Beruflich Dokumente
Kultur Dokumente
Operating Manual
For
Feeder Protection Relay
Note:
The features mentioned may not be a part of standard product. Product development is a continuous
process. Consequently the data indicated is subject to change without prior notice.
Please accept our thanks for giving us the privilege to serve you by choosing a CG make
‘Feeder Protection Relay’.
If this is your first CG Protection Relay, we hope it is the beginning of a long relationship
which delivers value to your organization. If you already own and use a CG product, we
are doubly honored by your decision of continuing this relationship.
It is our constant endeavor to partner you for the growth and success of your business.
This philosophy is reflected in our Mission statement “Smart Solutions. Strong
Relationships”. Please do give us feedback to help us realize our Mission.
This manual contains information concerning the Operation of the AEGIS Series Feeder
Protection Relay for the Switchgear Systems.
All relevant parts of the manual should be read prior to commencing installation.
The Relay must be commissioned by an engineer approved by the manufacturer (or his
agent) before being put into service. Failure to observe this condition will invalidate any
implied warranty.
The AEGIS Series Feeder Protection Relay has been designed for Industrial use only.
If you encounter any problem with the procedures contained in this manual you should
seek immediate assistance from Crompton Greaves Limited, Sales Office from whom the
equipment was purchased. Alternatively contact the Crompton Greaves Limited
Customer Service & Support department at the address shown below:
1. General 1
3. Relay Settings 16
4. Technical Data 54
4.1. Connections 54
4.1.1. Measuring Circuitry 54
4.1.2. Auxiliary Voltage 54
4.1.3. Binary Inputs 55
4.1.4. Binary Outputs 55
4.1.5. Local Serial Communication Port 55
4.1.6. Remote Control Connections 55
4.2. Test & Environmental Conditions 56
4.2.1. Type Test 56
4.2.2. Casing 57
4.2.3. Package 57
4.3. Protection Stages 58
4.3.1. Non Direction Current Protection Stage 58
4.3.2. Directional Current Protection Stage 61
4.3.3. Voltage Protection Stage 63
4.4. Circuit Breaker Failure Protection 64
4.5. Supporting Functions 65
4.6. Supervision Functions 66
5. Connections 67
6. Dimensions 75
7. Curves 76
8. Ordering Information 83
9. Customer Settings 84
10. Notes 92
PTFF Supervision
74TCS Trip Circuit Supervision
Three Phase Current
Neutral current
Sequence Components of Voltages & Currents
Phase to earth, Phase to Phase Voltage
Phase Angle
55 Power factor
Active, Reactive & Apparent Power
Energy Measurement
CB Wear
CB Control
Average & Maximum Demand measurement
2nd to 15th harmonic and THD of Voltages & Currents
Phasor diagram of Voltages & Currents
Frequency
Actual RMS value of Voltages & Currents
COMMUN
FUNCTIO
ICATION
IEC 60870-5-103
NS
IEC61850
It is assumed that everyone who will be associated with the equipment will be familiar
with the contents of that Safety Section, or this Safety Guide.
Proper and safe operation of the equipment depends on appropriate shipping and
handling, proper storage, installation and commissioning, and on careful operation,
maintenance and Servicing. For this reason only qualified personnel may work on or
operate the equipment.
The operating manual for the equipment gives instructions for its installation,
commissioning, and operation. However, the manual cannot cover all conceivable
circumstances or include detailed information on all topics. In the event of questions or
specific problems, do not take any action without proper authorization.
Any disassembly of the equipment may expose parts at hazardous voltage, also
electronic parts may be damaged if suitable electrostatic voltage discharge (ESD)
precautions are not taken.
If there is unlocked access to the rear of the equipment, care should be taken by all
personnel to avoid electric shock or energy hazards.
Voltage and current connections should be made using insulated crimp terminations to
ensure that terminal block insulation requirements are maintained for safety.
To ensure that wires are correctly terminated the correct crimp terminal and tool for the
wire size should be used.
Equipment use
If the equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Removal of the equipment front panel/cover may expose hazardous live parts which
must not be touched until the electrical power is removed.
The equipment should be operated within the specified electrical and environmental
limits.
Do not open the secondary circuit of a live CT since the high voltage produced may be
lethal to personnel and could damage insulation. Generally, for safety, the secondary of
the line CT must be shorted before opening any connections to it.
For most equipment with ring-terminal connections, the threaded terminal block for
current transformer termination has automatic CT shorting on removal of the module.
Therefore external shorting of the CTs may not be required; the equipment
documentation should be checked to see if this applies.
For equipment with pin-terminal connections, the threaded terminal block for current
transformer termination does NOT have automatic CT shorting on removal of the
module.
Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of
each part of the test, the voltage should be gradually reduced to zero, to discharge
capacitors, before the test leads are disconnected.
Modules and PCB cards must not be inserted into or withdrawn from the equipment
whilst it is energised, since this may result in damage.
Cleaning
The equipment may be cleaned using a lint free cloth dampened with clean water, when
no connections are energised.
