Remote-Output Driver Modules

REMOTE-OUTPUT DRIVER MODULES,


MODELS ATM-L AND ATM-R
1-1 DESCRIPTION
The Model ATM-L Annunciator Driver Module, P/N 76-200004-032, provides Kidde intelligent systems with
up to 32 programmable outputs for remote LEDs, along with six (6) system-level LEDs and five (5) system-
level functional switches.
The system-level LEDs correspond to the following general conditions:
• Module Power/Lockout
• Alarm
• Pre-Alarm
• Alarm Silence
• Supervisory
• Trouble
The functional switches provide for the following operator intervention:
• System Reset
• Event Acknowledgment
• Alarm Silence
• Fire Drill
• Lamp Test
All ATM-Ls will not respond to local commands from functional switches for ten (10) seconds after a key is
pressed on the keypad/display of the control unit. A flashing module-power LED will signify this lockout condition.
The Model ATM-R Relay Driver Module, P/N 76-200005-032, provides the system with up to 32 programmable
outputs for remote relays.
The ATM-L and -R Modules communicate with the control unit via an external RS-485 communications circuit,
with the most remote module capable of being located up to 4,000 feet from the control unit. Up to 31 ATM-Ls and
ATM-Rs, in any combination but subject to a limitation of 16 for each type of driver module, can be connected in
a daisy-chained loop to the RS-485 communications circuit. No “t-tapping” is allowed in the communications
circuit.
Both modules can be powered from the intelligent control unit's power supply, or from an external, regulated and
power-limited power supply Listed for use with fire protective signaling systems, depending upon the total load of
the remote outputs. A typical external power supply is Kidde Fire Systems P/N 297106.
Note: Refer to the appropriate control unit design, installation and maintenance manual for auxiliary power
output ratings.
When using any other Listed power supply to power either the ATM-L or ATM-R, ensure that the power supply has
a means to isolate the common-negative power line from earth ground to prevent system ground faults. Both the
ATM-L and ATM-R have an initiating circuit labeled “PS FLT” to monitor a normally-closed power supply fault
contact. Refer to Figures 2, 3 and 4.
The ATM-L and ATM-R modules are supported by Kidde Intelligent control units, including the ARIESTM, ARIES NET
LinkTM and PEGAsysTM control unit with firmware version 81.0 or higher.

January 2012 1 06-236179-002


Remote-Output Drive Modules

2-1 INSTALLATION

! CAUTION
When performing installations, route field wiring away from sharp projections, corners and internal
components.
The ATM-L and ATM-R Modules are intended for mounting inside a UL-864/ULC S527 Listed enclosure with no
other electronics. Use the mounting hardware (hex spacers and screws) provided with the module. Any switches
installed with the ATM-L that are used for silencing must be either a key lock type with the key removable only in the
Normal position, or located inside a locked panel, or arranged to provide equivalent protection against unauthorized
use. Wire routing and installation methods are to be in accordance with the annunciator installation instructions.
Note: Maintain a minimum 1/2" clearance around the ATM-L and ATM-R modules when installed in the UL-864/
ULC S527 Listed enclosure. Select an enclosure with dimensions of at least 6" H x 9" W x 2" D.
Use consecutive LED outputs, starting from LED Output No. 1. There can be no gaps in the output-LED sequence.
Cut the next-higher supervised-output termination jumper after the last LED output that is being used. Refer to
Figure 2 for details.
The LEDs and functional switches for the ATM-L must be installed in conduit within 20 feet of the UL-864/ULC S527
Listed enclosure.
The relays for the ATM-R must be installed in conduit within 20 feet of the UL-864/ULC S527 Listed enclosure.
Use consecutive relay outputs, starting from Relay Output No. 1. There can be no gaps in the output-relay sequence.
Cut the next-higher supervised-output termination jumper after the last relay output that is being used. Refer to
Figure 3 for details.
See Figure 1 for module mounting dimensions.

2-1.1 Electrical
Table 1. Electrical Specifications

Operating Voltage: 16.0 to 28.8 Vdc (non-resettable)

Standby Current: 0.045 A Max.

