one circuit breaker configuration, it is
calculated from three phase currents, i.e. 3I0=Ia+Ib+Ic. However, for two circuit breakers
configuration, it is calculated from two groups of three phase currents, i.e.
3I0=Ia1+Ib1+Ic1+Ia2+Ib2+Ic2)

 Magnitude of phase currents of two groups of CTs Ia1, Ib1, Ic1, Ia2, Ib2, Ic2 (Only displayed
for two circuit breakers configuration with two groups of CTs, for example, one and a half
breakers arrangement)

 Magnitude of residual currents of two groups of CTs 3I01, 3I02 (Only displayed for two circuit
breakers configuration with two groups of CTs, for example, one and a half breakers
arrangement)

 Frequency of protection voltage (f_Prot)

 Frequency of synchronism voltage (f_Syn)

 Frequency difference (f_Diff)

 Voltage difference (u_Diff)

PCS-902 Line Distance Relay 5-1


Date: 2011-03-21
5 Meaurement and Recording

2. Phase Angle

Access path:

1) Press key “▲” to enter main menu firstly.

2) Select the item “Measurements “ and press key “ENT” to enter, and then

3) Select submenu “Measurements1” (from protection DSP) or “Measurements2” (from fault


detector DSP).

4) Press key “ENT” to display corresponding measurement values as below on the LCD.

These displayed phase angles of three-phase current and three-phase voltage are based on
phase A voltage.

 Phase angle of (Ua, Ub, Uc)

 Phase angle of (Ia, Ib, Ic)

 Phase angle of (Ia1, Ib1, Ic1) (Only displayed for two circuit breakers configuration with two
groups of CTs, for example, one and a half breakers arrangement)

 Phase angle of (Ia2, Ib2, Ic2) (Only displayed for two circuit breakers configuration with two
groups of CTs, for example, one and a half breakers arrangement)

 Phase angle difference between two synchronism voltages (phi_Diff)

No. Symbol Definition

1 Ang(Ua) Phase angle of A-phase voltage (Ua), it is taken as reference (i.e. zero degree)

Phase angle difference for B-phase voltage (Ub) relative to the reference voltage
2 Ang(Ub)
(A-phase voltage (Ua))

Phase angle difference for C-phase voltage (Uc) relative to the reference voltage
3 Ang(Uc)
(A-phase voltage (Ua))

Phase angle difference for A-phase current (Ia) relative to the reference voltage
5 Ang(Ia)
(A-phase voltage (Ua))

Phase angle difference for B-phase current (Ib) relative to the reference voltage
6 Ang(Ib)
(A-phase voltage (Ua))

Phase angle difference for C-phase current (Ic) relative to the reference voltage
7 Ang(Ic)
(A-phase voltage (Ua))

Phase angle difference for A-phase current (Ia of CT1 for CB1) relative to the reference
8 Ang(Ia1)
voltage (A-phase voltage (Ua))

Phase angle difference for B-phase current (Ib of CT1 for CB1) relative to the reference
9 Ang(Ib1)
voltage (A-phase voltage (Ua))

Phase angle difference for C-phase current (Ic of CT1 for CB1) relative to the reference
10 Ang(Ic1)
voltage (A-phase voltage (Ua))

Phase angle difference for A-phase current (Ia of CT2 for CB2) relative to the reference
11 Ang(Ia2)
voltage (A-phase voltage (Ua))

5-2 PCS-902 Line Distance Relay


Date: 2011-03-21
5 Meaurement and Recording

Phase angle difference for B-phase current (Ib of CT2 for CB2) relative to the reference
12 Ang(Ib2)
voltage (A-phase voltage (Ua))

Phase angle difference for C-phase current (Ic of CT2 for CB2) relative to the reference
13 Ang(Ic2)
voltage (A-phase voltage (Ua))

14 Ang(phi_Diff) Phase angle difference between two synchronism voltages

3. Metering of the primary value

Access path:

1) Press key “▲” to enter main menu firstly.

2) Select the item “Measurements “ and press key “ENT” to enter, and then

3) Select submenu “Measurements3”.

4) Press key “ENT” to display corresponding measurement values as below on the LCD.

No. Symbol Definition Unit

1 LineBAY_Ua The primary value of A-phase voltage (Ua) kV

2 LineBAY_Ub The primary value of B-phase voltage (Ub) kV

3 LineBAY_Uc The primary value of C-phase voltage (Uc) kV

4 LineBAY_Uab The primary value of phase-to-phase voltage (Uab) kV

5 LineBAY_Ubc The primary value of phase-to-phase voltage (Ubc) kV

6 LineBAY_Uca The primary value of phase-to-phase voltage (Uca) kV

7 LineBAY_3U0 The primary value of calculated residual voltage (3U0) kV

8 LineBAY_Ia The primary value of A-phase current of line (Ia) A

9 LineBAY_Ib The primary value of B-phase current of line (Ib) A

10 LineBAY_Ic The primary value of C-phase current of line (Ic) A

The primary value of A-phase current of CT1 for CB1 (Only displayed for two
11 LineBAY_Ia1 A
circuit breakers configuration with two groups of CTs)

The primary value of B-phase current of CT1 for CB1 (Only displayed for two
12 LineBAY_Ib1 A
circuit breakers configuration with two groups of CTs)

The primary value of C-phase current of CT1 for CB1 (Only displayed for two
13 LineBAY_Ic1 A
circuit breakers configuration with two groups of CTs)

The primary value of A-phase current of CT2 for CB2 (Only displayed for two
14 LineBAY_Ia2 A
circuit breakers configuration with two groups of CTs)

The primary value of B-phase current of CT2 for CB2 (Only displayed for two
15 LineBAY_Ib2 A
circuit breakers configuration with two groups of CTs)

The primary value of C-phase current of CT2 for CB2 (Only displayed for two
16 LineBAY_Ic2 A
circuit breakers configuration with two groups of CTs)

17 LineBAY_UB1 The primary value of synchronism voltage (UB1) kV

18 LineBAY_UL2 The primary value of synchronism voltage (UL2) kV

PCS-902 Line Distance Relay 5-3


Date: 2011-03-21
5 Meaurement and Recording

19 LineBAY_UB2 The primary value of synchronism voltage (UB2) kV

20 LineBAY_P The primary value of active power (P) MW

21 LineBAY_Q The primary value of reactive power (Q) MVar

22 LineBAY_S The primary value of apparent power (S) MVA

23 LineBAY_Cos The value of power factor (Cos) -

5.2 Recording
5.2.1 Overview
PCS-902 provides the following recording functions:

1. Event recording

2. Disturbance recording

3. Present recording

All the recording information except waveform can be viewed on local LCD or by printing.
Waveform could only be printed or extracted with PCS-PC software tool and a waveform analysis
software.

5.2.2 Event Recording


5.2.2.1 Overview

The device can store the latest 1024 disturbance records, 1024 binary events, 1024 supervision
events and 1024 device logs. All the records are stored in non-volatile memory, and when the
available space is exhausted, the oldest record is automatically overwritten by the latest one.

5.2.2.2 Disturbance Records

When any protection element operates or drops off, such as fault detector, distance protection etc.,
they will be logged in event records.

5.2.2.3 Supervision Events

The device is under automatic supervision all the time. If there are any failure or abnormal
condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged in event
records.

5.2.2.4 Binary Events

When there is a binary input is energized or de-energized, i.e., its state has changed from “0” to “1”
or from “1” to “0”, it will be logged in event records.

5.2.2.5 Device Logs

If an operator implements some operations on the device, such as reboot protective device,
modify setting, etc., they will be logged in event records.

5-4 PCS-902 Line Distance Relay


Date: 2011-03-21
5 Meaurement and Recording

5.2.3 Disturbance Recording


5.2.3.1 Application

Disturbance records can be used to have a better understanding of the behavior of the power
network and related primary and secondary equipment during and after a disturbance. Analysis of
the recorded data provides valuable information that can be used to improve existing equipment.
This information can also be used when planning for and designing new installations.

5.2.3.2 Design

A disturbance record consists of fault record and fault waveform. A disturbance record is initiated
by fault detector element.

The disturbance record has two types:

1. Fault detector element picks up without operation of protective element

2. Fault detector element picks up with operation of protective elements.

5.2.3.3 Capacity and Information of Disturbance Records

The device can store up to 64 disturbance records with waveform in non-volatile memory. It is
based on first in first out queue that the oldest disturbance record will be overwritten by the latest
one.

For each disturbance record, the following items are included:

1. Sequence number

Each operation will be recorded with a sequence number in the record and displayed on LCD
screen.

2. Date and time of fault occurrence

The time resolution is 1ms using the relay internal clock synchronized via clock synchronized
device if connected. The date and time is recorded when a system fault is detected.

3. Relative operating time

An operating time (not including the operating time of output relays) is recorded in the record.

4. Faulty phase

5. Fault location

To get accurate result of fault location, the following settings shall be set correctly:

1) Positive-sequence line reactance [X1L]

2) Positive-sequence line resistance [R1L]

3) Zero-sequence line reactance [X0L]

4) Zero-sequence line resistance [R0L]

PCS-902 Line Distance Relay 5-5


Date: 2011-03-21
5 Meaurement and Recording

5) Zero-sequence line mutual reactance [X0M]

6) Zero-sequence line mutual resistance [R0M]

7) Line positive-sequence sensitive angle [phi1_Reach]

8) Line zero-sequence sensitive angle [ph0_Reach]

9) Line length in km [LineLength]

6. Protection elements

5.2.3.4 Capacity and Information of Fault Waveform

MON module can store 64 pieces of fault waveform oscillogram in non-volatile memory. If a new
fault occurs when 64 fault waveform have been stored, the oldest will be overwritten by the latest
one.

Each fault record consists of all analog and digital quantities related to protection, such as original
current and voltage, differential current, alarm elements, and binary inputs and etc.

Each time recording includes 10-cycle pre-fault waveform, and 250 cycles at least and 500 cycles
at most can be recorded.

5.2.4 Present Recording


Present recording is a waveform triggered manually on on the device′s LCD or remotely through
PCS-PC software. Recording content of present recording is same to that of disturbance
recording.

Each time recording includes 10-cycle waveform before triggering, and 250 cycles at most can be
recorded.

5-6 PCS-902 Line Distance Relay


Date: 2011-03-21
6 Hardware

6 Hardware

Table of Contents
6 Hardware .......................................................................................... 6-a
6.1 Overview .......................................................................................................... 6-1
6.2 Typical Wiring .................................................................................................. 6-4
6.2.1 Conventional CT/VT (For reference only) .......................................................................... 6-4

6.2.2 ECT/EVT (For reference only) ........................................................................................... 6-6

6.2.3 CT Requirement ................................................................................................................. 6-8

6.3 Plug-in Module Description ............................................................................ 6-9


6.3.1 PWR Plug-in Module (Power Supply) ................................................................................ 6-9

6.3.2 MON Plug-in Module (Monitor) ........................................................................................ 6-11

6.3.3 AI Plug-in Module (Analog Input) ..................................................................................... 6-14

6.3.4 DSP Plug-in Module (Fault Detector and Protection Calculation) .................................... 6-23

6.3.5 NET-DSP Plug-in Module (GOOSE and SV) ................................................................... 6-24

6.3.6 CH Plug-in Module (Fibre Optical Channel Interface) ...................................................... 6-25

6.3.7 BI Plug-in Module (Binary Input) ...................................................................................... 6-26

6.3.8 BO Plug-in Module (Binary Output) .................................................................................. 6-30

6.3.9 HMI Module...................................................................................................................... 6-31

List of Figures
Figure 6.1-1 Rear view of fixed module position ....................................................................6-1

Figure 6.1-2 Hardware diagram ................................................................................................6-2

Figure 6.1-3 Front view of PCS-902 ..........................................................................................6-3

Figure 6.1-4 Typical rear view of PCS-902 ...............................................................................6-4

Figure 6.2-1 Typical wiring of PCS-902 (conventional CT/VT) ...............................................6-5

Figure 6.2-2 Typical wiring of PCS-902 (ECT/EVT) .................................................................6-7

Figure 6.3-1 View of PWR plug-in module .............................................................................6-10

Figure 6.3-2 Output contacts of PWR plug-in module ..........................................................6-10

PCS-902 Line Distance Relay 6-a


Date: 2011-07-06
6 Hardware

Figure 6.3-3 View of MON plug-in module .............................................................................6-12

Figure 6.3-4 Connection of communication terminal ...........................................................6-14

Figure 6.3-5 Current connection of AI plug-in module .........................................................6-15

Figure 6.3-6 Voltage connection 1 of AI plug-in module ......................................................6-15

Figure 6.3-7 Voltage connection 2 of AI plug-in module ......................................................6-16

Figure 6.3-8 View of AI plug-in module for one CT group input ..........................................6-16

Figure 6.3-9 Current connection of AI plug-in module .........................................................6-18

Figure 6.3-10 Voltage connection of AI plug-in module .......................................................6-18

Figure 6.3-11 View of AI plug-in module for two CT group input .........................................6-19

Figure 6.3-12 Current connection of AI plug-in module .......................................................6-20

Figure 6.3-13 Voltage connection of AI plug-in module .......................................................6-21

Figure 6.3-14 View of AI plug-in module for two CT group input ........................................6-21

Figure 6.3-15 View of DSP plug-in module ............................................................................6-23

Figure 6.3-16 View of NET-DSP plug-in module ....................................................................6-24

Figure 6.3-17 View of CH plug-in module ..............................................................................6-25

Figure 6.3-18 View of BI plug-in module (NR1503) ...............................................................6-26

Figure 6.3-19 View of BI plug-in module (NR1504) ...............................................................6-27

Figure 6.3-20 View of BO plug-in module (NR1521A) ...........................................................6-30

Figure 6.3-21 View of BO plug-in module (NR1521C) ...........................................................6-31

Table of Tables
Table 6.3-1 Terminals′ definition and description..............................................................6-10

Table 6.3-2 Terminal definition of AI module .........................................................................6-16

Table 6.3-3 Terminal definition of AI module .........................................................................6-19

Table 6.3-4 Terminal definition of AI module .........................................................................6-22

6-b PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

6.1 Overview
PCS-902 adopts 64-bit microchip processor CPU produced by FREESCALE as control core for
fault detector and management function, meanwhile, adopts high-speed digital signal processor
DSP for all the protection calculation. 24 points are sampled in every cycle and parallel processing
of sampled data can be realized in each sampling interval to ensure ultrahigh reliability and safety
of the device.

PCS-902 is comprised of intelligent plug-in modules, except that few particular plug-in modules’
position cannot be changed in the whole device (gray plug-in modules as shown in Figure 6.1-1),
other plug-in modules like AI (analog input) and IO (binary input and binary output) can be flexibly
configured in the remaining slot positions.
MON module

PWR module
DSP module

CH Module

BO module

BO module

BO module

BO module
AI module

BI module

BI module

Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1

Figure 6.1-1 Rear view of fixed module position

PCS-902 has 16 slots, PWR plug-in module, MON plug-in module, DSP plug-in module and CH
plug-in module are assigned at fixed slots.

Besides 4 fixed modules are shown in above figure, there are 12 slots can be flexibly configured.
AI plug-in module, BI plug-in module and BO plug-in module can be configured at position
between slot 02, 03 and 06~15. It should be pay attention that AI plug-in module will occupy two
slots.

This device is developed on the basis of our latest software and hardware platform, and the new
platform major characteristics are of high reliability, networking and great capability in
anti-interference. See Figure 6.1-2 for hardware diagram.

PCS-902 Line Distance Relay 6-1


Date: 2011-07-06
6 Hardware

Output Relay
Binary Input
External
Protection
Conventional CT/VT A/D Calculation
DSP

ECVT

Fault
A/D Detector Pickup
DSP Relay

ECVT
ETHERNET
LCD +E
Clock SYN
Power
Uaux LED CPU
Supply
RJ45
Keypad
PRINT

Figure 6.1-2 Hardware diagram

The working process of the device is as shown in above figure: current and voltage from
conventional CT/VT are converted into small voltage signal and sent to DSP module after filtered
and A/D conversion for protection calculation and fault detector respectively (ECVT signal is sent
to the device without small signal and A/D convertion). When DSP module completes all the
protection calculation, the result will be recorded in 64-bit CPU on MON module. DSP module
carries out fault detector, protection logic calculation, tripping output, and MON module perfomes
SOE (sequence of event) record, waveform recording, printing, communication between the
device and SAS and communication between HMI and CPU. When fault detector detects a fault
and picks up, positive power supply for output relay is provided.

The items can be flexibly configured depending on the situations like sampling method of the
device (conventional CT/VT or ECT/EVT), and the mode of binary output (conventional binary
output or GOOSE binary output). The configurations for PCS-900 series based on microcomputer
are classified into standard and optional modules.

Table 6.1-1 PCS-902 module configuration

No. ID Module description Remark


1 NR1101/NR1102 Management and monitor module (MON module) standard
2 NR1401 Analog input module (AI module ) standard

3 NR1161 Protection calculation and fault detector module (DSP module) standard

4 NR1213 Protection communication channel module (CH module) option


5 NR1503/NR1504 Binary input module (BI module) standard

6 NR1521 Binary output module (BO module) standard

7 NR1301 Power supply module (PWR module) standard

6-2 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

No. ID Module description Remark


GOOSE and SV from merging unit by IEC61850-9-2 (NET-DSP
8 NR1136 option
module)
9 Human machine interface module (HMI module) standard

 MON module provides functions like communication with SAS, event record, setting
management etc.

 AI module converts AC current and voltage from current transformers and voltage
transformers respectively to small voltage signal.

 DSP module performs filtering, sampling, protection calculation and fault detector calculation.

 CH module performs information exchange with the remote device through a dedicated
optical fibre channel, multiplex optical fibre channel or PLC channel.

 BI module provides binary inputs via opto-couplers with rating voltage among
24V/110V/125V/220V/250V (configurable).

 BO module provides output contacts for tripping, and signal output contact for annunciation
signal, remote signal, fault and disturbance signal, operation abnormal signal etc.

 PWR module converts DC 250/220/125/110V into various DC voltage levels for modules of
the device.

 HMI module is comprised of LCD, keypad, LED indicators and multiplex RJ45 ports for user
as human-machine interface.

 NET-DSP module receives and sends GOOSE messages, sampled values (SV) from
merging unit by IEC61850-9-2 protocol.

PCS-902 series is made of a 4U height 19” chassis for flush mounting. Components mounted on
its front include a 320×240 dot matrix LCD, a 9 button keypad, 20 LED indicators and a multiplex
RJ45 port. A monolithic micro controller is installed in the equipment for these functions.

Following figures show front and rear views of PCS-902 respectively.

1 11
HEALTHY PCS-902
2 12
ALARM
3 13

4 14
GRP

5 15

6 16 ENT
ESC

7 17

8 18

9 19

10 20

Figure 6.1-3 Front view of PCS-902

PCS-902 Line Distance Relay 6-3


Date: 2011-07-06
6 Hardware

20 LED indicators are, from top to bottom, operation (HEALTHY), self-supervision (ALARM),
others are configurable.

For the 9-button keypad, “ENT” is “enter”, “GRP” is “group number” and “ESC” is “escape”.

NR1102 NR1401 NR1161 NR1213 NR1504 NR1504 NR1521 NR1521 NR1521 NR1521 NR1301
1 5V OK ALM

TX
2 BO_ALM BO_FAIL

RX

TX

RX

DANGER
1 BO_COM1
2 BO_FAIL

3 BO_ALM

4 BO_COM2

5 BO_FAIL

6 BO_ALM

7 OPTO+

8 OPTO-

9
10 PWR+

11 PWR-

12 GND

Figure 6.1-4 Typical rear view of PCS-902

6.2 Typical Wiring


6.2.1 Conventional CT/VT (For reference only)

NR1102 NR1401 NR1161 NR1213 NR1504 NR1521A NR1521C NR1521C NR1301


MON module

PWR module
DSP module

CH Module

BO module

BO module

BO module
AI module

BI module

Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1

The following typical wiring is given based on above hardware configuration

6-4 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

Power supply supervision 0801


Dedicated Channel CH-TX
or
Telecom Equipment CH-RX
BI_01 + 0802
Fibre Optic FC/PC Type (Rear)

*BI plug-in module can be independent common terminal


option


0201
Ia BI_06 + 0807
0202
0203 Not used 0808
0204 Ib
BI_07 + 0809
0205
To parallel line 0206 Ic


0207
From parallel line 0208 IM0 BI_12 + 0814

0213 Not used 0815


Ua Protection Voltage
0214
BI_13 + 0816
0215
0216 Ub


0217
0218 Uc BI_18 + 0821

- 0822
0219
Synchronism Voltage

0220 UB1
1101
0221

Controlled by fault detector


BO_01 1102
0222 UL2
1103
0223 BO_02
element

UB2 1104
0224
1105
BO_03 1106
PWR+ P110


External DC power Power
1121
supply P111 Supply
PWR- BO_11 1122
OPTO+ P107
Power supply for
opto-coupler (24V) P108 1201
OPTO-
BO_01 1202
Signal Binary Output

P101 BO_FAIL 1203


P102 BO_ALM BO_02 1204
P103 COM 1205
P104 BO_FAIL BO_03 1206
P105 BO_ALM

P106 COM 1221


BO_11 1222
485-1A 0101
cable with single point earthing
To the screen of other coaxial

485-1B 0102
COM

1301
Signal Binary Output (option)

SGND 0103 BO_01 1302


0104 1303
BO_02 1304
SYN+ 0101
Clock SYN

SYN- 0102 1305


BO_03 1306
SGND 0103

0104 1321
BO_11 1322
PRINTER

RTS 0105
PRINT

TXD 0106
Multiplex 0012
SGND 0107 RJ45 (Front)
0225
Grounding
Bus

Figure 6.2-1 Typical wiring of PCS-902 (conventional CT/VT)

PCS-902 Line Distance Relay 6-5


Date: 2011-07-06
6 Hardware

PCS-902 (conventional CT/VT and conventional binary input and binary output)

Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1

Module ID NR1102 NR1401 NR1161 NR1213 NR1504 NR1504 NR1521 NR1521 NR1521 NR1521 NR1301

MON AI DSP CH BI BI BO BO BO BO PWR

PCS-902 (conventional CT/VT and GOOSE binary input and binary output)

Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1

Module ID NR1102 NR1401 NR1161 NR1213 NR1136 NR1504 NR1301


NET-
MON AI DSP CH BI PWR
DSP

6.2.2 ECT/EVT (For reference only)

NR1102 NR1161 NR1213 NR1503 NR1521A NR1521C NR1301


MON module

PWR module
DSP module

CH Module

BO module

BO module
BI module

Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1

The following typical wiring is given based on above hardware configuration

6-6 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

Dedicated Channel CH-TX BI_01 + 0801

*BI plug-in module can be common negative


Or
Telecom Equipment CH-RX - 0802

Fibre Optic FC/PC Type (Rear)


BI_02 + 0803
option

- 0804

terminal
Phase A RX BI_03 + 0805

FO interface for SV channel


SV from
ECT/EVT
MU

Phase B - 0806

(LC Type)


Up to 8
Phase C TX
BI_11 + 0821

- 0822

1101

Controlled by fault detector


BO_01 1102
PWR+ P110
External DC power Power 1103
supply Supply BO_02

element
PWR- P111 1104

OPTO+ P107 1105


Power supply for BO_03 1106
opto-coupler (24V) P108
OPTO-


1121
P101 BO_FAIL BO_11 1122
P102 BO_ALM
P103 COM 1201

Signal Binary Output (option)


P104 BO_FAIL BO_01 1202
P105 BO_ALM 1203
P106 COM BO_02 1204

485-1A 0101 1205


BO_03 1206
485-1B 0102
COM
cable with single point earthing
To the screen of other coaxial


SGND 0103 1221
0104 BO_11 1222

SYN+ 0101
Clock SYN

0012
SYN- 0102
SGND 0103 Grounding
0104 Bus
Multiplex
RJ45 (Front)
PRINTER

RTS 0105
PRINT

TXD 0106
SGND 0107 0225

IRIG-B

Figure 6.2-2 Typical wiring of PCS-902 (ECT/EVT)

PCS-902 ECT/EVT, GOOSE binary input and binary output

Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1

Module ID NR1102 NR1161 NR1213 NR1136 NR1504 NR1301


NET-
MON DSP CH BI PWR
DSP

PCS-902 ECT/EVT, conventional binary input and binary output

Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1

Module ID NR1102 NR1161 NR1213 NR1136 NR1504 NR1504 NR1521 NR1521 NR1521 NR1521 NR1301
NET-
MON DSP CH BI BI BO BO BO BO PWR
DSP

In the protection system adopting electronic current and voltage transformer (ECT/EVT), the
merging unit will merge the sample data from ECT/EVT, and then send it to the device through

PCS-902 Line Distance Relay 6-7


Date: 2011-07-06
6 Hardware

multi-mode optical fibre. DSP module receives the data from merging unit through the optical-fibre
interface to complete the protection calculation and fault detector.

The difference between the hardware platform based on ECT/EVT and the hardware platform
based on conventional CT/VT lies in the receiving module of sampled values only, and the device
receives the sampled value from merging unit through multi-mode optical fibre.

6.2.3 CT Requirement
-Rated primary current Ipn:

According to the rated current or maximum load current of primary apparatus.

-Rated continuous thermal current Icth:

According to the maximum load current.

-Rated short-time thermal current Ith and rated dynamic current Idyn:

According to the maximum fault current.

-Rated secondary current Isn

-Accuracy limit factor Kalf:

Ipn Rated primary current (amps)


Icth Rated continuous thermal current (amps)
Ith Rated short-time thermal current (amps)
Idyn Rated dynamic current (amps)
Isn Rated secondary current (amps)
Kalf Accuracy limit factor ()Kalf=Ipal/Ipn
IPal Rated accuracy limit primary current (amps)

Performance verification

Esl > Esl′

Rated secondary limiting e.m.f (volts)


Esl
Esl = kalf×Isn×(Rct+Rbn)
Kalf Accuracy limit factor (Kalf=Ipal/Ipn)
IPal Rated accuracy limit primary current (amps)
Ipn Rated primary current (amps)
Isn Rated secondary current (amps)
Rct Current transformer secondary winding resistance. (ohms)
Rated resistance burden (ohms)
Rbn
Rbn=Sbn/Isn2
Sbn Rated burden (VAs)

Required secondary limiting e.m.f (volts)


Esl′
Esl′ = k×Ipcf ×Isn×(Rct+Rb)/Ipn
k stability factor = 2

6-8 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

Protective checking factor current (amps)


Ipcf
Same as the maximum prospective fault current
Isn Rated secondary current (amps)
Rct Current transformer secondary winding resistance. (ohms)
Real resistance burden (ohms)
Rb
Rb=Rr+2×RL+Rc
Rc Contact resistance, 0.05-0.1 ohm (ohms)
RL Resistance of a single lead from relay to current transformer (ohms)
Rr Impedance of relay phase current input (ohms)
Ipn Rated primary current (amps)

For example:

1. Kalf=30, Isn=5A, Rct=1ohm, Sbn=60VA

Esl = kalf×Isn×(Rct+Rbn) = kalf×Isn×(Rct+ Sbn/Isn2)

= 30×5×(1+60/52)=510V

2. Ipcf=40000A, RL=0.5ohm, Rr=0.1ohm, Rc=0.1ohm, Ipn=2000A

Esl′ = 2×Ipcf×Isn×(Rct+Rb)/Ipn

= 2×Ipcf ×Isn×(Rct+(Rr+2×RL+Rc))/Ipn

= 2×40000×5×(1+(0.1+2×0.5+0.1))/2000=440V

Thus, Esl > Esl′

6.3 Plug-in Module Description


The device consists of PWR plug-in module, MON plug-in module, DSP plug-in module, AI plug-in
module, BI plug-in module, BO plug-in module, CH plug-in module and NET-DSP plug-in module.
Terminal definitions and application of each plug-in module are introduced as follows.

6.3.1 PWR Plug-in Module (Power Supply)


PWR module is a DC/DC or AC/DC converter with electrical insulation between input and output. It
has an input voltage range as described in Chapter 2 “Technical Data”. The standardized output
voltages are +3.3V, +5V, ±12V and +24V DC. The tolerances of the output voltages are
continuously monitored.

The +3.3V DC output provides power supply for the microchip processors, and the +5V DC output
provides power supply for all the electrical elements that need +5V DC power supply in this device.
The ±12V DC output provides power supply for A/D conversion circuits in this device, and the
+24V DC output provides power supply for the static relays of this device.

The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device is
in cold reserve.

PCS-902 Line Distance Relay 6-9


Date: 2011-07-06
6 Hardware

A 12-pin connector is fixed on PWR module. The terminal definition of the connector is described
as below.

NR1301A

5V OK ALM

BO_ALM BO_FAIL

1 BO_COM1
2 BO_FAIL
3 BO_ALM
4 BO_COM2
5 BO_FAIL
6 BO_ALM
7 OPTO+
8 OPTO-
9
10 PWR+
11 PWR-
12 GND

Figure 6.3-1 View of PWR plug-in module

01
BO_FAIL
02
BO_ALM
03

04
BO_FAIL
05
BO_ALM
06

Figure 6.3-2 Output contacts of PWR plug-in module

Terminals′ definition and description is shown as follows:

Table 6.3-1 Terminals′ definition and description

Terminal No. Symbol Description

01 BO_COM1 Common terminal 1

02 BO_FAIL Device failure output 1 (01-02, NC)

03 BO_ALM Device abnormality alarm output 1 (01-03, NO)

04 BO_COM2 Common terminal 2

05 BO_FAIL Device failure output 2 (04-05, NC)

6-10 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

Terminal No. Symbol Description

06 BO_ALM Device abnormality alarm output 2 (04-06, NO)

07 OPTO+ Positive power supply for BI module (24V)

08 OPTO- Negative power supply for BI module (24V)

09 Blank Not used

10 PWR+ Positive input of power supply for the device (250/220V/125/110V)

11 PWR- Negative input of power supply for the device (250/220V/125/110V)

12 GND Grounded connection of the device

Note!

The standard rated voltage of PWR module is self-adaptive to 88~300 Vdc. For
non-standard rated voltage power supply module please specify when place order, and
check if the rated voltage of power supply module is the same as the voltage of power
source before the device being put into service.

PWR module provides terminal 12 and grounding screw for device grounding. Terminal 12
shall be connected to grounding screw and then connected to the earth copper bar of
panel via dedicated grounding wire.

Effective grounding is the most important measure for a device to prevent EMI, so effective
grounding must be ensured before the device is put into service.

PCS-902, like almost all electronic relays, contains electrolytic capacitors. These
capacitors are well known to be subject to deterioration over time if voltage is not applied
periodically. Deterioration can be avoided by powering the relays up once a year.

6.3.2 MON Plug-in Module (Monitor)


MON module consists of high-performance built-in processor, FLASH, SRAM, SDRAM, Ethernet
controller and other peripherals. Its functions include management of the complete device, human
machine interface, communication and waveform recording etc.

MON module uses the internal bus to receive the data from other modules of the device. It
communicates with the LCD module by RS-485 bus. This module comprises 100BaseT Ethernet
interfaces, RS-485 communication interfaces, PPS/IRIG-B differential time synchronization
interface and RS-232 printing interface.

Modules with various combinations of memory and interface are available as shown in the table
below.

