Split Type
Air Conditioners
FTK(X)S-E/F Series
FTKS25EVMV RKS25EBVMV
FTKS35EVMV RKS35EBVMV
Cooling Only FTKS50FVMV RKS50FVMV
FTKS60FVMV RKS60FVMV
FTKS71FVMV RKS71FVMV
FTXS25EVMV RXS25EBVMV
FTXS35EVMV RXS35EBVMV
Heat Pump FTXS50FVMV RXS50FVMV
FTXS60FVMV RXS60FVMV
FTXS71FVMV RXS71FVMV
1. Power Supply
Indoor Unit Outdoor Unit Power Supply
FTKS25EVMV RKS25EBVMV
FTKS35EVMV RKS35EBVMV
FTKS50FVMV RKS50FVMV
FTKS60FVMV RKS60FVMV
FTKS71FVMV RKS71FVMV 1 φ, 220 ~ 240 V, 50 Hz
FTXS25EVMV RXS25EBVMV 1 φ, 220 ~ 230 V, 60 Hz
FTXS35EVMV RXS35EBVMV
FTXS50FVMV RXS50FVMV
FTXS60FVMV RXS60FVMV
FTXS71FVMV RXS71FVMV
2. Functions
2.1 Cooling Only
FTKS50/60/71FVMV
FTKS50/60/71FVMV
RKS50/60/71FVMV
RKS50/60/71FVMV
RKS25/35EBVMV
RKS25/35EBVMV
FTKS25/35EVMV
FTKS25/35EVMV
Category Functions Category Functions
10 10
Operation limit for cooling (°CDB) ~ 46 ~ 46 Photocatalytic deodorising filter — —
Operation limit for heating (°CWB) — — Air purifying filter with photocatalytic — —
deodorising function
PAM control z z Titanium apatite photocatalytic
air-purifying filter z z
Compressor Oval scroll compressor — —
Swing compressor z z Air filter (prefilter) z z
Rotary compressor — — Wipe-clean flat panel z z
Reluctance DC motor z z Washable grille — —
Comfortable Power-airflow flap — — MOULD PROOF operation z —
Airflow
Power-airflow dual flaps z z Heating dry operation — —
Power-airflow diffuser — — Good-sleep cooling operation — —
Wide-angle louvres z z Timer 24-hour ON/OFF TIMER z z
Vertical auto-swing z z NIGHT SET mode z z
(up and down)
Horizontal auto-swing Worry Free Auto-restart
(right and left) — z “Reliability & (after power failure) z z
Durability”
3-D airflow — z
Self-diagnosis (digital, LED) display z z
COMFORT AIRFLOW operation — —
Comfort Control Auto fan speed z z Wiring error check function — —
Indoor unit quiet operation z z Anticorrosion treatment of outdoor
heat exchanger z z
NIGHT QUIET mode (automatic) — —
OUTDOOR UNIT QUIET operation z z
Flexibility Multi-split / split type compatible — —
(manual) indoor unit
FTXS50/60/71FVMV
FTXS50/60/71FVMV
RXS50/60/71FVMV
RXS50/60/71FVMV
RXS25/35EBVMV
RXS25/35EBVMV
FTXS25/35EVMV
FTXS25/35EVMV
Category Functions Category Functions
10 10
Operation limit for cooling (°CDB) ~ 46 ~ 46 Photocatalytic deodorising filter — —
Operation limit for heating (°CWB) –15 –15 Air purifying filter with photocatalytic — —
~ 20 ~ 18 deodorising function
PAM control z z Titanium apatite photocatalytic z z
Compressor Oval scroll compressor — — air-purifying filter
Swing compressor z z Air filter (prefilter) z z
Rotary compressor — — Wipe-clean flat panel z z
Reluctance DC motor z z Washable grille — —
Comfortable Power-airflow flap — — MOULD PROOF operation z —
Airflow
Power-airflow dual flaps z z Heating dry operation — —
Power-airflow diffuser — — Good-sleep cooling operation — —
Wide-angle louvres z z Timer 24-hour ON/OFF TIMER z z
Vertical auto-swing z z NIGHT SET mode z z
(up and down)
Horizontal auto-swing Worry Free Auto-restart
(right and left) — z “Reliability & (after power failure) z z
Durability”
3-D airflow — z
Self-diagnosis (digital, LED) display z z
COMFORT AIRFLOW operation — —
Comfort Control Auto fan speed z z Wiring error check function — —
Indoor unit quiet operation z z Anticorrosion treatment of outdoor
heat exchanger z z
NIGHT QUIET mode (automatic) — —
OUTDOOR UNIT QUIET operation z z
Flexibility Multi-split / split type compatible — —
(manual) indoor unit
3. Specifications
3.1 Cooling Only
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V
Indoor Unit FTKS25EVMV FTKS35EVMV
Models
Outdoor Unit RKS25EBVMV RKS35EBVMV
kW 2.5 (1.2 ~ 3.0) 3.5 (1.2 ~ 3.8)
Capacity (Rated) Btu/h 8,500 (4,100 ~ 10,200) 11,900 (4,100 ~ 12,950)
kcal/h 2,150 (1,030 ~ 2,580) 3,010 (1,030 ~ 3,260)
Moisture Removal L/h 1.2 1.9
Running Current (Rated) A 3.5 - 3.3 - 3.2 / 3.5 - 3.3 4.9 - 4.7 - 4.5 / 4.9 - 4.7
Power Consumption (Rated) W 600 (300 ~ 800) 1,020 (300 ~ 1,200)
Power Factor % 77.9 - 79.1 - 78.1 / 77.9 - 79.1 94.6 - 94.4 - 94.4 / 94.6 - 94.4
COP (Rated) W/W 4.17 (4.00 ~ 3.75) 3.43 (4.00 ~ 3.17)
Liquid mm φ 6.4 φ 6.4
Piping Gas mm φ 9.5 φ 9.5
Connections
Drain mm φ 18.0 φ 18.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 20 20
Max. Interunit Height Difference m 15 15
Chargeless m 10 10
Amount of Additional Charge of g/m 20 20
Refrigerant
Indoor Unit FTKS25EVMV FTKS35EVMV
Front Panel Colour White White
H 8.7 (307) 8.9 (314)
M m³/min 6.7 (237) 6.9 (244)
Airflow Rate (cfm)
L 4.7 (166) 4.8 (169)
SL 3.9 (138) 4.0 (141)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 40 40
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards
Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof
Running Current (Rated) A 0.17 - 0.16 - 0.15 / 0.17 - 0.16 0.19 - 0.18 - 0.17 / 0.19 - 0.18
Power Consumption (Rated) W 35 - 35 - 35 / 35 - 35 40 - 40 - 40 / 40 - 40
Power Factor % 93.6 - 95.1 - 97.2 / 93.6 - 95.1 95.7 - 96.6 - 98.0 / 95.7 - 96.6
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) mm 283 × 800 × 195 283 × 800 × 195
Packaged Dimensions (H × W × D) mm 265 × 855 × 340 265 × 855 × 340