Output Activation: Common Positive; Individual-output negative pull downs

ATM-L Outputs:

LED 0.015 A maximum (28.8 Vdc)

Audible Appliance 0.015 A maximum (28.8 Vdc)

ATM-R Outputs: 0.080 A maximum (28.8 Vdc)

Total Alarm Current: Depends upon output load. Must be calculated for each application.

Wire Sizes:

RS-485 Communications #14 - #18 AWG, (twisted, shielded)

24 Vdc Power #14 - #18 AWG (as required)

LEDs #18 AWG (or as required by annunciator)

Functional Switches #18 AWG

Audible Appliance #18 AWG (or as required by annunciator)

Power-Supply Supv.Initiating Circuit #14 - #18 AWG

Relays #14 - #18 AWG

06-236179-002 2 January 2012


Remote-Output Driver Modules

Refer to the wiring diagrams for point-to-point connections.

S2 S1 LK17

LK32

ATM-L/R
LK16 LK15
Out B 16 32
LK31 LK30
Out A 15 31
In B LK14 LK13 14 30
In A 13 LK29 LK28 29
12 28
W1 LK12 LK11 11 27
10 LK27 LK26 26
9 25
4.625 +24 V
LK10 LK9
8 LK25 LK24 24
5.000 Com 7 23
PS Flt LK8 LK7
6 22
Earth Gnd 5 LK23 LK22
21
LK6 LK5 4 20
3 19
A Trouble Lamp Test LK21 LK20
2 18
B Sup. Com LK4 LK3 1 17
Sil. Out Ack LK19 LK18
Pre Alm Reset
Alarm Silence LK2 LK1
Pwr On Drill
0.188

1.375 5.175
8.000

Note:

Maintain a minumum one-half (1/2) inch clearance around ATM-L


and ATM-R Modules when installed in mounting enclosure.

Figure 1. Module Mounting Dimensions

3-1 POWER SUPPLY CALCULATION

3-1.1 ATM-L Power Supply Calculation


ATM-Ls will operate down to 16.0 Vdc. If the nominal power supply output is 24 Vdc, the minimum system voltage
after 24 hours of battery operation is 20.4 Vdc. Therefore, the maximum voltage drop to any ATM-L is 4.4 Vdc.
Calculate the total ATM-L current and maximum power-line resistance using the following procedure.
1. Count the total number of output LEDs from all ATM-Ls that will be powered from the control unit power supply.
Output LED current:
# LEDs x 0.012 = ____A
2. Count the total number of ATM-Ls.
ATM-L current:
# ATM-Ls x 0.045 = ____A
3. Count the total number of ATM-Ls whose status lights will be powered from the control unit power supply.
Status LED current:
#ATM-Ls x 0.072 = ____A
4. Add 1 + 2 + 3 for total current from the control unit power supply ____A
5. Calculate maximum allowable resistance.
Divide 4.4 Vdc by total current (Step 4)
____ohms

January 2012 3 06-236179-002


Remote-Output Drive Modules

Example:
• ATM-L # 1 has 20 point- or group-specific output LEDs.
• ATM-L #2 has 15 point- or group-specific output LEDs.
• ATM-L #3 has 8 point- or group-specific output LEDs.
• All ATM-Ls are utilizing the system status lights.
• All outputs will be powered by a Kidde intelligent control unit power supply.
• Total LEDs = 43
• Total output LED current = 43 x 0.012 = 0.516 A
• Total ATM-Ls = 3
• Total ATM-L current = 3 x 0.045 = 0.135 A
• Total ATM-Ls status lights
• Total Status LED current = 3 x 0.072 = 0.216 A
• Total Current = 0.867 A
• Maximum Power-Line Resistance = 4.4 V/0.867 A = 5.1 ohms