The supply input (auxiliary) for the equipment may include capacitors across the supply
or to earth. To avoid electric shock or energy hazards, after completely isolating the
supplies to the equipment (both poles of any dc supply), the capacitors should be safely
discharged via the external terminals prior to decommissioning.
Disposal:
Electrostatic discharge
The relays use components that are sensitive to electrostatic discharges. The electronic
circuits are well protected by the metal case and the internal module should not be
withdrawn unnecessarily. When handling the module outside its case, care should be
taken to avoid contact with components and electrical connections. If removed from the
case for storage, the module should be placed in an electrically conducting antistatic bag.
There are no setting adjustments within the module and it is advised that it is not
unnecessarily disassembled. Although the printed circuit boards are plugged together, the
connectors are a Manufacturing aid and not intended for frequent dismantling; in fact
considerable effort may be required to separate them. Touching the printed circuit board
should be avoided, since complementary metal oxide semiconductors (CMOS) are used,
which can be damaged by static electricity discharged from the body.
The electronic circuits are completely safe from electrostatic discharge when housed in
the case. Do not expose them to risk of damage by withdrawing modules unnecessarily.
Each module incorporates the highest practicable protection for its semiconductor
devices. However, if it becomes necessary to withdraw a module, the following
precautions should be taken to preserve the high reliability and long life for which the
equipment has been designed and manufactured.
Before removing a module, ensure that you are at the same electrostatic potential as
the equipment by touching the case.
Handle the module by its front plate, frame or edges of the printed circuit board.
Avoid touching the electronic components, printed circuit track or connectors.
Do not pass the module to another person without first ensuring you are both at the
same electrostatic potential. Shaking hands achieves equipotential.
Place the module on an antistatic surface, or on a conducting surface which is at the
same potential as yourself.
Store or transport the module in a conductive bag.
If a wrist strap is not available you should maintain regular contact with the case to
prevent a build-up of static. Instrumentation which may be used for making
measurements should be earthed to the case whenever possible.
1.3.5. STORAGE
If relays are not to be installed immediately upon receipt they should be stored in a place
free from dust and moisture in their original cartons. Where de-humidifier bags have
been included in the packing they should be retained. The action of the de-humidifier
crystals will be impaired if the bag has been exposed to ambient conditions and may be
restored by gently heating the bag for about an hour, prior to replacing it in the carton.
Dust which collects on a carton may, on subsequent unpacking, find its way into the
relay; in damp conditions the carton and packing may become impregnated with
moisture and the dehumidifier will lose its efficiency.
The below figure 2.1-1 shows, as an example, the front panel of the AEGIS Series
Feeder Protection Relay and the location of the user interface elements for the local
control of Relay.
1 1
3 4
1. LED Indicators
2. 160x160 LCD Display
3. Keypad
4. USB Communication for PC
5. Model Number
Power
Alarm
Trip
Error
LED
Meaning Remarks
Indicator
Auxiliary power has been
Power Normal operation state
switched on
Indicates that any one of the Fault indication of the
Alarm Protection or Monitoring function Protection and Monitoring
has been picked up due to fault functions
Indicates that Protection,
Monitoring functions has been Refer fault record for type of
Trip
operated due to faults which are in faults
the enabled condition.
Indicates the internal faults of the For the particular error in the
Error
Relay Relay refer section 3.3
All the LEDs, Output Relays can be configured by using the menu‟s in the BI/BO
window.
1. If any protection function is operated and LEDs/Output Relays are Hand Reset, then
acknowledgement or Resetting is done by pressing the Esc( ) key in the keypad
2. We can activate or deactivate the LEDs/Output Relays by using the external Binary
Input.
AEGIS Feeder Relay is having the display 160*160 Graphical display. The purpose of
this display is to show the configuration and parameterization values of the relay.
Use the arrow keys UP ( ) and DOWN ( ) to move up and down in the main
Menu, that is on the left side of the display, the active main menu option is indicated
with a cursor. The options in the main menu are abbreviations
Ex: INFO (Information)
After any selection in the Main Menu, the possible navigating directions are indicated
on the top of the Display window by arrows (,)
The complete description of the selected menu is indicated on the top of Display
window(Ex: Information)
Backlight control
The display backlit is automatically switched OFF after 1 minute when left idle. It can
be switched on by pressing any key.
3 4
5 6
The Front port of the relay is a standard USB port provided for interfacing with PC. This
port is used for relay configuration, downloading fault, event and disturbance records.
The rear port is either a,
Standard RS-485 port
Ethernet port
This port is used for communication with standard SCADA master/client software‟s.
All the menu functions are based on the main menu/sub menu structure:
1. Use the arrow keys UP and DOWN to move up and down in the main menu.
2. To move to a sub menu, repeatedly push the RIGHT, LEFT key until the requested
submenu is shown as per the Indicated Arrows on the top of Display window
3. To move up and down in the Submenu use the UP and DOWN
4. At the any time to edit the value use the ENTER key, to increase or decrease the any
parameter value use UP and DOWN keys. Use the enter key for confirmations.