Weight (Mass) kg 9 9
Gross Weight (Gross Mass) kg 12 12
Sound Pressure H / M / L / SL dB(A) 37 / 31 / 25 / 22 38 / 32 / 26 / 23
Level
Outdoor Unit RKS25EBVMV RKS35EBVMV
Casing Colour Ivory White Ivory White
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Compressor Model 1YC23NXD 1YC23NXD
Motor Output W 600 600
Type FVC50K FVC50K
Refrigerant Oil
Charge L 0.375 0.375
Type R-410A R-410A
Refrigerant
Charge kg 1.0 1.0
H m³/min 33.5 (1,183) 33.5 (1,183)
Airflow Rate (cfm)
L 23.4 (826) 23.4 (826)
Type Propeller Propeller
Fan
Motor Output W 50 50
Running Current (Rated) A 3.33 - 3.14 - 3.05 / 3.33 - 3.14 4.71 - 4.52 - 4.33 / 4.71 - 4.52
Power Consumption (Rated) W 565 - 565 - 565 / 565 - 565 980 - 980 - 980 / 980 - 980
Power Factor % 77.1 - 78.2 - 77.2 / 77.1 - 78.2 94.6 - 94.3 - 94.3 / 94.6 - 94.3
Starting Current A 3.5 4.9
Dimensions (H × W × D) mm 550 × 765 × 285 550 × 765 × 285
Packaged Dimensions (H × W × D) mm 589 × 882 × 363 589 × 882 × 363
Weight (Mass) kg 34 34
Gross Weight (Gross Mass) kg 40 40
Sound Pressure H / L dB(A) 46 / 43 47 / 44
Level
Drawing No. 3D078157A 3D078158A
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Piping Length
Indoor ; 27°CDB / 19°CWB kcal/h = kW × 860
Outdoor ; 35°CDB / 24°CWB 7.5 m Btu/h = kW × 3412
cfm = m³/min × 35.3
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Piping Length
Indoor ; 27°CDB / 19°CWB kcal/h = kW × 860
Outdoor ; 35°CDB / 24°CWB 7.5 m Btu/h = kW × 3412
cfm = m³/min × 35.3
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Piping Length
Indoor ; 27°CDB / 19°CWB kcal/h = kW × 860
Outdoor ; 35°CDB / 24°CWB 7.5 m Btu/h = kW × 3412
cfm = m³/min × 35.3
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Heating Piping Length
Indoor ; 27°CDB / 19°CWB Indoor ; 20°CDB kcal/h = kW × 860
Outdoor ; 35°CDB / 24°CWB Outdoor ; 7°CDB / 6°CWB 7.5 m Btu/h = kW × 3412
cfm = m³/min × 35.3
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Heating Piping Length
kcal/h = kW × 860
Indoor ; 27°CDB / 19°CWB Indoor ; 20°CDB 7.5 m Btu/h = kW × 3412
Outdoor ; 35°CDB / 24°CWB Outdoor ; 7°CDB / 6°CWB cfm = m³/min × 35.3
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Heating Piping Length
kcal/h = kW × 860
Indoor ; 27°CDB / 19°CWB Indoor ; 20°CDB 7.5 m Btu/h = kW × 3412
Outdoor ; 35°CDB / 24°CWB Outdoor ; 7°CDB / 6°CWB cfm = m³/min × 35.3
4. Dimensions
4.1 Indoor Unit
4.1.1 Cooling Only
FTKS25/35EVMV
PERFORMANCE)
THE MARK (→) SHOWS PIPING DIRECTION
(SPACE FOR
AIRFLOW (INDOOR)
30MIN.
REAR
800
LEFT RIGHT
( INCLUDING
MOUNTING PLATE ) 50MIN. 50MIN.
197 (SPACE FOR (SPACE FOR
REQUIRED SPACE
195 MAINTENANCE) MAINTENANCE)
SIGNAL RECEIVER
NAME PLATE
OPERATION LAMP
283
TIMER LAMP TERMINAL BLOCK
WITH EARTH
INTELLIGENT EYE LAMP
TERMINAL
INTELLIGENT EYE SENSOR
BOTTOM GAS PIPE 9.5Cut
INDOOR UNIT ON/OFF SWITCH (THE LENGTH OF PIPE OUTSIDE DRAIN HOSE
FRONT PANEL FIXED SCREWS (CONNECTING PART
ROOM TEMP. THERMISTOR (INSIDE) THE UNIT : ABOUT 390)
FLAPS (INSIDE) I.D. φ14
LIQUID PIPE 6.4CuT O.D. φ18
(THE LENGTH OF PIPE OUTSIDE THE HOSE LENGTH OF OUTSIDE
THE UNIT : ABOUT 340) THE UNIT IS APPROX. 440)
SIGNAL TRANSMITTER
800
711 49
13
17
58 18 BLADE ANGLE
UP/DOWN (AUTOMATIC)
DAIKIN
180
COOLING, DRY FAN
283
44.5
163
10˚ 5˚
44.5
60 110
WALL HOLE FOR EMBEDDED PIPING
50˚ φ65 HOLE
70˚ WALL HOLE
φ65 HOLE
WIRELESS REMOTE CONTROLLER RIGHT/LEFT (MANUAL) STANDARD LOCATIONS OF WALL HOLES
(ARC433B47)
45˚ 3D077916
45˚
FTKS50/60FVMV
AIRFLOW (INDOOR)
PERFORMANCE)
(FOR PERFORMANCE AND MAINTENANCE)
THE MARK (→) SHOWS PIPING DIRECTION
(SPACE FOR
REAR REAR
MIN.30
1050
LEFT RIGHT
(SPACE FOR
MAINTENANCE)
MIN.50 MIN.50
(SPACE FOR
( INCLUDING
INSTALLATION PLATE ) REQUIRED SPACE MAINTENANCE)
240
238
OPERATION LAMP
MODEL NAME
SIGNAL RECEIVER
PLATE
INDOOR UNIT ON/OFF
290
58 18 1050
HORIZONTAL BLADE BLADE ANGLES
(AUTOMATIC) 893.5 52.5
30
14.5
COOLING DRY
155.5
163
290
10˚ 5˚
52
40˚ 10˚ 5˚
35˚
40˚ 35˚
WIRELESS REMOTE
52
FTKS71FVMV
AIRFLOW (INDOOR)
PERFORMANCE)
(FOR PERFORMANCE AND MAINTENANCE)
THE MARK (→) SHOWS PIPING DIRECTION
(SPACE FOR
REAR REAR
MIN.30
1050
LEFT RIGHT
(SPACE FOR
MAINTENANCE)
MIN.50 MIN.50
(SPACE FOR
( INCLUDING
INSTALLATION PLATE ) REQUIRED SPACE MAINTENANCE)
240
238
OPERATION LAMP
MODEL NAME
SIGNAL RECEIVER
PLATE
INDOOR UNIT ON/OFF
290
SWITCH TERMINAL BLOCK WITH
ROOM TEMP. THERMISTOR EARTH TERMINAL
(INSIDE) (INSIDE)
INTELLIGENT EYE SENSOR
TIMER LAMP GAS PIPE φ15.9 CuT DRAIN HOSE FOR VP13
HOME LEAVE LAMP (THE LENGTH OF PIPE OUTSIDE (CONNECTING PART
FRONT GRILLE FIXING SCREWS
FLAPS (INSIDE) THE UNIT : ABOUT 430) I.D. 14.0, O.D. 18.0)
(THE HOSE LENGTH OF
LIQUID PIPE φ6.4 CuT OUTSIDE THE UNIT :
SIGNAL (THE LENGTH OF PIPE OUTSIDE ABOUT 530)
TRANSMITTER THE UNIT : ABOUT 480)
58 18 1050
HORIZONTAL BLADE BLADE ANGLES
(AUTOMATIC) 893.5 52.5
30
14.5
COOLING DRY
155.5
163
290
10˚ 5˚
52
40˚ 10˚ 5˚
35˚
40˚ 35˚
WIRELESS REMOTE
52
FAN 60 WALL HOLE
VERTICAL BLADE (AUTOMATIC) 99.5
CONTROLLER φ80 HOLE
5˚ WALL HOLE FOR STANDARD LOCATIONS OF WALL HOLES
(ARC433B71) EMBEDDED PIPING
5˚ 50 ˚
50˚ φ80 HOLE 3D077937
55˚
55˚
FTXS25/35EVMV
PERFORMANCE)
THE MARK (→) SHOWS PIPING DIRECTION
(SPACE FOR
AIRFLOW (INDOOR)
30MIN.