3-1.2 ATM-R Power Supply Calculation


ATM-Rs will also operate down to 16.0 Vdc. If the nominal power supply output is 24 Vdc, the minimum system
voltage after 24 hours of battery operation is 20.4 Vdc. Use UL Listed/Recognized relays with a nominal 24 Vdc
rating, and with an operating voltage range between 18.0 and 30.0 Vdc. Refer to the manufacturer supplied
information for listed operating voltage range.
Relay coil currents vary widely from about 15 mA to 80 mA. Refer to the manufacturer’s data sheet for the coil
current of the specific relay being utilized in the application.
Calculate the total ATM-R current and maximum power-line resistance using the following procedure.
1. Count total number of output relays from all ATM-Rs that will be powered from the control unit power supply.
Output relay current:
# relays x current/relay = ____A
2. Count the total number of ATM-Rs.
ATM-R current:
# ATM-Rs x 0.045 = ____A
3. Add 1 + 2 for total current from the control unit power supply ____A
4. Calculate maximum allowable resistance. Use the minimum relay operating voltage of 18 Vdc in this calculation.
Divide 2.4 Vdc by total current (Step 3)
_____ohms
Example:
• An ATM-R has 15 relay outputs. Each relay has a coil current of 25 mA.
• All outputs will be powered by a Kidde intelligent control unit power supply.
• Total Relays = 15
• Total output Relay current = 15 x 0.025 = 0.375 A
• Total ATM-Rs = 1
• Total ATM-R current = 1 x 0.045 = 0.045 A
• Total Current = 0.420 A
• Maximum Power-Line Resistance 2.4 V/0.420A = 5.7 ohms

06-236179-002 4 January 2012


Remote-Output Driver Modules

4-1 REGISTRATION
The ATM-L and ATM-R Modules are automatically registered into the intelligent system when they are uploaded into
the system configuration software. They may also be registered manually, but without point or group-specific device
mapping, by means of the keypad on the control unit. The manual registration procedure is documented in the
appropriate control unit design, installation and maintenance manual.

January 2012 5 06-236179-002


RS-485 Termination Jumper W1
Install if ATM-L is last assembly in RS-485 communications ATM-L Address Table
loop from CCM Display PCB.
Remove if ATM-L is intermediate assembly in RS-485 loop. S1 Switch Setting 1 2 3 4 5 6 7 8 9 A B C D E F 0

06-236179-002
Reset Switch S2
ATM-L Address 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Address Switch S1
S L
(See Table)

RS-485 Communications to B Output Supervision Termination Jumper


next ATM-L/R, RDCM, or RDM Cut the jumper following the last supervised LED
A S2 S1 LK17 output (e.g., if last LED output is 15, cut Jumper LK16).

LK32 S L
RS-485 Communications 5
LK16 LK15
Remote-Output Drive Modules

from Control Unit LED 32


6 Out B 16 32
LK31 LK30 LED 31
Out A 15 31
LED 30
S L In B
ATM-L LK14 LK13 14 30
In A 13 LED 29
LK29 LK28 29
12 28 LED 28
W1 LK12 LK11 11 27 LED 27
10 LK27 LK26 26 LED 26
S L LK10 LK9 9 25 LED 25
Non-resettable 24 VDC from
+24 V LED 24
Control Unit Power Supply Module 8 LK25 LK24 24
(Aux. Pwr. Output) Com 7 23 LED 23
PS Flt LK8 LK7 22 LED 22
6
Earth Gnd LK23 LK22 LED 21
5 21
Install 20 K, 0.25 W Resistor from +24 V to Alarm- LED 20
Silence Output when Alarm-Silence Output not used. LK6 LK5 4 20
Normally-closed, trouble contact from 3 LED 19
Trouble Lamp Test LK21 LK20 19
Remote Power Supply P/N 297106 A 18 LED 18
2
B Sup. Com LK4 LK3
Note: Locate local audible applicance 1 17 LED 17
in conduit in the same room within 20
Sil. Out Ack LK19 LK18
feet of the ATM-L. Pre Alm Reset
Alarm Silence LK2 LK1 Note:
(Jumper "PS Flt" to "Com" when not used.).
Pwr On Drill Maximum 15 ma per LED

6
S L
L
LED 16
LED 15
LED 14
LED 13
LED 12
Local Audible Appliance LED 11
(mimics control unit sonalert, LED 10
15 ma maximum) S L LED 9
LED 8
N.O. Lamp-Test Switch
LED 7
L Trouble LED LED 6
L Supervisory LED LED 5
S L Alm. Sil. LED N.O. Acknowledge Switch LED 4

L Pre-Alm LED LED 3


L Alarm LED LED 2
N.O. Reset Switch
L Power LED LED 1

N.O. Alm Sil Switch Note:

N.O. Drill Switch Use consecutive LED outputs, starting from LED
S Supervised Circuit (Press "Alm Sil" Switch to cancel Drill) Output No. 1. There can be no gaps in the output LED
sequence. Cut the next-higher supervised output
termination jumper after the last LED output used.
L Power-Limited Circuit 10 k, 0.5 W EOL Resistor
Typ for each N.O. Input Switch

Figure 2. ATM-L Wiring Diagram

January 2012
RS-485 Termination Jumper W1

January 2012
Install if ATM-R is last assembly in RS-485 communications ATM-R Address Table
loop from CCM Display PCB.
Remove if ATM-R is intermediate assembly in RS-485 loop. S1 Switch Setting 1 2 3 4 5 6 7 8 9 A B C D E F 0

Reset Switch S2
ATM-R Address 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Address Switch S1
S L
(See Table)

RS-485 Communications to B Output Supervision Termination Jumper


next ATM-L/R, RDCM, or RDM Cut the jumper following the last supervised relay
A S2 S1 LK17 output (e.g., if last relay output is 15, cut Jumper LK16).

LK32 S L
RS-485 Communications 5
LK16 LK15
from Control Unit Relay 32
6 Out B 16 32
LK31 LK30 Relay 31
Out A 15 31
S L In B 30 Relay 30
LK14 LK13 14
In A 13 Relay 29
LK29 LK28 29
12 28 Relay 28
W1 LK12 LK11 11 27 Relay 27
10 LK27 LK26 26 Relay 26
S L LK10 LK9 9 25 Relay 25
Non-Resettable 24 Vdc from
+24 V Relay 24
Control Unit Power Supply 8 LK25 LK24 24
(Aux. Pwr. Output) Com 7 23 Relay 23
PS Flt LK8 LK7 22 Relay 22
6
LK23 LK22 Relay 21
5 21
4 20 Relay 20
LK6 LK5
Normally-closed, trouble contact from 3 Relay 19
LK21 LK20 19
Remote Power Supply P/N 297106 18 Relay 18
2
(Jumper "PS Flt" to "Com" when not used.)
ATM-R LK4 LK3 1 17 Relay 17
LK19 LK18

7
LK2 LK1
Note:
Maximum 80 mA per relay.

S L

Relay 16
Relay 15
Relay 14
Relay 13
Relay 12
Relay 11
Relay 10
Relay 9
Relay 8
Relay 7
Relay 6
Relay 5
Relay 4
Relay 3
Relay 2
Relay 1

Note:
Use consecutive relay outputs, starting from Relay
S Supervised Circuit Output No. 1. There can be no gaps in the output relay
sequence. Cut the next-higher supervised output
termination jumper after the last relay output used.
L Power-Limited Circuit

Figure 3. ATM-R Wiring Diagram - Common Power Supply for Module and Outputs

06-236179-002
Remote-Output Driver Modules
RS-485 Termination Jumper W1

06-236179-002
Install if ATM-R is last assembly in RS-485 communications ATM-R Address Table
loop from CCM Display PCB.
Remove if ATM-R is intermediate assembly in RS-485 loop. S1 Switch Setting 1 2 3 4 5 6 7 8 9 A B C D E F 0

Reset Switch S2
ATM-R Address 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Address Switch S1
S L
(See Table)

RS-485 Communications to B Output Supervision Termination Jumper


next ATM-L/R, RDCM, or RDM Cut the jumper following the last supervised relay
A S2 S1 LK17 output (e.g., if last relay output is 15, cut Jumper LK16).
Remote-Output Drive Modules

LK32 S L
RS-485 Communications 5
LK16 LK15
from Control Unit Relay 32
6 Out B 16 32
LK31 LK30 Relay 31
Out A 15 31
S L In B 30 Relay 30
LK14 LK13 14
In A 13 Relay 29
LK29 LK28 29
12 28 Relay 28
W1 LK12 LK11 11 27 Relay 27
10 LK27 LK26 26 Relay 26
S L LK10 LK9 9 25 Relay 25
Non- Resettable 24 Vdc from
+24 V Relay 24
Power Supply 8 LK25 LK24 24
Com 7 23 Relay 23
PS Flt LK8 LK7 22 Relay 22
6
Earth Gnd LK23 LK22 Relay 21
5 21
4 20 Relay 20
LK6 LK5
3 Relay 19
LK21 LK20 19
2 18 Relay 18
LK4 LK3 1 17 Relay 17
LK19 LK18
ATM-R