5. To cancel the settings at any time press the Esc key.
6. At any time to return to main Menu Press the Esc key.
Description of
Parameters in
Main Menu
Parameters
Submenus
Submenus
No. of
Information 2 Relay Description, Model No. and Serial No.
INFO Password 2 Setting Password and Default load password
Error 19 Internal faults in the Relay indication
Currents Primary 5
Voltages Primary(L-N) 5
Measured Values for the System Currents &
Currents Secondary 7
Voltages
Voltages Secondary(L-N) 7
Voltages Secondary(L-L) 3
MESR True RMS power L1 6
True RMS power L2 6 Power Calculation for the phase wise
True RMS power L3 6
Date & Time 2 Indication of Date and Time
Representation of System Voltages and Currents
Currents & Voltages
in Graphical Display
Harmonics IL1 -
Harmonics IL2 - Graphical representation of the Harmonics in the
Harmonics IL3 - Bar-Graph format & the Calculation of THD(%)
HRMN
Harmonics UL1 - by the Phase wise for the both Currents &
Harmonics UL2 - Voltages
Harmonics UL3 -
Last 10 faults can be stored by the Relay. Fault
description shows the Fault No, Date & time,
Magnitudes and Phase angles of the Fault
FL-R Fault Recorder 22
Currents and Voltages and also we can clear the
fault recorder by “CLEAR FAULT REC:NO”
command
Contains features for enabling/disabling , Pre &
DR Disturbance Recorder 4 Post fault conditions, sample rate & trigger
options for DR
CT/VT Setting 6 Primary and Secondary Settings for the CT,VT
REF, SEF Primary and Secondary Settings for
REF/SEF CT Setting 4
CONF the CT,VT
Breaker control settings i.e. Close ,trip and IRF
Configuration 2
BO etc
Description
Parameters
Parameters
Submenus
No. of
of
Parameters of the Over Current element by this
3I> OC settings 6 Menu i.e. Setting, TMS, Curve, DT and RST
DT can be set.
Parameters for the Instantaneous Over Current
3I>> OC Settings 4 element by this Menu i.e. Setting, Curve, DT
and RST DT can be set.
OC
This Setting allows the user to use the Relay as
Breaker failure Settings 2
a Breaker back up relay
LEDs & output Relays for the indication of
LED & S/W BI Settings 2
Over Current element can be set.
LEDs & output Relays for the Breaker failure
LED & S/W BI Settings 2
element can be set.
Io> E/F settings 6 Parameters of the Earth fault Current element
by this Menu i.e. Setting, TMS, Curve, DT and
RST DT can be set.
Io>> E/F Settings 4 Parameters of the Instantaneous Earth fault
EF
current element by this Menu i.e. Setting,
Curve, DT and RST DT can be set.
LED & S/W BI Settings 2 LEDs & output Relays for the indication of
Earth fault Current element can be set.
SEF Setting 4 Parameters of the SEF element by this Menu i.e.
Setting, Curve, DT and RST DT can be set.
SEF
LED & S/W BI Settings 2 LEDs & output Relays for the indication of SEF
element can be set.
REF Setting 4 Parameters of the REF element by this Menu
i.e. Setting, Curve, DT and RST DT can be set.
REF
LED & S/W BI Settings 2 LEDs & output Relays for the indication of
REF element can be set.
Directional 3I> Settings Parameters of the directional over current
11 element by this Menu i.e. Setting, TMS, Curve,
DT, RST DT, Directional angle, Polarization
can be set.
D-OC Directional 3I>> 4 Parameters of the Instantaneous directional over
Settings current element by this Menu i.e. Setting, TMS,
Curve, DT and RST DT can be set.
LED & S/W BI Settings 2 LEDs & output Relays for the indication of
Directional over current element can be set.
Directional Io> Settings 9 Parameters of the directional Earth fault Current
element by this Menu i.e. Setting, TMS, Curve,
DT, RST DT, Directional angle, Polarization
can be set.
Directional Io>> 4 Parameters of the Instantaneous directional
D-EF
Settings Earth fault current element by this Menu i.e.
Setting, TMS, Curve, DT and RST DT can be
set.
LED & S/W BI Settings 2 LEDs & output Relays for the indication of
Directional over current elements can be set.
Description
Parameters
Parameters
Submenus
No. of
of
3U> OV settings 6 Parameters of the Over voltage element by this
Menu i.e. Setting, TMS, Curve, DT and RST
DT can be set.
3U>> OV Settings 4 Parameters of the Instantaneous Over Voltage
OV
current element by this Menu i.e. Setting,
Curve, DT and RST DT can be set.
LED & S/W BI Settings 2 LEDs & output Relays for the indication of
Over Voltage element can be set.
3U> UV settings 8 Parameters of the under voltage element by this
Menu i.e. Setting, TMS, Curve, DT and RST
DT can be set.
3U>> UV Settings 6 Parameters of the Instantaneous under Voltage
UV
element by this Menu i.e. Setting, Curve, DT
and RST DT can be set.
LED & S/W BI Settings 2 LEDs & output Relays for the indication of
Over Voltage element can be set.