REAR
800
LEFT RIGHT
( INCLUDING
MOUNTING PLATE ) 50MIN. 50MIN.
197 (SPACE FOR (SPACE FOR
REQUIRED SPACE
195 MAINTENANCE) MAINTENANCE)
SIGNAL RECEIVER
NAME PLATE
OPERATION LAMP
283
TIMER LAMP TERMINAL BLOCK
WITH EARTH
INTELLIGENT EYE LAMP
TERMINAL
INTELLIGENT EYE SENSOR
BOTTOM GAS PIPE 9.5Cut
INDOOR UNIT ON/OFF SWITCH (THE LENGTH OF PIPE OUTSIDE DRAIN HOSE
FRONT PANEL FIXED SCREWS (CONNECTING PART
ROOM TEMP. THERMISTOR (INSIDE) THE UNIT : ABOUT 390)
FLAPS (INSIDE) I.D. φ14
LIQUID PIPE 6.4CuT O.D. φ18
(THE LENGTH OF PIPE OUTSIDE
THE HOSE LENGTH OF OUTSIDE
THE UNIT : ABOUT 340) THE UNIT IS APPROX. 440)
SIGNAL TRANSMITTER
800
711 49
13
17
58 18 BLADE ANGLE
UP/DOWN (AUTOMATIC)
DAIKIN
180
COOLING, DRY HEATING FAN
283
44.5
163
10˚ 5˚
44.5
60 110
WALL HOLE FOR EMBEDDED PIPING
50˚ 30˚
φ65 HOLE
70˚ WALL HOLE
65˚
STANDARD LOCATIONS OF WALL HOLES φ65 HOLE
WIRELESS REMOTE CONTROLLER RIGHT/LEFT (MANUAL)
(ARC433B46)
45˚ 3D077894
45˚
FTXS50/60FVMV
AIRFLOW (INDOOR)
PERFORMANCE)
(FOR PERFORMANCE AND MAINTENANCE)
THE MARK (→) SHOWS PIPING DIRECTION
(SPACE FOR
REAR REAR
MIN.30
1050
LEFT RIGHT
(SPACE FOR
MAINTENANCE)
MIN.50 MIN.50
(SPACE FOR
( INCLUDING
INSTALLATION PLATE ) REQUIRED SPACE MAINTENANCE)
240
238
OPERATION LAMP
MODEL NAME
SIGNAL RECEIVER
PLATE
INDOOR UNIT ON/OFF
290
58 18 1050
HORIZONTAL BLADE BLADE ANGLES
(AUTOMATIC) 893.5 52.5
30
14.5
290
10˚ 5˚
52
15˚
40˚ 10˚ 5˚
15˚ 35˚
40˚ 55˚ 35˚
55˚
WIRELESS REMOTE
52
FTXS71FVMV
PERFORMANCE)
AIR FLOW (INDOOR)
(FOR PERFORMANCE AND MAINTENANCE)
(SPACE FOR
THE MARK (→) SHOWS PIPING DIRECTION
MIN. 30
REAR 1050 REAR
LEFT RIGHT
(SPACE FOR
MAINTENANCE)
MIN. 50 MIN. 50
(SPACE FOR
( INCLUDING
INSTALLATION PLATE ) REQUIRED SPACE MAINTENANCE)
240
238
OPERATION LAMP
SIGNAL RECEIVER MODEL NAME
PLATE
INDOOR UNIT ON/OFF
290
SWITCH TERMINAL BLOCK WITH
ROOM TEMP. THERMISTOR EARTH TERMINAL
(INSIDE) (INSIDE)
INTELLIGENT EYE SENSOR
TIMER LAMP GAS PIPE φ15.9 CuT DRAIN HOSE FOR VP13
FRONT GRILLE FIXING SCREWS HOME LEAVE LAMP (THE LENGTH OF PIPE OUTSIDE (CONNECTING PART I.D.