8
LK2 LK1
Note:
Maximum 80 mA per relay.

S L
S L
Relay 16
Relay 15
(+) (-) Relay 14
W2
C BA (+) (-)
Relay 13
GND BATT BATT
FLT OPR TBL (-) (+) Relay 12
28 VDC Load1 Relay 11
DS3 DS1 DS2 Relay 10
(+)
Relay 9
Load2
(-) Relay 8
Relay 7
(+)
Batt1 Relay 6
Power Supply, (-)
Relay 5
(+) Relay 4
Batt2
P/N 297106 (-) Relay 3
S L
N/O/C
Relay 2
(Refer to Installation Sheet 77.103) Trouble
Relay 1
N.C.
N.O.

COM

AC
ON
W3 Note:
(Set W3 to N.C. Position)
Use consecutive relay outputs, starting from Relay
S Supervised Circuit
W1 Output No. 1. There can be no gaps in the output relay
C BA
sequence. Cut the next-higher supervised output
termination jumper after the last relay output used.
L Power-Limited Circuit

Figure 4. ATM-R Wiring Diagram - Separate Power Supplies for Module and Outputs

January 2012
January 2012
W1 S2 S1 LK17 S2 S1 LK17
USE VR1 TO ADJUST CONTRAST. VR2 See Table 1 LK32
See Table 1 LK32
VR1
USE VR2 TO ADJUST BRIGHTNESS. LK16 LK15 LK16 LK15
Out B 16 32 Out B 16 32
LK31 LK30 LK31 LK30
Out A ATM-L 15 31 Out A ATM-L 15 31
1 TB1 In B LK14 LK13 14 30 In B LK14 LK13 14 30
2 In A 13 LK29 LK28 29 In A 13 LK29 LK28 29
3 JK2 12 28 12 28
4 W1 LK12 LK11 11 W1 LK12
DISPLAY PCB 27 LK11 11 27
5 10 LK27 LK26 26 10 LK27 LK26 26
6 REMOVE W1 9 25
INSTALL W1 9 25
LK10 LK9 LK10 LK9
7 JK1 +24 V +24 V
(on CCM) 8 LK25 LK24 24 8 LK25 LK24 24
8 Com 7 23 Com 7 23
PS Flt LK8 LK7 6 22 PS Flt LK8 LK7 6 22
W2 REMOVE W2 LK23 LK22 LK23 LK22
5 21 5 21
SW3 SW2 LK6 LK5 4 20 LK6 LK5 4 20
DS1 3 LK21 LK20 19 3 LK21 LK20 19
A Trouble Lamp Test A Trouble Lamp Test
2 18 2 18
SKT2 B Sup. Com LK4 LK3 B Sup. Com LK4 LK3
1 17 1 17
Sil. Out Ack LK19 LK18
Sil. Out Ack LK19 LK18
NOTE: Pre Alm Reset Pre Alm Reset
Alarm Silence LK2 LK1 Alarm Silence LK2 LK1

Pwr On Drill Pwr On Drill


Twisted, Shielded Wire to ATM-Ls.
(Total circuit length 4,000 FT. MAX.)
Table 1
Jumper Note: S1 Switch ATM-L/R
Driver Type Maximum Quantity
W1: RS-485 Communications to ATM-L.
Setting Address
AC OUT AC IN DC IN1 DC IN2
1 2
SOUNDER 1 SOUNDER 2
(on RS-485 Circuit)

2 4V
24V
N L N L L N G

RET
SPV
RET
SPV

SHARE
W5
W1
N N N N N N
A B A B C
O C
O C C O C C
Remove from CCM'S Display and
TB4 TB5 TB1 TB2 TB3 1 01
SKT1
NO
GREEN LED
intermediate ATM-Ls. Install on last ATM-L 16
C