NDR Settings 6 Parameters of the NDR element by this Menu
i.e. Setting, Curve, DT and RST DT can be set.
NDR
LED & S/W BI Settings 2 LEDs & output Relays for the indication of
NDR element can be set.
Broken conductor 4 Parameters of the Broken element by this
Settings Menu i.e. Setting, DT and RST DT can be
BR.C set.
LED & S/W BI Settings 2 LEDs & output Relays for the indication of
Broken conductor element can be set.
Parameters
Parameters in
Submenus
Submenus
No. of
Inrush Current 11 This setting allows the user to set the
INRUSH Settings for the 2nd & parameters to block 2nd & 5th
5th Harmonic Blocking Harmonic blocking
CT Supervision 5 This setting allows the user to set CT
Settings Supervision parameter settings
CTSV LED & S/W BI 2 LEDs & output Relays for the
Settings indication of CTSV element can be
set.
VT Supervision 5 This setting allows the user to set VT
Settings Supervision parameter settings
VTFF LED & S/W BI 2 LEDs & output Relays for the
Settings indication of VTFF element can be
set.
Negative phase 6 Parameters of the I2> element by this
sequence over current Menu i.e. Setting, Curve, DT and
I2> Settings RST DT can be set.
LED & S/W BI 2 LEDs & output Relays for the
Settings indication of I2> element can be set.
ARCL Auto Recloser Settings 12 This Menu allows the user to set
Dead times, Reclaim times and no of
shots
THRM Thermal overload 3 Parameters of the THRM element by
settings this Menu i.e. Setting, DT and RST
DT can be set.
LED & S/W BI 2 LEDs & output Relays for the
Settings indication of THRM element can be
set.
RP Reverse power settings 5 Parameters of the RP element by this
Menu i.e. Setting, DT and RST DT
can be set.
LED & S/W BI 2 LEDs & output Relays for the
Settings indication of RP element can be set.
This menu allows the user to set type
Communication
COMM 6 of Protocol ,Baud rate, Parity, Relay
Settings
address, Period, Scaling etc.
This Menu allows the user to set the
External BIs, LED, Output Relays
Configuration, Out puts Operation,
BI-O BI-BO Settings 5
Binary Input action on the Protection
parameters. For the complete
description refer section 3.20
As you POWER ON the relay INFORMATION window will appear on the screen. It
will give the information about the Relay‟s Type, Version, Model number & Serial
number.
Below figure 3.1-1 gives the complete idea about this menu.
Enter the password needed for the desired level: the password contains four digits. The digits
are entered from left to right one by one by first moving to the position of the digit using the
RIGHT key and then setting the desired digit value using the UP key & to save the password
push the ENTER key. Please note that the relay password is 0002.
This window is used to determine the type of internal error generated in the relay. The
errors can be Calibration Error, Memory Error, Protection function or Monitoring function
related error. Whenever the relay encounters a particular type of error, the ERROR LED
glows, and the corresponding status Ok/Not Ok value is indicated in error window
To navigate the Error window follow procedure described below in figure 3.3-1.
1 2 3
This menu displays measured values of system Primary, Secondary voltages and currents,
Line to Neutral, Line to Line voltages, Sequence components of currents & voltages along
with Date and Time. It also displays Phase wise power parameters of KW, KVAR, KVA,
Power factor and system frequency.
1 2 3
3 4 5 6
6 7 8 9
The Last window in the measurement menu displays vector representation of 3 phase
system Voltages and Currents along with residual voltage & current as shown in below
figure 3.4-2.
IL3 UL3
IL1 UL1
IL2 UL2
If you left the measurement window idle for 5 sec you can observe the larger view than
the default one as shown in the figure 3.4-3.
This menu indicates the 1st to 15th harmonics in the bar graph manner to understand the
system conditions by phase wise for the both currents and voltages along with the THD
% (Total harmonic Distortion).
Harmonics: IL1
THD = 7.020 %
5.000
I
1 3 5 7 9 11 13 15
Freq
Configuration Menu allows the user to set the System parameters like phase, REF and
SEF CT, VT Primary, Secondary ratios, system frequency and the setting group for the
protection parameters.
6 7 8
Permissible Values:
CT PRIM : 020A - 4000A (In steps of 1A)
CT SEC : 1A/5A
VT PRIM : 3.3kV, 6.6kV, 11.00kV, 17.50kV, 22.00kV, 33.00kV
VT SEC : 100V – 120V (In steps of 1V)
SYS FRQ : 50Hz/60Hz
SETTING GROUP : 1, 2, 3, 4
Over current protection is used against the short circuit faults and the heavy over loads.
This protection measures the fundamental frequency components of the phase currents.
The protection is sensitive for the highest of the three phase currents. Whenever this value
exceeds the user pick up setting of a particular stage, that stage starts picking up and
Alarm signal is generated. If the fault situation persists for longer than the estimated trip
time configured in the relay, a trip signal is issued.
After protection function generates a trip command, it is expected that the circuit breaker
opens and/or the fault current drops below the pre-defined normal level. If not, then
additional trip command will be generated for all back up circuit breakers to clear the
fault.