FLAPS (INSIDE) THE UNIT : ABOUT 430) 14.0, O.D. 18.0)
(THE HOSE LENGTH OF
LIQUID PIPE φ6.4 CuT
(THE LENGTH OF PIPE OUTSIDE OUTSIDE THE UNIT :
SIGNAL ABOUT 530)
TRANSMITTER THE UNIT : ABOUT 480)
58 18 1050
BLADE ANGLES
HORIZONTAL BLADE 893.5 52.5
30
(AUTOMATIC)
14.5
COOLING HEATING DRY
155.5
163
290
10˚ 5˚
52
15˚
40˚ 10˚ 5˚
15˚ 35˚
40˚ 55˚ 35˚
55˚
WIRELESS REMOTE FAN WALL HOLE
52
VERTICAL BLADE (AUTOMATIC) 60 99.5
CONTROLLER φ80 HOLE
5˚ WALL HOLE FOR STANDARD LOCATIONS OF WALL HOLES
(ARC433B70)
EMBEDDED PIPING
50˚
5˚ 50˚ φ80 HOLE 3D077942
55˚
55˚
RK(X)S25/35EBVMV
150
(I.Dφ15.9 HOSE FOR CONNECTION) (M8 OR M10)
574 105.5
490
13
100
150
29.5
50 50
300
50
311
50
100
HANDLE BRAND NAME LABEL
285 8 12 765 63
OUTDOOR AIR THERMISTOR
MANUFACTURE'S
LIQUID
LABEL
STOP VALVE
(φ6.4CuT)
WIRING
INLET
550
SERVICE
PORT
165
105
196 22
IN CASE OF REMOVING
STOP VALVE COVER GAS STOP VALVE
(φ9.5CuT)
3D077982
RK(X)S50/60FVMV
825 78 100
325
100
350
124 580
2
50 50
36
350
50
350
330
300
100
350
IN CASE OF REMOVING
10
25
89 64
3D077994
RK(X)S71FVMV
100
350
102 71
(345~355)
320
350
380
100
50 50
117
100
30
30
350
350
45 376 191
DRAIN OUTLET
I. D.φ25 HOSE FOR CONNECTION. 50
410
126
GAS PIPE
90
50
3D078005
5. Wiring Diagrams
5.1 Indoor Unit
FTK(X)S25/35EVMV
FG
F1U
H1P~H3P
M1F
M1S
PCB1~PCB4
R1T, R2T
S1~S36
S1W
X1M
3D078575
FTK(X)S50/60/71FVMV
FG
Fu
H1~H3
H1P~H3P
M1F
M1S, M2S
PCB1~PCB5
R1T, R2T
S1~S38
S1W
X1M
3D078576A
RK(X)S25/35EBVMV
C74, C75
C94, C95, C100
DB1, DB2
FU1, FU2, FU3
IC11 N SA1
IPM1 PCB1, PCB2 V1, V2, V3
L Q1L X1M
L1 R1T, R2T, R3T, R12T Y1E
L1R S10, S11, S20 Y1R
M1C S30, S40, S70 Z1C, Z2C
M1F S80, S80, S91
MRCW, MRM10,MRM20 HC3, HC4, HL3, HN3
3D078579
RK(X)S50/60FVMV
3D078580
RKS71FVMV
Z1C~Z7C
X1M, X2M MRM10, MRM20 L M1C
Y1E MRC/W N M1F
V2, V3, V5, V9, V100 R1T~R3T SW1 L1R
SA2 S2~S102 SW4 Q1L
FU1, FU2, FU3 LEDA PM1
AC1, AC2 PCB1, 2
U,V, W, X11A, X12A
E1, E2
HR1, HR2
3D078584B
RXS71FVMV
Z1C~Z7C
X1M, X2M MRM10, MRM20 L M1C
Y1E MRC/W N M1F
V2, V3, V5, V9, V100 R1T~R3T SW1 L1R
SA2 S2~S102 SW4 Q1L
FU1, FU2, FU3 LEDA PM1
AC1, AC2 PCB1, 2
U, V, W, X11A, X12A Y1R
E1, E2
HR1, HR2
3D078581B
6. Piping Diagrams
6.1 Indoor Unit
6.1.1 Cooling Only
FTKS25/35EVMV FTKS50/60FVMV
ON HEAT EXCH.
6.4CuT
THERMISTOR
ON HEAT EXCH.
CROSS FLOW FAN
FIELD PIPING
CROSS FLOW FAN
(6.4CuT) FIELD PIPING
M
(6.4CuT) M
FAN MOTOR
FAN MOTOR
FIELD PIPING
FIELD PIPING 9.5CuT
(12.7CuT) (12.7CuT)
(9.5CuT)
4D078462 4D077924
FTKS71FVMV
INDOOR UNIT
(7.9CuT)
HEAT EXCHANGER
THERMISTOR
ON HEAT EXCH.
REFRIGERANT FLOW
COOLING
4D077936
FTXS25/35EVMV FTXS50/60FVMV
INDOOR UNIT
INDOOR UNIT
MUFFLER ASSY HEAT EXCHANGER
7.0CuT
6.4CuT (7.9CuT)
THERMISTOR 6.4CuT
HEAT EXCHANGER
7.9CuT
ON HEAT EXCH.
6.4CuT
THERMISTOR
ON HEAT EXCH.
CROSS FLOW FAN
FIELD PIPING
CROSS FLOW FAN
(6.4CuT) FIELD PIPING
M
(6.4CuT) M
FAN MOTOR
FAN MOTOR
9.5CuT FIELD PIPING
FIELD PIPING
(12.7CuT) (12.7CuT)
(9.5CuT)
4D078439 4D077898
FTXS71FVMV
INDOOR UNIT
(7.9CuT)
HEAT EXCHANGER
THERMISTOR
ON HEAT EXCH.
REFRIGERANT FLOW
COOLING
HEATING
4D077941
RKS25/35EBVMV
OUTDOOR UNIT
OUTDOOR TEMPERATURE
7.0CuT HEAT EXCHANGER THERMISTOR
9.5CuT
7.0CuT
HEAT EXCHANGER
THERMISTOR MOTOR OPERATED
VALVE
4.8CuT
6.4CuT 6.4CuT
4.8CuTMUFFLER MUFFLER
φ.4.0xID.2.0CuT
M WITH WITH
FILTER FILTER
PROPELLER FAN
9.5CuT
9.5CuT MUFFLER
WITH
FILTER
6.4CuT
FOUR WAY
VALVE
7.9CuT
9.5CuT
3D078123
RKS50/60FVMV
OUTDOOR UNIT
7.9CuT HEAT EXCHANGER OUTDOOR TEMPERATURE
7.9CuT THERMISTOR
7.9CuT
7.9CuT
12.7CuT 7.9CuT CAPILLARY TUBE 1
7.9CuT 7.9CuT 4.0CuT MUFFLER
7.9CuT 7.9CuT 4.0CuT WITH
REFRIGERANT FLOW
CAPILLARY TUBE 2 FILTER
7.9CuT 6.4CuT COOLING
CAPILLARY TUBE 3
6.4CuT
4.0CuT
HEAT 4.0CuT
EXCHANGER
THERMISTOR CAPILLARY TUBE 4
M
6.4CuT
PROPELLER FAN
12.7CuT
ELECTRONIC
EV
EXPANSION
VALVE
12.7CuT 12.7CuT
MUFFLER
WITH FILTER
FOUR WAY
7.9CuT
VALVE
12.7CuT
NORMALLY : OFF
MUFFLER MUFFLER FIELD PIPING
6.4CuT (6.4 CuT)
LIQUID
7.9CuT
3D078132
RKS71FVMV
OUTDOOR UNIT
HEAT EXCHANGER
OUTDOOR TEMPERATURE
7.9CuT THERMISTOR
7.9CuT
HEADER
7.9CuT
7.9CuT
7.9CuT
12.7CuT
7.9CuT
7.9CuT HEAT EXCHANGER (CONDENSER)
7.9CuT THERMISTOR
RECEIVER
4.0CuT
7.9CuT 9.5CuT 9.5CuT 9.5CuT EV 9.5CuT 9.5CuT
9.5CuT
DISTRIBUTOR FILTER MOTOR FILTER
DC FAN MOTOR M OPERATED
CAPILLARY TUBE VALVE
PROPELLER FAN
STOP VALVE
LIQUID LINE
4-WAY
VALVE
15.9CuT NORMALLY : OFF 15.9CuT
9.5CuT
7.9CuT
7.9CuT
MUFFLER
15.9CuT
15.9CuT
FIELD PIPING
9.5CuT LIQUID (6.4 CuT)
7.9CuT
GAS LINE
REFRIGERANT FLOW ACCUMULATOR STOP VALVE
COOLING COMPRESSOR ACCUMULATOR FIELD PIPING
15.9CuT 15.9CuT GAS (15.9 CuT)
3D078133
RXS25/35EBVMV
OUTDOOR UNIT
OUTDOOR TEMPERATURE
7.0CuT HEAT EXCHANGER THERMISTOR
9.5CuT
7.0CuT
φ.4.0xID.2.0CuT
4.8CuT MUFFLER MUFFLER
M WITH WITH
FILTER FILTER
PROPELLER FAN
9.5CuT
9.5CuT MUFFLER
WITH
FILTER
6.4CuT
FOUR WAY
7.9CuT
9.5CuT
FIELD PIPING
VALVE
(6.4CuT)
ON : HEATING LIQUID STOP
VALVE
MUFFLER
DISCHARGE PIPE
THERMISTOR