PCS-902 Line Distance Relay 6-11


Date: 2011-07-06
6 Hardware

NR1102A NR1102C NR1102B NR1102D NR1102H NR1102I NR1101E

TX TX
ETHERNET ETHERNET ETHERNET ETHERNET ETHERNET
RX RX

TX TX

RX RX

ETHERNET ETHERNET

Figure 6.3-3 View of MON plug-in module

Module ID Memory Interface Terminal No. Usage Physical Layer


2 RJ45 Ethernet To SCADA
01 SYN+
02 SYN- To clock Twisted pair wire
RS-485
03 SGND synchronization
NR1102A 64M DDR
04
05 RXD
RS-232 06 TXD To printer Cable
07 SGND
4 RJ45 Ethernet To SCADA
01 SYN+
02 SYN- To clock Twisted pair wire
RS-485
03 SGND synchronization
NR1102B 64M DDR
04
05 RXD
RS-232 06 TXD To printer Cable
07 SGND
2 RJ45 Ethernet To SCADA
01 SYN+
NR1102C 128M DDR 02 SYN- To clock Twisted pair wire
RS-485
03 SGND synchronization
04

6-12 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

05 RXD
RS-232 06 TXD To printer Cable
07 SGND
4 RJ45 Ethernet To SCADA
01 SYN+
02 SYN- To clock Twisted pair wire
RS-485
03 SGND synchronization
NR1102D 128M DDR
04
05 RXD
RS-232 06 TXD To printer Cable
07 SGND
2 RJ45 Ethernet To SCADA Twisted pair wire
2 FO Ethernet To SCADA Optical fibre SC
01 SYN+
02 SYN- To clock
RS-485 Twisted pair wire
NR1102H 128M DDR 03 SGND synchronization
04
05 RXD
RS-232 06 TXD To printer Cable
07 SGND
2 RJ45 Ethernet To SCADA Twisted pair wire
2 FO Ethernet To SCADA Optical fibre ST
01 SYN+
02 SYN- To clock
RS-485 Twisted pair wire
NR1102I 128M DDR 03 SGND synchronization
04
05 RXD
RS-232 06 TXD To printer Cable
07 SGND
2 RJ45 Ethernet To SCADA
01 485-1A
02 485-1B
RS-485 To SCADA
03 SGND
04
05 485-1A
06 485-1B Twisted pair wire
NR1101E 128M DDR RS-485 To SCADA
07 SGND
08
09 SYN+
10 SYN- To clock
RS-485
11 SGND synchronization
12
RS-232 13 RXD To printer Cable

PCS-902 Line Distance Relay 6-13


Date: 2011-07-06
6 Hardware

14 TXD
15 SGND
16 FGND To earth

The correct connection is shown in Figure 6.3-4. Generally, the shielded cable with two pairs of
twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to connect
the “+” and “–” terminals of difference signal. The other pair of twisted pairs are used to connect
the signal ground of the communication interface. The module reserves a free terminal for all the
communication ports. The free terminal has no connection with any signal of the device, and it is
used to connect the external shields of the cable when connecting multiple devices in series. The
external shield of the cable shall be grounded at one of the ends only.

Twisted pair wire


485-1A 01

485-1B 02

COM
cable with single point earthing
To the screen of other coaxial

SGND 03

04

Twisted pair wire


SYN+ 01

Clock SYN
SYN- 02

SGND 03

04

Cable
RTS 05 PRINT
TXD 06

SGND 07

Figure 6.3-4 Connection of communication terminal

6.3.3 AI Plug-in Module (Analog Input)


AI module is applicable for power plant or substation with conventional VT and CT. It is assigned to
slot numbers 02 and 03. However, the module is not required if the device is used with ECT/EVT.

There are two types of AI module with rating 5 A or 1 A. Please declare which kind of AI module is
needed before ordering. Maximum linear range of the current converter is 40In.

1. One CT group input without synchronism voltage switchover

For one CT group input, three phase currents (Ia, Ib and Ic) and residula current from parallel line
(for mutual compensation) are input to AI module separately. Terminal 01, 03, 05 and 07 are
polarity marks. It is assumed that polarity mark of CT installed on line is at line side.

Three phase voltages (Ua, Ub, and Uc) for protection calculation and one synchronism are input to
AI module. The synchronism voltage could be any phase-to-ground voltage or phase-to-phase
voltage.

If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage
should be disconnected.

6-14 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

P2 S2 P2 S2

P1 S1 P1 S1

02 01 02 01

04 03 04 03

06 05 06 05

08 07 08 07

Figure 6.3-5 Current connection of AI plug-in module

Relevant description about parallel line to refer to “Section 3.25 Fault Location”.

13 14

15 16

17 18

19 20

Figure 6.3-6 Voltage connection 1 of AI plug-in module

PCS-902 Line Distance Relay 6-15


Date: 2011-07-06
6 Hardware

13 14

15 16

17 18

19 20

Figure 6.3-7 Voltage connection 2 of AI plug-in module

NR1401

Ia 01 Ian 02

Ib 03 Ibn 04

Ic 05 Icn 06

IM0 07 IM0n 08

09 10

11 12

Ua 13 Uan 14

Ub 15 Ubn 16

Uc 17 Ucn 18

Us 19 Usn 20

21 22

23 24

Figure 6.3-8 View of AI plug-in module for one CT group input

Table 6.3-2 lists the terminal number and definition of AI module.

Table 6.3-2 Terminal definition of AI module

Terminal No. Definition Definition


01 Ia The current of A-phase (Polarity mark)

6-16 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

Terminal No. Definition Definition


02 Ian The current of A-phase
03 Ib The current of B-phase (Polarity mark)
04 Ibn The current of B-phase
05 Ic The current of C-phase (Polarity mark)
06 Icn The current of C-phase
07 IM0 Residual current of parallel line (Polarity mark)
08 IM0n Residual current of parallel line
09 Reserve
10 Reserve
11 Reserve
12 Reserve
13 Ua The voltage of A-phase (Polarity mark)
14 Uan The voltage of A-phase
15 Ub The voltage of B-phase (Polarity mark)
16 Ubn The voltage of B-phase
17 Uc The voltage of C-phase (Polarity mark)
18 Ucn The voltage of C-phase
19 Us Synchronism voltage (Polarity mark)
20 Usn Synchronism voltage
21 Reserve
22 Reserve
23 Reserve
24 Reserve
25 GND Ground

2. Two CT groups input with synchronism voltage switchover

For two circuit breakers configuration with two CT groups input, three phase currents
corresponding to CB1 and CB2 respectively (Ia1, Ib1, Ic1 and Ia2, Ib2, Ic2) are input to AI module.
Terminal 01, 03, 05, 07, 09 and 11 are polarity marks. It is assumed that polarity mark of CT
installed on line is at line side.

Three phase voltages (Ua, Ub, and Uc) are input to AI module. UB1, UB2 and UL2 are the
synchronism voltage from bus VT and line VT used for synchrocheck, it could be any
phase-to-ground voltage or phase-to-phase voltage. The device can automatically switch
synchronism voltage according to auxiliary contact of CB position or DS position.

If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage
should be disconnected.

PCS-902 Line Distance Relay 6-17


Date: 2011-07-06
6 Hardware

P2 P1 P1 P2 A

S2 S1 S1 S2 C

02 01

04 03

06 05

08 07

10 09

12 11

Figure 6.3-9 Current connection of AI plug-in module

A B C A B C

13 14

15 16

17 18

19 20

21 22

23 24

Figure 6.3-10 Voltage connection of AI plug-in module

6-18 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

NR1401

Ia1 01 Ia1n 02

Ib1 03 Ib1n 04

Ic1 05 Ic1n 06

Ia2 07 Ia2n 08

Ib2 09 Ib2n 10

Ic2 11 Ic2n 12

Ua 13 Uan 14

Ub 15 Ubn 16

Uc 17 Ucn 18

UB1 19 UB1n 20

UL2 21 UL2n 22

UB2 23 UB2n 24

Figure 6.3-11 View of AI plug-in module for two CT group input

Table 6.3-3 lists the terminal number and definition of AI module.

Table 6.3-3 Terminal definition of AI module

Terminal No. Definition Definition


01 Ia1 The current of A-phase (Polarity mark)
02 Ia1n The current of A-phase
03 Ib1 The current of B-phase (Polarity mark)
04 Ib1n The current of B-phase
05 Ic1 The current of C-phase (Polarity mark)
06 Ic1n The current of C-phase
07 Ia2 The current of A-phase (Polarity mark)
08 Ia2n The current of A-phase
09 Ib2 The current of B-phase (Polarity mark)
10 Ib2n The current of B-phase
11 Ic2 The current of C-phase (Polarity mark)
12 Ic2n The current of C-phase
13 Ua The voltage of A-phase (Polarity mark)
14 Uan The voltage of A-phase
15 Ub The voltage of B-phase (Polarity mark)
16 Ubn The voltage of B-phase
17 Uc The voltage of C-phase (Polarity mark)
18 Ucn The voltage of C-phase
19 UB1 The voltage of bus 1 (Polarity mark)
20 UB1n The voltage of bus 1

PCS-902 Line Distance Relay 6-19


Date: 2011-07-06
6 Hardware

Terminal No. Definition Definition


21 UL2 The voltage of line 2 (Polarity mark)
22 UL2n The voltage of line 2
23 UB2 The voltage of bus 2 (Polarity mark)
24 UB2n The voltage of bus 2
25 GND Ground

3. Two CT groups input without synchronism voltage switchover

For two circuit breakers configuration with two CT groups input, three phase currents
corresponding to CB1 and CB2 respectively (Ia1, Ib1, Ic1 and Ia2, Ib2, Ic2), and residula current
from parallel line (for mutual compensation) are input to AI module. Terminal 01, 03, 05, 07, 09, 11
and 13 are polarity marks. It is assumed that polarity mark of CT installed on line is at line side.

Three phase voltages (Ua, Ub, and Uc) for protection calculation and one synchronism are input to
AI module. The synchronism voltage could be any phase-to-ground voltage or phase-to-phase
voltage.

If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage
should be disconnected.

P2 P1 P1 P2 A

S2 S1 S1 S2 C

02 01

04 03

06 05

08 07

10 09

12 11

To parallel line
14 13
From parallel line

Figure 6.3-12 Current connection of AI plug-in module

6-20 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

A B C A B C

15 16

17 18

19 20

21 22

23 24

Figure 6.3-13 Voltage connection of AI plug-in module

NR1401

Ia1 01 Ia1n 02

Ib1 03 Ib1n 04

Ic1 05 Ic1n 06

Ia2 07 Ia2n 08

Ib2 09 Ib2n 10

Ic2 11 Ic2n 12

IM0 13 IM0n 14

Ua 15 Uan 16

Ub 17 Ubn 18

Uc 19 Ucn 20

Us 21 Usn 22

23 24

Figure 6.3-14 View of AI plug-in module for two CT group input

Table 6.3-4 lists the terminal number and definition of AI module.

PCS-902 Line Distance Relay 6-21


Date: 2011-07-06
6 Hardware

Table 6.3-4 Terminal definition of AI module

Terminal No. Definition Definition


01 Ia1 The current of A-phase (Polarity mark)
02 Ia1n The current of A-phase
03 Ib1 The current of B-phase (Polarity mark)
04 Ib1n The current of B-phase
05 Ic1 The current of C-phase (Polarity mark)
06 Ic1n The current of C-phase
07 Ia2 The current of A-phase (Polarity mark)
08 Ia2n The current of A-phase
09 Ib2 The current of B-phase (Polarity mark)
10 Ib2n The current of B-phase
11 Ic2 The current of C-phase (Polarity mark)
12 Ic2n The current of C-phase
13 IM0 Residual current of parallel line (Polarity mark)
14 IM0n Residual current of parallel line
15 Ua The voltage of A-phase (Polarity mark)
16 Uan The voltage of A-phase
17 Ub The voltage of B-phase (Polarity mark)
18 Ubn The voltage of B-phase
19 Uc The voltage of C-phase (Polarity mark)
20 Ucn The voltage of C-phase
21 Us Synchronism voltage (Polarity mark)
22 Usn Synchronism voltage
23 Reserve
24 Reserve
25 GND Ground

6-22 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

6.3.4 DSP Plug-in Module (Fault Detector and Protection Calculation)

NR1161

Figure 6.3-15 View of DSP plug-in module

The module consists of high-performance double DSP (digital signal processor),16-digit


high-accuracy ADC that can perform synchronous sampling and manage other peripherals. One
of double DSP is responsible for protection calculation, and can fulfill analog data acquisition,
protection logic calculation and tripping output. The other is responsible for fault detector, and can
fulfill analog data acquisition, fault detector and providing power supply to output relay.

When the module is connected with conventional CT/VT, it can perform the synchronous data
acquisition through AI plug-in module. When the module is connected with ECT/EVT, it can
receive the real-time synchronous sampled value from merging unit through NET-DSP plug-in
module.

PCS-902 Line Distance Relay 6-23


Date: 2011-07-06
6 Hardware

6.3.5 NET-DSP Plug-in Module (GOOSE and SV)

NR1136A NR1136C

RX

Figure 6.3-16 View of NET-DSP plug-in module

This module consists of high-performance DSP (digital signal processor), 2~8 100Mbit/s
optical-fibre interface (LC type) and selectable IRIG-B interface (ST type). It supports GOOSE and
SV by IEC 61850-9-2 protocols. It can receive and send GOOSE messages to intelligent control
device, and receive SV from MU (merging unit).

This module supports IEEE1588 network time protocol, E2E and P2P defined in IEEE1588
protocol can be selected.This module supports Ethernet IEEE802.3 time adjustment message
format, UDP time adjustment message format and GMRP.

6-24 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

6.3.6 CH Plug-in Module (Fibre Optical Channel Interface)

NR1213

TX

RX

TX

RX

Figure 6.3-17 View of CH plug-in module

PCS-902 series can exchange information with the device at the remote end through a dedicated
optical fibre channel or multiplex channel. The module transmits and receives optical signal using
FC/PC optical connector.

The parameters are shown as follows:

Fiber Optic: Single mode,Rec.G652,1310nm

Transmission power: -12.0±2.0 dBm

Receiving sensitivity: <-40 dBm

Transmission distance: <50 km

Optical overload point: >-8 dBm

Note!

When using dedicated optical fibre channel, if the transmission distance is longer than
50kM, the transmitted power may be enchanced to ensure received power larger than
receiving sensitivity. Please notify supplier before ordering and it will be considered as
special project using 1550nm laser diode.

When using multiplex channel, the sending power of the device is fixed.

PCS-902 Line Distance Relay 6-25


Date: 2011-07-06
6 Hardware

When using channel multiplexing equipment, the parameters are shown as follows:

1. Channel type: digital optical fibre or digital microwave.

2. Interface standard: 2048kbit/s E1

The device′s requirements on the channel are shown as follows:

1. The routine of both direction shall be same to each other, so the time delays of both direction
are the same.

2. The maximum one-way channel propagation delay shall be less than 15 ms.

6.3.7 BI Plug-in Module (Binary Input)


There are two kinds of BI modules available, NR1503 and NR1504. Up to 3 BI modules can be
equipped with one device. The rated voltage can be selected to be 24V/48V (NR1503D or
NR1504D) or 110V/220V/125V/250V (NR1503A or NR1504A).

Each BI module is with a 22-pin connector for 11 binary inputs (NR1503) or 18 binary inputs
(NR1504).

For NR1503, each binary input has independent negative power input of opto-coupler, and can be
configurable. The terminal definition of the connector of BI plug-in module is described as below.
[BI_n] (n=01, 02,…,11 can be configured as a specified binary input by PCS-PC software.)

NR1503

BI_01 01
Opto01- 02
BI_02 03
Opto02- 04
BI_03 05
Opto03- 06
BI_04 07
Opto04- 08
BI_05 09
Opto05- 10
BI_06 11
Opto06- 12
BI_07 13
Opto07- 14
BI_08 15
Opto08- 16
BI_09 17
Opto09- 18
BI_10 19
Opto10- 20
BI_11 21
Opto11- 22

Figure 6.3-18 View of BI plug-in module (NR1503)

For NR1504, all binary inputs share one common negative power input, and can be configurable.
The terminal definition of the connector of BI plug-in module is described as below. [BI_n] (n=01,

6-26 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

02,…,18 can be configured as a specified binary input by PCS-PC software.)

NR1504

Opto+ 01
BI_01 02
BI_02 03
BI_03 04
BI_04 05
BI_05 06
BI_06 07
08
BI_07 09
BI_08 10
BI_09 11
BI_10 12
BI_11 13
BI_12 14
15
BI_13 16
BI_14 17
BI_15 18
BI_16 19
BI_17 20
BI_18 21
COM- 22

Figure 6.3-19 View of BI plug-in module (NR1504)

Terminal description for NR 1503 and NR1504 are shown as follows respectively.

1. NR1503

Terminal No. Symbol Description


01 BI_01 Configurable binary input 1
02 Opto01- Negative supply of configurable binary input 1
03 BI_02 Configurable binary input 2
04 Opto02- Negative supply of configurable binary input 2
05 BI_03 Configurable binary input 3
06 Opto03- Negative supply of configurable binary input 3
07 BI_04 Configurable binary input 4
08 Opto04- Negative supply of configurable binary input 4
09 BI_05 Configurable binary input 5
10 Opto05- Negative supply of configurable binary input 5
11 BI_06 Configurable binary input 6
12 Opto06- Negative supply of configurable binary input 6
13 BI_07 Configurable binary input 7
14 Opto07- Negative supply of configurable binary input 7
15 BI_08 Configurable binary input 8
16 Opto08- Negative supply of configurable binary input 8
17 BI_09 Configurable binary input 9

PCS-902 Line Distance Relay 6-27


Date: 2011-07-06
6 Hardware

Terminal No. Symbol Description


18 Opto09- Negative supply of configurable binary input 9
19 BI_10 Configurable binary input 10
20 Opto10- Negative supply of configurable binary input 10
21 BI_11 Configurable binary input 11
22 Opto11- Negative supply of configurable binary input 11

2. NR1504

Terminal No. Symbol Description


01 Opto+ Positive supply of power supply of the module
02 BI_01 Configurable binary input 1
03 BI_02 Configurable binary input 2
04 BI_03 Configurable binary input 3
05 BI_04 Configurable binary input 4
06 BI_05 Configurable binary input 5
07 BI_06 Configurable binary input 6
08 Blank Not used
09 BI_07 Configurable binary input 7
10 BI_08 Configurable binary input 8
11 BI_09 Configurable binary input 9
12 BI_10 Configurable binary input 10
13 BI_11 Configurable binary input 11
14 BI_12 Configurable binary input 12
15 Blank Not used
16 BI_13 Configurable binary input 13
17 BI_14 Configurable binary input 14
18 BI_15 Configurable binary input 15
19 BI_16 Configurable binary input 16
20 BI_17 Configurable binary input 17
21 BI_18 Configurable binary input 18
22 COM- Common terminal of negative supply of binary inputs

First four binary signals (BI_01, BI_02, BI_03, BI_04) in first BI plug-in module are fixed, they are
[BI_TimeSyn], [BI_Print], [BI_Maintenance] and [BI_RstTarg] respectively.

1. Binary input: [BI_TimeSyn]

It is used to receive clock synchronization signal from clock synchronization device, the binary
input [BI_TimeSyn] will change from “0” to “1” once pulse signal is received. When the device
adopts “Conventional” mode as clock synchronization mode (refer to “Section 7.1 Communication
Settings”), the device can receives PPM (pulse per minute) and PPS (pulse per second). If the
setting [Opt_TimeSyn] is set as other values, this binary input is invalid.

2. Binary input: [BI_Print]

It is used to manually trigger printing latest report when the equipment is configured as manual

6-28 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

printing mode by logic setting [En_AutoPrint]=0. The printer button is located on the panel usually.
If the equipment is configured as automatic printing mode ([En_AutoPrint]=1), report will be printed
automatically as soon as it is formed.

3. Binary input: [BI_Maintenance]

It is used to block communication export when this binary input is energized. During device
maintenance or testing, this binary input is then energized not to send reports via communication
port, local display and printing still work as usual. This binary input should be de-energized when
the device is restored back to normal.

The application of the binary input [BI_Maintenance] for digital substation communication adopting
IEC61850 protocol is given as follows.

1) Processing mechanism for MMS (Manufacturing Message Specification) message

a) The protection device should send the state of this binary input to client.

b) When this binary input is energized, the bit “Test” of quality (Q) in the sent message changes
to “1”.

c) When this binary input is energized, the client cannot control the isolator link and circuit
breaker, modify settings and switch setting group remotely.

d) According to the value of the bit “Test” of quality (Q) in the message sent, the client
discriminate whether this message is maintenance message, and then deal with it correspondingly.
If the message is the maintenance message, the content of the message will not be displayed on
real-time message window, audio alarm not issued, but the picture is refreshed so as to ensure
that the state of the picture is in step with the actual state. The maintenance message will be
stored, and can be inquired, in independent window.

2) Processing mechanism for GOOSE message

a) When this binary input is energized, the bit “Test” in the GOOSE message sent by the
protection device changes to “1”.

b) For the receiving end of GOOSE message, it will compare the value of the bit “Test” in the
GOOSE message received by it with the state of its own binary input (i..e [BI_Maintenance]), the
message will be thought as invalid unless they are conformable.

3) Processing mechanism for SV (Sampling Value) message

a) When this binary input of merging unit is energized, the bit “Test” of quality (Q) of sampling
data in the SV message sent change “1”.

b) For the receiving end of SV message, if the value of bit “Test” of quality (Q) of sampling data
in the SV message received is “1”, the relevant protection functions will be disabled, but under
maintenance state, the protection device should calculate and display the magnitude of sampling
data.

c) For duplicated protection function configurations, all merging units of control module
configured to receive sampling should be also duplicated. Both dual protection devices and dual

PCS-902 Line Distance Relay 6-29


Date: 2011-07-06
6 Hardware

merging units should be fully independent each other, and one of them is in maintenance state will
not affect the normal operation of the other.

4. Binary input: [BI_RstTarg]

It is used to reset latching signal relay and LCD displaying. The reset is done by pressing a button
on the panel.

Note!

The rated voltage of binary input is optional: 24V, 48V, 110V, 125V, 220V or 250V, which
must be specified when placed order. It is necessary to check whether the rated voltage of
BI module complies with site DC supply rating before put the relay in service.

6.3.8 BO Plug-in Module (Binary Output)


NR1521A and NR1521C modules are two standard binary output modules. The contacts provided
by NR1521A and NR1521C are all normally open (NO) contacts. Output contact can be configured
as a specified tripping output contact and a signal output contact respectively by PCS-PC software
according to user requirement.

NR1521A can provide 11 output contacts controlled by fault detector.

NR1521A

BO_01+ 01 01
BO_01
BO_01- 02 02
BO_02+ 03 03
BO_02
BO_02- 04 04
BO_03+ 05 05
BO_03
BO_03- 06 06
BO_04+ 07 07
BO_04
BO_04- 08 08
BO_05+ 09 09
BO_05
BO_05- 10 10
BO_06+ 11 11
BO_06
BO_06- 12 12
BO_07+ 13 13
BO_07
BO_07- 14 14
BO_08+ 15 15
BO_08
BO_08- 16 16
BO_09+ 17 17
BO_09
BO_09- 18 18
BO_10+ 19 19
BO_10
BO_10- 20 20
BO_11+ 21 21
BO_11
BO_11- 22 22

Figure 6.3-20 View of BO plug-in module (NR1521A)

NR1521C can provide 11 output contacts without controlled by fault detector.

6-30 PCS-902 Line Distance Relay


Date: 2011-07-06
6 Hardware

NR1521C

BO_01+ 01 01
BO_01
BO_01- 02 02
BO_02+ 03 03
BO_02
BO_02- 04 04
BO_03+ 05 05
BO_03
BO_03- 06 06
BO_04+ 07 07
BO_04
BO_04- 08 08
BO_05+ 09 09
BO_05
BO_05- 10 10
BO_06+ 11 11
BO_06
BO_06- 12 12
BO_07+ 13 13
BO_07
BO_07- 14 14
BO_08+ 15 15
BO_08
BO_08- 16 16
BO_09+ 17 17
BO_09
BO_09- 18 18
BO_10+ 19 19
BO_10
BO_10- 20 20
BO_11+ 21 21
BO_11
BO_11- 22 22

Figure 6.3-21 View of BO plug-in module (NR1521C)

6.3.9 HMI Module


The display panel consists of liquid crystal display module, keyboard, LED and ARM processor.
The functions of ARM processor include display control of the liquid crystal display module,
keyboard processing, and exchanging data with the CPU through LAN port etc. The liquid crystal
display module is a high-performance grand liquid crystal panel with soft back lighting, which has a
user-friendly interface and an extensive display range.

PCS-902 Line Distance Relay 6-31


Date: 2011-07-06
6 Hardware

6-32 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

7 Settings

Table of Contents
7 Settings ............................................................................................. 7-a
7.1 Communication Settings ................................................................................ 7-1
7.1.1 Setting Description ............................................................................................................. 7-2

7.1.2 Access Path ....................................................................................................................... 7-5

7.2 System Settings .............................................................................................. 7-5


7.2.1 Setting Description ............................................................................................................. 7-5

7.2.2 Access Path ....................................................................................................................... 7-6

7.3 Device Settings ............................................................................................... 7-6


7.3.1 Setting Description ............................................................................................................. 7-6

7.3.2 Access Path ....................................................................................................................... 7-7

7.4 Protection Settings ......................................................................................... 7-7


7.4.1 Setting Description ............................................................................................................. 7-7

7.4.2 Access Path ..................................................................................................................... 7-24

Table of Tables
Table 7.1-1 Communication settings........................................................................................7-1

Table 7.2-1 System settings ......................................................................................................7-5

Table 7.3-1 Device settings .......................................................................................................7-6

PCS-902 Line Distance Relay 7-a


Date: 2011-07-06
7 Settings

7-b PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

The device has some setting groups for protection to coordinate with the mode of power system
operation, one of which is assigned to be active. However, equipment parameters are common for
all protection setting groups.

Note!

All current settings in this chapter are secondary current converted from primary current by
CT ratio. Zero-sequence current or voltage setting is configured according to 3I0 or 3U0
and negative sequence current setting according to I2 or U2.

7.1 Communication Settings


Table 7.1-1 Communication settings

No. Item Range


1 IP_LAN1 000.000.000.000~255.255.255.255
2 Mask_LAN1 000.000.000.000~255.255.255.255
3 IP_LAN2 000.000.000.000~255.255.255.255
4 Mask_LAN2 000.000.000.000~255.255.255.255
5 En_LAN2 0 or 1
6 IP_LAN3 000.000.000.000~255.255.255.255
7 Mask_LAN3 000.000.000.000~255.255.255.255
8 En_LAN3 0 or 1

9 IP_LAN4 000.000.000.000~255.255.255.255
10 Mask_LAN4 000.000.000.000~255.255.255.255
11 En_LAN4 0 or 1

12 Gateway 000.000.000.000~255.255.255.255
13 En_Broadcast 0 or 1
14 Addr_RS485A 0~255

15 Baud_RS485A 4800,9600,19200,38400,57600,115200 (bps)

16 Protocol_RS485A 0, 1 or 2

17 Addr_RS485B 0~255

18 Baud_RS485B 4800,9600,19200,38400,57600,115200 (bps)

19 Protocol_RS485B 0, 1 or 2

20 Threshold_Measmt 0~100%
21 Period_Measmt 0~65535s
22 Format_Measmt 0, 1
23 Baud_Printer 4800,9600,19200,38400,57600,115200 (bps)

24 En_AutoPrint 0 or 1
Conventional
SAS
25 Opt_TimeSyn
Advanced
NoTImeSyn

PCS-902 Line Distance Relay 7-1


Date: 2011-07-06
7 Settings

No. Item Range


26 IP_Server_SNTP 000.000.000.000~255.255.255.255
27 OffsetHour_UTC -12~+12 (hrs)
28 OffsetMinute_UTC 0~60 (min)

7.1.1 Setting Description


1. IP_LAN1, IP_LAN2, IP_LAN3, IP_LAN4

IP address of Ethernet port 1, Ethernet port 2, Ethernet port 3 and Ethernet port 4

2. Mask_LAN1, Mask_LAN2, Mask_LAN3, Mask_LAN4

Subnet mask of Ethernet port 1, Ethernet port 2, Ethernet port 3 and Ethernet port 4

3. En_LAN2, En_LAN3, En_LAN4

Put Ethernet port 2, Ethernet port 3 and Ethernet port 4 in service

They are used for Ethernet communication based on the IEC 60870-5-103 protocol. When the IEC
61850 protocol is applied, the IP address of Ethernet A will be GOOSE source MAC address.

Ethernet port 1 is always in service by default.

4. Gateway

IP address of Gateway (router)

5. En_Broadcast

This setting is only used only for IEC 60870-5-103 protocol. If NR network IEC 60870-5-103
protocol is used, the setting must be set as “1”.

0: the device does not send UDP messages through network

1: the device sends UDP messages through network

6. Addr_RS485A, Addr_RS485B

They are the device′s communication address used to communicate with the SCADA or RTU via
serial ports (port A and port B).

7. Baud_RS485A, Baud_RS485B

Baud rate of rear RS-485 serial port A or B

8. Protocol_RS485A, Protocol_RS485B

Communication protocol of rear RS-485 serial port A or B

0: IEC 60870-5-103 protocol

1: Reserved

2: Modbus Protocol

7-2 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

Note!

Above table listed all the communication settings, the device delivered to the user maybe
only show some settings of them according to the communication interface configuration.
If only the Ethernet ports are applied, the settings about the serial ports (port A and port B)
are not listed in this submenu. And the settings about the Ethernet ports only listed in this
submenu according to the actual number of Ethernet ports.

The standard arrangement of the Ethernet port is two, at most four (predetermined when
ordering). Set the IP address according to actual arrangement of Ethernet numbers and
the un-useful port/ports need not be configured. If the PCS-PC configuration tool auxiliary
software is connected with this device through the Ethernet, the IP address of the PCS-PC
must be set as one of the available IP address of this device.

9. Threshold_Measmt

Threshold value of sending measurement values to SCADA through IEC 60870-5-103 or


IEC61850 protocol.

Default value: “1%”

10. Period_Measmt

The time period for equipment sends measurement data to SCADA through IEC 60870-5-103
protocol.

Default value: “60”

11. Format_Measmt

The setting is used to select the format of measurement data sent to SCADA through IEC
60870-5-103 protocol.

0: GDD data type through IEC103 protocol is 12

1: GDD data type through IEC103 protocol is 7, i.e. 754 short real number of IEEE standard

12. Baud_Printer

Baud rate of printer port

13. En_AutoPrint

If automatic print is required for fault report after protection operating, it is set as “1”. Otherwise, it
should be set to “0”.

14. Opt_TimeSyn

There are four selections for clock synchronization of device, shown as follows.

 Conventional

PPS (RS-485): Pulse per second (PPS) via RS-485 differential level

PCS-902 Line Distance Relay 7-3


Date: 2011-07-06
7 Settings

IRIG-B (RS-485): IRIG-B via RS-485 differential level

PPM (DIN): Pulse per minute (PPM) via the binary input [BI_TimeSyn]

PPS (DIN): Pulse per second (PPS) via the binary input [BI_TimeSyn]

 SAS

SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network

SNTP (BC): Broadcast SNTP mode via Ethernet network

Message (IEC103): Clock messages through IEC103 protocol

 Advanced

IEEE1588: Clock message via IEEE1588

IRIG-B (Fiber): IRIG-B via optical-fibre interface

PPS (Fiber) PPS: Pulse per second (PPS) via optical-fibre interface

 NoTimeSync

When no time synchronization signal is connected to the device, please select this option and the
alarm message [Alm_TimeSync] will not be issued anymore.