Three phase time over current protection includes definite time and IDMT characteristics
as per IEC and IEEE standards.
Permissible Values:
3I> PROT : Enable/Disable
3I>SET : 5% -400% (In steps of 1%)
3I>Curve : IEC SI3, IECSI1, IEC VI, IEC EI, IEC LTI, IEEE VI, IEEE EI, IEEE
SI3, RI, RD, IAC SI3, IAC VI, IAC EI
3I>TMS : IEC Curves: 0.02 - 2(In steps of 0.01)
IAC, IEEE, RI & RD: 1.000-100.0 (In steps of 0.1)
3I>RST DT : 0.10S – 50.0S (In steps of 100ms)
3I>DT : INST & 0.100S-600.0S (In steps of 100ms)
Permissible Values:
3I>>PROT : Enable/Disable
3I>>SET : 50% -4000% (In steps of 1%)
3I>>DT : INST & 0.100S-600.0S (In steps of 100ms)
3I>>RST DT : 0.10S – 50.0S (In steps of 100ms)
7 8 9 10 11
PAGE
23
3.8. NON DIRECTIONAL EARTH FAULT PROTECTION
(51N) (EF):
The Non directional earth fault function is sensitive to the fundamental frequency component
of the residual current 3I0. Whenever this value exceeds the user pick up setting of a
particular stage, that stage starts picking up and Alarm signal is generated. If the fault
situation persists for longer than the estimated trip time configured in the relay, a trip signal is
issued.
8 9 10
Permissible Values:
Io> PROT : Enable/Disable
Io>SET : 5% -400% (In steps of 1%)
Io>Curve : IEC SI3, IECSI1, IEC VI, IEC EI, IEC LTI, IEEE VI, IEEE EI, IEEE
SI3, RI, RD, IAC SI3, IAC VI, IAC EI
Io>TMS : IEC Curves: 0.02 - 2(In steps of 0.01)
IAC, IEEE, RI & RD: 1.000-100.0 (In steps of 0.1)
Io>RST DT : 0.10S – 50.0S (In steps of 100ms)
Io>DT : INST & 0.100S-600.0S (In steps of 100ms)
Permissible Values:
Io>>PROT : Enable/Disable
Io>>SET : 50% -4000% (In steps of 1%)
Io>>DT : INST & 0.100S-600.0S (In steps of 100ms)
Io>>RST DT : 0.10S – 50.0S (In steps of 100ms)
If the fault current can flow in both directions through a relay location, it is necessary to
add directionality to over current relays to obtain the exact fault finding. For example
parallel feeders and Ring main systems.
In order to give directionality to over current element there should be a suitable reference
or Polarization angle. System voltages should be taken as a reference because under fault
conditions also there is no change in the Reference angle. Under system fault conditions
fault current vector will generally lags its nominal phase voltage by an angle. To achieve
the maximum sensitivity for the currents directional element should be act in required
region; this can be achieved by directional angle of the relay. The stages are sensitive to
the amplitude of the highest fundamental frequency current of the three measured phase
currents.
Three phase time over current protection includes definite time and IDMT characteristics
as per IEC and IEEE standards.
Permissible Values:
3I> PROT : Enable/Disable
3I>SET : 005% -400% (In steps of 1%)
3I>Curve : IEC SI3, IECSI1, IEC VI, IEC EI, IEC LTI, IEEE VI, IEEE EI, IEEE
SI3 RI, RD, IAC SI3, IAC VI, IAC EI
3I>TMS : IEC Curves: 0.02 - 2(In steps of 0.01)
IEEE RI & RD: 1.000-100.0 (In steps of 0.1)
RST DT : 0.10S – 50.0S (In steps of 100ms)
3I>DT : INST & 0.100S-600.0S (In steps of 100ms)
Permissible Values:
3I>>PROT : Enable/Disable
3I>>SET : 050% -4000% (In steps of 1%)
3I>>DT : INST & 0.100S-600.0S (In steps of 100ms)
RST DT : 0.10S – 50.0S (In steps of 100ms)
Permissible Values:
DIR ANG: 180° to -180° (In steps of 1°)
Polarization TYPE: PH-N, PH-PH, CROSS
In the PH-N polarization we can assign the reference parameters as per our requirement
w.r.t phase wise currents.
e.g. IL1: Va FWD can be set as IL1: Vb FWD or IL1: Vc FWD
POLARIZATION : PH-PH
In the PH-PH polarization we can assign the reference parameters as per our requirement
w.r.t phase wise currents.
e.g. IL1: Vab REV can be set as IL1: Vbc REV or IL1: Vca REV
POLARIZATION: CROSS
In the case of CROSS Polarization we can change only operating regions for the
directional element.
e.g. IL1: Vbc FWD can be set as IL1: Vbc REV only.
9 10 11 12
PAGE
28
3.10. DIRECTIONAL EARTH FAULT PROTECTION (67N)
(D-EF):
The directional earth fault elements are available with independently settable two stages.