7.9CuT
3D078991
RXS50/60FVMV
OUTDOOR UNIT
7.9CuT HEAT EXCHANGER OUTDOOR TEMPERATURE
7.9CuT THERMISTOR
7.9CuT
7.9CuT
12.7CuT 7.9CuT CAPILLARY TUBE 1
7.9CuT 7.9CuT 4.0CuT MUFFLER
7.9CuT 7.9CuT 4.0CuT WITH
REFRIGERANT FLOW
7.9CuT CAPILLARY TUBE 2 6.4CuT FILTER COOLING
CAPILLARY TUBE 3
6.4CuT 6.4CuT
4.0CuT HEATING
HEAT 4.0CuT
EXCHANGER
THERMISTOR CAPILLARY TUBE 4
M ELECTRONIC
EV
12.7CuT FILTER
6.4CuT
12.7CuT 9.5CuT
12.7CuT
LIQUID
STOP VALVE
MUFFLER
7.9CuT
12.7CuT FIELD PIPING
DISCHARGE PIPE (12.7 CuT)
THERMISTOR GAS STOP VALVE
COMPRESSOR WITH SERVICE PORT
3D078127
RXS71FVMV
OUTDOOR UNIT
HEAT EXCHANGER
OUTDOOR TEMPERATURE
7.9CuT THERMISTOR
HEADER 7.9CuT
7.9CuT
7.9CuT
7.9CuT
12.7CuT
7.9CuT
7.9CuT HEAT EXCHANGER (CONDENSER)
7.9CuT THERMISTOR ELECTRONIC
EXPANSION RECEIVER
4.0CuT VALVE
7.9CuT EV
9.5CuT 9.5CuT 9.5CuT 9.5CuT 9.5CuT
9.5CuT
DISTRIBUTOR FILTER FILTER
DC FAN MOTOR M
CAPILLARY TUBE
PROPELLER FAN
STOP VALVE
LIQUID LINE
4-WAY
VALVE
15.9CuT ON : HEATING 15.9CuT
9.5CuT
7.9CuT
7.9CuT
MUFFLER FIELD PIPING
15.9CuT
15.9CuT
7.9CuT
GAS LINE
ACCUMULATOR STOP VALVE
REFRIGERANT FLOW
COOLING COMPRESSOR ACCUMULATOR FIELD PIPING
HEATING 15.9CuT 15.9CuT GAS (15.9CuT)
3D078128
7. Capacity Tables
7.1 Cooling Only
Symbols: Note:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. Capacities are based on the following conditions.
BF : Bypass factor Corresponding refrigerant piping length : 7.5 m
EWB : Entering wet bulb temp. (°C) Level difference : 0 m
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D078211
Symbols: Note:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. Capacities are based on the following conditions.
BF : Bypass factor Corresponding refrigerant piping length : 7.5 m
EWB : Entering wet bulb temp. (°C) Level difference : 0 m
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D078210
Symbols: Note:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. Capacities are based on the following conditions.
BF : Bypass factor Corresponding refrigerant piping length : 7.5 m
EWB : Entering wet bulb temp. (°C) Level difference : 0 m
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D078717
Symbols: Note:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. Capacities are based on the following conditions.
BF : Bypass factor Corresponding refrigerant piping length : 7.5 m
EWB : Entering wet bulb temp. (°C) Level difference : 0 m
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D078718
Symbols: Note:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. Capacities are based on the following conditions.
BF : Bypass factor Corresponding refrigerant piping length : 7.5 m
EWB : Entering wet bulb temp. (°C) Level difference : 0 m
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D078223
AFR 8.7
BF 0.24
Heating
AFR 9.4
Symbols: Note:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. Capacities are based on the following conditions.
BF : Bypass factor Corresponding refrigerant piping length : 7.5 m
EWB : Entering wet bulb temp. (°C) Level difference : 0 m
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D078712A
AFR 8.9
BF 0.24
Heating
AFR 9.7
Symbols: Note:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. Capacities are based on the following conditions.
BF : Bypass factor Corresponding refrigerant piping length : 7.5 m
EWB : Entering wet bulb temp. (°C) Level difference : 0 m
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D078711A
AFR 14.7
BF 0.18
Heating
AFR 16.2
Symbols: Note:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. Capacities are based on the following conditions.
BF : Bypass factor Corresponding refrigerant piping length : 7.5 m
EWB : Entering wet bulb temp. (°C) Level difference : 0 m
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D078163
AFR 16.2
BF 0.28
Heating
AFR 17.4
Symbols: Note:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. Capacities are based on the following conditions.
BF : Bypass factor Corresponding refrigerant piping length : 7.5 m
EWB : Entering wet bulb temp. (°C) Level difference : 0 m
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D078164
AFR 17.4
BF 0.27
Heating
AFR 21.5
Symbols: Note:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. Capacities are based on the following conditions.
BF : Bypass factor Corresponding refrigerant piping length : 7.5 m
EWB : Entering wet bulb temp. (°C) Level difference : 0 m
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D078169
1
Capacity correction factor
0.9
5 10 15 20
7.3.2 50 Class
R-410A (50 Class)
1
Capacity correction factor
0.9
0.8
Range of the Refrigerant Additional Charge
5 10 15 20 25 30
1
Capacity correction factor
0.9
0.8
Range of the Refrigerant Additional Charge
5 10 15 20 25 30
Note: The graphs show the factor when additional refrigerant of the proper quantity is charged.