“Conventional” mode and “SAS” mode are always be supported by the device, but “Advanced”
mode is only supported when NET-DSP module is equipped. The alarm signal [Alm_TimeSyn]
may be issued to remind user loss of time synchronization signals.

1) When “SAS” is selected, if there is no conventional clock synchronization signal, the device
will not send the alarm signal [Alm_TimeSyn]. When “Conventional” mode is selected, if there
is no conventional clock synchronization signal, “SAS” mode will be enabled automatically
with the alarm signal [Alm_TimeSyn] issued simultaneously.

2) When “Advanced” mode is selected, if there is no conventional clock synchronization signal


connected to NET-DSP module, “SAS” mode is enabled automatically with the alarm signal
[Alm_TimeSyn] issued simultaneously.

3) When “NoTimeSyn” mode is selected, the device will not send alarm signals without time
synchronization signal. But the device can be still synchronized if receiving time
synchronization signal.

Note!

The clock message via IEC 60870-5-103 protocol is invalid when the device receives the
IRIG-B signal through RCS-485 port.

15. IP_Server_SNTP

It is the address of the SNTP time synchronization server which sends SNTP timing messages to
the relay or BCU.

7-4 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

16. OffsetHour_UTC, OffsetMinute_UTC

If the IEC61850 protocol is adopted in substations, the time tags of communication messages are
required according to UTC (Universal Time Coordinated) time.

The setting [OffsetHour_UTC] is used to set the hour offset of the current time zone to the GMT
(Greenwich Mean Time) zone; for example, if a relay is applied in China, the time zone of China is
east 8th time zone, so this setting is set as “8”. The setting [OffsetMinute_UTC] is used to set the
minute offset of the current time zone to the GMT zone.

Time zone GMT zone East 1st East 2nd East 3rd East 4th East 5th
Setting 0 1 2 3 4 5
th th th th th
Time zone East 6 East 7 East 8 East 9 East 10 East 11th
Setting 6 7 8 9 10 11
th st nd rd th
Time zone East/West 12 West 1 West 2 West 3 West 4 West 5th
Setting 12/-12 -1 -2 -3 -4 -5
th th th th th
Time zone West 6 West 7 West 8 West 9 West 10 West 11th
Setting -6 -7 -8 -9 -10 -11

7.1.2 Access Path


MainMenuSettingsDevice SetupComm Settings

7.2 System Settings


Table 7.2-1 System settings

No. Item Range Unit

1 Active_Grp 1~10
2 Opt_SysFreq 50 or 60 Hz

3 PrimaryEquip_Name Maximum 12 character


4 U1n 33~65500 kV

5 U2n 80~220 V

6 I1n 0~6000 A

7 I2n 1 or 5 A

7.2.1 Setting Description


1. Active_Grp

The number of active setting group, 10 setting groups can be configured for protection settings,
and only one is active at a time.

2. PrimaryEquip_Name

It is recognized by the device automatically. Such setting is used for printing messages.

3. Opt_SysFreq

It is option of system frequency, and can be set as 50Hz or 60Hz.

PCS-902 Line Distance Relay 7-5


Date: 2011-07-06
7 Settings

4. Un1

Primary rated voltage of VT;

5. Un2

Secondary rated voltage of VT;

6. In1

Primary rated current of CT;

7. In2

Secondary rated current of CT;

7.2.2 Access Path


MainMenuSettingsSystem Settings

7.3 Device Settings


Table 7.3-1 Device settings

No. Item Range


1 HDR_EncodeMode GB18030, UTF-8
2 Opt_Caption_103 0 or 1
3 Bxx.Un_BinaryInput 24V, 48V, 110V, 220V

7.3.1 Setting Description


1. HDR_EncodeMode

Select encoding format of header (HDR) file COMTRADE recording file. Default value is “UTF-8”.

2. Opt_Caption_103

Select the caption language sent to SAS via IEC103 protocol.

Default value is 0.

0: Local language; 1: Chinese

Two logic settings to select encoding format of header file and caption language of IEC103
protocol.

Default value of [HDR_EncodeMode] is 1 (i.e. UTF-8 code) and please set it to 0(i.e. GB18030)
according to the special requirement.

Default value of [Opt_Caption_103] is 1 (i.e. Chinese), and please set it to 0 (i.e. local language) if
the SAS is supplied by China Manufacturer.

3. Bxx.Un_BinaryInput

This setting is used to set voltage level of binary input module. If low-voltage BI module is

7-6 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

equipped, 24V or 48V can be set according to the actual requirement, and if high-voltage BI
module is equipped, 110V or 220V can be set according to the actual requirement.

Bxx: this plug-in module is inserted in slot Bxx.

7.3.2 Access Path


MainMenuSettingsDevice SetupDevice Settings

7.4 Protection Settings


All settings of protection are based on secondary ratings of VT and CT. For the specific project,
some settings relevant to synchrocheck module, auto-reclosing module and breaker failure
protection module maybe with the suffix of “_CB1” and “_CB2” what represent the settings
correspond to synchrocheck module, auto-reclosing module and breaker failure protection module
for circuit breaker 1 and circuit breaker 2 respectively.

Unn: rated secondary phase-to-phase voltage.

Un: rated secondary phase-to-ground voltage.

In: rated secondary current.

7.4.1 Setting Description


7.4.1.1 Line Parameters

No. Item Remark Range


1 X1L Positive sequence reactance of the line (0.000~2Unn)/In (ohm)
2 R1L Positive sequence resistance of the line (0.000~2Unn)/In (ohm)
3 X0L Zero-sequence reactance of the line (0.000~2Unn)/In (ohm)
4 R0L Zero-sequence resistance of the line (0.000~2Unn)/In (ohm)
5 X0M Line mutual zero-sequence reactance (0.000~2Unn)/In (ohm)
6 R0M Line mutual zero-sequence resistance (0.000~2Unn)/In (ohm)
7 LineLength Total length of the line 0.00~655.35 (km)
8 phi1_Reach Phase angle of line positive sequence impedance 45.00~89.00 (Deg)
9 phi0_Reach Phase angle of line zero-sequence impedance 45.00~89.00 (Deg)
10 K0 Zero-sequence compensation factor 0.000~4.000

7.4.1.2 Fault Detector Settings (FD)

No. Item Remark Range


1 FD.DPFC.I_Set Current setting of DPFC current FD element (0.050~30.000)×In (A)
2 FD.ROC.3I0_Set Current setting of neutral current FD element (0.050~30.000)×In (A)

7.4.1.3 DPFC Distance Protection Settings (21D)

No. Item Remark Range


1 21D.Z_DPFC Impedance setting of DPFC distance protection (0.000~2Unn)/In (ohm)
2 21D.En_DPFC Enable DPFC distance protection 0 or 1

PCS-902 Line Distance Relay 7-7


Date: 2011-07-06
7 Settings

7.4.1.4 Distance Protection Settings with Mho Characteristic (21M)

No. Item Remark Range


Phase shift angle of phase-to-ground distance
1 21M.ZG.phi_Shift 0, 15 or 30 (Deg)
element
2 21M.ZP.phi_Shift Phase shift angle of phase-to-phase distance element 0, 15 or 30 (Deg)
Impedance setting of zone 1 of phase-to-ground
3 21M.ZG1.Z_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 1 of phase-to-ground distance
4 21M.ZG1.t_Op 0.000~10.000 (s)
element
5 21M.ZG1.En Enable zone 1 of phase-to-ground distance element 0 or 1
Enable phase-to-ground zone 1 of distance protection
6 21M.ZG1.En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 1 of phase-to-phase
7 21M.ZP1. Z_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 1 of phase-to-phase distance
8 21M.ZP1.t_Op 0.000~10.000 (s)
element
9 21M.ZP1.En Enable zone 1 of phase-to-phase distance element 0 or 1
Enable phase-to-phase zone 1 of distance protection
10 21M.ZP1.En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 2 of phase-to-ground
11 21M.ZG2.Z_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 2 of phase-to-ground distance
12 21M.ZG2.t_Op 0.000~10.000 (s)
element
13 21M.ZG2.En Enable zone 2 of phase-to-ground distance element 0 or 1
Enable phase-to-ground zone 2 of distance protection
14 21M.ZG2.En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 2 of phase-to-phase
15 21M.ZP2. Z_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 2 of phase-to-phase distance
16 21M.ZP2.t_Op 0.000~10.000 (s)
element
17 21M.ZP2.En Enable zone 2 of phase-to-phase distance element 0 or 1
Enable phase-to-phase zone 2 of distance protection
18 21M.ZP2.En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 3 of phase-to-ground
19 21M.ZG3. Z_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 3 of phase-to-ground distance
20 21M.ZG3. t_Op 0.000~10.000 (s)
element
21 21M.ZG3.En Enable zone 3 of phase-to-ground distance element 0 or 1
Enable phase-to-ground zone 3 of distance protection
22 21M.ZG3.En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 3 of phase-to-phase
23 21M.ZP3. Z_Set (0.000~2Unn)/In (ohm)
distance element

7-8 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

Time delay of zone 3 of phase-to-phase distance


24 21M.ZP3.t_Op 0.000~10.000 (s)
element
25 21M.ZP3.En Enable zone 3 of phase-to-phase distance element 0 or 1
Enable phase-to-phase zone 3 of distance protection
26 21M.ZP3.En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 4 of pilot positive distance
27 21M.Z4.Z_Fwd (0.000~2Unn)/In (ohm)
element
Impedance setting of zone 4 of pilot reversal distance
28 21M.Z4.Z_Rev (0.000~2Unn)/In (ohm)
element
29 21M.Z4.t_Op Time delay of zone 4 of distance element 0.000~10.000 (s)
30 21M.ZG4.En Enable zone 4 of phase-to-ground distance element 0 or 1
31 21M.ZP4.En Enable zone 4 of phase-to-phase distance element 0 or 1
Enable phase-to-ground zone 4 of distance protection
32 21M.ZG4.En_BlkAR 0 or 1
operation to block AR
Enable phase-to-phase zone 4 of distance protection
33 21M.ZP4.En_BlkAR 0 or 1
operation to block AR
34 21M.R_Blinder Resistive impedance reach of distance element (0.000~2Unn)/In (ohm)
35 21M.En_Blinder Enable blinder element 0 or 1

7.4.1.5 Distance Protection Settings with Quad Characteristic (21Q)

No. Item Remark Range


Resistive component of zero-sequence compensation
1 21Q.Real_K0 -2.000~2.000
coefficient
Imaginary component of zero-sequence
2 21Q.Imag_K0 -2.000~2.000
compensation coefficient
Impedance setting of zone 1 of phase-to-ground
3 21Q.ZG1.Z_Set (0.000~2Unn)/In (ohm)
distance element
Resistance setting of zone 1 of phase-to-ground
4 21Q.ZG1.R_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 1 of phase-to-ground distance
5 21Q.ZG1.t_Op 0.000~10.000 (s)
element
6 21Q.ZG1.En Enable zone 1 of phase-to-ground distance element 0 or 1
Enable phase-to-ground zone 1 of distance protection
7 21Q.ZG1.En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 1 of phase-to-phase
8 21Q.ZP1. Z_Set (0.000~2Unn)/In (ohm)
distance element
Resistance setting of zone 1 of phase-to-phase
9 21Q.ZP1.R_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 1 of phase-to-phase distance
10 21Q.ZP1.t_Op 0.000~10.000 (s)
element
11 21Q.ZP1.En Enable zone 1 of phase-to-phase distance element 0 or 1
Enable phase-to-phase zone 1 of distance protection
12 21Q.ZP1.En_BlkAR 0 or 1
operation to block AR

PCS-902 Line Distance Relay 7-9


Date: 2011-07-06
7 Settings

Impedance setting of zone 2 of phase-to-ground


13 21Q.ZG2.Z_Set (0.000~2Unn)/In (ohm)
distance element
Resistance setting of zone 2 of phase-to-ground
14 21Q.ZG2.R_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 2 of phase-to-ground distance
15 21Q.ZG2.t_Op 0.000~10.000 (s)
element
16 21Q.ZG2.En Enable zone 2 of phase-to-ground distance element 0 or 1
Enable phase-to-ground zone 2 of distance protection
17 21Q.ZG2.En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 2 of phase-to-phase
18 21Q.ZP2.Z_Set (0.000~2Unn)/In (ohm)
distance element
Resistance setting of zone 2 of phase-to-phase
19 21Q.ZP2.R_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 2 of phase-to-phase distance
20 21Q.ZP2. t_Op 0.000~10.000 (s)
element
21 21Q.ZP2.En Enable zone 2 of phase-to-phase distance element 0 or 1
Enable phase-to-phase zone 2 of distance protection
22 21Q.ZP2. En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 3 of phase-to-ground
23 21Q.ZG3.Z_Set (0.000~2Unn)/In (ohm)
distance element
Resistance setting of zone 3 of phase-to-ground
24 21Q.ZG3.R_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 3 of phase-to-ground distance
25 21Q.ZG3.t_Op 0.000~10.000 (s)
element
26 21Q.ZG3.En Enable zone 3 of phase-to-ground distance element 0 or 1
Enable phase-to-ground zone 3 of distance protection
27 21Q.ZG3. En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 3 of phase-to-phase
28 21Q.ZP3.Z_Set (0.000~2Unn)/In (ohm)
distance element
Resistance setting of zone 3 of phase-to-phase
29 21Q.ZP3.R_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 3 of phase-to-phase distance
30 21Q.ZP3. t_Op 0.000~10.000 (s)
element
31 21Q.ZP3.En Enable zone 3 of phase-to-phase distance element 0 or 1
Enable phase-to-phase zone 3 of distance protection
32 21Q.ZP3. En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 4 of phase-to-ground
33 21Q.ZG4.Z_Set (0.000~2Unn)/In (ohm)
distance element
Resistance setting of zone 4 of phase-to-ground
34 21Q.ZG4.R_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 4 of phase-to-ground distance
35 21Q.ZG4.t_Op 0.000~10.000 (s)
element
36 21Q.ZG4.En Enable zone 4 of phase-to-ground distance element 0 or 1

7-10 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

Enable phase-to-ground zone 4 of distance protection


37 21Q.ZG4. En_BlkAR 0 or 1
operation to block AR
Impedance setting of zone 4 of phase-to-phase
38 21Q.ZP4.Z_Set (0.000~2Unn)/In (ohm)
distance element
Resistance setting of zone 4 of phase-to-phase
39 21Q.ZP4.R_Set (0.000~2Unn)/In (ohm)
distance element
Time delay of zone 4 of phase-to-phase distance
40 21Q.ZP4. t_Op 0.000~10.000 (s)
element
41 21Q.ZP4.En Enable zone 4 of phase-to-phase distance element 0 or 1
Enable phase-to-phase zone 4 of distance protection
42 21Q.ZP4. En_BlkAR 0 or 1
operation to block AR

7.4.1.6 Pilot Distance Zone Settings

No. Item Remark Range


1 21M.Pilot.Z_Set Impedance setting of pilot distance element (0.000~2Unn)/In (ohm)
2 21Q.Pilot.Z_Set Impedance setting of pilot distance element (0.000~2Unn)/In (ohm)
3 21M.Pilot.Z_Rev Impedance setting of pilot reversal distance element (0.000~2Unn)/In (ohm)
4 21Q.Pilot.Z_Rev Impedance setting of pilot reversal distance element (0.000~2Unn)/In (ohm)
5 21Q.Pilot.R_Set Resistance setting of pilot distance element (0.000~2Unn)/In (ohm)
6 21Q.Pilot.R_Rev Resistance setting of pilot reversal distance element (0.000~2Unn)/In (ohm)

7.4.1.7 Power Swing Detection Settings (68)

No. Item Remark Range


1 68.En Enable power swing detection 0 or 1

7.4.1.8 Power Swing Blocking Releasing Settings (PSBR)

No. Item Remark Range


1 21M.I_PSBR Current setting of PSBR (0.050~30.000)×In (A)
2 21Q.I_PSBR Current setting for power swing blocking (0.050~30.000)×In (A)
3 21M.Z1.En_PSBR Enable PSBR for zone 1 of distance element 0 or 1
4 21Q.Z1.En_PSBR Enable PSBR for zone 1 of distance element 0 or 1
5 21M.Z2.En_PSBR Enable PSBR for zone 2 of distance element 0 or 1
6 21Q.Z2.En_PSBR Enable PSBR for zone 2 of distance element 0 or 1
7 21M.Z3.En_PSBR Enable PSBR for zone 3 of distance element 0 or 1
8 21Q.Z3.En_PSBR Enable PSBR for zone 3 of distance element 0 or 1
9 21M.Z4.En_PSBR Enable PSBR for zone 4 of distance element 0 or 1
10 21Q.Z4.En_PSBR Enable PSBR for zone 4 of distance element 0 or 1
11 21M.Pilot.En_PSBR Enable PSBR for pilot distance element 0 or 1
12 21Q.Pilot.En_PSBR Enable PSBR for pilot element 0 or 1

7.4.1.9 Distance SOTF Protection Settings (21SOTF)

No. Item Remark Range


1 21SOTF.En Enable accelerating distance protection to trip 0 or 1

PCS-902 Line Distance Relay 7-11


Date: 2011-07-06
7 Settings

Enable stage 2 of accelerating distance protection


2 21SOTF.Z2.En_ManCls to trip when manual closing or auto-reclosing onto 0 or 1
an existing fault
Enable stage 3 of accelerating distance protection
3 21SOTF.Z3.En_ManCls to trip when manual closing or auto-reclosing onto 0 or 1
an existing fault
Enable stage 4 of accelerating distance protection
4 21SOTF.Z4.En_ManCls to trip when manual closing or auto-reclosing onto 0 or 1
an existing fault
5 21SOTF.Z2.En_3PAR Enable 3-pole auto-reclosing mode for zone 2 0 or 1
6 21SOTF.Z3.En_3PAR Enable 3-pole auto-reclosing mode for zone 3 0 or 1
7 21SOTF.Z4.En_3PAR Enable 3-pole auto-reclosing mode for zone 4 0 or 1
8 21SOTF.Z2.En_PSBR Enable PSBR for zone 2 of distance element 0 or 1
9 21SOTF.Z3.En_PSBR Enable PSBR for zone 3 of distance element 0 or 1
10 21SOTF.Z4.En_PSBR Enable PSBR for zone 4 of distance element 0 or 1
Enable accelerating distance protection to trip
11 21SOTF.En_PDF when fault occurs on healthy phase under pole 0 or 1
discrepancy situation
Time delay of accelerating distance protection to
12 21SOTF.t_PDF trip when fault occurs on healthy phase under pole 0.000~10.000 (s)
discrepancy situation
13 SOTF.Opt_Mode_ManCls Option of manual SOTF mode 0, 1 or 2

7.4.1.10 Optical Pilot Channel Settings

No. Item Remark Range


1 FOx.LocID Indentity code of the device at local end 0-65535
2 FOx.RmtID Indentity code of the device at remote end 0-65535
3 FOx.En_IntClock Option of internal clock or external clock 0 or 1

7.4.1.11 Pilot Distance Protection Settings (85)

No. Item Remark Range


1 85.Opt_PilotMode Option of pilot scheme 0~2
Option of phase-segregated signal scheme or
2 85.Opt_Ch_PhSeg 0 or 1
three-phase signal scheme
3 85.En_WI Enable weak infeed scheme 0 or 1
4 85.U_UV_WI Undervoltage setting of weak infeed logic 0~0.8Un (V)
5 85.Z.En Enable pilot distance protection 0 or 1
6 85.En_Unblocking1 Enable unblocking scheme 0 or 1
Time delay for blocking scheme of pilot distance
7 85.t_DPU_Blocking1 0.000~1.000 (s)
protection operation
8 85.t_DDO_CR1 Time delay dropoff for current reversal logic 0.000~1.000 (s)
9 85.t_DPU_CR1 Time delay pickup for current reversal logic 0.000~1.000 (s)

7-12 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

10 85.ZX.En Enable zone extension protection 0 or 1


Pickup time delay for zone extension protection
11 85.t_DPU_ZX 0.000~10.000 (s)
operation

7.4.1.12 Pilot Directional Earth-fault Protection Settings (85)

No. Item Remark Range


1 85.DEF.En Enable pilot directional earth-fault protection 0 or 1
Enable pilot directional earth-fault protection operate
2 85.DEF.En_BlkAR 0 or 1
to block AR
Enable independent pilot channel for pilot directional
3 85.DEF_En_IndepCh 0 or 1
earth-fault protection
Enable unblocking scheme for pilot DEF via pilot
4 85.En_Unblocking2 0 or 1
channel 2
Current setting of pilot directional earth-fault
5 85.DEF.3I0_Set (0.050~30.000)×In (A)
protection
6 85.DEF.t_DPU Time delay of pilot directional earth-fault protection 0.001~10.000 (s)
Time delay pickup for current reversal logic when pilot
7 85.t_DPU_CR2 directional earth-fault protection adopts independent 0.000~1.000 (s)
pilot channel 2
Time delay dropoff for current reversal logic when
8 85.t_DDO_CR2 pilot directional earth-fault protection adopts 0.000~1.000 (s)
independent pilot channel 2

7.4.1.13 Current Direction Settings

No. Item Remark Range


The characteristic angle of directional phase
1 RCA_OC 45.00~89.00 (Deg)
overcurrent element
The characteristic angle of directional earth fault
2 RCA_ROC 45.00~89.00 (Deg)
element
The characteristic angle of directional
3 RCA_NegOC 45.00~89.00 (Deg)
negative-sequence overcurrent element
4 Z0_Comp Zero-sequence compensation impedance setting (0.000~2Unn)/In (ohm)
5 Z2_Comp Negative-sequence compensation impedance setting (0.000~2Unn)/In (ohm)

7.4.1.14 Phase Overcurrent Protection (50/51P)

No. Item Remark Range


Setting of second harmonic component for blocking
1 50/51P.k_Hm2 0.000~1.000
phase overcurrent elements
Current setting for stage 1 of phase overcurrent
2 50/51P1.I_Set (0.050~30.000)×In (A)
protection
Time delay for stage 1 of phase overcurrent
3 50/51P1.t_Op 0.000~20.000 (s)
protection
4 50/51P1.En Enable stage 1 of phase overcurrent protection 0 or 1

PCS-902 Line Distance Relay 7-13


Date: 2011-07-06
7 Settings

Direction option for stage 1 of phase overcurrent


5 50/51P1.Opt_Dir 0, 1 or 2
protection
Enable second harmonic blocking for stage 1 of
6 50/51P1.En_Hm2 0 or 1
phase overcurrent protection
Option of characteristic curve for stage 1 of phase
7 50/51P1.Opt_Curve 0~13
overcurrent protection
Time multiplier setting for stage 1 of inverse-time
8 50/51P1.TMS 0.010~200.000
phase overcurrent protection
Minimum operating time for stage 1 of inverse-time
9 50/51P1.tmin 0.000~20.000 (s)
phase overcurrent protection
Constant “α” for stage 1 of customized inverse-time
10 50/51P1.Alpha 0.010~5.000
characteristic phase overcurrent protection
Constant “C” for stage 1 of customized inverse-time
11 50/51P1.C 0.000~200.000
characteristic phase overcurrent protection
Constant “K” for stage 1 of customized inverse-time
12 50/51P1.K 0.050~20.000
characteristic phase overcurrent protection
Current setting for stage 2 of phase overcurrent
13 50/51P2.I_Set (0.050~30.000)×In (A)
protection
Time delay for stage 2 of phase overcurrent
14 50/51P2.t_Op 0.000~20.000 (s)
protection
15 50/51P2.En Enable stage 2 of phase overcurrent protection 0 or 1
Direction option for stage 2 of phase overcurrent
16 50/51P2.Opt_Dir 0, 1 or 2
protection
Enable second harmonic blocking for stage 2 of
17 50/51P2.En_Hm2 0 or 1
phase overcurrent protection
Option of characteristic curve for stage 2 of phase
18 50/51P2.Opt_Curve 0~12
overcurrent protection
Time multiplier setting for stage 2 of inverse-time
19 50/51P2.TMS 0.010~200.000
phase overcurrent protection.
Minimum operating time for stage 2 of inverse-time
20 50/51P2.tmin 0.000~20.000 (s)
phase overcurrent protection
Current setting for stage 3 of phase overcurrent
21 50/51P3.I_Set (0.050~30.000)×In (A)
protection
Time delay for stage 3 of phase overcurrent
22 50/51P3.t_Op 0.000~20.000 (s)
protection
23 50/51P3.En Enable stage 3 of phase overcurrent protection 0 or 1
Direction option for stage 3 of phase overcurrent
24 50/51P3.Opt_Dir 0, 1 or 2
protection
Enable second harmonic blocking for stage 3 of
25 50/51P3.En_Hm2 0 or 1
phase overcurrent protection
Option of characteristic curve for stage 3 of phase
26 50/51P3.Opt_Curve 0~12
overcurrent protection

7-14 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

Time multiplier setting for stage 3 of inverse-time


27 50/51P3.TMS 0.010~200.000
phase overcurrent protection.
Minimum operating time for stage 3 of inverse-time
28 50/51P3.tmin 0.000~20.000 (s)
phase overcurrent protection
Current setting for stage 4 of phase overcurrent
29 50/51P4.I_Set (0.050~30.000)×In (A)
protection
Time delay for stage 4 of phase overcurrent
30 50/51P4.t_Op 0.000~20.000 (s)
protection
31 50/51P4.En Enable stage 4 of phase overcurrent protection 0 or 1
Direction option for stage 4 of phase overcurrent
32 50/51P4.Opt_Dir 0, 1 or 2
protection
Enable second harmonic blocking for stage 4 of
33 50/51P4.En_Hm2 0 or 1
phase overcurrent protection
Option of characteristic curve for stage 4 of phase
34 50/51P4.Opt_Curve 0~12
overcurrent protection
Time multiplier setting for stage 4 of inverse-time
35 50/51P4.TMS 0.010~200.000
phase overcurrent protection.
Minimum operating time for stage 4 of inverse-time
36 50/51P4.tmin 0.000~20.000 (s)
phase overcurrent protection

7.4.1.15 Direction Earth Fault Protection Settings (50/51G)

No. Item Remark Range


Setting of second harmonic component for blocking
1 50/51G.K_Hm2 0.000~1.000
earth fault elements
2 50/51G1.3I0_Set Current setting for stage 1 of earth fault protection (0.050~30.000)×In (A)
3 50/51G1.t_Op Time delay for stage 1 of earth fault protection 0.000~20.000 (s)
4 50/51G1.En Enable stage 1 of earth fault protection 0 or 1
5 50/51G1.Opt_Dir Direction option for stage 1 of earth fault protection 0, 1 or 2
Enable second harmonic blocking for stage 1 of
6 50/51G1.En_Hm2 0 or 1
earth fault protection
Enable blocking for stage 1 of earth fault protection
7 50/51G1.En_Abnor_Blk 0 or 1
under abnormal conditions
Enable blocking for stage 1 of earth fault protection
8 50/51G1.En_CTS_Blk 0 or 1
under CT failure conditions
Option of characteristic curve for stage 1 of earth
9 50/51G1.Opt_Curve 0~13
fault protection
Time multiplier setting for stage 1 of inverse-time
10 50/51G1.TMS 0.010~200.000
earth fault protection
Minimum operating time for stage 1 of inverse-time
11 50/51G1.tmin 0.050~200.000 (t)
earth fault protection
Constant “α” for stage 1 of customized inverse-time
12 50/51G1.Alpha 0.010~5.000
characteristic earth fault protection

PCS-902 Line Distance Relay 7-15


Date: 2011-07-06
7 Settings

Constant “C” for stage 1 of customized inverse-time


13 50/51G1.C 0.000~20.000
characteristic earth fault protection
Constant “K” for stage 1 of customized inverse-time
14 50/51G1.K 0.050~20.000
characteristic earth fault protection
15 50/51G2.3I0_Set Current setting for stage 2 of earth fault protection (0.050~30.000)×In (A)
16 50/51G2.t_Op Time delay for stage 2 of earth fault protection 0.000~20.000 (s)
17 50/51G2.En Enable stage 2 of earth fault protection 0 or 1
18 50/51G2.Opt_Dir Direction option for stage 2 of earth fault protection 0, 1 or 2
Enable second harmonic blocking for stage 2 of
19 50/51G2.En_Hm2 0 or 1
earth fault protection
Enable blocking for stage 2 of earth fault protection
20 50/51G2.En_Abnor_Blk 0 or 1
under abnormal conditions
Enable blocking for stage 2 of earth faultv protection
21 50/51G2.En_CTS_Blk 0 or 1
under CT failure conditions
Option of characteristic curve for stage 2 of earth
22 50/51G2.Opt_Curve 0~12
fault protection
Time multiplier setting for stage 2 of inverse-time
23 50/51G2.TMS 0.010~200.000
earth fault protection
Minimum operating time for stage 2 of inverse-time
24 50/51G2.tmin 0.050~200.000 (s)
earth fault protection
25 50/51G3.3I0_Set Current setting for stage 3 of earth fault protection (0.050~30.000)×In (A)
26 50/51G3.t_Op Time delay for stage 3 of earth fault protection 0.000~20.000 (s)
27 50/51G3.En Enable stage 3 of earth fault protection 0, 1 or 2
28 50/51G3.Opt_Dir Direction option for stage 3 of earth fault protection 0 or 1
Enable second harmonic blocking for stage 3 of
29 50/51G3.En_Hm2 0 or 1
earth fault protection
Enable blocking for stage 3 of earth fault protection
30 50/51G3.En_Abnor_Blk 0 or 1
under abnormal conditions
Enable blocking for stage 3 of earth fault protection
31 50/51G3.En_CTS_Blk 0 or 1
under CT failure conditions
Option of characteristic curve for stage 3 of earth
32 50/51G3.Opt_Curve 0~12
fault protection
Time multiplier setting for stage 3 of inverse-time
33 50/51G3.TMS 0.010~200.000
earth fault protection
Minimum operating time for stage 3 of inverse-time
34 50/51G3.tmin 0.050~200.000 (s)
earth fault protection
35 50/51G4.3I0_Set Current setting for stage 4 of earth fault protection (0.050~30.000)×In (A)
36 50/51G4.t_Op Time delay for stage 4 of earth fault protection 0.000~20.000 (s)
37 50/51G4.En Enable stage 4 of earth fault protection 0, 1 or 2
38 50/51G4.Opt_Dir Direction option for stage 4 of earth fault protection 0 or 1
Enable second harmonic blocking for stage 4 of
39 50/51G4.En_Hm2 0 or 1
earth fault protection

7-16 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

Enable blocking for stage 4 of earth fault protection


40 50/51G4.En_Abnor_Blk 0 or 1
under abnormal conditions
Enable blocking for stage 4 of earth fault protection
41 50/51G4.En_CTS_Blk 0 or 1
under CT failure conditions
Option of characteristic curve for stage 4 of earth
42 50/51G4.Opt_Curve 0~12
fault protection
Time multiplier setting for stage 4 of inverse-time
43 50/51G4.TMS 0.010~200.000
earth fault protection
Minimum operating time for stage 4 of inverse-time
44 50/51G4.tmin 0.050~200.000 (s)
earth fault protection

7.4.1.16 Overcurrent Protection Settings for VT Circuit Failure (51PVT/51GVT)

No. Item Remark Range


Current setting of ground overcurrent protection
1 51GVT.3I0_Set (0.050~30.000)×In (A)
when VT circuit failure
Time delay of ground overcurrent protection when
2 51GVT.t_Op 0.000~10.000 (s)
VT circuit failure
Enable ground overcurrent protection when VT
3 51GVT.En 0 or 1
circuit failure
Current setting of phase overcurrent protection
4 51PVT.I_Set (0.050~30.000)×In (A)
when VT circuit failure
Time delay of phase overcurrent protection when
5 51PVT.t_Op 0.000~10.000 (s)
VT circuit failure
Enable phase overcurrent protection when VT
6 51PVT.En 0 or 1
circuit failure