In the case of Earth fault directional elements are internally polarized by Zero sequence
voltage (Uo), Neutral voltage (ULo) and also Reactive and capacitive components which
are useful in the case of Compensated networks & Un-earthed networks.
Whenever the size of current and reference parameter and the phase angle between them
fulfils the pickup Criteria, that stage starts picking up and Alarm signal is generated. If the
fault situation persists for longer than the estimated trip time configured in the relay, a trip
signal is issued.
Permissible Values:
Io> PROT : Enable/Disable
Io>SET : 005% -400% (In steps of 1%)
Io>Curve : IEC SI3, IECSI1, IEC VI, IEC EI, IEC LTI, IEEE VI, IEEE EI, IEEE
SI3 RI, RD, IAC SI3, IAC VI, IAC EI
Io>TMS : IEC Curves: 0.02 - 2(In steps of 0.01)
IEEE RI & RD: 1.000-100.0 (In steps of 0.1)
RST DT : 0.10S – 50.0S (In steps of 100ms)
Io>DT : INST & 0.100S-600.0S (In steps of 100ms)
Permissible Values:
Io>>PROT : Enable/Disable
Io>>SET : 050% -2000% (In steps of 1%)
Io>>DT : INST & 0.100S-600.0S (In steps of 100ms)
Io>>RST DT : 0.10S – 50.0S (In steps of 100ms)
Permissible Values:
Io DIR ANG : 180° to -180° (In steps of 1°)
Io Pol TYPE : Vn-In, Vo-Io, I Sinϴ , Icosϴ
F/R Dir : FWD,REV
9 9 9 9
PAGE
30
3.11. OVER VOLTAGE PROTECTION (59) (OV):
Over Voltage conditions generally related to loss of load conditions. Under load
shedding conditions, supply voltage will increase in the magnitude. This situation would
normally rectify by the voltage regulating equipments such as AVRs or On Load Tap
changers. However failure of this equipments to bring back the system to normal
condition, this would create over voltage which should be identified with the Over
voltage protection element otherwise system insulation life will decrease.
10
11 12 13
The IDMT Stage of AEGIS Feeder Protection Relay consists of variable Characteristics
i.e. Curve1, Curve2, Curve3, Curve4 and DT for the Relay operation
Permissible Values:
3U> PROT : Enable/Disable
3U>SET : 105% -170% (In steps of 1%)
3U>Curve : Curve1, Curve2, Curve3, Curve4 and DT
3U>TMS : 0.02 - 2(In steps of 0.01)
3U>RST DT : 0.10S – 50.0S (In steps of 100ms)
3U>DT : INST & 0.100S-600.0S (In steps of 100ms)
Permissible Values:
3U>>PROT : Enable/Disable
3U>>SET : 150% -200% (In steps of 1%)
3U>DT : INST & 0.100S-600.0S (In steps of 100ms)
3U>RST DT : 0.10S – 50.0S (In steps of 100ms)
Voltage regulating equipments such as AVRs and On Load Tap changers should take
action in maintaining the healthy voltage in the system. If those voltage regulating
equipments are unsuccessful to bring back the system to healthy condition, then tripping
signal will be issued by the under voltage element with assigned delay.
The proportion by which voltage decreases depends on the type of fault and location of the
relay with respect to the fault point.
Even dead bus setting can also be configured through the NV PROT element.
11
12 13 14
The IDMT Stage of AEGIS Feeder Protection Relay consists of variable Characteristics
i.e. Curve1, Curve2, Curve3, Curve4 and DT for the Relay operation
Permissible Values:
3U< PROT : Enable/Disable
3U<SET : 45% -90% (In steps of 1%)
3U<Curve : Curve1, Curve2 and DT
3U<TMS : 0.02 – 2.00 (In steps of 0.01)
NV PROT : Enable/Disable
Permissible Values:
3U<<PROT : Enable/Disable
3U<<SET : 25% -50% (In steps of 1%)
3U<<DT : INST & 0.100S-600.0S (In steps of 100ms)
3U<<RST DT : 0.10S – 50.0S (In steps of 100ms)
NV PROT : Enable/Disable
NO Volt : 003% - 020%
On a healthy three phase power system, the addition of the each of the three phases to
earth voltages is zero nominally, as these results from the vector addition of the three
balanced vectors displaced by 120°.When an earth fault occurs this balance will be
disturbed and residual voltage is produced. This can be measured by Residual voltage
measuring element .This condition causes a rise in the neutral voltage with respect to
earth, which is commonly referred to as a “Neutral Voltage Displacement”
Voltage Setting applied to the protection elements is dependent on the magnitude of the
residual voltage that is expected to occur during the fault conditions. There are two ways
for calculating the neutral voltage displacement described below.
3VO: The zero sequence voltage is calculated internally from the phase voltages.
OPEN DELTA: The zero sequence voltage is measured with open delta voltage.
12
13 14
The most of the faults in the power system are shunt type of faults, due to this kind of
faults there is appreciable amount of current will increase and are easily detectable in most
applications. Another type of unbalanced system condition is the series or open circuit
fault .This fault can arise from broken conductor, mal operation of single phase
switchgear, or the operation of fuses. Open circuit faults should not produce over current
to sense, however they will produce unbalance components of currents (Negative sequence
over current) which can be identified.