TBL RL Y
NC
SYS
2 02
GND ATM-L only. ATM-R 16
JP4 JP3
3 03
W3
INSTALL W3
JP1 W2 W6 4 04
S3 (HARD RESET) 5 05
SW1
1 S1
JP2
Notes:
2
15A BAT
6 06
1 FUSE
JK5 S2
A

I/O
2

PORT
RS485
B 24V
W4 RET
INSTALL W4
7 07
TO DISPLAY TO DISPLAY 24V

RET
Any combination of ATM-Ls and ATM-Rs that does not

CCM
JK4
24V

9
JK1 JK2 JK3
PLG2

RX/TX
PORT
RET
8 08

EARTH
FAULT
SUPPLY
FAULT
0V
24 V
V
exceed 16 can be used on the RS-485 circuit. There

RET
RET
24 V
24

BOARD
24V 5V 0V

MOTHER
DISP PRINT PC
5V 0V TB6
PORT PORT PORT
PLG1 DISPLAY
9 09

SYSTEM PO WER
AUX1 AUX2
can be a maximum of 31 RS-485 assemblies in the
system, including RDMs and RDCMs. A 10
B 11
C 12
Use consecutive LED outputs, starting from LED
24 Vdc from Power Supply D 13
Output No. 1, for each ATM-L/R. There can be no gaps
E 14
(Install W3 for Non-Resettable Power) in the output sequences. Cut the next-higher
F 15
supervised output termination jumper after the last
output used. 0 16

PEGAsys Note: 1.5A Maximum for Each


Auxiliary Power Output.
Control Unit

1 2 34
Figure 5. Typical PEGAsys Control Unit/ATM-L/R Wiring Diagram

06-236179-002
Remote-Output Driver Modules
Maximum Length: 4,000 Ft.

06-236179-002
(Twisted, Shielded, Low-Capacitance Wire)
S2 S1 LK17

LK32
LK16 LK15
Out B 16 32
LK31 LK30
Out A ATM-L 15 31
In B LK14 LK13 14 30
In A 13 LK29 LK28 29
12 28
W1 LK12 LK11 11 27
Remote-Output Drive Modules

10 LK27 LK26 26
Remove W1 9 25
LK10 LK9
+24 V 8 LK25 LK24 24
Com 7 23
PS Flt LK8 LK7
6 22
LK23 LK22
5 21
LK6 LK5 4 20
3 LK21 LK20
19
A Trouble Lamp Test
Connect wire for shield to earth-ground Sup. Com
2 18
B LK4 LK3 1 17
screw in upper-edge of PCB. Sil. Out Ack LK19 LK18
Pre Alm Reset
Alarm Silence LK2 LK1
Pwr On Drill
TB1 TB15
4 3 2 1 4 3 2 1

J3 J5 RS-232 A
J6 J3
SLC RS 485 USB A
USB B
RS-232 B J8
Connect wires for shields together at each
intermediate annunciator driver. Do not connect
SLC wires for shields to the earth-ground screw in
remote enclosures.

Relay 1

NO NC C NO NC C

10
SYSTEM
AC POWER SYSTEM TROUBLE SILENCE
ACKNOWLEDGE
ALARM SUPERVISORY

NO NC C
SYSTEM
SCROLL
Leave shield wire floating at last annunciator driver. Do not
PRE-ALARM SILENCE RESET
connect wire for shield to the earth-ground screw in remote

NO NC C
1 2 3 4 5

Relay 2 Relay 3 Trouble


J10
enclosure. Trim shield wire as much as possible.
6 7 8 9 0

S2

Style 4
S2 S1 LK17

LK32
LK16 LK15
Out B

NAC 2
16 32

1 2 3 4
TB3 LK31 LK30
Out A ATM-L 15 31
TB14 In B LK14 LK13 14 30

- -
+ In A 13 LK29 LK28 29
+ 12 28
W1 LK12 LK11 11 27
Batt Out

NAC 1
1 2 3 4
10 LK27 LK26 26
ARIES Install W1 9 25
TB5 LK10 LK9
+24 V 8 LK25 LK24 24
Control Unit Com 7 23
PS Flt LK8 LK7

J12
PSU
6 22
LK23 LK22
5 21
LK6 LK5 4 20

N
240 3 19
Release 1 Release 2 Aux 24 VDC Combo 1 Combo 2 Trouble Lamp Test LK21 LK20

AC IN
L
A 2 18
120 TB11 TB2 TB7 TB6 B Sup. Com LK4 LK3 1 17
TB13 Sil. Out Ack LK19 LK18
TB12 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Pre Alm Reset
Alarm Silence LK2 LK1
Pwr On Drill
Configure Auxiliary Power
for Continuous Output

Install Jumper when Remote


Power Supply not used.