7.4.1.17 Residual Current SOTF Protection Settings (50SOTF)

No. Item Remark Range


1 50SOTF.3I0_Set Current setting of residual current SOTF protection (0.050~30.000)×In (A)
2 50SOTF.En_3I0 Enable residual current SOTF protection 0 or 1

7.4.1.18 Overvoltage Protection Settings (59P)

No. Item Remark Range


1 59P1.U_Set Voltage setting for stage 1 of overvoltage protection Un~2Unn (V)
2 59P1.t_Op Time delay for stage 1 of overvoltage protection 0.000~30.000 (s)
3 59P1.En Enable stage 1 of overvoltage protection 0 or 1
4 59P1.Opt_1P/3P Option of 1-out-of-3 mode or 3-out-of-3 mode 0 or 1
5 59P1.Opt_Up/Upp Option of phase-to-phase voltage or phase voltage 0 or 1
Enable stage 1 of overvoltage protection for alarm
6 59P1.En_Alm 0 or 1
purpose
Enable transfer trip controlled by CB open position for
7 59P1.En_52b_TT 0 or 1
stage 1 of overvoltage protection

PCS-902 Line Distance Relay 7-17


Date: 2011-07-06
7 Settings

Enable stage 1 of overvoltage protection operate to


8 59P1.En_TT 0 or 1
initiate transfer trip
Option of characteristic curve for stage 1 of overvoltage
9 59P1.Opt_Curve 0~13
protection
Time multiplier setting for stage 1 of inverse-time
10 59P1.Opt_TMS 0.010~200.000
overvoltage protection
Minimum delay for stage 1 of inverse-time overvoltage
11 59P1.tmin 0.050~20.000 (s)
protection
12 59P2.U_Set Voltage setting for stage 2 of overvoltage protection Un~2Unn (V)
13 59P2.t_Op Time delay for stage 2 of overvoltage protection 0.000~30.000 (s)
14 59P2.En Enable stage 2 of overvoltage protection 0 or 1
15 59P2.Opt_1P/3P Option of 1-out-of-3 mode or 3-out-of-3 mode 0 or 1
16 59P2.Opt_Up/Upp Option of phase-to-phase voltage or phase voltage 0 or 1
Enable stage 2 of overvoltage protection for alarm
17 59P2.En_Alm 0 or 1
purpose
Enable transfer trip controlled by CB open position for
18 59P2.En_52b_TT 0 or 1
stage 2 of overvoltage protection
Enable stage 2 of overvoltage protection operate to
19 59P2.En_TT 0 or 1
initiate transfer trip
Option of characteristic curve for stage 2 of overvoltage
20 59P2.Opt_Curve 0~12
protection
Time multiplier setting for stage 2 of inverse-time
21 59P2.Opt_TMS 0.010~200.000
overvoltage protection
Minimum delay for stage 2 of inverse-time overvoltage
22 59P2.tmin 0.050~20.000 (s)
protection

7.4.1.19 Undervoltage Protection Settings (27P)

No. Item Remark Range


1 27P1.U_Set Voltage setting for stage 1 of undervoltage protection 0~Unn (V)
2 27P1.t_Op Time delay for stage 1 of undervoltage protection 0.000~30.000 (s)
3 27P1.En Enable stage 1 of undervoltage protection 0 or 1
4 27P1.Opt_1P/3P Option of 1-out-of-3 mode or 3-out-of-3 mode 0 or 1
Option of voltage criterion adopting phase-to-phase
5 27P1.Opt_Up/Upp 0 or 1
voltage or phase voltage
Enable stage 1 of undervoltage protection operate to
6 27P1.En_Alm 0 or 1
alarm
Option of characteristic curve for stage 1 of
7 27P1.Opt_Curve 0~13
undervoltage protection
Time multiplier setting for stage 1 of inverse-time
8 27P1.Opt_TMS 0.010~200.000
undervoltage protection
Minimum delay for stage 1 of inverse-time undervoltage
9 27P1.tmin 0.050~20.000 (s)
protection
10 27P2.U_Set Voltage setting for stage 2 of undervoltage protection 0~Unn (V)

7-18 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

11 27P2.t_Op Time delay for stage 2 of undervoltage protection 0.000~30.000 (s)


12 27P2.En Enable stage 2 of undervoltage protection 0 or 1
13 27P2.Opt_1P/3P Option of 1-out-of-3 mode or 3-out-of-3 mode 0 or 1
Option of voltage criterion adopting phase-to-phase
14 27P2.Opt_Up/Upp 0 or 1
voltage or phase voltage
Enable stage 2 of undervoltage protection operate to
15 27P2.En_Alm 0 or 1
alarm
Option of characteristic curve for stage 2 of
16 27P2.Opt_Curve 0~12
undervoltage protection
Time multiplier setting for stage 2 of inverse-time
17 27P2.Opt_TMS 0.010~200.000
undervoltage protection
Minimum delay for stage 2 of inverse-time undervoltage
18 27P2.tmin 0.050~20.000 (s)
protection

7.4.1.20 Overfrequency Protection Settings (81O)

No. Item Remark Range


Frequency setting for stage 1 of overfrequency
1 81O1.f_Set 50.00~65.00 (Hz)
protection
2 81O1.t_Op Time delay for stage 1 of overfrequency protection 0.000~100.000 (s)
Frequency setting for stage 2 of overfrequency
3 81O2.f_Set 50.00~65.00 (Hz)
protection
4 81O2.t_Op Time delay for stage 2 of overfrequency protection 0.000~100.000 (s)
Frequency setting for stage 3 of overfrequency
5 81O3.f_Set 50.00~65.00 (Hz)
protection
6 81O3.t_Op Time delay for stage 3 of overfrequency protection 0.000~100.000 (s)
Frequency setting for stage 4 of overfrequency
7 81O4.f_Set 50.00~65.00 (Hz)
protection
8 81O4.t_Op Time delay for stage 4 of overfrequency protection 0.000~100.000 (s)
Enabling/disabling stage 1 of overfrequency protection
9 81O1.En 0: disable 0 or 1
1: enable
Enabling/disabling stage 2 of overfrequency protection
10 81O2.En 0: disable 0 or 1
1: enable
Enabling/disabling stage 3 of overfrequency protection
11 81O3.En 0: disable 0 or 1
1: enable
Enabling/disabling stage 4 of overfrequency protection
12 81O4.En 0: disable 0 or 1
1: enable

7.4.1.21 Underfrequency Protection Settings (81U)

No. Item Remark Range

PCS-902 Line Distance Relay 7-19


Date: 2011-07-06
7 Settings

Frequency setting for stage 1 of underfrequency


1 81U1.f_Set 40.00~50.00 (Hz)
protection
2 81U1.t_Op Time delay for stage 1 of underfrequency protection 0.000~100.000 (s)
Frequency setting for stage 2 of underfrequency
3 81U2.f_Set 40.00~50.00 (Hz)
protection
4 81U2.t_Op Time delay for stage 2 of underfrequency protection 0.000~100.000 (s)
Frequency setting for stage 3 of underfrequency
5 81U3.f_Set 40.00~50.00 (Hz)
protection
6 81U3.t_Op Time delay for stage 3 of underfrequency protection 0.000~100.000 (s)
Frequency setting for stage 4 of underfrequency
7 81U4.f_Set 40.00~50.00 (Hz)
protection
8 81U4.t_Op Time delay for stage 4 of underfrequency protection 0.000~100.000 (s)
Rate of frequency change for blocking underfrequency
9 81U.df/dt_Blk 0.20~20.00 (Hz/s)
protection
Enabling/disabling stage 1 of underfrequency protection
10 81U1.En 0: disable 0 or 1
1: enable
Enabling/disabling stage 2 of underfrequency protection
11 81U2.En 0: disable 0 or 1
1: enable
Enabling/disabling stage 3 of underfrequency protection
12 81U3.En 0: disable 0 or 1
1: enable
Enabling/disabling stage 4 of underfrequency protection
13 81U4.En 0: disable 0 or 1
1: enable

7.4.1.22 Breaker Failure Protection Settings (50BF)

No. Item Remark Range


1 50BF.I_Set Current setting of phase current criterion for BFP (0.050~30.000 )×In (A)
Current setting of zero-sequence current criterion
2 50BF.3I0_Set (0.050~30.000 )×In (A)
for BFP
Current setting of negative-sequence current
3 50BF.I2_Set (0.050~30.000 )×In (A)
criterion for BFP
4 50BF.t_ReTrp Time delay of re-tripping for BFP 0.000~10.000 (s)

5 50BF.t1_Op Time delay of stage 1 for BFP 0.000~10.000 (s)

6 50BF.t2_Op Time delay of stage 2 for BFP 0.000~10.000 (s)

7 50BF.En Enable breaker failure protection 0 or 1


8 50BF.En_ReTrip Enable re-trip function for BFP 0 or 1
Enable zero-sequence current criterion for BFP
9 50BF.En_3I0_1P 0 or 1
initiated by single-phase tripping contact
Enable zero-sequence current criterion for BFP
10 50BF.En_3I0_3P 0 or 1
initiated by three-phase tripping contact

7-20 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

Enable negative-sequence current criterion for BFP


11 50BF.En_I2_3P 0 or 1
initiated by three-phase tripping contact
Enable breaker failure protection can be initiated by
12 50BF.En_CB_Ctrl 0 or 1
normally closed contact of circuit breaker

7.4.1.23 Thermal Overload Protection (49)

No. Item Remark Range


The factor setting for stage 1 of thermal overload
1 49-1.K protection which is associated to the thermal state 1.000~3.000
formula
The factor setting for stage 2 of thermal overload
2 49-2.K protection which is associated to the thermal state 1.000~3.000
formula
The reference current setting of the thermal
3 49.Ib_Set (0.050~30.000 )×In (A)
overload protection
The time constant setting of the IDMT overload
4 49.Tau 0.100~100.000 (min)
protection
Enable stage 1 of thermal overload protection for
5 49-1.En_Alm 0 or 1
alarm purpose
Enable stage 1 of thermal overload protection for
6 49-1.En_Trp 0 or 1
trip purpose
Enable stage 2 of thermal overload protection for
7 49-2.En_Alm 0 or 1
alarm purpose
Enable stage 2 of thermal overload protection for
8 49-2.En_Trp 0 or 1
trip purpose

7.4.1.24 Stub Overcurrent Protection (50STB)

No. Name Remark Range


1 50STB.I_Set Current setting of stub overcurrent protection (0.050~30.000)×In (A)
2 50STB.t_Op Time delay of stub overcurrent protection 0.000~10.000 (s)
3 50STB.En Enable stub overcurrent protection 0 or 1

7.4.1.25 Pole Discrepancy Protection Settings (62PD)

No. Item Remark Range


Current setting of residual current criterion for pole
1 62PD.3I0_Set (0.050~30.000 )×In (A)
discrepancy protection
Current setting of negative-sequence current
2 62PD.I2_Set (0.050~30.000 )×In (A)
criterion for pole discrepancy protection
3 62PD.t_Op Time delay of pole discrepancy protection 0.000~10.000 (s)

4 62PD.En Enable pole discrepancy protection 0 or 1


Enable residual current criterion and
5 62PD.En_3I0/I2_Ctrl negative-sequence current criterion for pole 0 or 1
discrepancy protection

7.4.1.26 Synchrocheck Settings (25)

No. Item Remark Range


1 25.Opt_Source_UL Voltage selecting mode of line 0~5

PCS-902 Line Distance Relay 7-21


Date: 2011-07-06
7 Settings

2 25.Opt_Source_UB Voltage selecting mode of bus 0~5

3 25.U_Dd Voltage threshold of dead check 0.05Un~0.8Un (V)

4 25.U_Lv Voltage threshold of live check 0.5Un~Un (V)

5 25.K_Usyn Compensation coefficient for synchronism voltage 0.20-5.00

6 25.phi_Diff Phase difference limit of synchronism check for AR 0~ 89 (Deg)

Compensation for phase difference between two


7 25.phi_Comp 0~359 (Deg)
synchronous voltages

8 25.f_Diff Frequency difference limit of synchronism check for AR 0.02~1.00 (Hz)

9 25.U_Diff Voltage difference limit of synchronism check for AR 0.02Un~0.8Un (V)

10 25.t_DeadChk Time delay to confirm dead check condition 0.010~25.000 (s)

11 25.t_SynChk Time delay to confirm synchronism check condition 0.010~25.000 (s)

12 25.En_fDiffChk Enable frequency difference check 0 or 1


13 25.En_SynChk Enable synchronism check 0 or 1
14 25.En_DdL_DdB Enable dead line and dead bus (DLDB) check 0 or 1
15 25.En_DdL_LvB Enable dead line and live bus (DLLB) check 0 or 1
16 25.En_LvL_DdB Enable live line and dead bus (LLDB) check 0 or 1
17 25.En_NoChk Enable AR without any check 0 or 1

7.4.1.27 Auto-reclosing Settings (79)

No. Item Remark Range


1 79.N_Rcls Maximum number of reclosing attempts 1~4
2 79.t_Dd_1PS1 Dead time of first shot 1-pole reclosing 0.000~600.000 (s)
3 79.t_Dd_3PS1 Dead time of first shot 3-pole reclosing 0.000~600.000 (s)
4 79.t_Dd_3PS2 Dead time of second shot 3-pole reclosing 0.000~600.000 (s)
5 79.t_Dd_3PS3 Dead time of third shot 3-pole reclosing 0.000~600.000 (s)
6 79.t_Dd_3PS4 Dead time of fourth shot 3-pole reclosing 0.000~600.000 (s)
Time delay of circuit breaker in closed position before
7 79.t_CBClsd 0.000~600.000 (s)
reclosing
Time delay to wait for CB healthy, and begin to timing
when the input signal [79.CB_Healthy] is de-energized
8 79.t_CBReady 0.000~600.000 (s)
and if it is not energized within this time delay, AR will
be blocked.
9 79.t_WaitChk Maximum wait time for synchronism check 0.000~600.000 (s)
Time delay allow for CB status change to conform
10 79.t_Fail 0.000~600.000 (s)
reclosing successful
11 79.t_DDO_AR Pulse width of AR closing signal 0.000~600.000 (s)
12 79.t_Reclaim Reclaim time of AR 0.000~600.000 (s)
Time delay of excessive trip signal to block
13 79.t_PersistTrp 0.000~600.000 (s)
auto-reclosing

7-22 PCS-902 Line Distance Relay


Date: 2011-07-06
7 Settings

Drop-off time delay of blocking AR, when blocking


14 79.t_DDO_BlkAR signal for AR disappears, AR blocking condition drops 0.000~600.000 (s)
off after this time delay
15 79.t_AddDly Additional time delay for auto-reclosing 0.000~600.000 (s)
Maximum wait time for reclosing permissive signal from
16 79.t_WaitMaster 0.000~600.000 (s)
master AR
Time delay of discriminating another fault, and begin to
times after 1-pole AR initiated, 3-pole AR will be
17 79.t_SecFault 0.000~600.000 (s)
initiated if another fault happens during this time delay.
AR will be blocked if another fault happens after that.
Enable auto-reclosing blocked when a fault occurs
18 79.En_PDF_Blk 0 or 1
under pole disagreement condition
Enable auto-reclosing with an additional dead time
19 79.En_AddDly 0 or 1
delay
20 79.En_CutPulse Enable adjust the length of reclosing pulse 0 or 1
Enable confirm whether AR is successful by checking
21 79.En_FailCheck 0 or 1
CB state
22 79.En Enable auto-reclosing 0 or 1
Enable AR by external input signal besides logic setting
23 79.En_ExtCtrl 0 or 1
[79.En]
24 79.En_CBInit Enable AR be initiated by open state of circuit breaker 0 or 1
25 79.Opt_Priority Option of AR priority 0, 1 or 2
26 79.SetOpt Control option of AR mode 0 or 1
27 79.En_1PAR Enable 1-pole AR mode 0 or 1
28 79.En_3PAR Enable 3-pole AR mode 0 or 1
29 79.En_1P/3PAR Enable 1/3-pole AR mode 0 or 1

7.4.1.28 Transfer Trip Settings (TT)

No. Item Remark Range


1 TT.t_Op Time delay of transfer trip 0.000~10.000 (s)
2 TT.En_FD_Ctrl Enable transfer trip controlled by local fault detector 0 or 1

7.4.1.29 Tripping Logic Settings

No. Item Remark Range


Enable auto-reclosing blocked when multi-phase fault
1 En_MPF_Blk_AR 0 or 1
happens
Enable auto-reclosing blocked when three-phase fault
2 En_3PF_Blk_AR 0 or 1
happens
Enable auto-reclosing blocked when selection of faulty
3 En_PhSF_Blk_AR 0 or 1
phase fails
4 En_3PTrp Enable phase A,phase B and phase C breaker tripping 0 or 1

PCS-902 Line Distance Relay 7-23


Date: 2011-07-06
7 Settings

The dwell time of tripping command, empirical value is


5 t_Dwell_Trp 0.000~1000.000 (s)
0.04

7.4.1.30 VTS Settings (VTS)

No. Item Remark Range


1 VTS. En_Out_LineVT VT is not connected to the protection device 0 or 1
If three-phase voltage used for protection measurement
comes from line side (for example, 3/2 breaker), it
2 VTS.En_Line_VT 0 or 1
should be set as “1”. If three-phase voltage comes from
busbar side, it should be set as “0”.
3 VTS.En Enable alarm function of VT circuit supervision 0 or 1

7.4.2 Access Path


MainMenuSettingsProtection Settings

7-24 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

8 Human Machine Interface

Table of Contents
8 Human Machine Interface ............................................................... 8-a
8.1 Overview .......................................................................................................... 8-1
8.1.1 Keypad Operation .............................................................................................................. 8-2

8.1.2 LED Indications .................................................................................................................. 8-3

8.1.3 Front Communication Port ................................................................................................. 8-3

8.1.4 Ethernet Port Setup ........................................................................................................... 8-4

8.2 Menu Tree ........................................................................................................ 8-5


8.2.1 Overview ............................................................................................................................ 8-5

8.2.2 Main Menus ....................................................................................................................... 8-6

8.2.3 Sub Menus ......................................................................................................................... 8-7

8.3 LCD Display ................................................................................................... 8-19


8.3.1 Overview .......................................................................................................................... 8-19

8.3.2 Normal Display................................................................................................................. 8-19

8.3.3 Display Disturbance Records ........................................................................................... 8-20

8.3.4 Display Supervision Event ............................................................................................... 8-21

8.3.5 Display IO Events ............................................................................................................ 8-22

8.3.6 Display Device Logs ........................................................................................................ 8-23

8.4 Keypad Operation ......................................................................................... 8-24


8.4.1 View Device Measurements ............................................................................................. 8-24

8.4.2 View Device Status .......................................................................................................... 8-24

8.4.3 View Device Records ....................................................................................................... 8-24

8.4.4 Print Device Report .......................................................................................................... 8-25

8.4.5 View Device Setting ......................................................................................................... 8-26

8.4.6 Modify Device Setting ...................................................................................................... 8-26

8.4.7 Copy Device Setting ........................................................................................................ 8-29

PCS-902 Line Distance Relay 8-a


Date: 2011-07-06
8 Human Machine Interface

8.4.8 Switch Setting Group ....................................................................................................... 8-29

8.4.9 Delete Device Records .................................................................................................... 8-30

8.4.10 Modify Device Clock ...................................................................................................... 8-31

8.4.11 View Module Information ................................................................................................ 8-31

8.4.12 Check Software Version ................................................................................................. 8-32

8.4.13 Communication Test....................................................................................................... 8-32

8.4.14 Select Language ............................................................................................................ 8-33

List of Figures
Figure 8.1-1 Front panel ............................................................................................................8-1

Figure 8.1-2 Keypad buttons ....................................................................................................8-2

Figure 8.1-3 LED indications ....................................................................................................8-3

Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel ..................................8-4

Figure 8.1-5 Rear view and terminal definition of NR1102C...................................................8-5

Figure 8.2-1 Menu tree ..............................................................................................................8-7

List of Tables
Table 8.1-1 Definition of the 8-core cable ................................................................................8-4

Table 8.3-1 Tripping report messages....................................................................................8-21

Table 8.3-2 User operating event list......................................................................................8-23

8-b PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

The operator can access the protective device from the front panel. Local communication with the
protective device is possible using a computer via a multiplex RJ45 port on the front panel.
Furthermore, remote communication is also possible using a PC with the substation automation
system via rear RS485 port or rear Ethernet port. The operator is able to check the protective
device status at any time.

This chapter describes human machine interface (HMI), and give operator a instruction about how
to display or print event report, setting and so on through HMI menu tree and display metering
value, including r.m.s. current, voltage and frequency etc. through LCD. Procedures to change
active setting group or a settable parameter value through keypad is also described in details.

8.1 Overview
The human-machine interface consists of a human-machine interface (HMI) module which allows
a communication to be as simple as possible for the user. The HMI module helps to draw your
attention to something that has occurred which may activate a LED or a report displayed on the
LCD. Operator can locate the data of interest by navigating the keypad.

1 11
HEALTHY PCS-902
2 12
5
ALARM
3 13

4 14
GRP

5 15

6 16 ENT
ESC

7 17
4
8 18

1
9 19
3
10 20

Figure 8.1-1 Front panel

The function of HMI module:

No. Item Description


A 320×240 dot matrix backlight LCD display is visible in dim lighting
1 LCD conditions. The corresponding messages are displayed when there is
operation implemented.
20 status indication LEDs, 2 LEDs are fixed as the signals of “HEALTHY”
2 LED (green) and “ALARM” (yellow), 18 LEDs are configurable with selectable
color among green, yellow and red.
3 Keypad Navigation keypad and command keys for full access to device
4 Communication port a multiplex RJ45 port for local communication with a PC
5 Logo Type and designation and manufacturer of device

PCS-902 Line Distance Relay 8-1


Date: 2011-07-06
8 Human Machine Interface

8.1.1 Keypad Operation

GR
P
ENT

ESC
Figure 8.1-2 Keypad buttons

1. “ESC”:

 Cancel the operation

 Quit the current menu

2. “ENT”:

 Execute the operation

 Confirm the interface

3. “GRP”

 Activate the switching interface of setting group

4. leftward and rightward direction keys (“◄” and “►”):

 Move the cursor horizontally

 Enter the next menu or return to the previous menu

5. upward and downward direction keys (“▲” and “▼”)

 Move the cursor vertically

 Select command menu within the same level of menu

6. plus and minus sign keys (“+” and “-”)

 Modify the value

 Modify and display the message number

 Page up/down

8-2 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

8.1.2 LED Indications

HEALTHY
ALARM

Figure 8.1-3 LED indications

A brief explanation has been made as bellow.

LED Display Description


When the equipment is out of service or any hardware error is defected during
Off
HEALTHY self-check.

Steady Green Lit when the equipment is in service and ready for operation.

Off When equipment in normal operating condition.


ALARM
Steady Yellow Lit when VT circuit failure, CT circuit failure or other abnormal alarm is issued.

Note!

“HEALTHY” LED can only be turned on by energizing the device and no abnormality
detected.

“ALARM” LED is turned on when abnormalities of device occurs like above mentioned
and can be turned off after abnormalities are removed except alarm report [CTS.Alm]
which can only be reset only when the failure is removed and the device is rebooted or
re-energized.

Other LED indicators with no labels are configurable and user can configure them to be lit
by signals of operation element, alarm element and binary output contact according to
requirement through PCS-PC software, but as drawed in figure, 2 LEDs are fixed as the
signals of “HEALTHY” (green) and “ALARM” (yellow), 18 LEDs are configurable with
selectable color among green, yellow and red.

8.1.3 Front Communication Port


There is a multiplex RJ45 port on the front panel. This port can be used as an RS-232 serial port
as well as a twisted-pair ethernet port. As shown in the following figure, a customized cable is
applied for debugging via this multiplex RJ45 port.

PCS-902 Line Distance Relay 8-3


Date: 2011-07-06
8 Human Machine Interface

Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel

In the above figure and the following table:

P1: To connect the multiplex RJ45 port. An 8-core cable is applied here.

P2: To connect the twisted-pair ethernet port of the computer.

P3: To connect the RS-232 serial port of the computer.

The definition of the 8-core cable in the above figure is introduced in the following table.

Table 8.1-1 Definition of the 8-core cable

Terminal Device side Computer side


Core color Function
No. (Left) (Right)
1 Orange TX+ of the ethernet port P1-1 P2-1
2 Orange & white TX- of the ethernet port P1-2 P2-2
3 Green & white RX+ of the ethernet port P1-3 P2-3
4 Blue TXD of the RS-232 serial port P1-4 P3-2
5 Brown & white RXD of the RS-232 serial port P1-5 P3-3
6 Green RX- for the ethernet port P1-6 P2-6
7 Blue & white The ground connection of the RS-232 port. P1-7 P3-5

8.1.4 Ethernet Port Setup


MON plug-in module is equipped with two or four 100Base-TX Ethernet interface, take NR1102C
as an example, as shown in Figure 8.1-5. Its rear view and the definition of terminals.

The Ethernet port can be used to communication with PC via auxiliary software (PCS-PC) after
connecting the protection device with PC, so as to fulfill on-line function (please refer to the
instruction manual of PCS-PC). At first, the connection between the protection device and PC
must be established. Through setting the IP address and subnet mask of corresponding Ethernet
interface in the menu “Settings→Device Setup→Comm Settings”, it should be ensured that the
protection device and PC are in the same network segment. For example, setting the IP address
and subnet mask of network A. (using network A to connect with PC)

PC: IP address is set as “198.87.96.102”, subnet mask is set as “255.255.255.0”

The IP address and subnet mask of protection device should be [IP_LAN1]= 198.87.96.XXX,

8-4 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

[Mask_LAN1]=255.255.255.0, [En_LAN1]=1. (XXX can be any value from 0 to 255 except 102)

If the logic setting [En_LAN1] is non-available, it means that network A is always enabled.

NR1102C

ETHERNET

Network A

Network B

SYN+
SYN-
SGND
GND
RXD
TXD
SGND
GND

Figure 8.1-5 Rear view and terminal definition of NR1102C

Note!

If using other Ethernet port, for example, Ethernet B, the logic setting [En_LAN2] must be
set as “1”.

8.2 Menu Tree


8.2.1 Overview
Press “▲” of any running interface and enter the main menu. Select different submenu by “▲” and
“▼”. Enter the selected submenu by pressing “ENT” or “►”. Press “◄” and return to the previous
menu. Press “ESC” back to main menu directly. For sake of entering the command menu again, a
command menu will be recorded in the quick menu after its execution. Five latest command
menus can be recorded in the quick menu. When five command menus are recorded, the latest
command menu will cover the earliest one, adopting the “first in first out” principle. It is arranged
from top to bottom and in accordance with the execution order of command menus.

Press “▲” to enter the main menu with the interface as shown in the following diagram:

PCS-902 Line Distance Relay 8-5


Date: 2011-07-06
8 Human Machine Interface

MainMenu

Language
Clock

Quick Menu

For the first powered protective device, there is no record in quick menu. Press “▲” to enter the
main menu with the interface as shown in the following diagram:

Measurements

Status

Records

Settings

Print

Local Cmd

Information

Test

Clock

Language

The descriptions about menu is based on the maximized configuration, for a specific project, if
some function is not available, the corresponding submenu will hidden.

8.2.2 Main Menus


The menu of the PCS-902 is organized into main menu and submenus, much like a PC directory
structure. The menu of the PCS-902 is divided into 10 sections:

8-6 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

Main Menu

Measurements

Status

Records

Settings

Print

Local Cmd

Information

Test

Clock

Language

Figure 8.2-1 Menu tree

Under the main interface, press “▲” to enter the main menu, and select submenu by pressing “▲”,
“▼” and “ENT”. The command menu adopts a tree shaped content structure. The above diagram
provides the integral structure and all main menus under menu tree of the protection device.

8.2.3 Sub Menus


8.2.3.1 Measurements

Main Menu

Measurements

Measurements1

Measurements2

Measurements3

This menu is used to display real-time measured values, including AC voltage, AC current, phase
angle and calculated quantities. These data can help users to acquaint the device′s status. This
menu comprises following submenus. Please refer to “section measurement” about the detailed
measured values.

No. Item Function description

1 Measurement1 Display measured values from protection calculation DSP (Displayed by

PCS-902 Line Distance Relay 8-7


Date: 2011-07-06
8 Human Machine Interface

secondary value)

Display sampled values from fault detector DSP (Displayed by


2 Measurement2
secondary value)

3 Measurement3 Display measured primary values and other calculated quantities

8.2.3.2 Status

Main Menu

Status

Inputs

Contact Inputs

GOOSE Inputs

Prot Ch Inputs

Outputs

Contact Outputs

GOOSE Outputs

Prot Ch Outputs

Superv State

Prot Superv

FD Superv

GOOSE Superv

SV Superv

This menu is used to display real time input signals, output signals and alarm signals of the device.
These data can help users to acquaint the device′s status. This menu comprises following
submenus. Please refer to “section signal list” about the detailed inputs, output and alarm signals.

No. Item Function description

1 Inputs Display all input signal states

2 Outputs Display all output signal states

3 Superv State Display supervision alarm states

The submenu “Inputs” comprises the following command menus.

No. Item Function description

1 Contact Inputs Display states of binary inputs derived from opto-isolated channels

8-8 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

2 GOOSE Inputs Display states of GOOSE binary inputs.

3 Prot Ch Inputs Display states of binary inputs received from protection channel.

The submenu “Outputs” comprises the following command menus.

No. Item Function description

1 Contact Outputs Display states of contact binary outputs

2 GOOSE Outputs Display states of GOOSE binary outputs

3 Prot Ch Outputs Display states of channel outputs

The submenu “Superv State” comprises the following command menus.

No. Item Function description

1 Prot Superv Display states of self-supervision signals from protection calculation DSP

2 FD Superv Display states of self-supervision signals from fault detector DSP

3 GOOSE Superv Display states of GOOSE self-supervision signals

4 SV Superv Display states of SV self-supervision signals

8.2.3.3 Records

Main Menu

Records

Disturb Records

Superv Events

IO Events

Device Logs

Clear Records

This menu is used to display all kinds of records, including the disturbance records, supervision
events, binary events and device logs, so that the operator can load to view and use as the
reference of analyzing accidents and repairing the device. All records are stored in non-volatile
memory, it can still record them even if it loses its power.

This menu comprises the following submenus.

No. Item Function description


1 Disturb Records Display disturbance records of the device
2 Superv Events Display supervision events of the device
3 IO Events Display binary events of the device
4 Device Logs Display device logs of the device
5 Clear Records Clear all recods.

PCS-902 Line Distance Relay 8-9


Date: 2011-07-06
8 Human Machine Interface

8.2.3.4 Settings

Main Menu

Settings

System Settings

Prot Settings

Logic Links

Function Links

GOOSE Links

SV Links

Spare Links

Device Setup

Device Settings

Comm Settings

Label Settings

Copy Settings

This menu is used to check the device setup, system parameters, protection settings and logic
links settings, as well as modifying any of the above setting items. Moreover, it can also execute
the setting copy between different setting groups.

This menu comprises the following submenus.

No. Item Function description

1 System Settings Check or modify the system parameters

2 Prot Settings Check or modify the protection settings

Check or modify the logic links settings, including function links, SV links,
3 Logic Links
GOOSE links and spare links

4 Device Setup Check or modify the device setup

5 Copy_Settings Copy setting between different setting groups

The submenu “Prot Settings” includes the following command menus.