8. Operation Limit
8.1 Cooling Only
RKS25/35EBVMV
50
46
40
Continuous operation
Pull-down period
30
20
10
10 14 20 23 28 30
Indoor temp. (˚CWB)
Notes :
The graph is based
on the following conditions.
• Equivalent piping length 7.5m
• Level difference 0m
• Air flow rate High
4D078144
RKS50/60/71FVMV
50
46
40
Outdoor temp. (˚CDB)
Continuous operation
Pull-down period
30
20
10
10 14 20 23 28 30
Indoor temp. (˚CWB)
Notes :
The graph is based
on the following conditions.
• Equivalent piping length 7.5m
• Level difference 0m
• Air flow rate High
4D078148
RXS25/35EBVMV
Cooling Heating
20
15
50
46 10
Outdoor temp. (˚CDB)
40
Continuous operation
5
Pull-down period
30
0
20
-5
10
-10
10 14 20 23 28 30
Indoor temp. (˚CWB) -15
(-15˚CDB)
Notes :
The graphs are based 10 20 30
on the following conditions. Indoor temp. (˚CDB)
• Equivalent piping length 7.5m
• Level difference 0m
• Air flow rate High 3D078142
RXS50/60/71FVMV
Cooling 20 Heating
50
18
46
15
40
Continuous operation
10
Pull-down period
30
Outdoor temp. (˚CDB)
5
20
Continuous operation
0
10
-5
0
-10
-10
-15
(-15˚CDB)
10 14 20 23 28 30
Indoor temp. (˚CWB) 10 20 30
Notes :
Indoor temp. (˚CDB)
The graphs are based
on the following conditions.
• Equivalent piping length 7.5m
• Level difference 0m
3D078146
• Air flow rate High
9. Sound Level
9.1 Measuring Location
1m
1m
0.8 m
(R1759) (R1003)
FTKS25EVMV FTKS35EVMV
dB (0dB=0.0002µ bar)
50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60 Hz POWER SOURCE 220-240/220-230V 50/60 Hz
20 APPROXIMATE 20 APPROXIMATE
THRESHOLD HEARING NC-20 THRESHOLD HEARING NC-20
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D077918 63 125 250 500 1000 2000 4000 8000 4D077921
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
FTKS50FVMV FTKS60FVMV
dB (0dB=0.0002µ bar)
50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60 Hz POWER SOURCE 220-240/220-230V 50/60 Hz
20 APPROXIMATE 20 APPROXIMATE
THRESHOLD HEARING NC-20 THRESHOLD HEARING NC-20
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D077929 63 125 250 500 1000 2000 4000 8000 4D077931
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
FTKS71FVMV
60 (H) (L)
NC-60
A 46 37
(B.G.N IS ALREADY RECTIFIED)
dB (0dB=0.0002µ bar)
50
NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60 Hz
40 JIS STANDARD
NC-40 STANDARD EXTERNAL STATIC PRESSURE
50/60Hz 220-240/220-230V (H)
20 APPROXIMATE
THRESHOLD HEARING NC-20
FOR CONTINUOUS
NOISE
63 125 250 500 1000 2000 4000 8000 4D077938
OCTAVE BAND CENTER FREQUENCY (Hz)
FTXS25EVMV
COOLING HEATING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
dB (0dB=0.0002µ bar)
50 50
dB (0dB=0.0002µ bar)
NC-50 NC-50
OPERATING CONDITIONS OPERATING CONDITIONS
40 POWER SOURCE 220-240/220-230V 50/60Hz 40 POWER SOURCE 220-240/220-230V 50/60Hz
NC-40 JIS STANDARD NC-40 JIS STANDARD
STANDARD EXTERNAL STATIC PRESSURE STANDARD EXTERNAL STATIC PRESSURE
30 50/60Hz 220-240/220-230V (H) 30 50/60Hz 220-240/220-230V (H)
NC-30 NC-30
50/60Hz 220-240/220-230V (L) 50/60Hz 220-240/220-230V (L)
Cooling Heating
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING NC-20
FOR CONTINUOUS NC-20 FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 3D077896
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
FTXS35EVMV
COOLING HEATING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
dB (0dB=0.0002µ bar)
50 50
NC-50 NC-50
OPERATING CONDITIONS OPERATING CONDITIONS
FTXS50FVMV
COOLING HEATING
70 70
NC-70 OVER ALL (dB) NC-70 OVER ALL (dB)
dB (0dB=0.0002µ bar)
NC-50 NC-50
OPERATING CONDITIONS OPERATING CONDITIONS
40 POWER SOURCE 220-240/220-230V 50/60Hz 40 POWER SOURCE 220-240/220-230V 50/60Hz
NC-40 JIS STANDARD NC-40 JIS STANDARD
STANDARD EXTERNAL STATIC PRESSURE STANDARD EXTERNAL STATIC PRESSURE
30 50/60Hz 220-240/220-230V (H) 30 50/60Hz 220-240/220-230V (H)
NC-30
NC-30 50/60Hz 220-240/220-230V (L) 50/60Hz 220-240/220-230V (L)
Cooling Heating
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS NC-20 FOR CONTINUOUS NC-20
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 3D077900
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
FTXS60FVMV
COOLING HEATING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
50 50
NC-50 NC-50
OPERATING CONDITIONS OPERATING CONDITIONS
FTXS71FVMV
COOLING HEATING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
dB (0dB=0.0002µ bar)
50 50
NC-50 NC-50
OPERATING CONDITIONS OPERATING CONDITIONS
40 POWER SOURCE 220-240/220-230V 50/60Hz 40 POWER SOURCE 220-240/220-230V 50/60Hz
NC-40 JIS STANDARD NC-40 JIS STANDARD
STANDARD EXTERNAL STATIC PRESSURE STANDARD EXTERNAL STATIC PRESSURE
30 50/60Hz 220-240/220-230V (H) 30 50/60Hz 220-240/220-230V (H)
NC-30 50/60Hz 220-240/220-230V (L) NC-30 50/60Hz 220-240/220-230V (L)
Cooling Heating
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
NC-20 NC-20
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 3D077904
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
RKS25EBVMV RKS35EBVMV
dB (0dB=0.0002µ bar)
50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60 Hz POWER SOURCE 220-240/220-230V 50/60 Hz
20 APPROXIMATE 20 APPROXIMATE
THRESHOLD HEARING NC-20 THRESHOLD HEARING NC-20
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D078011 63 125 250 500 1000 2000 4000 8000 4D078598
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
RKS50FVMV RKS60FVMV
220-240/220-230V 220-240/220-230V
60 60
NC-60 A 47 NC-60 A 49
(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)
dB (0dB=0.0002µ bar)
dB (0dB=0.0002µ bar)
50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60 Hz POWER SOURCE 220-240/220-230V 50/60 Hz