But at light load conditions I2 may close to the full load steady state unbalance arising
from CT errors, load unbalance etc. By taking the ratio of I2/I1, we can achieve the better
efficiency because ratio is constant with the variations of load current.
13
14 15
The Broken conductor Stage of AEGIS Feeder Protection Relay consists of definite time
Characteristics for the Relay operation
Permissible Values:
BC PROT : Enable/Disable
BC SET : 020% - 100% (In steps of 1%)
BC DT : INST & 0.100S - 600.0S (In steps of 100ms)
BC RST DT : 0.10S - 50.0S (In steps of 100ms)
14
15 16
Permissible Values:
3I2f>PROT : Enable/Disable
LOW SET : 005% - 100% (In steps of 1%)
(It depends on the value of HIGH SET i.e. we can‟t set LOW SET above
HIGH SET)
HIGH SET : 005% - 100% (In steps of 1%)
(It depends on the value of LOW SET i.e. we can‟t set HIGH SET below
LOW SET)
DT : INST & 0.10 – 1.00 (In steps of 100ms)
If2/If1 : 000% - 100% (In steps of 1%)
If5/If1 : 000% - 100% (In steps of 1%)
If2 AND/OR If5
I>PROT : Enable/Disable
I>>PROT : Enable/Disable
I>PROT : Enable/Disable
I>>PROT : Enable/Disable
Current transformer supervision is provided to detect loss of phase CT signals and inhibit
the operation of current dependent protection elements.
The CT supervisor function measures phase currents. If one of the three phase currents drops
below Imin< setting, while another phase current is exceeding the Imax> setting, the
function will issue an alarm after the operation delay has elapsed.
15
16 17
Permissible Values:
PROT : Enable/Disable
Imax : 000% - 1000% (In steps of 1%)
(It depends on the value of Imin i.e. we can‟t set Imax below Imin)
Imin : 000% - 1000% (In steps of 1%)
(It depends on the value of Imax i.e. we can‟t set Imin above Imax)
DT : INST & 0.100S-600.0S (In steps of 100ms)
RST DT : 0.10S – 50.0S (In steps of 100ms)
The VT fuse failure supervision detects failures between the voltage measurement circuit
and the Relay. The failures are detected by the delta voltage and delta current algorithm.
Upon the detection of fuse failure supervision function based on the time of operation
relay will operate.
The VTFF function measures the three phase voltages and currents. The negative sequence
voltage U2 and the negative sequence current I2 are calculated. If U2 exceed the
U2> setting and at the same time, I2 is less than the I2< setting, the function will issue an
alarm after the operation delay has elapsed.
16
17 18
Permissible Values:
PROT : Enable/Disable
I2< SET :005% - 200% (In steps of 1%)
U2> SET : 001% - 170% (In steps of 1%)
DT : INST & 0.100S-600.0S (In steps of 100ms)
RST DT : 0.10S – 50.0S (In steps of 100ms)
17
18 19
Permissible Values:
I2> PROT : Enable/Disable
SET : 001% - 050% (In steps of 1%)
CURVE : DT,IEC SI1, IEC SI3, IEC VI, IEC EI, IEC LTI, IEEE SI3, IEEE EI,
IEEE VI, CURVE1 & CURVE2
TMS : 0.02 – 2.00 (In steps of 0.01)
K : 1.000 – 100.0 (In steps of 0.1)
K1 : 0.90 – 1.20 (In steps of 0.1)
RST DT : 0.10S – 50.0S (In steps of 100ms)
DT : INST & 0.100S-600.0S (In steps of 100ms)
10
9
Permissible Values:
PROT : Enable/Disable
SET : 0.5%-95% (In steps of 1%)
DT : INST & 0.100S-600.0S (In steps of 100ms)
RST DT : 0.10S – 50.0S (In steps of 100ms)
10 11
Permissible Values:
PROT : Enable/Disable
SET : 1%-100% (In steps of 1%)
DT : INST & 0.100S-600.0S (In steps of 100ms)
RST DT : 0.10S – 50.0S (In steps of 100ms)
20
21 22
Permissible Values:
PROT : Enable/Disable
SET : 0% to -200% (In steps of 1%)
DT : INST & 0.100S-600.0S (In steps of 100ms)
RST DT : 0.10S – 50.0S (In steps of 100ms)
Thermal overload protection can be applied to prevent the damages to the equipment of the
electrical plant when operating at temperatures that are above values are designed for
maximum withstand. A prolonged overloading causes excessive heating, which may result in
deterioration of insulation and insulation failure.
AEGIS Relay incorporates a current based thermal replica, using load current to reproduce
the heating and cooling of the equipment to be protected.
The thermal state is calculated using the measured True RMS values of current.