No. Item Function description

1 Line Settings Check or modify line parameters

2 FD Settings Check or modify fault detector element settings

3 Direction Settings Check or modify direction control element settings

8-10 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

Check or modify pilot distance protection and pilot directional earth-fault


4 Pilot Scheme Settings
protection settings

5 DPFC DistP Settings Check or modify DPFC distance protection settings

6 Mho Settings Check or modify distance protection with mho characteristic settings

7 Quad Settings Check or modify distance protection with Quad characteristic settings

8 ROC Settings Check or modify directional earth-fault protection settings

9 SOTF Settings Check or modify SOTF distance and overcurrent protection settings

10 OC Settings Check or modify phase overcurrent protection settings

11 OCVT Settings Check or modify overcurrent protection settings for VT circuit failure

12 BFP Settings Check or modify breaker failure protection settings

13 OV Settings Check or modify overvoltage protection settings

14 UV Settings Check or modify undervoltage protection settings

15 OF Settings Check or modify overfrequency protection settings

16 UF Settings Check or modify underfrequency protection settings

17 Overload Settings Check or modify thermal overload protection settings

18 MiscProt Settings Check or modify miscellaneous protection settings

Check or modify VT circuit supervision and CT circuit supervision


19 VTS/CTS Settings
settings

20 Trip Logic Settings Check or modify trippling logic settings

21 AR/Syn Settings Check or modify synchronism check and auto-reclosing settings

22 STB Settings Check or modify stub overcurrent protection settings

The submenu “Logic Links” comprises the following command menus.

No. Item Function description

1 Function Links Check or modify function links settings

2 GOOSE Links Check or modify GOOSE links settings

3 SV Links Check or modify SV links settings

4 Spare Links Check or modify spare links settings (used for programmable logic)

The submenu “Device Setup” comprises the following command menus.

No. Item Function description

1 Device Settings Check or modify the device settings.

2 Comm Settings Check or modify the communication settings.

3 Label Settings Check or modify the label settings of each protection element.

PCS-902 Line Distance Relay 8-11


Date: 2011-07-06
8 Human Machine Interface

8.2.3.5 Print

Main Menu

Print

Device Info

Settings

System Settings

Prot Settings

Logic Links

Function Links

GOOSE Links

SV Links

Spare Links

Device Setup

Device Settings

Comm Settings

Label Settings

All Settings

Latest Modified

Disturb Records

Superv Events

IO Events

Prot Ch Superv

Channel 1

Channel 2

Prot Ch Statistics

Channel 1

Channel 2

Device Status

Waveform

IEC103 Info

Cancel Print

8-12 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

This menu is used to print device description, settings, all kinds of records, waveform, information
related with IEC60870-5-103 protocol, channel state and channel statistic.

This menu comprises the following submenus.

No. Item Function description

Print the description information of the device, including software


1 Device Info
version.

Print device setup, system parameters, protection settings and logic


links settings. It can print by different classifications as well as printing all
2 Settings
settings of the device. Besides, it can also print the latest modified
settings.

3 Disturb Records Print the disturbance records

4 Superv Events Print the supervision events

5 IO Events Print the binary events

Print the self-check information of optical fibre channel, which is made of


6 Prot Ch Superv some hexadecimal characters and used to developer analyze channel
state

Print the statistic report of optical fibre channel, which is formed A.M.
7 Prot Ch Statistics
9:00 every day

Print the current state of the device, including the sampled value of
8 Device Status
voltage and current, the state of binary inputs, setting and so on

9 Waveform Print the recorded waveform

Print 103 Protocol information, including function type (FUN),


10 IEC103 Info information serial number (INF), general classification service group
number, and channel number (ACC)

11 Cancel Print Cancel the print command

The submenu “Settings” comprises the following submenus.

No. Item Function description

1 System Settings Print the system parameters

2 Prot Settings Print the protection settings

3 Logic Links Print the logic links settings

4 Device Setup Print the settings related to device setup

Print all settings including device setup, system parameters, protection


5 All Settings
settings and logic links settings

6 Latest Modified Print the setting latest modified

The submenu “Prot Settings” comprises the following command menus.

No. Item Function description

PCS-902 Line Distance Relay 8-13


Date: 2011-07-06
8 Human Machine Interface

1 Line Settings Print line parameters

2 FD Settings Print fault detector element settings

3 Direction Settings Print direction control element settings

Print pilot distance protection and pilot directional earth-fault protection


4 Pilot Scheme Settings
settings

5 DPFC DistP Settings Print DPFC distance protection settings

6 Mho Settings Print distance protection with mho characteristic settings

7 Quad Settings Print distance protection with Quad characteristic settings

8 ROC Settings Print directional earth-fault protection settings

9 SOTF Settings Print SOTF distance and overcurrent protection settings

10 OC Settings Print phase overcurrent protection settings

11 OCVT Settings Print overcurrent protection settings for VT circuit failure

12 BFP Settings Print breaker failure protection settings

13 OV Settings Print overvoltage protection settings

14 UV Settings Print undervoltage protection settings

15 OF Settings Print overfrequency protection settings

16 UF Settings Print underfrequency protection settings

17 Overload Settings Print thermal overload protection settings

18 MiscProt Settings Print miscellaneous protection settings

19 VTS/CTS Settings Print VT circuit supervision and CT circuit supervision settings

20 Trip Logic Settings Print trippling logic settings

21 AR/Syn Settings Print synchronism check and auto-reclosing settings

22 STB Settings Print stub overcurrent protection settings

The submenu “Logic Links” comprises the following command menus.

No. Item Function description

1 Function Links Print function links settings

2 GOOSE Links Print GOOSE links settings

3 SV Links Print SV links settings

4 Spare Links Print spare links settings (used for programmable logic)

The submenu “Device Setup” comprises the following command menus.

No. Item Function description

1 Device Settings Print the device settings.

2 Comm Settings Print the communication settings.

3 Label Settings Print the label settings of each protection element.

The submenu “Prot Ch Superv” comprises the following command menus.

8-14 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

No. Item Function description

Print the self-check information of optical fibre channel 1, which is made of some
1 Channel 1
hexadecimal characters and used to developer analyze channel state

Print the self-check information of optical fibre channel 2, which is made of some
2 Channel 2
hexadecimal characters and used to developer analyze channel state

The submenu “Prot Ch Statistics” includes the following command menus.

No. Item Function description

Print the statistic report of optical fibre channel 1, which is formed A.M. 9:00 every
1 Channel 1
day

Print the statistic report of optical fibre channel 2, which is formed A.M. 9:00 every
2 Channel 2
day

8.2.3.6 Local Cmd

Main Menu

Local Cmd

Reset Target

Trig Oscillograph

Download

Clear Counter

This menu is used to reset the tripping relay with latch, indicator LED, LCD display, and as same
as the resetting function of binary inputs. This menu provides a method of manually recording the
current waveform data of the device under normal condition for printing and uploading SAS.
Besides, it can send out the request of program download, clear statistic information about
GOOSE, SV, AR and FO channel.

This menu comprises the following submenus.

No. Item Function description

1 Reset Target Reset the local signal, indicator LED, LCD display and so on

2 Trig Oscillograph Trigger waveform recording

3 Download Send out the request of downloading program

4 Clear Counter Clear all statistic data

PCS-902 Line Distance Relay 8-15


Date: 2011-07-06
8 Human Machine Interface

8.2.3.7 Information

Main Menu

Information

Version Info

Board Info

In this menu, the LCD displays software information of all kinds of intelligent plug-in modules,
which consists of version, creating time of software, CRC codes and management sequence
number. Besides, plug-in module information can also be viewed.

This menu comprises the following command menus.

No. Item Function description

Display software information of DSP module, MON module and HMI module,
1 Version Info which consists of version, creating time of software, CRC codes and
management sequence number.

2 Board Info Monitor the current working state of each intelligent module.

8-16 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

8.2.3.8 Test

Main Menu

Test

Prot Ch Counter

Ch1 Counter

Ch2 Counter

GOOSE Comm Counter

SV Comm Counter

AR Counter

Device Test

Prot Elements

All Test

Select Test

Superv Events

All Test

Select Test

IO Events

All Test

Select Test

This menu is mainly used for developers to debug the program and for engineers to maintain the
protection device. It can be used to fulfill the communication test function. It is also used to
generate all kinds of reports or events to transmit to the SAS without any external input, so as to
debug the communication on site. Besides, it can also display statistic information about GOOSE,
SV, AR and FO channel.

This menu comprises the following submenus.

No. Item Function description

1 Prot Ch Couter Check communication statistics data of protection FO channel

2 GOOSE Couters Check communication statistics data of GOOSE

3 SV Couters Check communication statistics data of SV (Sampled Values)

PCS-902 Line Distance Relay 8-17


Date: 2011-07-06
8 Human Machine Interface

4 AR Couters Check AR counters

Automatically generate all kinds of reports or events to transmit to SCADA,


including disturbance records, self-supervision events and binary events. It can
5 Device Test
realize the report uploading by different classification, as well as the uploading
of all kinds of reports

The submenu “Prot Ch Counter” comprises the following command menus.

No. Item Function description

1 Ch1 Counter Check communication statistic information of channel 1

2 Ch2 Counter Check communication statistic information of channel 2

The submenu “Device Test” comprises the following submenus.

No. Item Function description

View the relevant information about disturbance records (only used for
1 Protection Elements
debugging persons)

View the relevant information about supervision events (only used for
2 Superv Events
debugging persons)

View the relevant information about binary events (only used for debugging
3 IO Events
persons)

Users can respectively execut the test automatically or manually by selecting commands “All Test”
or “Select Test”.

The submenu “Prot Elements” comprises the following command menus.

No. Item Description

1 All Test Ordinal test of all protection elements

2 Select Test Selective test of corresponding classification

The submenu “Superv Events” comprises the following command menus.

No. Item Description

1 All Test Ordinal test of all self-supervisions

2 Select Test Selective test of corresponding classification

The submenu “IO Events” comprises the following command menus.

No. Item Description

1 All Test Ordinal test of change of all binary inputs

2 Select Test Selective test of corresponding classification

8.2.3.9 Clock

The current time of internal clock can be viewed here. The time is displayed in the form
YY-MM-DD and hh:mm:ss. All values are presented with digits and can be modified.

8-18 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

8.2.3.10 Language

This menu is mainly used to set LCD display language.

8.3 LCD Display


8.3.1 Overview
There are five kinds of LCD display, SLD (single line diagram) display, tripping reports, alarm
reports, binary input changing reports and control reports. Tripping reports and alarm reports will
not disappear until these reports are acknowledged by pressing the “RESET” button in the
protection panel (i.e. energizing the binary input [BI_RstTarg]). User can press both “ENT” and
“ESC” at the same time to switch the display among trip reports, alarm reports and the SLD display.
IO events will be displayed for 5s and then it will return to the previous display interface
automatically. Device logs will not pop up and can only be viewed by navigating the corresponding
menu.

8.3.2 Normal Display


After the protection device is powered and entered into the initiating interface, it takes 30 seconds
to complete the initialization of protection device. During the initialization of protection device, the
“HEALTHY” indicator lamp of the protection device goes out.

Under normal condition, the LCD will display the following. The LCD adopts white color as its
backlight that is activated if once there is any keyboard operation, and is extinguished
automatically after 60 seconds of no operation.

2010-06-08 10:10:00
Ia 0.00A
Ib 0.00A
Ic 0.00A
3I0 0.00A
Ua 0.02V
Ub 0.00V
Uc 0.00V
3U0 0.02V
UB1 0.00V
UL2 0.00V
UB2 0.00V
f_Line 50.00Hz

Addr 24343 Group 01

The content displayed on the screen contains: the current date and time of the protection device
(with a format of yyyy-mm-dd hh:mm:ss:), the active setting group number, the three-phase
current sampling value, the neutral current sampling value, the three-phase voltage sampling
value, the neutral voltage sampling value, the synchronism voltage sampling value, line frequency

PCS-902 Line Distance Relay 8-19


Date: 2011-07-06
8 Human Machine Interface

and the address relevant to IP address of Ethernet A. If all the sampling values of the voltage and
the current can’t be fully displayed within one screen, they will be scrolling-displayed automatically
from the top to the bottom.

If IP address of Ethernet A is “xxx.xxx.a.b”, the displayed address equals to (a×256+b). For


example, If IP address of Ethernet A is “198.087.095.023”, the displayed address will be “95×
256+23=24343”.

If the device has detected any abnormal state, it′ll display the self-check alarm information.

8.3.3 Display Disturbance Records


This device can store 1024 disturbance records and 64 disturbance records with fault waveform.
When there is protection element operating, the LCD will automatically display the latest
disturbance record, and two kinds of LCD display interfaces will be available depending on
whether there are supervision events at present.

For the situation that the disturbance records and the supervision events coexist, the upper half
part is the disturbance record, and the lower half part is the supervision event. As to the upper half
part, it displays separately the record number of the disturbance record, fault name, generating
time of the disturbance record (with a format of yyyy-mm-dd hh:mm:ss), protection element and
tripping element. If there is protection element operation, faulty phase and relative operation time
with reference to fault detector element are displayed. At the same time, if displayed rows of
protection element and tripping element are more than 3, a scroll bar will appear at the right. The
height of the black part of the scroll bar basically indicates the total lines of protection element and
tripping element, and its position suggests the position of the currently displayed line of the total
lines. The scroll bar of protection element and tripping element will roll up at the speed of one line
per time. When it rolls to the last three lines, it will roll from the earliest protection element and
tripping element again. The displayed content of the lower half part is similar to that of the upper
half part.

If the device has no the supervision event, the display interface will only show the disturbance
record.

1. Disturb Records NO.2


2008-11-28 07:10:00:200
0 ms DPFC.Pkp

24 ms A 21Q.Z1.Op

8-20 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

If the device has the supervision event, the display interface will show the disturbance record and
the supervision event at the same time.

1. Disturb Records NO.2


2008-11-28 07:10:00:200
0 ms DPFC.Pkp

24 ms A 21Q.Z1.Op

2. Superv Events NO.3


2008-11-28 07:09:00:200
Alm_52b

Disturb Records NO.2 shows the title and SOE number of the disturbance record.

2008-11-28 07:10:00:200 shows the time when fault detector picks up, the format is
year–month-date and hour:minute:second:millisecond.

0ms DPFC.Pkp shows fault detector element and its operating time (set as 0ms
fixedly).

24ms A 21Q.Z1.Op shows operation element and its relative operation time

All the protection elements have been listed in Chapter “Operation Theory”, and please refer to
each protection element for details. Operation reports of fault detector and the reports related to
oscillography function are showed in the following table.

Table 8.3-1 Tripping report messages

No. Message Description


1 ManTrigDFR Oscillography function is triggered manually.
2 RmtTrigDFR Oscillography function is triggered remotely.

8.3.4 Display Supervision Event


This device can store 1024 pieces of supervision events. During the running of the device, the
supervision event of hardware self-check errors or system running abnormity will be displayed
immediately.

PCS-902 Line Distance Relay 8-21


Date: 2011-07-06
8 Human Machine Interface

2. Superv Events NO.4


2008-12-29 9:18:47:500ms

Alm_52b 0 1

Superv_Events NO.4 shows the SOE number and title of the supervision event

2008-11-28 09:18:47:500 shows the real time of the report: year–month-date and
hour:minute:second:millisecond

Alm_52b 0→1 shows the content of abnormality alarm

8.3.5 Display IO Events


This device can store 1024 pieces of binary events. During the running of the device, the binary
input will be displayed once its state has changed, i.e. from “0” to “1” or from “1” to “0”.

3. IO Events NO.4
2008-11-29 09:18:47:500ms

BI_RstTarg 0 1

IO Events NO.4 shows the number and title of the binary event

2008-11-28 09:18:47:50 shows date and time when the report occurred, the format is
year–month-date and hour:minute:second:millisecond

BI_RstTarg 0→1 shows the state change of binary input, including binary input

8-22 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

name, original state and final state

8.3.6 Display Device Logs


This device can store 1024 pieces of device logs. During the running of the device, the device log
will be displayed after any operation of it is conducted.

4. Device Logs NO.4


2008-11-28 10:18:47:569ms
Reboot

Device Logs NO. 4 shows the title and the number of the device log

2008-11-28 10:18:47:569 shows date and time when the report occurred, the format is
year–month-date and hour:minute:second:millisecond

Reboot shows the manipulation content of the device log

User operating information listed below may be displayed.

Table 8.3-2 User operating event list

No. Message Description


1 Reboot The device has been reboot.
2 Settings_Chg The device′s settings have been changed.
3 ActiveGrp_Chgd Active setting group has been changed.
4 Report_Cleared All reports have been deleted. (Device logs can not be deleted)
5 Waveform_Cleared All waveforms have been deleted.
6 Process_Exit A process has exited.
7 Counter_Cleared Clear counter
8 Signal_Reset Reset signal

It will be displayed on the LCD before the fault report and self-check report are confirmed. Only
pressing the restore button on the protection screen or pressing both “ENT” and “ESC” at the
same time can switch among the fault report, the self-check report and the normal running state of
protection device to display it. The binary input change report will be displayed for 5s and then it
will return to the previous display interface automatically.

PCS-902 Line Distance Relay 8-23


Date: 2011-07-06
8 Human Machine Interface

8.4 Keypad Operation


8.4.1 View Device Measurements
The operation is as follows:

1. Press the “▲” to enter the main menu;

2. Press the “▲” or “▼” to move the cursor to the “Measurements” menu, and then press
the “ENT” or “►” to enter the menu;

3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;

4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most);

5. Press the “◄” or “►” to select pervious or next command menu;

6. Press the “ENT” or “ESC” to exit this menu (returning to the “Measurements” menu);

8.4.2 View Device Status


The operation is as follows:

1. Press the key “▲” to enter the main menu.

2. Press the key “▲” or “▼” to move the cursor to the “Status” menu, and then press the
“ENT” or “►” to enter the menu.

3. Press the key “▲” or “▼” to move the cursor to any command menu item, and then press
the key “ENT” to enter the submenu.

4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most).

5. Press the key “◄” or “►” to select pervious or next command menu.

6. Press the key “ENT” or “ESC” to exit this menu (returning to the “Status” menu).

8.4.3 View Device Records


The operation is as follows:

1. Press the “▲” to enter the main menu;

2. Press the “▲” or “▼” to move the cursor to the “Records” menu, and then press the
“ENT” or “►” to enter the menu;

3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;

4. Press the “▲” or “▼” to page up/down;

5. Press the “+” or “-” to select pervious or next record;

8-24 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

6. Press the “◄” or “►” to select pervious or next command menu;

7. Press the “ENT” or “ESC” to exit this menu (returning to the “Records” menu);

8.4.4 Print Device Report


The operation is as follows:

1. Press the “▲” to enter the main menu;

2. Press the “▲” or “▼” to move the cursor to the “Print” menu, and then press the “ENT” or
“►” to enter the menu;

3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;

 Selecting the “Disturb Records”, and then press the “+” or “-” to select pervious
or next record. After pressing the key “ENT”, the LCD will display “Start Printing... ”,
and then automatically exit this menu (returning to the menu “Print”). If the printer
doesn’t complete its current print task and re-start it for printing, and the LCD will
display “Printer Busy…”. Press the key “ESC” to exit this menu (returning to the
menu “Print”).

 Selecting the command menu “Superv Events” or “IO Events”, and then press the
key “▲” or “▼” to move the cursor. Press the “+” or “-” to select the starting and
ending numbers of printing message. After pressing the key “ENT”, the LCD will
display “Start Printing…”, and then automatically exit this menu (returning to the
menu “Print”). Press the key “ESC” to exit this menu (returning to the menu “Print”).

4. If selecting the command menu “Device Info”, “Device Status“ or “IEC103_Info”,


press the key “ENT”, the LCD will display “Start printing..”, and then automatically exit this
menu (returning to the menu “Print”).

5. If selecting the “Settings”, press the key “ENT” or “►” to enter the next level of menu.

6. After entering the submenu “Settings”, press the key “▲” or “▼” to move the cursor, and
then press the key “ENT” to print the corresponding default value. If selecting any item to
printing:

Press the key “+” or “-” to select the setting group to be printed. After pressing the key
“ENT”, the LCD will display “Start Printing…”, and then automatically exit this menu
(returning to the menu “Settings”). Press the key “ESC” to exit this menu (returning to the
menu “Settings”).

7. After entering the submenu “Waveforms”, press the “+” or “-” to select the waveform
item to be printed and press ”ENT” to enter. If there is no any waveform data, the LCD will
display “No Waveform Data!” (Before executing the command menu “Waveforms”, it is
necessary to execute the command menu “Trig Oscillograph” in the menu “Local Cmd”,
otherwise the LCD will display “No Waveform Data!”). With waveform data existing:

Press the key “+” or “-” to select pervious or next record. After pressing the key “ENT”, the LCD

PCS-902 Line Distance Relay 8-25


Date: 2011-07-06
8 Human Machine Interface

will display “Start Printing…”, and then automatically exit this menu (returning to the menu
“Waveforms”). If the printer does not complete its current print task and re-start it for printing, and
the LCD will display “Printer Busy…”. Press the key “ESC” to exit this menu (returning to the menu
“Waveforms”).

8.4.5 View Device Setting


The operation is as follows:

1. Press the “▲” to enter the main menu;

2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the
“ENT” or “►” to enter the menu;

3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;

4. Press the “▲” or “▼” to move the cursor;

5. Press the “+” or “-” to page up/down;

6. Press the “◄” or “►” to select pervious or next command menu;

7. Press the “ESC” to exit this menu (returning to the menu “Settings”).

Note!

If the displayed information exceeds 14 lines, the scroll bar will appear on the right side of
the LCD to indicate the quantity of all displayed information of the command menu and the
relative location of information where the current cursor points at.

8.4.6 Modify Device Setting


The operation is as follows:

1. Press the “▲” to enter the main menu;

2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the
“ENT” or “►” to enter the menu;

3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;

4. Press the “▲” or “▼” to move the cursor;

5. Press the “+” or “-” to page up/down;

6. Press the “◄” or “►” to select pervious or next command menu;

7. Press the “ESC” to exit this menu (returning to the menu “Settings” );

8. If selecting the command menu “System Settings”, move the cursor to the setting
item to be modified, and then press the “ENT”;

8-26 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

Press the “+” or “-” to modify the value (if the modified value is of multi-bit, press the “◄” or “►”
to move the cursor to the digit bit, and then press the “+” or “-” to modify the value), press the
“ESC” to cancel the modification and return to the displayed interface of the command menu
“System Settings”. Press the “ENT” to automatically exit this menu (returning to the displayed
interface of the command menu “System Settings”).

Move the cursor to continue modifying other setting items. After all setting values are modified,
press the “◄”, “►” or “ESC”, and the LCD will display “Save or Not?”. Directly press the “ESC” or
press the “◄” or “►” to move the cursor. Select the “Cancle”, and then press the “ENT” to
automatically exit this menu (returning to the displayed interface of the command menu “System
Settings”).

Press the “◄” or “►” to move the cursor. Select “No” and press the “ENT”, all modified setting item
will restore to its original value, exit this menu (returning to the menu “Settings”).

Press the “◄” or “►” to move the cursor to select “Yes”, and then press the “ENT”, the LCD will
display password input interface.

Please Input Password:

____

Input a 4-bit password (“+”, “◄”, “▲” or “-”). If the password is incorrect, continue inputting it,
and then press the “ESC” to exit the password input interface and return to the displayed interface
of the command menu “System Settings”. If the password is correct, LCD will display “Save
Setting Now…”, and then exit this menu (returning to the displayed interface of the command
menu “System Settings”), with all modified setting items as modified values.

Note!

For different setting items, their displayed interfaces are different but their modification
methods are the same. The following is ditto.

9. If selecting the submenu “Prot Settings”, and press “ENT” to enter. After selecting
different command menu, the LCD will display the following interface: (take “FD
Settings” as an example)

PCS-902 Line Distance Relay 8-27


Date: 2011-07-06
8 Human Machine Interface

Line Settings

Please Select Group for Config

Active Group: 01

Selected Group: 02

Press the “+” or “-” to modify the value, and then press the “ENT” to enter it. Move the cursor to
the setting item to be modified, press the “ENT” to enter.

Take the setting [FD.DPFC.I_Set] as an example is selected to modify, then press the “ENT” to
enter and the LCD will display the following interface. is shown the “+” or “-” to modify the value
and then press the “ENT” to confirm.

FD.DPFC.I_Set

Current Value 0.200

Modified Value 0.202

Min Value 0.050

Max Value 30.000

Note!

After modifying protection settings in current active setting group or system parameters of
the device, the “HEALTHY” indicator lamp of the device will go out, and the device will
automatically restart and re-check them. If the check doesn’t pass, the device will be
blocked.

8-28 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

8.4.7 Copy Device Setting


The operation is as follows:

1. Press the “▲” to enter the main menu;

2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the
“ENT” or “►” to enter the menu;

3. Press the “▲” or “▼” to move the cursor to the command menu “Copy Settings”, and
then press the “ENT” to enter the menu.

Copy Settings

Active Group: 01

Copy To Group: 02

Press the “+” or “-” to modify the value. Press the “ESC”, and return to the menu “Settings”.
Press the “ENT”, the LCD will display the interface for password input, if the password is incorrect,
continue inputting it, press the “ESC” to exit the password input interface and return to the menu
“Settings”. If the password is correct, the LCD will display “copy setting OK!”, and exit this menu
(returning to the menu “Settings”).

8.4.8 Switch Setting Group


The operation is as follows:

1. Exit the main menu;

2. Press the “GRP”

PCS-902 Line Distance Relay 8-29


Date: 2011-07-06
8 Human Machine Interface

Change Active Group

Active Group: 01

Change To Group: 02

Press the “+” or “-” to modify the value, and then press the “ESC” to exit this menu (returning to
the main menu). After pressing the “ENT”, the LCD will display the password input interface. If the
password is incorrect, continue inputting it, and then press the “ESC” to exit the password input
interface and return to its original state. If the password is correct, the “HEALTHY” indicator lamp
of the protection device will go out, and the protection device will re-check the protection setting. If
the check doesn’t pass, the protection device will be blocked. If the check is successful, the LCD
will return to its original state.

8.4.9 Delete Device Records


The operation is as follows:

1. Exit the main menu;

2. Press the “+”, “-”, “+”, “-” and “ENT”; Press the “ESC” to exit this menu (returning to
the original state). Press the “ENT” to carry out the deletion.

Press <ENT> To Clear


Press <ESC> To Exit

8-30 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

Note!

The operation of deleting device message will delete all messages saved by the protection
device, including disturbance records, supervision events, binary events, but not including
device logs. Furthermore, the message is irrecoverable after deletion, so the application of
the function shall be cautious.

8.4.10 Modify Device Clock


The operation is as follows:

1. Press the “▲” to enter the main menu;

2. Press the “▲” or “▼” to move the cursor to the “Clock” menu, and then press the “ENT”
to enter clock display

3. Press the “▲” or “▼” to move the cursor to the date or time to be modified;

4. Press the “+” or “-” to modify value, and then press the “ENT” to save the modification
and return to the main menu;

5. Press the “ESC” to cancel the modification and return to the main menu.

Clock

Year 2008
Month 11
Day 28
Hour 20
Minute 59
Second 14

8.4.11 View Module Information


The operation is as follows:

1. Press the “▲” to enter the main menu;

2. Press the “▲” or “▼” to move the cursor to the “Information” menu, and then press the
“ENT” or “►” to enter the menu;

3. Press the “▲” or “▼” to move the cursor to the command menu “Board Info”, and then
press the “ENT” to enter the menu;

4. Press the “▲” or “▼” to move the scroll bar;

PCS-902 Line Distance Relay 8-31


Date: 2011-07-06
8 Human Machine Interface

5. Press the “ENT” or “ESC” to exit this menu (returning to the “Information” menu).

8.4.12 Check Software Version


The operation is as follows:

1. Press the “▲” to enter the main menu.

2. Press the “▲” or “▼” to move the cursor to the “Information” menu, and then press the
“ENT” to enter the submenu.

3. Press the key “▲” or “▼” to move the cursor to the command menu “Version Info”, and
then press the key “ENT” to display the software version.

4. Press the “ESC” to return to the main menu.

8.4.13 Communication Test


The operation is as follows:

1. Press the key “▲” to enter the main menu.

2. Press the key “▲” or “▼” to move the cursor to the “Test” menu, and then press the key
“ENT” or “►” to enter the menu.

3. Press the key “▲” or “▼” to move the cursor to the submenu “Device Test”, and then
press the key “ENT” to enter the submenu,to select test item. If “Prot Elements” “Superv
Events” or “IO Events” is selected, two options “All Test” and “Select Test” are
provided.

Prot Element

All Test

Select Test

4. Press the key “▲” or “▼” to move the cursor to select the corresponding command menu
“All Test” or “Select Test”. If selecting the “All Test”, press the “ENT”, and the device will
successively carry out all operation element message test one by one.

5. If “Select Test” is selected, press the key “ENT”. Press the “+” or “-” to page up/down,
and then press the key “▲” or “▼” to move the scroll bar. Move the cursor to select the

8-32 PCS-902 Line Distance Relay


Date: 2011-07-06
8 Human Machine Interface

corresponding protection element. Press the key “ENT” to execute the communication
test of this protection element, the substation automatic system (SAS) will receive the
corresponding message.

Note!

If no input operation is carried out within 60s, exit the communication transmission and
return to the “Test” menu, at this moment, the LCD will display “Communication Test
Timeout and Exiting...”.

Press the key “ESC” to exit this menu (returning to the menu “Test”, at this moment, the LCD will
display “Communication Test Exiting…”.

8.4.14 Select Language


The operation is as follows:

1. Press the key “▲” to enter the main menu.

2. Press the key “▲” or “▼” to move the cursor to the command menu “Language”, and
then press the key “ENT” to enter the menu and the following display will be shown on
LCD.

Please Select Language:

1 中文
2 English

3. Press the key “▲” or “▼” to move the cursor to the language user preferred and press
the key “ENT” to execute language switching. After language switching is finished, LCD
will return to the menu “Language”, and the display language is changed. Otherwise,
press the key “ESC” to cancel language switching and return to the menu “Language”.

Note!

LCD interface provided in this chapter is only a reference and available for explaining
specific definition of LCD. The displayed interface of the actual device may be some
different from it, so you shall be subject to the actual protection device.

PCS-902 Line Distance Relay 8-33


Date: 2011-07-06
8 Human Machine Interface

8-34 PCS-902 Line Distance Relay


Date: 2011-07-06
9 Configurable Function

9 Configurable Function

Table of Contents
9 Configurable Function..................................................................... 9-a
9.1 Overview .......................................................................................................... 9-1
9.2 Introduction on PCS-PC software.................................................................. 9-1
9.3 Protective Device Configuration .................................................................... 9-1
9.3.1 System Configuration ......................................................................................................... 9-1

9.3.2 Function Configuration ....................................................................................................... 9-3

9.3.3 Configuration of LED Indicators ......................................................................................... 9-3

9.3.4 Configuration of Binary Input.............................................................................................. 9-4

9.3.5 Configuration of Binary Output ........................................................................................... 9-5

9.3.6 Setting Configuration ......................................................................................................... 9-6

9.4 Signal List ........................................................................................................ 9-6


9.4.1 Input Signal ........................................................................................................................ 9-6

9.4.2 Output Signal ................................................................................................................... 9-11

List of Tables
Table 9.4-1 Configurable input signals ....................................................................................9-6

Table 9.4-2 Internal input signals .............................................................................................9-9

Table 9.4-3 Configurable output signals ................................................................................ 9-11

Table 9.4-4 Internal output signals .........................................................................................9-14

PCS-902 Line Distance Relay 9-a


Date: 2011-07-06
9 Configurable Function

9-b PCS-902 Line Distance Relay


Date: 2011-07-06
9 Configurable Function

9.1 Overview

By adoption of PCS-PC software, it is able to make system configuration, function configuration,


binary input and binary output configuration, LED indicator configuration and programming logic
for PCS-902.