20 APPROXIMATE 20 APPROXIMATE
THRESHOLD HEARING NC-20 THRESHOLD HEARING NC-20
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D078020 63 125 250 500 1000 2000 4000 8000 4D078038
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
RKS71FVMV
COOLING
70 OVER ALL (dB)
NC-70
50/60Hz
SCALE
OCTAVE BAND SOUND PRESSURE LEVEL
220-240/220-230V
60
NC-60 A 52
(B.G.N IS ALREADY RECTIFIED)
dB (0dB=0.0002µ bar)
50
NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60 Hz
40 JIS STANDARD
NC-40
STANDARD EXTERNAL STATIC PRESSURE
50/60Hz 220-240/220-230V
30 NC-30 Cooling
20 APPROXIMATE
THRESHOLD HEARING NC-20
FOR CONTINUOUS
NOISE
63 125 250 500 1000 2000 4000 8000 4D078111
OCTAVE BAND CENTER FREQUENCY (Hz)
RXS25EBVMV
COOLING HEATING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
50/60Hz 50/60Hz
60 SCALE 60 SCALE
220-240/220-230V 220-240/220-230V
NC-60 NC-60
A 46 A 47
(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)
dB (0dB=0.0002µ bar)
50 50
dB (0dB=0.0002µ bar)
NC-50 NC-50
OPERATING CONDITIONS OPERATING CONDITIONS
40 POWER SOURCE 220-240/220-230V 50/60Hz 40 POWER SOURCE 220-240/220-230V 50/60Hz
NC-40 JIS STANDARD NC-40 JIS STANDARD
STANDARD EXTERNAL STATIC PRESSURE STANDARD EXTERNAL STATIC PRESSURE
30 50/60Hz 220-240/220-230V 30 50/60Hz 220-240/220-230V
NC-30 Cooling NC-30 Heating
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS NC-20 FOR CONTINUOUS NC-20
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 3D078008
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
RXS35EBVMV
COOLING HEATING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
50/60Hz 50/60Hz
OCTAVE BAND SOUND PRESSURE LEVEL
OCTAVE BAND SOUND PRESSURE LEVEL
60 SCALE 60 SCALE
220-240/220-230V 220-240/220-230V
NC-60 NC-60
A 47 A 48
(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)
dB (0dB=0.0002µ bar)
50 50
dB (0dB=0.0002µ bar)
NC-50 NC-50
OPERATING CONDITIONS OPERATING CONDITIONS
40 POWER SOURCE 220-240/220-230V 50/60Hz 40 POWER SOURCE 220-240/220-230V 50/60Hz
NC-40 JIS STANDARD NC-40 JIS STANDARD
STANDARD EXTERNAL STATIC PRESSURE STANDARD EXTERNAL STATIC PRESSURE
30 50/60Hz 220-240/220-230V 30 50/60Hz 220-240/220-230V
NC-30 Cooling NC-30 Heating
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS NC-20 FOR CONTINUOUS NC-20
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 3D078009
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
RXS50FVMV
COOLING HEATING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
50/60Hz 50/60Hz
OCTAVE BAND SOUND PRESSURE LEVEL
OCTAVE BAND SOUND PRESSURE LEVEL
60 SCALE 60 SCALE
220-240/220-230V 220-240/220-230V
NC-60 NC-60
A 47 A 48
(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)
dB (0dB=0.0002µ bar)
50 50
dB (0dB=0.0002µ bar)
NC-50 NC-50
OPERATING CONDITIONS OPERATING CONDITIONS
40 POWER SOURCE 220-240/220-230V 50/60Hz 40 POWER SOURCE 220-240/220-230V 50/60Hz
NC-40 JIS STANDARD NC-40 JIS STANDARD
STANDARD EXTERNAL STATIC PRESSURE STANDARD EXTERNAL STATIC PRESSURE
30 50/60Hz 220-240/220-230V 30 50/60Hz 220-240/220-230V
NC-30 Cooling NC-30 Heating
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS NC-20 FOR CONTINUOUS NC-20
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 3D078015
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
RXS60FVMV
COOLING HEATING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
50/60Hz 50/60Hz
OCTAVE BAND SOUND PRESSURE LEVEL
OCTAVE BAND SOUND PRESSURE LEVEL
60 SCALE 60 SCALE
220-240/220-230V 220-240/220-230V
NC-60 NC-60
A 49 A 49
(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)
dB (0dB=0.0002µ bar)
50 50
dB (0dB=0.0002µ bar)
NC-50 NC-50
OPERATING CONDITIONS OPERATING CONDITIONS
40 POWER SOURCE 220-240/220-230V 50/60Hz 40 POWER SOURCE 220-240/220-230V 50/60Hz
NC-40 NC-40
JIS STANDARD JIS STANDARD
STANDARD EXTERNAL STATIC PRESSURE STANDARD EXTERNAL STATIC PRESSURE
30 50/60Hz 220-240/220-230V 30 50/60Hz 220-240/220-230V
NC-30 Cooling NC-30 Heating
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
NC-20 FOR CONTINUOUS NC-20
FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 3D078016
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
RXS71FVMV
COOLING HEATING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
50/60Hz 50/60Hz
60 SCALE 60 SCALE
220-240/220-230V 220-240/220-230V
NC-60 NC-60
A 52 A 52
(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)
dB (0dB=0.0002µ bar)
50 50
dB (0dB=0.0002µ bar)
NC-50 NC-50
OPERATING CONDITIONS OPERATING CONDITIONS
40 POWER SOURCE 220-240/220-230V 50/60Hz 40 POWER SOURCE 220-240/220-230V 50/60Hz
NC-40 JIS STANDARD NC-40 JIS STANDARD
STANDARD EXTERNAL STATIC PRESSURE STANDARD EXTERNAL STATIC PRESSURE
30 50/60Hz 220-240/220-230V 30 50/60Hz 220-240/220-230V
NC-30 Cooling NC-30 Heating
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS NC-20 FOR CONTINUOUS NC-20
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 3D078017
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
Symbols: Note:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB
MFA : Max. fuse amps (A) Outdoor temp. 35°CDB.
RHz : Rated operating frequency (Hz) 2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the value of MCA.
RLA : Rated load amps (A) 4. Instead of fuse, use circuit breaker.
OFM : Outdoor fan motor 5. Be sure to install an earth leak detector. (One that can handle
higher harmonics.)
IFM : Indoor fan motor (This unit uses an inverter, which means that it must be used an
W : Fan motor rated output (W) earth leak detector capable handling high harmonics in order to
prevent malfunctioning of the earth leak detector itself.)