Figure 6. Typical ARIES Control Unit/ATM-L/R Wiring Diagram

January 2012
Remote-Output Driver Modules

S2

. Out B
Out A
Out B
Out A
In B
In B In A
In A
Installation Notes: Non-Resettable 24 VDC from W1

Control Unit Power Supply


(Aux. Pwr. Output) +24 V
1. RS-485 circuits must be terminated at the S L
Com
PS Flt
first and last device in the circuit. Set +24 V Earth Gnd
Com
termination resistor SW2 (located on the back PS Flt
of the Keypad/Display and RDCM boards) to
the ON (terminated) position by moving the
tiny white lever.

Communications Circuit (J8 ) ATM-R


Voltage: 24 VDC
Current: Per RS-485 Standard S2
Recommended Wire: Twisted, shielded,
low-capacitance, fire-alarm wire Out B Out B
Max. Wire Length: 4,000 Ft. per twisted pair Out A Out A
In B
In B In A
In A W1

Non-Resettable 24 VDC from


Control Unit Power Supply +24 V

Figure 7. Wiring Diagram for ARIES NETLink/ATM-L/R


(Aux. Pwr. Output) Com
PS Flt
S L Earth Gnd
+24 V
Com A Trouble
Sup.
PS Flt B
Sil. Out
Pre Alm
Alarm
Pwr On

ATM-L

IN-A

RS485
IN-B
OUT-A

J8 OUT-B

On the R-LAM, the location of these J8


For Dual Channel Installation

2 connectors is reversed; i.e., its J6


(PWR IN) 24 Vdc connector is at
the top, and its J8 (RS485) bus IN+
24 VDC PWR

connector is at the bottom. J4 IN-


OUT+
OUT-

J4
RDCM
IN- IN+ OUT+ OUT+
NORM ISOL OUT- NORM ISOL IN- OUT- IN+
SLC 1 SLC 2
J20 J19
USB HOST USB DEVICE
NO C
RELAY 1

IN-A
TB1

RS485

IN-B
NC

OUT-A
NO C
RELAY 2

OUT-B
TB2

RS232 A
NC

J8 J8
S P
NO C
RELAY 3

TB3
NC
NC C NO

RS232 B
TBL RELAY

TB3

Installation Notes:

2. If ATM-R or ATM-L is last device,


BACKPLANE
COMMS OUT

insert W1 jumper to terminate. If


not last device, remove jumper.
J9

Main-Controller Board
(MCB)
ARIES NET Link
PMU COMMS
OUT
J2
24 VDC IN
J10

J17 J18 J16 J15


R-NAC 1 R-NAC 2 NAC 1 NAC 2
OUT+ IN+ IN- OUT- ISOL NORM OUT+ IN+ IN- OUT- ISOL NORM OUT+ IN+ IN- OUT- ISOL NORM OUT+ IN+ IN- OUT- ISOL NORM

January 2012 11 06-236179-002


Remote-Output Drive Modules

THIS PAGE INTENTIONALLY LEFT BLANK.

06-236179-002 12 January 2012


Kidde is a registered trademark of Kidde-Fenwal, Inc.
PEGAsys, ARIES and ARIES NETLink are trademarks of Kidde-Fenwal, Inc.

These instructions do not purport to cover all the details or variations in the equipment described,
nor do they provide for every possible contingency to be met in connection with installation,
operation and maintenance. All specifications subject to change without notice. Should further
information be desired or should particular problems arise which are not covered sufficiently
for the purchaser’s purposes, the matter should be referred to KIDDE-FENWAL INC., Ashland,
A UTC Fire & Security Company Masssachusetts