9.2 Introduction on PCS-PC software

PCS-PC software is developed in order to meet customer‟s demand on functions of UAPC


platform device such as device configuration and programmable design. It selects substation as
the core of data management and the device as fundamental unit, supporting one substation to
govern many devices. The software provides on-line and off-line functions: on-line mode: Ethernet
connected with the device supporting IEC60870-5-103 and capable of uploading and downloading
configuration files through Ethernet net; off-line mode: off-line setting configuration. In addition, it
also supports programmable logic to meet customer‟s demand. Please refer to Instruction
Manual of PCS-PC Auxiliary Software for details.

Overall functions:

 Programmable logic (off-line function)

 System configuration (off-line function)

 Function configuration (off-line function)

 LED indicators configuration (off-line function)

 Binary signals configuration (off-line function)

 Setting configuration (off-line & on-line function)

 Real-time display of analogue and digital quantity of device (on-line function)

 Display of sequence of report (SOE) (on-line function)

 Analysis of waveform (off-line & on-line function)

 File downloading/uploading (on-line function)

9.3 Protective Device Configuration

9.3.1 System Configuration

Warning!

The system configuration shall only be operated by professionals who are familiar with
protection object and protection device. Or else, any incorrect configuration may cause

PCS-902 Line Distance Relay 9-1


Date: 2011-07-06
9 Configurable Function

relay mal-operation or failure to operate. In general, these configuration works have been
completed before equipment leaving factory.

Warning!

If the system configuration is really needed, user must select “Execute whole script” item in
the right click menu before other configuration operations.

9.3.1.1 CB Configuration

One CB configuration or two CB configuration can be selected by the menu of


“CB_Number_Config”.

9.3.1.2 Configuration of GOOSE Function

GOOSE function can be enabled or disabled by the menu of “GOOSE_Module”.

9.3.1.3 Configuration of Communication Channel

“PLC” (PLC channel) or “FO” (optical fibre channel) can be chose by the menu of
“GOOSE_Module”.

9-2 PCS-902 Line Distance Relay


Date: 2011-07-06
9 Configurable Function

9.3.2 Function Configuration


Whether some protection is enabled or disabled shall be configured. In case of “Disable” is
selected, the protective function in protective equipment will be hidden.

9.3.3 Configuration of LED Indicators


1. This protection device provides 20 LED indicators, 2 LED indicators are defined as,
“HEALTHY” LED and “ALARM“ LED, the rest 18 LEDs can be configured by users as
required.

2. The column “ ” in the right hand side of PCS_PC software/Binary


signal config/LED_indicator_configuration provides elements including protection elements,
alarm elements and binary input elements for LEDs.

3. “Latched” check boxes with the LEDS are available. When a check box is selected, the
respective LED could only be reset by energizing [BI_RstTarg] once it is lit. If the check box is
not selected, the signals will reset automatically once the trigger signal resets.

4. The column “ ” is used to choose color for each LED. “yellow”, “green” and “red” are
provided to choose from.

PCS-902 Line Distance Relay 9-3


Date: 2011-07-06
9 Configurable Function

5. If the “LED_5” is used to indicate the device ready for AR of CB1, configure it as the following
picture.

6. The label of the “LED_5” can be edited by double-click it.

7. The signal in the column of “Signal” can be deleted by right-click, and then left-click to execute
“delete” command.

9.3.4 Configuration of Binary Input

1. Pin number of user-defined binary input on module is provided by the column “ ”

on the right of the interface.

2. The next step is to set delay pick up and drop off time in the columns of “ ” and

“ ” (unit: ms) respectively for individual binary inputs.

3. The column “ ” at the right hand side of the screen is a


list of functions available for selection to individual binary inputs. They can be directly dragged
from the list to assigned binary input.

4. The signal in the column of “Int. Signal” can be deleted by right-click, and then left-click to
execute delete command.

5. The displayed content of the column “ ” can be edited by double-click according


to user‟s requirement.

9-4 PCS-902 Line Distance Relay


Date: 2011-07-06
9 Configurable Function

9.3.5 Configuration of Binary Output


1. Pin number of user-defined binary output on module is provided by the column

“ ” on the left of the interface.

2. Elements in the column “ ” at the right hand side of the screen


can be dragged to point to a or several binary output contacts. The optional signals include:
Trip Elements, Alarm, Binary Change and Other Type (Reserved or spare).

3. For example, the contact “ ” is intended for closing CB1, the


corresponding output signal in the right tree structure is then dragged to the position at the
crossing of column „Int. Signal‟ and row “Board11_Pin07-08”.

4. The signal added in the column of “Int. Signal” can be deleted by right-click, and then left-click
to execute delete command.

5. The displayed content of the column “ ” can be edited by double-click according to


user‟s requirement.

PCS-902 Line Distance Relay 9-5


Date: 2011-07-06
9 Configurable Function

9.3.6 Setting Configuration


After function configuration is finished, disabled protective function is hidden in device and in
setting configuration list of PCS-PC software.

Users can configure the equipment parameters, system settings and etc.

Users can select to show or hide some setting, and modify typical setting values

9.4 Signal List

9.4.1 Input Signal


All input signal for this device are listed in the following table (The value of any signal not
configured retains the default value).

For the specific project, some signals relevant to synchrocheck module, auto-reclosing module
and breaker failure protection module are with the suffix of “_CB1” and “_CB2” for circuit breaker 1
and circuit breaker 2 respectively.

Table 9.4-1 Configurable input signals

No. Item Description


1 52b_PhA Normally closed auxiliary contact of phase A of corresponding circuit breaker
2 52b_PhB Normally closed auxiliary contact of phase B of corresponding circuit breaker
3 52b_PhC Normally closed auxiliary contact of phase C of corresponding circuit breaker
4 52b Normally closed contact of three-phase of circuit breaker
5 52a Normally open contact of three-phase of circuit breaker
6 TCCS.Input Control circuit failure

9-6 PCS-902 Line Distance Relay


Date: 2011-07-06
9 Configurable Function

No. Item Description


7 21D.En_DPFC DPFC distance protection enabling input, it can be a binary input or a logic link.
8 21D.Blk_DPFC DPFC distance protection blocking input, such as a function blocking binary input.
9 21M.En Distance protection enabling input, it can be a binary input or a logic link
10 21M.Blk Distance protection blocking input, such as a function blocking binary input
11 21Q.En Distance protection enabling input, it can be a binary input or a logic link
12 21Q.Blk Distance protection blocking input, such as a function blocking binary input
13 68.In_En Power swing detection enabling input, it can be a binary input or a logic link.
14 68.Blk Power swing detection blocking input, such as a function blocking binary input.
15 21SOTF.En Distance SOTF protection enabling input, it can be a binary input or a logic link.
16 21SOTF.Blk Distance SOTF protection blocking input, such as a function blocking binary input.
17 FOx.Recv1 Receiving signal 1 of channel x
18 FOx.Recv2 Receiving signal 2 of channel x
19 FOx.Recv3 Receiving signal 3 of channel x
20 FOx.Recv4 Receiving signal 4 of channel x
21 FOx.Recv5 Receiving signal 5 of channel x
22 FOx.Recv6 Receiving signal 6 of channel x
23 FOx.Recv7 Receiving signal 7 of channel x
24 FOx.Recv8 Receiving signal 8 of channel x
25 85.Z_En1 Pilot distance protection enabling input 1, it can be a binary input or a logic link.
26 85.Z_En2 Pilot distance protection enabling input 2, it can be a binary input or a logic link.
27 85.Z_Blk Pilot distance protection blocking input, such as a function blocking binary input.
28 85.Abnor_Ch1 Input signal of indicating that pilot channel 1 is abnormal
Input signal of receiving permissive signal via channel No.1, or input signal of
29 85.Rcv1 receiving permissive signal of A-phase via channel No.1 (only for
phase-segregated command scheme)
Input signal of receiving permissive signal of B-phase via channel No.1 (only for
30 85.RcvB
phase-segregated command scheme)
Input signal of receiving permissive signal of C-phase via channel No.1 (only for
31 85.RcvC
phase-segregated command scheme)
32 85.ExTrp Input signal of initiating sending permissive signal from external tripping signal
33 85.Unblocking1 Unblocking signal 1
34 85.ZX_En1 Zone Extension enabling input 1, it can be a binary input or a logic link.
35 85.ZX_En2 Zone Extension enabling input 2, it can be a binary input or a logic link.
36 85.ZX_Blk1 Zone Extension blocking input 1, such as a function blocking binary input.
37 85.ZX_Blk2 Zone Extension blocking input 2, such as a function blocking binary input.
Pilot directional earth-fault protection enabling input 1, it can be a binary input or a
38 85.DEF.En1
logic link.
Pilot directional earth-fault protection enabling input 2, it can be a binary input or a
39 85.DEF.En2
logic link.
Pilot directional earth-fault protection blocking input, such as a function blocking
40 85.DEF.Blk
binary input.
41 85.Abnor_Ch2 Input signal of indicating that pilot channel 2 is abnormal

PCS-902 Line Distance Relay 9-7


Date: 2011-07-06
9 Configurable Function

No. Item Description


42 85.Rcv2 Input signal of receiving permissive signal via channel 2
43 85.Unblocking2 Unblocking signal 2
Stage x of phase overcurrent protection enabling input 1, it can be a binary input
44 50/51Px.En1
or a logic link.
Stage x of phase overcurrent protection enabling input 2, it can be a binary input
45 50/51Px.En2
or a logic link.
Stage x of phase overcurrent protection blocking input, such as a function
46 50/51Px.Blk
blocking binary input.
Stage x of earth fault protection enabling input 1, it can be a binary input or a logic
47 50/51Gx.En1
link.
Stage x of earth fault protection enabling input 2, it can be a binary input or a logic
48 50/51Gx.En2
link.
Stage x of earth fault protection blocking input, such as a function blocking binary
49 50/51Gx.Blk
input.
Residual current SOTF protection enabling input, it can be a binary input or a
50 50SOTF.En
logic link.
Residual current SOTF protection blocking input, such as a function blocking
51 50SOTF.Blk
binary input.
Stage x of overvoltage protection enabling input 1, it can be a binary input or a
52 59Px.En1
logic link.
Stage x of overvoltage protection enabling input 2, it can be a binary input or a
53 59Px.En2
logic link.
Stage x of overvoltage protection blocking input, such as a function blocking
54 59Px.Blk
binary input.
Stage x of undervoltage protection enabling input 1, it can be a binary input or a
55 27Px.En1
logic link.
Stage x of undervoltage protection enabling input 2, it can be a binary input or a
56 27Px.En2
logic link.
Stage x of undervoltage protection blocking input, such as a function blocking
57 27Px.Blk
binary input.
Stage x of overfrequency protection enabling input 1, it can be a binary input or a
58 81Ox.En1
logic link.
Stage x of overfrequency protection enabling input 2, it can be a binary input or a
59 81Ox.En2
logic link.
Stage x of overfrequency protection blocking input, such as a function blocking
60 81Ox.Blk
binary input.
Stage x of underfrequency protection enabling input 1, it can be a binary input or a
61 81Ux.En1
logic link.
Stage x of underfrequency protection enabling input 2, it can be a binary input or a
62 81Ux.En2
logic link.
Stage x of underfrequency protection blocking input, such as a function blocking
63 81Ux.Blk
binary input.

9-8 PCS-902 Line Distance Relay


Date: 2011-07-06
9 Configurable Function

No. Item Description


64 50BF.ExTrp3P_L Input signal of three-phase tripping contact from line protection
Input signal of three-phase tripping contact from generator or transformer
65 50BF.ExTrp3P_GT
protection
66 49.Clr Input signal of clear thermal accumulation value
67 49.En Thermal overload protection enabling input, it can be a binary input or a logic link.
Thermal overload protection blocking input, such as a function blocking binary
68 49.Blk
input.
69 50STB.In_En Stub overcurrent protection enabling input, it can be binary inputs or logic link.
70 50STB.Blk Stub overcurrent protection blocking input, such as function blocking binary input.
Pole discrepancy protection enabling input 1, it can be a binary input or a logic
71 62PD.En1
link.
Pole discrepancy protection enabling input 2, it can be a binary input or a logic
72 62PD.En2
link.
Pole discrepancy protection blocking input, such as a function blocking binary
73 62PD.Blk
input.
Input signal of enabling AR. If the logic setting [79.En_ExtCtrl] is set as “1”, AR will
74 79.In_En
be controlled to enable by external input signal.
Input signal of disabling AR. If the logic setting [79.En_ExtCtrl] is set as “1”, AR
75 79.Blk
will be controlled to disable by external input signal.
76 TT.Init Input signal of initiating transfer trip after receiving transfer trip
77 CTS.En CT circuit supervision enabling input, it can be a binary input or a logic link.
78 CTS.Blk CT circuit supervision blocking input, such as a function blocking binary input.

Table 9.4-2 Internal input signals

No. Item Description


1 I3P Three-phase current input
2 U3P Three-phase voltage input
3 21M.ZG1.In_En Zone 1 of phase-to-ground distance protection enabling input
4 21M.ZG1.In_Blk Zone 1 of phase-to-ground distance protection blocking input
5 21M.ZP1.In_En Zone 1 of phase-to-phase distance protection enabling input
6 21M.ZP1.In_Blk Zone 1 of phase-to-phase distance protection blocking input
7 21M.ZG2.In_En Zone 2 of phase-to-ground distance protection enabling input
8 21M.ZG2.In_Blk Zone 2 of phase-to-ground distance protection blocking input
9 21M.ZP2.In_En Zone 2 of phase-to-phase distance protection enabling input
10 21M.ZP2.In_Blk Zone 2 of phase-to-phase distance protection blocking input
11 21M.ZG3.In_En Zone 3 of phase-to-ground distance protection enabling input
12 21M.ZG3.In_Blk Zone 3 of phase-to-ground distance protection blocking input
13 21M.ZP3.In_En Zone 3 of phase-to-phase distance protection enabling input
14 21M.ZP3.In_Blk Zone 3 of phase-to-phase distance protection blocking input
15 21M.ZG4.In_En Zone 4 of phase-to-ground distance protection enabling input
16 21M.ZG4.In_Blk Zone 4 of phase-to-ground distance protection blocking input
17 21M.ZP4.In_En Zone 4 of phase-to-phase distance protection enabling input

PCS-902 Line Distance Relay 9-9


Date: 2011-07-06
9 Configurable Function

No. Item Description


18 21M.ZP4.In_Blk Zone 4 of phase-to-phase distance protection blocking input
19 21Q.ZG1.In_En Zone 1 of phase-to-ground distance protection enabling input
20 21Q.ZG1.In_Blk Zone 1 of phase-to-ground distance protection blocking input
21 21Q.ZP1.In_En Zone 1 of phase-to-phase distance protection enabling input
22 21Q.ZP1.In_Blk Zone 1 of phase-to-phase distance protection blocking input
23 21Q.ZG2.In_En Zone 2 of phase-to-ground distance protection enabling input
24 21Q.ZG2.In_Blk Zone 2 of phase-to-ground distance protection blocking input
25 21Q.ZP2.In_En Zone 2 of phase-to-phase distance protection enabling input
26 21Q.ZP2.In_Blk Zone 2 of phase-to-phase distance protection blocking input
27 21Q.ZG3.In_En Zone 3 of phase-to-ground distance protection enabling input
28 21Q.ZG3.In_Blk Zone 3 of phase-to-ground distance protection blocking input
29 21Q.ZP3.In_En Zone 3 of phase-to-phase distance protection enabling input
30 21Q.ZP3.In_Blk Zone 3 of phase-to-phase distance protection blocking input
31 21Q.ZG4.In_En Zone 4 of phase-to-ground distance protection enabling input
32 21Q.ZG4.In_Blk Zone 4 of phase-to-ground distance protection blocking input
33 21Q.ZP4.In_En Zone 4 of phase-to-phase distance protection enabling input
34 21Q.ZP4.In_Blk Zone 4 of phase-to-phase distance protection blocking input
35 21M.En_PSBR Enabling power swing blocking releasing (Mho characteristic)
36 21Q.En_PSBR Enabling power swing blocking releasing (Quad characteristic)
37 21M.Blk_PSBR Blocking power swing blocking releasing (Mho characteristic)
38 21Q.Blk_PSBR Blocking power swing blocking releasing (Quad characteristic)
39 FOx.Recv9 Receiving signal 9 of channel x
40 FOx.Recv10 Receiving signal 10 of channel x
41 FOx.Recv11 Receiving signal 11 of channel x
42 FOx.Recv12 Receiving signal 12 of channel x
43 50BF.ExTrpA Input signal of phase-A tripping contact from external device
44 50BF.ExTrpB Input signal of phase-B tripping contact from external device
45 50BF.ExTrpC Input signal of phase-C tripping contact from external device
Input signal of three-phase tripping contact from external device. Once it is
46 50BF.ExTrp_WOI energized, normally closed auxiliary contact of circuit breaker is chosen in
addition to breaker failure current check to trigger breaker failure timers.
47 62PD.In_PD Pole discrepancy binary input
48 25.Blk_Chk Input signal of blocking synchrocheck function for AR.
Input signal of blocking synchronism check for AR. If the value is “1”, the output of
49 25.Blk_SynChk
synchronism check is “0”.
50 25.Blk_DdChk Input signal of blocking dead charge check for AR.
Input signal of starting synchronism check, usually it was starting signal of AR
51 25.Start_Chk
from auto-reclosing module.
52 79.Sel_1PAR Input signal of selecting 1-pole AR mode of corresponding circuit breaker
53 79.Sel_3PAR Input signal of selecting 3-pole AR mode of corresponding circuit breaker
54 79.Sel_1P/3PAR Input signal of selecting 1/3-pole AR mode of corresponding circuit breaker
55 79.Trp Input signal of single-phase tripping from line protection to initiate AR

9-10 PCS-902 Line Distance Relay


Date: 2011-07-06
9 Configurable Function

No. Item Description


56 79.Trp3P Input signal of three-phase tripping from line protection to initiate AR
57 79.TrpA Input signal of A-phase tripping from line protection to initiate AR
58 79.TrpB Input signal of B-phase tripping from line protection to initiate AR
59 79.TrpC Input signal of C-phase tripping from line protection to initiate AR
Input signal of indicating that the circuit breaker has enough energy to perform
60 79.CB_Healthy
closing function
Input signal of blocking reclosing, usually it is connected with manual closing
61 79.LockOut contact or tripping contact of breaker failure protection, transformer protection and
busbar differential protection, etc.
62 79.PLC_Lost Input signal of indicating the alarm signal that signal channel is lost
Input signal of waiting for reclosing permissive signal from master AR (when
63 79.WaitMaster
reclosing multiple circuit breakers)
Input signal of blocking AR which will be latched and only can be released by
64 79.BlkOn
input signal [79.Rls_BlkOn]
65 79.Rls_BlkOn Releasing command of blocking signal of auto-reclosure [79.BlkOn]
66 VTS.MCB_VT Input signal for indicating protection VT is out of service
67 FPS_Fault Faulty phase selection

9.4.2 Output Signal


All output signal for this device have been listed in the following table.

Table 9.4-3 Configurable output signals

No. Signal Description


1 Alm_52b CB position is abnormal
2 TCCS.Alm Control circuit of circuit breaker is abnormal
3 FD.Pkp The device picks up
4 21D.Op_DPFC DPFC distance protection operates.
5 21M.Z1.Op Zone 1 of distance protection operates
6 21M.Z2.Op Zone 2 of distance protection operates
7 21M.Z3.Op Zone 3 of distance protection operates
8 21M.Z4.Op zone 4 of distance protection operates
9 21Q.Z1.Op Zone 1 of distance protection operates
10 21Q.Z2.Op Zone 2 of distance protection operates
11 21Q.Z3.Op Zone 3 of distance protection operates
12 21Q.Z4.Op zone 4 of distance protection operates
13 68.St Power swing detection takes into effect.
Accelerate distance protection to trip when manual closing or
14 21SOTF.Op
auto-reclosing to fault
Accelerate distance protection to trip when another fault happening
15 21SOTF.Op_PDF
under pole discrepancy conditions
16 FOx.Recv1 Receiving signal 1 of channel x
17 FOx.Recv2 Receiving signal 2 of channel x

PCS-902 Line Distance Relay 9-11


Date: 2011-07-06
9 Configurable Function

No. Signal Description


18 FOx.Recv3 Receiving signal 3 of channel x
19 FOx.Recv4 Receiving signal 4 of channel x
20 FOx.Recv5 Receiving signal 5 of channel x
21 FOx.Recv6 Receiving signal 6 of channel x
22 FOx.Recv7 Receiving signal 7 of channel x
23 FOx.Recv8 Receiving signal 8 of channel x
ID information received from the remote end by the device at local
24 FOx.RmtID
end now
25 FOx.Alm Channel x is abnormal
26 85.Op_Z Pilot distance protection operates.
Output signal of sending permissive signal 1 or sending A-phase
27 85.Send1
permissive signal (only for phase-segregated command scheme)
Output signal of sending B-phase permissive signal (only for
28 85.SendB
phase-segregated command scheme)
Output signal of sending C-phase permissive signal (only for
29 85.SendB
phase-segregated command scheme)
30 85.Op_ZX Zone extension protection operates.
31 85.Op_DEF Pilot directional earth-fault protection operates.
32 85.DEF_BlkAR Pilot directional earth-fault protection operates to block AR.
Output signal of sending permissive signal 1 when pilot directional
33 85.Send1 earth-fault protection sharing pilot channel 1 with pilot distance
protection
Output signal of sending permissive signal 2 only for pilot directional
34 85.Send2
earth-fault protection adopting independent pilot channel 2
35 50/51P1.Op Stage 1 of phase overcurrent protection operates.
36 50/51P2.Op Stage 2 of phase overcurrent protection operates.
37 50/51 P3.Op Stage 3 of phase overcurrent protection operates.
38 50/51P4.Op Stage 4 of phase overcurrent protection operates.
39 50/51P1.St Stage 1 of phase overcurrent protection starts.
40 50/51P2.St Stage 2 of phase overcurrent protection starts.
41 50/51P3.St Stage 3 of phase overcurrent protection starts.
42 50/51P4.St Stage 4 of phase overcurrent protection starts.
43 50/51G1.Op Stage 1 of earth fault protection operates.
44 50/51G2.Op Stage 2 of earth fault protection operates.
45 50/51 G3.Op Stage 3 of earth fault protection operates.
46 50/51G4.Op Stage 4 of earth fault protection operates
47 50/51G1.St Stage 1 of earth fault protection starts.
48 50/51G2.St Stage 2 of earth fault protection starts.
49 50/51G3.St Stage 3 of earth fault protection starts.
50 50/51G4.St Stage 4 of earth fault protection starts.
51 51PVT.Op Phase overcurrent protection for VT circuit failure operates.
52 51GVT.Op Ground overcurrent protection for VT circuit failure operates.

9-12 PCS-902 Line Distance Relay


Date: 2011-07-06
9 Configurable Function

No. Signal Description


53 50SOTF.Op Residual current SOTF protection operates.
54 59P1.Op Stage 1 of overvoltage protection operates.
55 59P2.Op Stage 2 of overvoltage protection operates
56 59P1.St Stage 1 of overvoltage protection starts.
57 59P2.St Stage 2 of overvoltage protection starts.
58 59P1.Op_InitTT Stage 1 of overvoltage protection operates to initiate transfer trip.
59 59P2.Op_InitTT Stage 2 of overvoltage protection operates to initiate transfer trip.
60 27P1.Op Stage 1 of undervoltage protection operates.
61 27P2.Op Stage 2 of undervoltage protection operates
62 27P1.St Stage 1 of undervoltage protection starts.
63 27P2.St Stage 2 of undervoltage protection starts.
64 27P1.Op_InitTT Stage 1 of undervoltage protection operates to initiate transfer trip.
65 27P2.Op_InitTT Stage 2 of undervoltage protection operates to initiate transfer trip.
66 80O1.Op Stage 1 of overfrequency protection operates.
67 80O2.Op Stage 2 of overfrequency protection operates.
68 80O3.Op Stage 3 of overfrequency protection operates.
69 80O4.Op Stage 4 of overfrequency protection operates.
70 80O1.St Stage 1 of overfrequency protection starts.
71 80O2.St Stage 2 of overfrequency protection starts.
72 80O3.St Stage 3 of overfrequency protection starts.
73 80O4.St Stage 4 of overfrequency protection starts.
74 80U1.Op Stage 1 of underfrequency protection operates.
75 80U2.Op Stage 2 of underfrequency protection operates.
76 80U3.Op Stage 3 of underfrequency protection operates.
77 80U4.Op Stage 4 of underfrequency protection operates.
78 80U1.St Stage 1 of underfrequency protection starts.
79 80U2.St Stage 2 of underfrequency protection starts.
80 80U3.St Stage 3 of underfrequency protection starts.
81 80U4.St Stage 4 of underfrequency protection starts.
82 50BF.Op_ReTrpA Breaker failure protection operates to re-trip phase-A circuit breaker
83 50BF.Op_ReTrpB Breaker failure protection operates to re-trip phase-B circuit breaker
84 50BF.Op_ReTrpC Breaker failure protection operates to re-trip phase-C circuit breaker
Breaker failure protection operates to re-trip three-phase circuit
85 50BF.Op_ReTrp3P
breaker
86 50BF.Op_t1 Stage 1 breaker failure protection operates
87 50BF.Op_t2 Stage 2 breaker failure protection operates
88 49.St Thermal overload protection starts.
89 49-1.Op Stage 1 of thermal overload protection operates to trip.
90 49-2.Op Stage 2 of thermal overload protection operates to trip.
91 49-1.Alm Stage 1 of thermal overload protection operates to alarm.
92 49-2.Alm Stage 2 of thermal overload protection operates to alarm.
93 50STB.Op Stub overcurrent protecton operates.

PCS-902 Line Distance Relay 9-13


Date: 2011-07-06
9 Configurable Function

No. Signal Description


94 62PD.Op Pole discrepancy protection operates to trip
95 79.On AR is enabled.
96 79.Off AR is disabled.
97 79.Ready AR has been ready for reclosing cycle.
98 79.AR_Blkd AR is blocked.
99 79.Active AR logic is active.
100 79.Inprog AR cycle is in progress.
101 79.Inprog_1P The first 1-pole AR cycle is in progress.
102 79.Inprog_3PS2 The first 3-pole AR cycle is in progress.
Waiting signal of AR which will be sent to slave AR (when reclosing
103 79.WaitToSlave
multiple circuit breakers)

104 79.AR_Out Auto-reclosing signal

Single-phase circuit breaker will be tripped once the device


105 79.Prep_Trp1P
operates.
106 79.Prep_Trp3P Three-phase circuit breaker will be tripped once the device operates.
107 79.Fail_Rcls Auto-reclosing fails.
108 79.Fail_Chk Synchrocheck of AR fails.
109 79.Mode_1PAR Output signal of 1-pole AR mode
110 79.Mode_3PAR Output signal of 3-pole AR mode
111 79.Mode_1/3PAR Output signal of 1/3-pole AR mode
112 TT.Alm Input signal of receiving transfer trip is abnormal
113 TT.Op Transfer trip operates
114 VTS.Alm Alarm signal to indicate VT circuit fails
115 CTS.Alm Alarm signal to indicate CT circuit fails

Table 9.4-4 Internal output signals

No. Signal Description


1 FD.DPFC.Pkp DPFC current fault detector element operates.
2 FD.ROC.Pkp Residual current fault detector element operates.
3 21M.Z1.En_PSBR PSBR operates to release zone 1 (Mho characteristic)
4 21Q.Z1.En_PSBR PSBR operates to release zone 1 (Quad characteristic)
5 21M.Z2.En_PSBR PSBR operates to release zone 2 (Mho characteristic)
6 21Q.Z2.En_PSBR PSBR operates to release zone 2 (Quad characteristic)
7 21M.Z3.En_PSBR PSBR operates to release zone 3 (Mho characteristic)
8 21Q.Z3.En_PSBR PSBR operates to release zone 3 (Quad characteristic)
9 21M.Z4.En_PSBR PSBR operates to release zone 4 (Mho characteristic)
10 21Q.Z4.En_PSBR PSBR operates to release zone 4 (Quad characteristic)
PSBR operates to release pilot distance protection (Mho
11 21M.Pilot.En_PSBR
characteristic)
PSBR operates to release pilot distance protection (Quad
12 21Q.Pilot.En_PSBR
characteristic)

9-14 PCS-902 Line Distance Relay


Date: 2011-07-06
9 Configurable Function

No. Signal Description


13 FOx.Recv9 Receiving signal 9 of channel x
14 FOx.Recv10 Receiving signal 10 of channel x
15 FOx.Recv11 Receiving signal 11 of channel x
16 FOx.Recv12 Receiving signal 12 of channel x
Received ID from the remote end is not as same as the setting
17 FOx.Alm_ID
[FO1.RmtID] of the device in local end
Calculated propagation delay of communication channel of the
18 FOx.t_ChDly
device at local end now
19 FOx.Alm_NoValFram No valid frame of channel x is received
Rate of error code of channel x is larger than 40 error codes per
20 FOx.Alm_CRC
second
21 FOx.N_CRCFail Total number of error frame of channel x
22 FOx.N_FramErr Total number of abnormal messages of channel x
23 FOx.N_FramLoss Total number of lost frames of channel x
Total number of abnormal messages from the remote end of channel
24 FOx.N_RmtAbnor
x
25 FOx.t_CRCFailSec Seconds of serious error frames of channel x
26 FOx.Alm_Connect Optical fibre of channel x is connected wrongly
27 FOx.N_LossSyn Total number of loss synchronization of channel x
28 UL1_Sel To select voltage of Line 1
29 UL2_Sel To select voltage of Line 2
30 UB1_Sel To select voltage of Bus 1
31 UB2_Sel To select voltage of Bus 2
32 Invalid_Sel Voltage selection is invalid.
To indicate that frequency difference condition for synchronisim
33 25.Ok_fDiff check of AR is met, frequency difference between UB and UL is
smaller than [25.f_Diff].
To indicate that voltage difference condition for synchronisim check
34 25.Ok_UDiff of AR is met, voltage difference between UB and UL is smaller than
[25.U_Diff]
To indicate phase difference condition for synchronisim check of AR
35 25.Ok_phiDiff is met, phase difference between UB and UL is smaller than
[25.phi_Diff].
36 25.Ok_DdL_DdB Dead line and dead bus condition is met
37 25.Ok_DdL_LvB Dead line and live bus condition is met
38 25.Ok_LvL_DdB Live line and dead bus condition is met
39 25.Chk_LvL Line voltage is greater than the voltage setting [25.U_Lv]
40 25.Chk_DdL Line voltage is smaller than the voltage setting [25.U_Dd]
41 25.Chk_LvB Bus voltage is greater than the voltage setting [25.U_Lv]
42 25.Chk_DdB Bus voltage is smaller than the voltage setting [25.U_Dd]
43 25.Ok_DdChk To indicate that dead charge check condition of AR is met
44 25.Ok_ChkChk To indicate that synchronism check condition of AR is met

PCS-902 Line Distance Relay 9-15


Date: 2011-07-06
9 Configurable Function

No. Signal Description


45 25.Ok_Chk To indicate that synchrocheck condition of AR is met
46 25.VTS_Alm_UB Synchronism voltage circuit is abnormal (UB)
47 25.VTS_Alm_UL Synchronism voltage circuit is abnormal (UL)
48 f_Prot Frequency of the voltage used by protection calculation
49 f_Syn Frequency of the voltage used by synchrocheck
50 u_Diff Voltage difference for synchronism check
51 f_Diff Frequency difference for synchronism check
52 phi_Diff Phase difference for synchronism check
53 79.N_Total_Rcls Total Recorded number of all reclosing attempts
54 79.N_Total_Rcls 1-pole Shot 1 Recorded number of first 1-pole reclosing attempts
55 79.N_Total_Rcls 3-pole Shot 1 Recorded number of first 3-pole reclosing attempts
56 79.N_Total_Rcls 3-pole Shot 2 Recorded number of second 3-pole reclosing attempts
57 79.N_Total_Rcls 3-pole Shot 3 Recorded number of third 3-pole reclosing attempts
58 79.N_Total_Rcls 3-pole Shot 4 Recorded number of fourth 3-pole reclosing attempts
59 TrpA Tripping A-phase circuit breaker
60 TrpB Tripping B-phase circuit breaker
61 TrpC Tripping C-phase circuit breaker
62 Trp Tripping any phase circuit breaker
63 3PTrp Tripping three-phase circuit breaker
Protection tripping signal of A-phase configured to initiate BFP, BFI
64 BFI_A
signal shall be reset immediately after tripping signal drops off.
Protection tripping signal of B-phase configured to initiate BFP, BFI
65 BFI_B
signal shall be reset immediately after tripping signal drops off.
Protection tripping signal of C-phase configured to initiate BFP, BFI
66 BFI_ C
signal shall be reset immediately after tripping signal drops off.
Protection tripping signal of three-phase configured to initiate BFP,
67 BFI_3P
BFI signal shall be reset immediately after tripping signal drops off.
68 Fault_Location The result of fault location
69 Faulty_Phase The selected faulty phase
70 Fault_Phase_Curr Maximum faulty current
71 Fault_Resid_Curr Maximum residual current

9-16 PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

10 Communication

Table of Contents
10 Communication ............................................................................ 10-a
10.1 Overview ...................................................................................................... 10-1
10.2 Rear Communication Port Information ..................................................... 10-1
10.2.1 RS-485 Interface ............................................................................................................ 10-1

10.2.2 Ethernet Interface .......................................................................................................... 10-3

10.2.3 IEC60870-5-103 Communication ................................................................................... 10-4

10.3 IEC60870-5-103 Interface over Serial Port ................................................ 10-4


10.3.1 Physical Connection and Link Layer .............................................................................. 10-4

10.3.2 Initialization .................................................................................................................... 10-5

10.3.3 Time Synchronization ..................................................................................................... 10-5

10.3.4 Spontaneous Events ...................................................................................................... 10-5

10.3.5 General Interrogation ..................................................................................................... 10-5

10.3.6 General Service ............................................................................................................. 10-6

10.3.7 Disturbance Records ..................................................................................................... 10-6

10.4 Messages Description for IEC61850 Protocol .......................................... 10-6


10.4.1 Overview ........................................................................................................................ 10-6

10.4.2 Communication profiles ................................................................................................. 10-7

10.4.3 Server data organization ................................................................................................ 10-8

10.4.4 Server features and configuration ................................................................................ 10-10

10.4.5 ACSI Conformance ...................................................................................................... 10-12

10.4.6 Logical Nodes .............................................................................................................. 10-16

10.5 DNP3.0 Interface ....................................................................................... 10-18


10.5.1 Overview ...................................................................................................................... 10-18

10.5.2 Link Layer Functions .................................................................................................... 10-19

10.5.3 Transport Functions ..................................................................................................... 10-19

PCS-902 Line Distance Relay 10-a


Date: 2011-07-06
10 Communication

10.5.4 Application Layer Functions ......................................................................................... 10-19

List of Figures
Figure 10.2-1 EIA RS-485 bus connection arrangements.....................................................10-2

Figure 10.2-2 Ethernet communication cable .......................................................................10-3

Figure 10.2-3 Ethernet communication structure .................................................................10-4

10-b PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

10.1 Overview

This section outlines the remote communications interfaces of NR Relays. The protective device
supports a choice of three protocols via the rear communication interface (RS-485 or Ethernet),
selected via the model number by setting. The protocol provided by the protective device is
indicated in the menu “Settings→Device Setup→Comm Settings”.