FLA : Full load amps (A)
3D078197
3D078199
3D078203A
3D078204A
3PN14832-8A
3PN14832-10A
11.1.4 71 Class
3PN14832-12A
3PN14832-9A
Van
cao Æp
3PN14832-11A
11.2.4 71 Class
3PN14832-13A
3PN14831-3A
C: 3PN14831-4A
12.4 71 Class
3PN14831-5A
Note: +1 A wiring adaptor (KRP413AB1S) is also required for each indoor unit.
+2 Timer clock and other devices ; obtained locally.
+3 An interface adaptor (KRP928BB2S) is also required for each indoor unit.
+4 Standard accessory
+ Standard accessory
3P248024-2
3P248024-1C
#ONNECTION TO 2EMOTE #ONTROL 0# BOARD
2EMOVAL OF UPPER (! CASING
① )NSERT A FLAT
BLADE SCREWDRIVER INTO 5PPER (! CASING
THE GROOVE BETWEEN THE UPPER
AND LOWER CASINGS
&LAT
BLADE
SCREWDRIVER
3ECURING OF LOWER (! CASING
-OUNT AND SECURE THE LOWER (!
CASING DIRECTLY ON THE WALL WITH THE -OUNT THE (! CASING IN A DIRECTION WHERE THE
PROVIDED SCREWS INSERTED INTO THE WIRING THROUGH
HOLES WILL BE HIDDEN IN ORDER TO
SCREW HOLES A ROUND HOLE AND TWO ./4% PREVENT INFANTS FROM PUTTING THEIR FINGERS INTO
ELLIPSE HOLES OF THE CASING THE (! CASING AND THE ,%$ LIGHT ON THE INTERNAL
0# BOARD FROM LEAKING OUTSIDE
#ONNECTION OF WIRING
#ONNECT THE WIRING TO THE
CONNECTOR TERMINALS
7IRING
,OWER (! CASING ,OWER (! CASING
&IXATION OF WIRING
① )NSERT THE PROVIDED BINDING BAND UNDER THE PILLAR OF THE (! ② )NSERT THE SECOND BINDING BAND INTO THE GROOVE ON THE
CASING AND SECURE THE COVERS OF THE WIRING WITH THE SIDE OF THE (! CASING AND FIX THE WIRING SECURELY SO THAT
BINDING BAND THE WIRING WILL NOT BE DISCONNECTED
0ILLAR
"INDING
"INDING BAND BAND
! LARGE NUMBER OF WIRES
-AKE A SLIT WITH AN APPROPRIATE TOOL SUCH AS A CUTTER 3LIT
KNIFE ON THE THIN PART OF THE UPPER (! CASING ALONG 5PPER (! CASING
THE FRAME 4HEN CUT THE PART WITH AN APPROPRIATE TOOL
SUCH AS A PAIR OF NIPPERS
./4% #UT OFF ONLY THE THIN PART REQUIRED FOR WIRING 4HIN PART
&INISHING
-OUNT THE UPPER (! CASING TO THE ORIGINAL 7HEN THE CONTACT INPUT DEVICE SUCH AS CARD KEYS AND
POSITION CENTRAL CONTROLLER ARE USED IN TANDEM
(OOK THE TAB
0RESS THE LOWER
%VEN WHEN THE OPERATING MODE OF THE 3 PIN IS SET TO PROHIBIT
TO THE LOWER
(! CASING PART OF THE UPPER ALL REMOTE CONTROLLER ACTIONS RUNSTOP OPERATION FROM THE CENTRAL
(! CASING AND CONTROLLER IS POSSIBLE 4HE OPERATION ALSO STARTS WHEN THE POWER
7IRING
PRESS FIT IT ONTO THE )NFORMATION /. TIMER OF THE INDOOR UNIT IS UP WHILE ALL REMOTE CONTROLLER
LOWER (! CASING
ACTIONS ARE PROHIBITED )N THIS CASE STOP THE OPERATION FROM THE
0RESS THE UPPER
(! CASING
CENTRAL CONTROLLER
PRECISELY UNTIL A &OR THE COMPATIBLE MODELS OF THE +2# SERIES¯ REMOTE
,OWER (! CASING CLICKING SOUND IS CONTROLLER THE OPERATION CAN BE PROHIBITED BY USING THE REMOTE
HEARD CONTROLLER IN TANDEM WITH THE CENTRAL CONTROLLER
3P248024-3C
Shape
With 4 screws
Quantity 1piece 1piece
Q Installation Procedure
Selection of Installation Location
Use when installing in a location that meets the following conditions.
zWhen installing near the border to a neighbor's house
zIf exhaust blows directly on passers-by because outdoor unit is installed facing a road.
zChanging the fan direction of the outdoor unit to prevent it blowing directly on shrubbery, etc.
4P104499-1A
Before installation
Check the following parts Name Louver Truss tapping screw Installation manual
Shape
M4×4screws(max.7.5kW class)
Quantity 1piece M5×4screws(8.0/9.0kW class)
1piece
Installation Procedure
Selection of Installation Location Space Needed for Installation
Use when installing in a location that meets the following conditions. O A minimum of 100mm is needed
O When installing near the border to a neighbor's house between the back of the outdoor
O If exhaust blows directly on passers-by because outdoor unit is instal- unit and any obstructions
led facing a road. (walls, etc.) 100
t han
O If exhaust blows directly on vegetation
m ore
Installation of Louvers
Caution
Attach the louvers overlapping the standard grille.
Installing the louvers without the grille would allow hands to enter the fan area,
which is dangerous, so be sure to install the standard grille.
(2) Install the louver pointed up. (2) Install the louver pointed down.
O Overlap the standard grille and O Overlap the standard grille and
screw both in together. screw both in together.
O The attachment screws O The attachment screws
are in the louvers. are in the louvers.
3P089958-2C
3P089958-1B
Organization: Organization:
DAIKIN INDUSTRIES, LTD. DAIKIN INDUSTRIES
AIR CONDITIONING MANUFACTURING DIVISION (THAILAND) LTD. All of the Daikin Group’s business
Scope of Registration: facilities and subsidiaries in Japan
Scope of Registration: are certified under the ISO 14001
THE DESIGN/DEVELOPMENT AND MANUFACTURE OF THE DESIGN/DEVELOPMENT
COMMERCIAL AIR CONDITIONING, HEATING, COOLING, international standard for
AND MANUFACTURE OF AIR environment management.
REFRIGERATING EQUIPMENT, HEATING EQUIPMENT, CONDITIONERS AND THE
RESIDENTIAL AIR CONDITIONING EQUIPMENT, HEAT COMPONENTS INCLUDING
RECLAIM VENTILATION, AIR CLEANING EQUIPMENT, COMPRESSORS USED FOR THEM
JMI-0107 JQA-1452
COMPRESSORS AND VALVES.
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
c All rights reserved
Specifications, designs and other content appearing in this brochure are current as of August 2012 but subject to change without notice.
EDVN041207
08/12 AK.B