The rear EIA RS-485 interface is isolated and is suitable for permanent connection of whichever
protocol is selected. The advantage of this type of connection is that up to 32 protective devices
can be “daisy chained” together using a simple twisted pair electrical connection.

It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.

10.2 Rear Communication Port Information

10.2.1 RS-485 Interface


This protective device provides two rear RS-485 communication ports, and each port has three
terminals in the 12-terminal screw connector located on the back of the relay and each port has a
ground terminal for the earth shield of the communication cable. The rear ports provide RS-485
serial data communication and are intended for use with a permanently wired connection to a
remote control center.

10.2.1.1 EIA RS-485 Standardized Bus

The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, and
the communication parameters match, then it is possible that the two-wire connection is reversed.

10.2.1.2 Bus Termination

The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (refer to Figure 10.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.

PCS-902 Line Distance Relay 10-1


Date: 2011-07-06
10 Communication

EIA RS-485
Master 120 Ohm

120 Ohm

Slave Slave Slave

Figure 10.2-1 EIA RS-485 bus connection arrangements

10.2.1.3 Bus Connections & Topologies

The EIA RS-485 standard requires that each device is directly connected to the physical cable that
is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop
bus topologies are not part of the EIA RS-485 standard and are forbidden by it also.

Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length must
not exceed 500m. The screen must be continuous and connected to ground at one end, normally
at the master connection point; it is important to avoid circulating currents, especially when the
cable runs between buildings, for both safety and noise reasons.

This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product’s chassis. This is for both safety and noise reasons.

10.2.1.4 Biasing

It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven. This can occur when
all the slaves are in receive mode and the master is slow to turn from receive mode to transmit
mode. This may be because the master purposefully waits in receive mode, or even in a high
impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss
the first bits of the first character in the packet, which results in the slave rejecting the message
and consequentially not responding. Symptoms of these are poor response times (due to retries),
increasing message error counters, erratic communications, and even a complete failure to
communicate.

Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There
should only be one bias point on the bus, which is best situated at the master connection point.
The DC source used for the bias must be clean; otherwise noise will be injected. Note that some
devices may (optionally) be able to provide the bus bias, in which case external components will
not be required.

10-2 PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

Note!

It is extremely important that the 120Ω termination resistors are fitted. Failure to do so will
result in an excessive bias voltage that may damage the devices connected to the bus.

As the field voltage is much higher than that required, NR cannot assume responsibility for
any damage that may occur to a device connected to the network as a result of incorrect
application of this voltage.

Ensure that the field voltage is not being used for other purposes (i.e. powering logic inputs)
as this may cause noise to be passed to the communication network.

10.2.2 Ethernet Interface


This protective device can provide four rear Ethernet interfaces (optional) and they are unattached
each other. Parameters of each Ethernet port can be configured in the menu “Settings→Device
Setup→Comm Settings”.

10.2.2.1 Ethernet Standardized Communication Cable

It is recommended to use twisted screened eight-core cable as the communication cable. A picture
is shown bellow.

Figure 10.2-2 Ethernet communication cable

10.2.2.2 Connections and Topologies

Each equipment is connected with an exchanger via communication cable, and thereby it forms a
star structure network. Dual-network is recommended in order to increase reliability. SCADA is
also connected to the exchanger and will play a role of master station, so the every equipment
which has been connected to the exchanger will play a role of slave unit.

PCS-902 Line Distance Relay 10-3


Date: 2011-07-06
10 Communication

SCADA

Exchanger A

Exchanger B

Equipment Equipment Equipment

Figure 10.2-3 Ethernet communication structure

10.2.3 IEC60870-5-103 Communication


The IEC specification IEC60870-5-103: Telecontrol Equipment and Systems, Part 5: Transmission
Protocols Section 103 defines the use of standards IEC60870-5-1 to IEC60870-5-5 to perform
communication with protective device. The standard configuration for the IEC60870-5-103
protocol is to use a twisted pair EIA RS-485 connection over distances up to 500m. It also supports
to use an Ethernet connection. The relay operates as a slave in the system, responding to
commands from a master station.

To use the rear port with IEC60870-5-103 communication, the relevant settings to the protective
device must be configured.

10.3 IEC60870-5-103 Interface over Serial Port

The IEC60870-5-103 interface over serial port (RS-485) is a master/slave interface with the
protective device as the slave device. It is properly developed by NR.

The protective device conforms to compatibility level 3.

The following IEC60870-5-103 facilities are supported by this interface:

 Initialization (reset)

 Time synchronization

 Event record extraction

 General interrogation

 General commands

 Disturbance records

10.3.1 Physical Connection and Link Layer


Two EIA RS-485 standardized ports are available for IEC60870-5-103 in this protective device.

10-4 PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

The transmission speed is optional: 4800 bit/s, 9600 bit/s, 19200 bit/s or 38400 bit/s.

The link layer strictly abides by the rules defined in the IEC60870-5-103.

10.3.2 Initialization
Whenever the protective device has been powered up, or if the communication parameters have
been changed, a reset command is required to initialize the communications. The protective
device will respond to either of the two reset commands (Reset CU or Reset FCB), the difference
is that the Reset CU will clear any unsent messages in the transmit buffer.

The protective device will respond to the reset command with an identification message ASDU 5,
the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command.

10.3.3 Time Synchronization


The protective device time and date can be set using the time synchronization feature of the
IEC60870-5-103 protocol. The protective device will correct for the transmission delay as specified
in IEC60870-5-103. If the time synchronization message is sent as a send/confirm message then
the protective device will respond with a confirmation. Whether the time-synchronization message
is sent as a send confirmation or a broadcast (send/no reply) message, a time synchronization
class 1 event will be generated/produced.

If the protective device clock is synchronized using the IRIG-B input then it will not be possible to
set the protective device time using the IEC60870-5-103 interface. An attempt to set the time via
the interface will cause the protective device to create an event with the current date and time
taken from the IRIG-B synchronized internal clock.

10.3.4 Spontaneous Events


Events are categorized using the following information:

 Type identification (TYP)

 Function type (FUN)

 Information number (INF)

Messages sent to substation automation system are grouped according to IEC60870-5-103


protocol. Operating elements are sent by ASDU2 (time-tagged message with relative time), and
status of binary signal and alarm element are sent by ASDU1 (time-tagged message). The cause
of transmission (COT) of these responses is 1.

All spontaneous events can be gained by printing, implementing submenu “IEC103 Info” in the
menu “Print”.

10.3.5 General Interrogation


The GI can be used to read the status of the relay, the function numbers, and information numbers
that will be returned during the GI cycle. The GI cycle strictly abides by the rules defined in the
IEC60870-5-103.

PCS-902 Line Distance Relay 10-5


Date: 2011-07-06
10 Communication

Refer the IEC60870-5-103 standard can get the enough details about general interrogation.

10.3.6 General Service


The generic functions can be used to read the setting and protection measurement of the
protective device, and modify the setting. Two supported type identifications are ASDU 21 and
ASDU 10. For more details about generic functions, see the IEC60870-5-103 standard.

All general classification service group numbers can be gained by printing, implementing submenu
“IEC103 Info” in the menu “Print”.

10.3.7 Disturbance Records


This protective device can store up to eight disturbance records in its memory. A pickup of the fault
detector or an operation of the relay can make the protective device store the disturbance records.

The disturbance records are stored in uncompressed format and can be extracted using the
standard mechanisms described in IEC60870-5-103.

All channel numbers (ACC) of disturbance data can be gained by printing, implementing submenu
“IEC103 Info” in the menu “Print”.

10.4 Messages Description for IEC61850 Protocol

10.4.1 Overview
The IEC 61850 standard is the result of years of work by electric utilities and vendors of electronic
equipment to produce standardized communications systems. IEC 61850 is a series of standards
describing client/server and peer-to-peer communications, substation design and configuration,
testing, environmental and project standards. The complete set includes:

 IEC 61850-1: Introduction and overview

 IEC 61850-2: Glossary

 IEC 61850-3: General requirements

 IEC 61850-4: System and project management

 IEC 61850-5: Communications and requirements for functions and device models

 IEC 61850-6: Configuration description language for communication in electrical substations


related to IEDs

 IEC 61850-7-1: Basic communication structure for substation and feeder equipment–
Principles and models

 IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract
communication service interface (ACSI)

 IEC 61850-7-3: Basic communication structure for substation and feeder equipment–
Common data classes

10-6 PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

 IEC 61850-7-4: Basic communication structure for substation and feeder equipment–
Compatible logical node classes and data classes

 IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3

 IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link

 IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3

 IEC 61850-10: Conformance testing

These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.

10.4.2 Communication profiles


The PCS-900 series relay supports IEC 61850 server services over TCP/IP communication
protocol stacks. The TCP/IP profile requires the PCS-900 series to have an IP address to establish
communications. These addresses are located in the menu “Settings→Device Setup→Comm
Settings”.

1. MMS protocol

IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. Actual IEC 61850-7-2 abstract services and objects are mapped to MMS protocol
services in IEC61850-8-1.

2. Client/server

This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation computers
running HMI programs or SOE logging software. Servers are usually substation equipment such
as protection relays, meters, RTUs, transformer, tap changers, or bay controllers.

3. Peer-to-peer

This is a non-connection-oriented, high speed type of communication usually between substation


equipment, such as protection relays, intelligent terminal. GOOSE is the method of peer-to-peer
communication.

4. Substation configuration language (SCL)

A substation configuration language is a number of files used to describe IED and communication
system realized according to IEC 61850-5 and IEC 61850-7. Each configured device has an IED
Capability Description (ICD) file and a Configured IED Description (CID) file. The substation single
line information is stored in a System Specification Description (SSD) file. The entire substation
configuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the

PCS-902 Line Distance Relay 10-7


Date: 2011-07-06
10 Communication

combination of the individual ICD files and the SSD file, moreover, add communication system
parameters (MMS, GOOSE, control block, SV control block) and the connection relationship of
GOOSE and SV to SCD file.

10.4.3 Server data organization


IEC61850 defines an object-oriented approach to data and services. An IEC61850 physical device
can contain one or more logical device(s) (for proxy). Each logical device can contain many logical
nodes. Each logical node can contain many data objects. Each data object is composed of data
attributes and data attribute components. Services are available at each level for performing
various functions, such as reading, writing, control commands, and reporting.

Each IED represents one IEC61850 physical device. The physical device contains one or more
logical device(s), and the logical device contains many logical nodes. The logical node LPHD
contains information about the IED physical device. The logical node LLN0 contains information
about the IED logical device.

10.4.3.1 Digital status values

The GGIO logical node is available in the PCS-900 series relays to provide access to digital status
points (including general I/O inputs and warnings) and associated timestamps and quality flags.
The data content must be configured before the data can be used. GGIO provides digital status
points for access by clients. It is intended that clients use GGIO in order to access digital status
values from the PCS-900 series relays. Clients can utilize the IEC61850 buffered reporting
features available from GGIO in order to build sequence of events (SOE) logs and HMI display
screens. Buffered reporting should generally be used for SOE logs since the buffering capability
reduces the chances of missing data state changes. All needed status data objects are transmitted
to HMI clients via buffered reporting, and the corresponding buffered reporting control block
(BRCB) is defined in LLN0.

10.4.3.2 Analog values

Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the else in MMXN, MSQI and so on. Each MMXU logical node provides data
from a IED current/voltage “source”. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides
data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects
are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding
unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the
following data for each source:

 MMXU.MX.Hz: frequency

 MMXU.MX.PPV.phsAB: phase AB voltage magnitude and angle

 MMXU.MX.PPV.phsBC: phase BC voltage magnitude and angle

 MMXU.MX.PPV.phsCA: Phase CA voltage magnitude and angle

 MMXU.MX.PhV.phsA: phase AG voltage magnitude and angle

10-8 PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

 MMXU.MX.PhV.phsB: phase BG voltage magnitude and angle

 MMXU.MX.PhV.phsC: phase CG voltage magnitude and angle

 MMXU.MX.A.phsA: phase A current magnitude and angle

 MMXU.MX.A.phsB: phase B current magnitude and angle

 MMXU.MX.A.phsC: phase C current magnitude and angle

10.4.3.3 Protection logical nodes

The following list describes the protection elements for PCS-902 series relays. The specified relay
will contain a subset of protection elements from this list.

 PDIS: Phase-to-phase distance, phase-to-ground distance and SOTF distance

 PTUC: Undercurrent

 PTOC: Phase overcurrent, zero-sequence overcurrent and overcurrent when VT circuit failure

 PTTR: Thermal overload

 PTUV: Undervoltage

 PTOV: Overvoltage and auxiliary overvoltage

 PTOF: Overfrequency

 PTUF: Underfrequency

 PSCH: Protection scheme

 RBRF:Breaker failure

 RPSB: Power swing detection/blocking

 RREC: Automatic reclosing

 RSYN: Synchronism-check

 RFLO: Fault location

The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags “PTRC.ST.Str.general”. The operate flag for PTOC1 is “PTOC1.ST.Op.general”. For
PCS-902 series relays protection elements, these flags take their values from related module for
the corresponding element. Similar to digital status values, the protection trip information is
reported via BRCB, and BRCB also locates in LLN0.

10.4.3.4 LLN0 and other logical nodes

Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defines for the whole device; the

PCS-902 Line Distance Relay 10-9


Date: 2011-07-06
10 Communication

common settings include all the setting items of communication settings. System settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked and those commands make effective until the item Loc is changed to false. In
PCS-900 series relays, besides the logical nodes we describe above, there are some other logical
nodes below in the IEDs:

 MMXU: This LN shall be used to acquire values from CTs and VTs and calculate measurands
such as r.m.s. values for current and voltage or power flows out of the acquired voltage and
current samples. These values are normally used for operational purposes such as power
flow supervision and management, screen displays, state estimation, etc. The requested
accuracy for these functions has to be provided.

 LPHD: Physical device information, the logical node to model common issues for physical
device.

 PTRC: Protection trip conditioning, it shall be used to connect the “operate” outputs of one or
more protection functions to a common “trip” to be transmitted to XCBR. In addition or
alternatively, any combination of “operate” outputs of protection functions may be combined to
a new “operate” of PTRC.

 RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers
to the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System”
(IEC 60255-24). All enabled channels are included in the recording, independently of the
trigger mode.

10.4.4 Server features and configuration


10.4.4.1 Buffered/unbuffered reporting

IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of protection trip information (in the Protection logical nodes), binary status
values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The
reporting control blocks can be configured in CID files, and then be sent to the IED via an
IEC61850 client. The following items can be configured.

 TrgOps: Trigger options.

The following bits are supported by the PCS-900 series relays:

- Bit 1: Data-change

- Bit 4: Integrity

- Bit 5: General interrogation

 OptFlds: Option Fields.

The following bits are supported by the PCS-900 series relays:

- Bit 1: Sequence-number

10-10 PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

- Bit 2: Report-time-stamp

- Bit 3: Reason-for-inclusion

- Bit 4: Data-set-name

- Bit 5: Data-reference

- Bit 7: EntryID (for buffered reports only)

- Bit 8: Conf-revision

- Bit 9: Segmentation

 IntgPd: Integrity period.

10.4.4.2 File transfer

MMS file services are supported to allow transfer of oscillography, event record or other files from
a PCS-900 series relay.

10.4.4.3 Timestamps

The Universal Time Coordinated(UTC for short) timestamp associated with all IEC61850 data
items represents the lastest change time of either the value or quality flags of the data item.

10.4.4.4 Logical node name prefixes

IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:

 A five or six-character name prefix.

 A four-character standard name (for example, MMXU, GGIO, PIOC, etc.).

 A one or two-character instantiation index.

Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.

10.4.4.5 GOOSE services

IEC61850 specifies the type of broadcast data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also function as servers. Each GOOSE
publisher contains a “GOOSE control block” to configure and control the transmission.

The GOOSE transmission (including subscribing and publishing) is controlled by GOOSE link
settings in device.

The PCS-900 series relays support IEC61850 Generic Object Oriented Substation Event (GOOSE)

PCS-902 Line Distance Relay 10-11


Date: 2011-07-06
10 Communication

communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this
dataset that is transferred using GOOSE message services. The GOOSE related dataset is
configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between PCS-900 series relays.

IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be
correct to achieve the successful transfer of data. It is critical that the configured datasets at the
transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.

The general steps required for transmission configuration are:

1. Configure the data.

2. Configure the transmission dataset.

3. Configure the GOOSE service settings.

The general steps required for reception configuration are:

1. Configure the data.

2. Configure the GOOSE service settings

3. Configure the reception data

10.4.5 ACSI Conformance


10.4.5.1 ACSI basic conformance statement

Services Client Server PCS-900 Series


Client-Server Roles
B11 Server side (of Two-party Application-Association) - C1 Y
B12 Client side (of Two-party Application-Association) C1 - N
SCSMS Supported
B21 SCSM: IEC 61850-8-1 used N N Y
B22 SCSM: IEC 61850-9-1 used N N N
B23 SCSM: IEC 61850-9-2 used N N N
B24 SCSM: other N N N
Generic Substation Event Model (GSE)
B31 Publisher side - O Y
B32 Subscriber side O - Y
Transmission Of Sampled Value Model (SVC)
B41 Publisher side - O N
B42 Subscriber side O - N

Where:

C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared

O: Optional

10-12 PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

M: Mandatory

Y: Supported by PCS-900 series relays

N: Currently not supported by PCS-900 series relays

10.4.5.2 ACSI models conformance statement

Services Client Server PCS-900 Series


M1 Logical device C2 C2 Y
M2 Logical node C3 C3 Y
M3 Data C4 C4 Y
M4 Data set C5 C5 Y
M5 Substitution O O Y
M6 Setting group control O O Y
Reporting
M7 Buffered report control O O Y
M7-1 sequence-number Y Y Y
M7-2 report-time-stamp Y Y Y
M7-3 reason-for-inclusion Y Y Y
M7-4 data-set-name Y Y Y
M7-5 data-reference Y Y Y
M7-6 buffer-overflow Y Y N
M7-7 entryID Y Y Y
M7-8 BufTm N N N
M7-9 IntgPd Y Y Y
M7-10 GI Y Y Y
M8 Unbuffered report control M M Y
M8-1 sequence-number Y Y Y
M8-2 report-time-stamp Y Y Y
M8-3 reason-for-inclusion Y Y Y
M8-4 data-set-name Y Y Y
M8-5 data-reference Y Y Y
M8-6 BufTm N N N
M8-7 IntgPd N Y Y
Logging
M9 Log control O O N
M9-1 IntgPd N N N
M10 Log O O N
GSE
M12 GOOSE O O Y
M13 GSSE O O N
M14 Multicast SVC O O N
M15 Unicast SVC O O N

PCS-902 Line Distance Relay 10-13


Date: 2011-07-06
10 Communication

M16 Time M M Y
M17 File transfer O O Y

Where:

C2: Shall be "M" if support for LOGICAL-NODE model has been declared

C3: Shall be "M" if support for DATA model has been declared

C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
been declared

C5: Shall be "M" if support for Report, GSE, or SMV models has been declared

M: Mandatory

Y: Supported by PCS-900 series relays

N: Currently not supported by PCS-900 series relays

10.4.5.3 ACSI Services conformance statement

Services Server/Publisher PCS-902


Server
S1 ServerDirectory M Y
Application association
S2 Associate M Y
S3 Abort M Y
S4 Release M Y
Logical device
S5 LogicalDeviceDirectory M Y
Logical node
S6 LogicalNodeDirectory M Y
S7 GetAllDataValues M Y
Data
S8 GetDataValues M Y
S9 SetDataValues M Y
S10 GetDataDirectory M Y
S11 GetDataDefinition M Y
Data set
S12 GetDataSetValues M Y
S13 SetDataSetValues O Y
S14 CreateDataSet O N
S15 DeleteDataSet O N
S16 GetDataSetDirectory M Y
Substitution
S17 SetDataValues M Y
Setting group control

10-14 PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

S18 SelectActiveSG M/O Y


S19 SelectEditSG M/O Y
S20 SetSGValuess M/O Y
S21 ConfirmEditSGValues M/O Y
S22 GetSGValues M/O Y
S23 GetSGCBValues M/O Y
Reporting
Buffered report control block
S24 Report M Y
S24-1 data-change M Y
S24-2 qchg-change M N
S24-3 data-update M N
S25 GetBRCBValues M Y
S26 SetBRCBValues M Y
Unbuffered report control block
S27 Report M Y
S27-1 data-change M Y
S27-2 qchg-change M N
S27-3 data-update M N
S28 GetURCBValues M Y
S29 SetURCBValues M Y
Logging
Log control block
S30 GetLCBValues O N
S31 SetLCBValues O N
Log
S32 QueryLogByTime O N
S33 QueryLogAfter O N
S34 GetLogStatusValues O N
Generic substation event model (GSE)
GOOSE control block
S35 SendGOOSEMessage M Y
S36 GetGoReference O Y
S37 GetGOOSEElementNumber O N
S38 GetGoCBValues M Y
S39 SetGoCBValuess M N
Control
S51 Select O N
S52 SelectWithValue M Y
S53 Cancel M Y
S54 Operate M Y
S55 Command-Termination O Y

PCS-902 Line Distance Relay 10-15


Date: 2011-07-06
10 Communication

S56 TimeActivated-Operate O N
File transfer
S57 GetFile M/O Y
S58 SetFile O N
S59 DeleteFile O N
S60 GetFileAttributeValues M/O Y
Time
SNTP M Y

10.4.6 Logical Nodes


10.4.6.1 Logical Nodes Table

The PCS-902 series relays support IEC61850 logical nodes as indicated in the following table.
Note that the actual instantiation of each logical node is determined by the product order code.

Nodes PCS-902 Series


L: System Logical Nodes
LPHD: Physical device information YES
LLN0: Logical node zero YES
P: Logical Nodes For Protection Functions
PDIF: Differential -
PDIR: Direction comparison -
PDIS: Distance YES
PDOP: Directional overpower -
PDUP: Directional underpower -
PFRC: Rate of change of frequency -
PHAR: Harmonic restraint -
PHIZ: Ground detector -
PIOC: Instantaneous overcurrent -
PMRI: Motor restart inhibition -
PMSS: Motor starting time supervision -
POPF: Over power factor -
PPAM: Phase angle measuring -
PSCH: Protection scheme YES
PSDE: Sensitive directional earth fault -
PTEF: Transient earth fault -
PTOC: Time overcurrent YES
PTOF: Overfrequency YES
PTOV: Overvoltage YES
PTRC: Protection trip conditioning YES
PTTR: Thermal overload YES
PTUC: Undercurrent -
PTUV: Undervoltage YES

10-16 PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

PUPF: Underpower factor -


PTUF: Underfrequency YES
PVOC: Voltage controlled time overcurrent -
PVPH: Volts per Hz -
PZSU: Zero speed or underspeed -
R: Logical Nodes For Protection Related Functions
RDRE: Disturbance recorder function YES
RADR: Disturbance recorder channel analogue -
RBDR: Disturbance recorder channel binary -
RDRS: Disturbance record handling -
RBRF: Breaker failure YES
RDIR: Directional element -
RFLO: Fault locator YES
RPSB: Power swing detection/blocking YES
RREC: Autoreclosing YES
RSYN: Synchronism-check or synchronizing YES
C: Logical Nodes For Control
CALH: Alarm handling -
CCGR: Cooling group control -
CILO: Interlocking -
CPOW: Point-on-wave switching -
CSWI: Switch controller -
G: Logical Nodes For Generic References
GAPC: Generic automatic process control YES
GGIO: Generic process I/O YES
GSAL: Generic security application -
I: Logical Nodes For Interfacing And Archiving
IARC: Archiving -
IHMI: Human machine interface -
ITCI: Telecontrol interface -
ITMI: Telemonitoring interface -
A: Logical Nodes For Automatic Control
ANCR: Neutral current regulator -
ARCO: Reactive power control -
ATCC: Automatic tap changer controller -
AVCO: Voltage control -
M: Logical Nodes For Metering And Measurement
MDIF: Differential measurements -
MHAI: Harmonics or interharmonics -
MHAN: Non phase related harmonics or interharmonic -
MMTR: Metering -
MMXN: Non phase related measurement -

PCS-902 Line Distance Relay 10-17


Date: 2011-07-06
10 Communication

MMXU: Measurement YES


MSQI: Sequence and imbalance -
MSTA: Metering statistics -
S: Logical Nodes For Sensors And Monitoring
SARC: Monitoring and diagnostics for arcs -
SIMG: Insulation medium supervision (gas) -
SIML: Insulation medium supervision (liquid) -
SPDC: Monitoring and diagnostics for partial discharges -
X: Logical Nodes For Switchgear
TCTR: Current transformer YES
TVTR: Voltage transformer YES
Y: Logical Nodes For Power Transformers
YEFN: Earth fault neutralizer (Peterson coil) -
YLTC: Tap changer -
YPSH: Power shunt -
YPTR: Power transformer -
Z: Logical Nodes For Further Power System Equipment
ZAXN: Auxiliary network -
ZBAT: Battery -
ZBSH: Bushing -
ZCAB: Power cable -
ZCAP: Capacitor bank -
ZCON: Converter -
ZGEN: Generator -
ZGIL: Gas insulated line -
ZLIN: Power overhead line -
ZMOT: Motor -
ZREA: Reactor -
ZRRC: Rotating reactive component -
ZSAR: Surge arrestor -
ZTCF: Thyristor controlled frequency converter -
ZTRC: Thyristor controlled reactive component -

10.5 DNP3.0 Interface

10.5.1 Overview
The descriptions given here are intended to accompany this relay. The DNP3.0 protocol is not
described here; please refer to the DNP3.0 protocol standard for the details about the DNP3.0
implementation. This manual only specifies which objects, variations and qualifiers are supported
in this relay, and also specifies what data is available from this relay via DNP3.0.

The relay operates as a DNP3.0 slave and supports subset level 2 of the protocol, plus some of

10-18 PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

the features from level 3. The DNP3.0 communication uses the Ethernet ports at the rear side of
this relay. The Ethernet ports are optional: electrical or optical.

10.5.2 Link Layer Functions


Please see the DNP3.0 protocol standard for the details about the linker layer functions.

10.5.3 Transport Functions


Please see the DNP3.0 protocol standard for the details about the transport functions.

10.5.4 Application Layer Functions


10.5.4.1 Time Synchronization

1. Time delay measurement

Master/Slave Function Code Object Variation Qualifier


Master 0x17 - - -
Slave 0x81 0x34 0x02 0x07

2. Read time of device

Master/Slave Function Code Object Variation Qualifier


Master 0x01 0x34 0x00, 0x01 0x07-
Slave 0x81 0x32 0x01 0x07

3. Write time of device

Master/Slave Function Code Object Variation Qualifier


Master 0x02 0x32 0x01 0x00, 0x01, 0x07, 0x08
Slave 0x81 - - -

10.5.4.2 Supported Writing Functions

1. Write time of device

See Section 10.5.4.1 for the details.

2. Reset the CU (Reset IIN bit7)

Master/Slave Function Code Object Variation Qualifier


Master 0x02 0x50 0x01 0x00, 0x01
Slave 0x81 - - -

10.5.4.3 Supported Reading Functions

1. Supported qualifiers

Master Qualifier 0x00 0x01 0x06 0x07 0x08


Slave Qualifier 0x00 0x01 0x01 0x07 0x08

2. Supported objects and variations

 Object 1, Binary inputs

PCS-902 Line Distance Relay 10-19


Date: 2011-07-06
10 Communication

Master Variation 0x00 0x01 0x02


Slave Variation 0x02 0x01 0x02

The protection operation signals, alarm signals and binary input state change signals are
transported respectively according to the variation sequence in above table.

 Object 2, SOE

Master Variation 0x00 0x01 0x02 0x03


Slave Variation 0x02 0x01 0x02 0x03

If the master qualifier is “0x07”, the slave responsive qualifier is “0x27”; and if the master
qualifier is “0x01”, “0x06” or “0x08”, the slave responsive qualifier is “0x28”.

 Object 30, Analog inputs

Master Variation 0x00 0x01 0x02 0x03 0x04


Slave Variation 0x01 0x01 0x02 0x03 0x04

The measurement values are transported firstly, and then the measurement values are
transported.

 Object 40, Analog outputs

Master Variation 0x00 0x01 0x02


Slave Variation 0x01 0x01 0x02

The protection settings are transported in this object.

 Object 50, Time Synchronization

See Section 10.5.4.1 for the details.

3. Class 0 data request

The master adopts the “Object 60” for the Class 0 data request and the variation is “0x01”.

The slave responds with the above mentioned “Object 1”, “Object 30” and “Object 40” (see
“Supported objects and variations” in Section 10.5.4.3).

4. Class 1 data request

The master adopts the “Object 60” for the Class 1 data request and the variation is “0x02”.

The slave responds with the above mentioned “Object 2” (see “Supported objects and
variations” in Section 10.5.4.3).

5. Multiple object request

The master adopts the “Object 60” for the multiple object request and the variation is “0x01”,
“0x02”, “0x03” and “0x04”.

The slave responds with the above mentioned “Object 1”, “Object 2”, “Object 30” and “Object
40” (see “Supported objects and variations” in Section 10.5.4.3).

10-20 PCS-902 Line Distance Relay


Date: 2011-07-06
10 Communication

10.5.4.4 Remote Control Functions

The function code 0x03 and 0x04 are supported in this relay. The function code 0x03 is for the
remote control with selection; and the function code 0x04 is for the remote control with execution.

The selection operation must be executed before the execution operation, and the single point
control object can be supported to this relay.

Master Qualifier 0x17 0x27 0x18 0x28


Slave Qualifier 0x17 0x27 0x18 0x28

The “Object 12” is for the remote control functions.

Master Variation 0x01 0x01: closing


Control Code
Slave Variation 0x01 0x10: tripping

PCS-902 Line Distance Relay 10-21


Date: 2011-07-06
10 Communication

10-22 PCS-902 Line Distance Relay


Date: 2011-07-06
11 Installation

11 Installation

Table of Contents
11 Installation .................................................................................... 11-a
11.1 Overview ....................................................................................................... 11-1
11.2 Safety Information ........................................................................................ 11-1
11.3 Checking Shipment ...................................................................................... 11-2
11.4 Material and Tools Required........................................................................ 11-2
11.5 Device Location and Ambient Conditions.................................................. 11-2
11.6 Mechanical Installation ................................................................................ 11-3
11.7 Electrical Installation and Wiring ................................................................ 11-4
11.7.1 Grounding Guidelines .................................................................................................... 11-4

11.7.2 Cubicle Grounding ......................................................................................................... 11-4

11.7.3 Ground Connection on the Device ................................................................................. 11-5

11.7.4 Grounding Strips and their Installation............................................................................ 11-6

11.7.5 Guidelines for Wiring ...................................................................................................... 11-6

11.7.6 Wiring for Electrical Cables ............................................................................................ 11-7

List of Figures
Figure 11.6-1 Dimensions of PCS-902 ................................................................................... 11-3

Figure 11.6-2 panel cut-out of PCS-902 ................................................................................. 11-3

Figure 11.6-3 Demonstration of plugging a board into its corresponding slot .................. 11-4

Figure 11.7-1 Cubicle grounding system ............................................................................... 11-5

Figure 11.7-2 Ground terminal of this relay ........................................................................... 11-6

Figure 11.7-3 Ground strip and termination .......................................................................... 11-6

Figure 11.7-4 Glancing demo about the wiring for electrical cables ................................... 11-7

PCS-902 Line Distance Relay 11-a


Date: 2011-02-28
11 Installation

11-b PCS-902 Line Distance Relay


Date: 2011-02-28
11 Installation

11.1 Overview
The device must be shipped, stored and installed with the greatest care.

Choose the place of installation such that the communication interface and the controls on the
front of the device are easily accessible.

Air must circulate freely around the equipment. Observe all the requirements regarding place of
installation and ambient conditions given in this instruction manual.

Take care that the external wiring is properly brought into the equipment and terminated correctly
and pay special attention to grounding. Strictly observe the corresponding guidelines contained in
this section.

11.2 Safety Information


Modules and units may only be replaced by correspondingly trained personnel. Always observe
the basic precautions to avoid damage due to electrostatic discharge when handling the
equipment.

In certain cases, the settings have to be configured according to the demands of the engineering
configuration after replacement. It is therefore assumed that the personnel who replace modules
and units are familiar with the use of the operator program on the service PC.

DANGER! Only insert or withdraw the PWR module while the power supply is switched

off. To this end, disconnect the power supply cable that connects with the PWR module.

WARNING! Only insert or withdraw other modules while the power supply is switched off.

WARNING! The modules may only be inserted in the slots designated in Section 6.2.

Components can be damaged or destroyed by inserting boards in the wrong slots.

DANGER! Improper handling of the equipment can cause damage or an incorrect

response of the equipment itself or the primary plant.

WARNING! Industry packs and ribbon cables may only be replaced or the positions of

jumpers be changed on a workbench appropriately designed for working on electronic


equipment. The modules, bus backplanes are sensitive to electrostatic discharge when
not in the unit's housing.

The basic precautions to guard against electrostatic discharge are as follows:

 Should boards have to be removed from this relay installed in a grounded cubicle in an HV
switchgear installation, please discharge yourself by touching station ground (the cubicle)
beforehand.

PCS-902 Line Distance Relay 11-1


Date: 2011-02-28
11 Installation

 Only hold electronic boards at the edges, taking care not to touch the components.

 Only works on boards that have been removed from the cubicle on a workbench designed for
electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.

 Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.

11.3 Checking Shipment


Check that the consignment is complete immediately upon receipt. Notify the nearest NR
Company or agent, should departures from the delivery note, the shipping papers or the order be
found.

Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or
agent.

If the equipment is not going to be installed immediately, store all the parts in their original packing
in a clean dry place at a moderate temperature. The humidity at a maximum temperature and the
permissible storage temperature range in dry air are listed in Chapter “Technical Data”.

11.4 Material and Tools Required


The necessary mounting kits will be provided, including screws, pincers and assembly
instructions.

A suitable drill and spanners are required to secure the cubicles to the floor using the plugs
provided (if this relay is mounted in cubicles).

11.5 Device Location and Ambient Conditions


The place of installation should permit easy access especially to front of the device, i.e. to the
human machine interface of the equipment.

There should also be free access at the rear of the equipment for additions and replacement of
electronic boards.

Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:

1. The location should not be exposed to excessive air pollution (dust, aggressive substances).

2. Severe vibration, extreme changes of temperature, high levels of humidity, surge voltages of
high amplitude and short rise time and strong induced magnetic fields should be avoided as
far as possible.

3. Air must not be allowed to circulate freely around the equipment.

The equipment can in principle be mounted in any attitude, but it is normally mounted vertically

11-2 PCS-902 Line Distance Relay


Date: 2011-02-28
11 Installation

(visibility of markings).

WARNING! Excessively high temperature can appreciably reduce the operating life of

this relay.

11.6 Mechanical Installation


The device adopts IEC standard chassis and is rack with modular structure. It uses an integral
faceplate and plug terminal block on backboard for external connections. PCS-902 series is IEC
4U high and 19” wide. Figure 11.6-1 shows its dimensions and Figure 11.6-2 shows the panel
cut-out.

482.6

291 465.0
101.6
177.0

Figure 11.6-1 Dimensions of PCS-902

465.0
101.6

179.0

4-Ф6.8

450.0

Figure 11.6-2 panel cut-out of PCS-902

NOTE! It is necessary to leave enough space top and bottom of the cut-out in the cubicle

for heat emission of this relay.

PCS-902 Line Distance Relay 11-3


Date: 2011-02-28
11 Installation

The safety instructions must be abided by when installing the boards, please see Section 11.2 for
the details.

Following figure shows the installation way of a module being plugged into a corresponding slot.

Figure 11.6-3 Demonstration of plugging a board into its corresponding slot

In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.

11.7 Electrical Installation and Wiring


11.7.1 Grounding Guidelines
Switching operations in HV installations generate transient over voltages on control signal cables.
There is also a background of electromagnetic RF fields in electrical installations that can induce
spurious currents in the devices themselves or the leads connected to them.

All these influences can influence the operation of electronic apparatus.

On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.

In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.

NOTE! All these precautions can only be effective if the station ground is of good quality.

11.7.2 Cubicle Grounding


The cubicle must be designed and fitted out such that the impedance for RF interference of the
ground path from the electronic device to the cubicle ground terminal is as low as possible.

Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.

NOTE! If the above conditions are not fulfilled, there is a possibility of the cubicle or parts

11-4 PCS-902 Line Distance Relay


Date: 2011-02-28
11 Installation

of it forming a resonant circuit at certain frequencies that would amplify the transmission
of interference by the devices installed and also reduce their immunity to induced
interference.

Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 11.7-1).

The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.

NOTE! For metallic connections please observe the voltage difference of both materials

according to the electrochemical code.

The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip
(braided copper).

Door or hinged
equipment frame

Cubicle ground
rail close to floor

Braided
copper strip
Station
ground

Conducting
connection

Figure 11.7-1 Cubicle grounding system

11.7.3 Ground Connection on the Device


There is a ground terminal on the rear panel, and the ground braided copper strip can be
connected with it. Take care that the grounding strip is always as short as possible. The main thing
is that the device is only grounded at one point. Grounding loops from unit to unit are not allowed.

There are some ground terminals on some connectors of this relay, and the sign is “GND”. All the
ground terminals are connected in the cabinet of this relay. So, the ground terminal on the rear
panel (see Figure 11.7-2) is the only ground terminal of this device.

PCS-902 Line Distance Relay 11-5


Date: 2011-02-28
11 Installation

Figure 11.7-2 Ground terminal of this relay

11.7.4 Grounding Strips and their Installation


High frequency currents are produced by interference in the ground connections and because of
skin effect at these frequencies, only the surface region of the grounding strips is of consequence.

The grounding strips must therefore be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.

Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting
them firmly to the items to be connected.

The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.

The following figure shows the ground strip and termination.

Press/pinch fit
cable terminal

Braided
copper strip Terminal bolt

Contact surface

Figure 11.7-3 Ground strip and termination

11.7.5 Guidelines for Wiring


There are several types of cables that are used in the connection of this relay: braided copper
cable, serial communication cable etc. Recommendation of each cable:

 Grounding: braided copper cable, 2.5mm2 ~ 6.0mm2

 Power supply, binary inputs & outputs: brained copper cable, 1.0mm2 ~ 2.5mm2

 AC voltage inputs: brained copper cable, 1.0mm2 ~ 2.5mm2

 AC current inputs: brained copper cable, 1.5mm2 ~ 4.0mm2

 Serial communication: 4-core shielded braided cable

 Ethernet communication: 4-pair screened twisted category 5E cable

11-6 PCS-902 Line Distance Relay


Date: 2011-02-28
11 Installation

11.7.6 Wiring for Electrical Cables


A female connector is used for connecting the wires with it, and then a female connector plugs into
a corresponding male connector that is in the front of one board. See Chapter “Hardware” for
further details about the pin defines of these connectors.

The following figure shows the glancing demo about the wiring for the electrical cables.

01 02

03 04

Tighten 05 06

07 08

09 10

11 12
01

13 14

15 16

17 18

19 20

21 22

23 24

Figure 11.7-4 Glancing demo about the wiring for electrical cables

DANGER! Never allow the current transformer (CT) secondary circuit connected to this
equipment to be opened while the primary system is live. Opening the CT circuit will produce a
dangerously high voltage.

PCS-902 Line Distance Relay 11-7


Date: 2011-02-28
11 Installation

11-8 PCS-902 Line Distance Relay


Date: 2011-02-28
12 Commissioning

12 Commissioning

Table of Contents
12 Commissioning ............................................................................ 12-a
12.1 Overview ...................................................................................................... 12-1
12.2 Safety Instructions ...................................................................................... 12-1
12.3 Commission Tools ...................................................................................... 12-2
12.4 Setting Familiarization ................................................................................ 12-2
12.5 Product Checks ........................................................................................... 12-3
12.5.1 With the Relay De-energized ......................................................................................... 12-3

12.5.2 With the Relay Energized............................................................................................... 12-5

12.5.3 Print Fault Report ........................................................................................................... 12-8

12.5.4 On-load Checks ............................................................................................................. 12-8

12.6 Final Checks ................................................................................................ 12-9

PCS-902 Line Distance Relay 12-a


Date: 2011-02-28
12 Commissioning

12-b PCS-902 Line Distance Relay


Date: 2011-02-28
12 Commissioning

12.1 Overview
This relay is fully numerical in their design, implementing all protection and non-protection
functions in software. The relay employs a high degree of self-checking and in the unlikely event of
a failure, will give an alarm. As a result of this, the commissioning test does not need to be as
extensive as with non-numeric electronic or electro-mechanical relays.

To commission numerical relays, it is only necessary to verify that the hardware is functioning
correctly and the application-specific software settings have been applied to the relay.

Blank commissioning test and setting records are provided at the end of this manual for
completion as required.

Before carrying out any work on the equipment, the user should be familiar with the contents of the
safety and technical data sections and the ratings on the equipment’s rating label.

12.2 Safety Instructions

WARNING! Hazardous voltages are present in this electrical equipment during operation.

Non-observance of the safety rules can result in severe personal injury or property
damage.

WARNING! Only the qualified personnel shall work on and around this equipment after

becoming thoroughly familiar with all warnings and safety notices of this manual as well
as with the applicable safety regulations.

Particular attention must be drawn to the following:

 The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.

 Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.

 Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!)

 The limit values stated in the Chapter “Technical Data” must not be exceeded at all, not even
during testing and commissioning.

 When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip circuits and
maybe also close commands to the circuit breakers and other primary switches are
disconnected from the device unless expressly stated.

DANGER! Current transformer secondary circuits must have been short-circuited before

the current leads to the device are disconnected.

PCS-902 Line Distance Relay 12-1


Date: 2011-02-28
12 Commissioning

WARNING! Primary test may only be carried out by qualified personnel, who are familiar

with the commissioning of protection system, the operation of the plant and safety rules
and regulations (switching, earthing, etc.).

12.3 Commission Tools


Minimum equipment required:

 Multifunctional dynamic current and voltage injection test set with interval timer.

 Multimeter with suitable AC current range and AC/DC voltage ranges of 0~440V and 0~250V
respectively.

 Continuity tester (if not included in the multimeter).

 Phase angle meter.

 Phase rotation meter.

NOTE! Modern test set may contain many of the above features in one unit.

Optional equipment:

 An electronic or brushless insulation tester with a DC output not exceeding 500V (for
insulation resistance test when required).

 A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).

 EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).

 PCS-900 serials dedicated protection tester HELP-2000.

12.4 Setting Familiarization


When commissioning this device for the first time, sufficient time should be allowed to become
familiar with the method by which the settings are applied. A detailed description of the menu
structure of this relay is contained in Chapter “Operation Theory” and Chapter “Settings”.

With the front cover in place all keys are accessible. All menu cells can be read. The LED
indicators and alarms can be reset. Protection or configuration settings can be changed, or fault
and event records cleared. However, menu cells will require the appropriate password to be
entered before changes can be made.

Alternatively, if a portable PC is available together with suitable setting software (such as


PCS-9700 SAS software), the menu can be viewed one page at a time to display a full column of
data and text. This PC software also allows settings to be entered more easily, saved to a file on
disk for future reference or printed to produce a setting record. Refer to the PC software user
manual for details. If the software is being used for the first time, allow sufficient time to become
familiar with its operation.

12-2 PCS-902 Line Distance Relay


Date: 2011-02-28
12 Commissioning

12.5 Product Checks

These product checks cover all aspects of the relay which should be checked to ensure that it has
not been physically damaged prior to commissioning, is functioning correctly and all input quantity
measurements are within the stated tolerances.

If the application-specific settings have been applied to the relay prior to commissioning, it is
advisable to make a copy of the settings so as to allow them restoration later. This could be done
by extracting the settings from the relay itself via printer or manually creating a setting record.

12.5.1 With the Relay De-energized


This relay is fully numerical and the hardware is continuously monitored. Commissioning tests can
be kept to a minimum and need only include hardware tests and conjunctive tests. The function
tests are carried out according to user’s correlative regulations.

The following tests are necessary to ensure the normal operation of the equipment before it is first
put into service.

 Hardware tests

These tests are performed for the following hardware to ensure that there is no hardware
defect. Defects of hardware circuits other than the following can be detected by
self-monitoring when the DC power is supplied.

 User interfaces test

 Binary input circuits and output circuits test

 AC input circuits test

 Function tests

These tests are performed for the following functions that are fully software-based. Tests of
the protection schemes and fault locator require a dynamic test set.

 Measuring elements test

 Timers test

 Measurement and recording test

 Conjunctive tests

The tests are performed after the relay is connected with the primary equipment and other
external equipment.

 On load test.

 Phase sequence check and polarity check.

PCS-902 Line Distance Relay 12-3


Date: 2011-02-28
12 Commissioning

12.5.1.1 Visual Inspection

After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected, contact the vendor. The following items listed is
necessary.

 Protection panel

Carefully examine the protection panel, protection equipment inside and other parts inside to
see that no physical damage has occurred since installation.

The rated information of other auxiliary protections should be checked to ensure it is correct
for the particular installation.

 Panel wiring

Check the conducting wire which is used in the panel to assure that their cross section
meeting the requirement.

Carefully examine the wiring to see that they are no connection failure exists.

 Label

Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.

 Device plug-in modules

Check each plug-in module of the equipments on the panel to make sure that they are well
installed into the equipment without any screw loosened.

 Earthing cable

Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.

 Switch, keypad, isolator binary inputs and push button

Check whether all the switches, equipment keypad, isolator binary inputs and push buttons
work normally and smoothly.

12.5.1.2 Insulation Test (if required)

Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.

Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:

 Voltage transformer circuits

 Current transformer circuits

 DC power supply

12-4 PCS-902 Line Distance Relay


Date: 2011-02-28
12 Commissioning

 Optic-isolated control inputs

 Output contacts

 Communication ports

The insulation resistance should be greater than 100MΩ at 500V.

Test method:

To unplug all the terminals sockets of this relay, and do the Insulation resistance test for each
circuit above with an electronic or brushless insulation tester.

On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection.

12.5.1.3 External Wiring

Check that the external wiring is correct to the relevant relay diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.

Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.

12.5.1.4 Auxiliary Power Supply

The relay only can be operated under the auxiliary power supply depending on the relay’s nominal
power supply rating.

The incoming voltage must be within the operating range specified in Chapter “Technical Data”,
before energizing the relay, measure the auxiliary supply to ensure it within the operating range.

Other requirements to the auxiliary power supply are specified in Chapter “Technical Data”. See
this section for further details about the parameters of the power supply.

WARNING! Energize this relay only if the power supply is within the specified operating
ranges in Chapter “Technical Data”.

12.5.2 With the Relay Energized


The following groups of checks verify that the relay hardware and software is functioning correctly
and should be carried out with the auxiliary supply applied to the relay.

The current and voltage transformer connections must remain isolated from the relay for these
checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.

12.5.2.1 Front Panel LCD Display

Connect the relay to DC power supply correctly and turn the relay on. Check program version and
forming time displayed in command menu to ensure that are corresponding to what ordered.

PCS-902 Line Distance Relay 12-5


Date: 2011-02-28
12 Commissioning

12.5.2.2 Date and Time

If the time and date is not being maintained by substation automation system, the date and time
should be set manually.

Set the date and time to the correct local time and date using menu item “Clock”.

In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date will
be maintained. Therefore when the auxiliary supply is restored the time and date will be correct
and not need to set again.

To test this, remove the auxiliary supply from the relay for approximately 30s. After being
re-energized, the time and date should be correct.

12.5.2.3 Light Emitting Diodes (LEDs)

On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
the relay is healthy.

The relay has latched signal relays which remember the state of the trip, auto-reclose when the
relay was last energized from an auxiliary supply. Therefore these indicators may also illuminate
when the auxiliary supply is applied. If any of these LEDs are on then they should be reset before
proceeding with further testing. If the LED successfully reset, the LED goes out. There is no testing
required for that that LED because it is known to be operational.

It is likely that alarms related to voltage transformer supervision will not reset at this stage.

12.5.2.4 Testing HEALTHY and ALARM LEDs

Apply the rated DC power supply and check that the “HEALTHY” LED is lighting in green. We
need to emphasize that the “HEALTHY” LED is always lighting in operation course except that the
equipment find serious errors in it.

Produce one of the abnormal conditions listed in Chapter “Supervision”, the “ALARM” LED will
light in yellow. When abnormal condition reset, the “ALARM” LED extinguishes.

12.5.2.5 Testing AC Current Inputs

This test verified that the accuracy of current measurement is within the acceptable tolerances.

Apply rated current to each current transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the relays menu.

The measurement accuracy of the protection is 2.5% or 0.02In. However, an additional allowance
must be made for the accuracy of the test equipment being used.

NOTE! The closing circuit should remain isolated during these checks to prevent

accidental operation of the associated circuit breaker.

Group No. Item Input Value Input Angle Display Value Display Angle

Three-phase current 1 Ia

12-6 PCS-902 Line Distance Relay


Date: 2011-02-28
12 Commissioning

Group No. Item Input Value Input Angle Display Value Display Angle

Ib

Ic

Ia

Three-phase current 2 Ib

Ic

Ia

Three-phase current 3 Ib

Ic

Ia

Three-phase current …… Ib

Ic

12.5.2.6 Testing AC Voltage Inputs

This test verified that the accuracy of voltage measurement is within the acceptable tolerances.

Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the relays menu.

The measurement accuracy of the relay is 2.5% or 0.1V. However an additional allowance must be
made for the accuracy of the test equipment being used.

NOTE! The closing circuit should remain isolated during these checks to prevent

accidental operation of the associated circuit breaker.

Group No. Item Input Value Input Angle Display Value Display Angle
Ua
Three-phase voltage 1 Ub
Uc
Ua
Three-phase voltage 2 Ub
Uc
Ua
Three-phase voltage 3 Ub
Uc
Ua
Three-phase voltage…… Ub
Uc

12.5.2.7 Testing Binary Inputs

This test checks that all the binary inputs on the equipment are functioning correctly.

The binary inputs should be energized one at a time, see external connection diagrams for

PCS-902 Line Distance Relay 12-7


Date: 2011-02-28
12 Commissioning

terminal numbers.

Ensure that the voltage applied on the binary input must be within the operating range.

The status of each binary input can be viewed using relay menu. Sign “1” denotes an energized
input and sign “0” denotes a de-energized input.

Terminal No. Signal Name BI Status on LCD Correct?

Test method:

To unplug all the terminals sockets of this protective device, and do the Insulation resistance test
for each circuit above with an electronic or brushless insulation tester.

On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection.

12.5.3 Print Fault Report


In order to acquire the details of protection operation, it is convenient to print the fault report of
protection device. The printing work can be easily finished when operator presses the print button
on panel of protection device to energize binary input [BI_Print] or operate control menu. What
should be noticed is that only the latest fault report can be printed if operator presses the print
button. A complete fault report includes the content shown as follows.

1) Trip event report

2) Binary input when protection devices start

3) Self-check and the transition of binary input in the process of devices start

4) Fault wave forms compatible with COMTRADE

5) The setting value when the protection device trips

12.5.4 On-load Checks


The objectives of the on-load checks are:

 Confirm the external wiring to the current and voltage inputs is correct.

 Measure the magnitude of on-load current and voltage (if applicable).

 Check the polarity of each current transformer.

However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant being protected.

Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has

12-8 PCS-902 Line Distance Relay


Date: 2011-02-28
12 Commissioning

been removed to allow testing.

If it has been necessary to disconnect any of the external wiring from the protection in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram. Confirm current and voltage
transformer wiring.

12.6 Final Checks

After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been
necessary to disconnect any of the external wiring from the protection in order to perform the
wiring verification tests, it should be ensured that all connections are replaced in accordance with
the relevant external connection or scheme diagram.

Ensure that the protection has been restored to service.

If the protection is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the protection is put into service.

Ensure that all event records, fault records, disturbance records and alarms have been cleared
and LED’s has been reset before leaving the protection.

PCS-902 Line Distance Relay 12-9


Date: 2011-02-28
12 Commissioning

12-10 PCS-902 Line Distance Relay


Date: 2011-02-28
13 Maintenance

13 Maintenance

Table of Contents
13 Maintenance ................................................................................. 13-a
13.1 Appearance Check ...................................................................................... 13-1
13.2 Failure Tracing And Repair ......................................................................... 13-1
13.3 Replace Failed Modules ............................................................................. 13-1
13.4 Cleaning ....................................................................................................... 13-3
13.5 Storage ......................................................................................................... 13-3

PCS-902 Line Distance Relay 13-a


Date: 2011-02-28
13 Maintenance

13-b PCS-902 Line Distance Relay


Date: 2011-02-28
13 Maintenance

NR numerical relay PCS-902 is designed to require no special maintenance. All measurement and
signal processing circuit are fully solid state. All input modules are also fully solid state. The output
relays are hermetically sealed.

Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are
not required.

Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.

13.1 Appearance Check


1. The relay case should be clean without any dust stratification. Case cover should be sealed
well. No component has any mechanical damage and distortion, and they should be firmly fixed in
the case. Relay terminals should be in good condition. The keys on the front panel with very good
feeling can be operated flexibly.

2. It is only allowed to plug or withdraw relay board when the supply is reliably switched off.
Never allow the CT secondary circuit connected to this equipment to be opened while the primary
system is live when withdrawing an AC module. Never try to insert or withdraw the relay board
when it is unnecessary.

3. Check weld spots on PCB whether they are well soldered without any rosin joint. All dual
inline components must be well plugged.

13.2 Failure Tracing And Repair


Failures will be detected by automatic supervision or regular testing.

When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “Superv Events” screen on the LCD.

When a failure is detected during regular testing, confirm the following:

 Test circuit connections are correct

 Modules are securely inserted in position

 Correct DC power voltage is applied

 Correct AC inputs are applied

 Test procedures comply with those stated in the manual

13.3 Replace Failed Modules


If the failure is identified to be in the relay module and the user has spare modules, the user can

PCS-902 Line Distance Relay 13-1


Date: 2011-02-28
13 Maintenance

recover the protection by replacing the failed modules.

Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.

Check that the replacement module has an identical module name (AI, PWR, CPU, SIG, BI, BO,
etc.) and hardware type-form as the removed module. Furthermore, the CPU module replaced
should have the same software version. In addition, the AI and PWR module replaced should have
the same ratings.

The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “Version Info”.

Caution!

When handling a module, take anti-static measures such as wearing an earthed wrist band
and placing modules on an earthed conductive mat. Otherwise, many of the electronic
components could suffer damage. After replacing the CPU module, check the settings.

1) Replacing a module

 Switch off the DC power supply

 Disconnect the trip outputs

 Short circuit all AC current inputs and disconnect all AC voltage inputs

 Unscrew the module.

Warning!

Hazardous voltage can be present in the DC circuit just after switching off the DC power
supply. It takes approximately 30 seconds for the voltage to discharge.

2) Replacing the Human Machine Interface Module (front panel)

 Open the relay front panel

 Unplug the ribbon cable on the front panel by pushing the catch outside.

 Detach the HMI module from the relay

 Attach the replacement module in the reverse procedure.

3) Replacing the AI, PWR, CPU, BI or BO module

 Unscrew the module connector

 Unplug the connector from the target module.

 Unscrew the module.

 Pull out the module

13-2 PCS-902 Line Distance Relay


Date: 2011-02-28
13 Maintenance

 Inset the replacement module in the reverser procedure.

 After replacing the CPU module, input the application-specific setting values again.

Warning!

Units and modules may only be replaced while the supply is switched off and only by
appropriately trained and qualified personnel. Strictly observe the basic precautions to
guard against electrostatic discharge.

Warning!

When handling a module, take anti-static measures such as wearing an earthed wrist band
and placing modules on an earthed conductive mat. Otherwise, many of the electronic
components could suffer damage. After replacing the CPU module, check the settings.

Danger!

After replacing modules, be sure to check that the same configuration is set as before the
replacement. If this is not the case, there is a danger of the unintended operation of
switchgear taking place or of protections not functioning correctly. Persons may also be
put in danger.

13.4 Cleaning
Before cleaning the relay, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean
the front panel. Do not use abrasive material or detergent chemicals.

13.5 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC standard
60255-1 the storage temperature should be from -40oC to +70oC, but the temperature of from 0oC
to +40oC is recommended for long-term storage.

PCS-902 Line Distance Relay 13-3


Date: 2011-02-28
13 Maintenance

13-4 PCS-902 Line Distance Relay


Date: 2011-02-28
14 Decommissioning and Disposal

14 Decommissioning and Disposal

Table of Contents
14 Decommissioning and Disposal................................................. 14-a
14.1 Decommissioning ....................................................................................... 14-1
14.2 Disposal ....................................................................................................... 14-1

PCS-902 Line Distance Relay 14-a


Date: 2011-02-28
14 Decommissioning and Disposal

14-b PCS-902 Line Distance Relay


Date: 2011-02-28
14 Decommissioning and Disposal

14.1 Decommissioning
1. Switching off

To switch off the PCS-902, switch off the external miniature circuit breaker of the power supply.

2. Disconnecting Cables

Disconnect the cables in accordance with the rules and recommendations made by relational
department.

Danger!

Before disconnecting the power supply cables that connected with the PWR module of the
PCS-902, make sure that the external miniature circuit breaker of the power supply is
switched off.

Danger!

Before disconnecting the cables that are used to connect analog input module with the
primary CTs and VTs, make sure that the circuit breaker for the primary CTs and VTs is
switched off.

3. Dismantling

The PCS-902 rack may now be removed from the system cubicle, after which the cubicles may
also be removed.

Danger!

When the station is in operation, make sure that there is an adequate safety distance to
live parts, especially as dismantling is often performed by unskilled personnel.

14.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.

Note!

Strictly observe all local and national regulations when disposing of the device.

PCS-902 Line Distance Relay 14-1


Date: 2011-02-28
14 Decommissioning and Disposal

14-2 PCS-902 Line Distance Relay


Date: 2011-02-28
15 Manual Version History

15 Manual Version History


In the latest version of the instruction manual, several descriptions on existing features have been
modified.

Manual version and modification history records

Manual Version Software


Date Description of change
Source New Version
R1.00 R1.00 2011-07-06 Form the original manual.
R1.00 R1.01 R1.00 2011-08-18

PCS-902 Line Distance Relay 15-1


Date: 2011-07-06
15 Manual Version History

15-2 PCS-902 Line Distance Relay


Date: 2011-07-06

Das könnte Ihnen auch gefallen