Formula for the calculating the operating time
20
21 22
Permissible Values:
49 PROT : Enable/Disable
49 SET : 10%-300% (In steps of 1%)
49 Topr : 1min-1000 min (In steps of 30s)
A transient fault is a self-clearing „non-damage‟ fault. This type of fault can be isolated and
Cleared by the immediate tripping of one or more circuit breakers, and does not recur when
the line is re-energized. The most common cause of transient faults are lightning, insulator
flashover clashing conductors and windblown debris. The immediate trip will not clear a non-
permanent or permanent fault, and the use of the recloser may be necessary to clear it.
Autoreclose schemes are used to automatically reclose a switching device once a time delay
has elapsed and starting after the CB has opened. Using the autoreclose minimizes time of
interruption and reduces operating costs.
This Autoreclose function can perform two, three or four shot cycle. The no. of shots can be
programmed to each and every function. Tripping of any function will trigger the Auto
Reclose provided
Breaker was closed before that. The Dead times (tD1, tD2, tD3 and tD4) starts when the CB
has tripped. The Reclaim time (tR) starts when the CB has closed.
If the protection operates during the tR, the Relay either advances to the next shot that is
programmed in Autoreclose cycle or if all the programmed reclose attempts have been
accomplished, it locks out. Lockout status can be cleared by pressing the Esc key. If the
circuit breaker does not trip during tR, the Auto Reclose function resets at the end of Reclaim
time.
“AR in Progress” and “AR Lockout” information can be programmed to a LEDS in the
Autoreclose Menu.
19
20 21 22
Permissible Values:
The rear port of the relay can be configured for various settings as listed below:
18
19
Permissible Values:
PROTOCOL : MODBUS, IEC 103, CG VIEW, IEC 61850
BAUDRATE : 2400, 4800, 9600, 19200, 38400, 57600
PARITY : NONE, EVEN, ODD
RLY ADRS : 000-254 (In steps of 001)
PERIOD : 000S – 060S (In steps of 001)
SCALING : 1.2X, 2.4X
Relay having multiple Binary inputs & Binary outputs. The configuration allows to
program or assign any relay output for any fault Pick-up and trip condition. The relay
outputs can be configured on Digital Inputs.
20
21
Aegis Feeder Protection Relay stores the latest 10 faults occurred in the system. Follow the
below procedure to view the fault records.
4 5 13
5 6 14
6 7 15
Aegis Feeder Protection Relay stores the latest 10 faults occurred in the system. Follow the
below procedure to view the fault records.
Fault Number
Fault Currents
4
Fault Voltages
Fault type
The disturbance recorder can be used to record all the measured signals, that is, currents,
voltages and the status information of digital inputs (DI) and digital outputs (DO) in
oscillographic manner. The recorder can be triggered by any start or trip signal from any
protection stage or by a digital input. The triggering signal is selected in the output matrix
(vertical signal DR). The recording can also be triggered manually. All recordings are time
stamped.
The disturbance records can be down loaded & viewed in Aegis relay configuration
software.
Permissible Values:
DIST. REC : ENABLE/DISABLE
PRE-FAULT : 000% - 100% (In steps of 1%)
SAMPLE : 8/Cycle, 16/Cycle, 32/Cycle
DR TRGR : YES/NO
- Burden <0.3VA@1A
<0.5VA@5A
- Burden <0.15VA@70VAC
<0.3VA@120VAC
4.2.2. CASING
Degree of protection (IEC 60529) IP54
Dimensions (W x H x D) 188.58 x 199.18 x 228.40 mm
Material 0.8mm AluZinc
Weight 750 gm
4.2.3. PACKAGE
Dimensions (W x H x D) 188.58 x 199.18 x 228.40
Weight (Terminal, Package and Manual) 5.4 kg
No of Shot 1/2/3/4/
Setting Range
Dead Time (tD1) 0.1s-300.0s (step 200ms)
Dead Time (tD2) 0.1s-300.0s (step 200ms)
Dead Time (tD3) 0.1s-300.0s (step 200ms)
Dead Time (tD4) 0.1s-300.0s (step 200ms)
ReCLM Time (tR) 0.1s-600.0s (step 200ms)
Inaccuracy :
Operating time at definite time function ± 1% or ± 30 ms
X1
NO. SYMBOL DESCRIPTION
1 1 REF
REF Current Input (1A/5A)
2 2 REF
3 3 SEF
SEF Current Input (1A/5A)
4 4 SEF
5 5 IL1
Rph Current Input (1A/5A)
6 6 IL1
7 7 IL2
Yph Current Input (1A/5A)
8 8 IL2
9 9 IL3
Bph Current Input (1A/5A)
10 10 IL3
11 11 ILo
Eph Current Input (1A/5A)
12 12 ILo
X2
X3
X5
FRONT VIEW
IEC SI3
(Standard Inverse 3)
IEC SI1
(Standard Inverse 1)
IEC VI
(Very Inverse)
IEC EI
(Extremely Inverse)
IEC LTI
(Long Time Inverse)
IEEE VI
(Very Inverse)
IEEE EI
(Extremely Inverse)
IEEE SI3
(Standard Inverse)
RI
RD
IAC SI3
(Standard Inverse 3)
IAC SI3
(Extremely Inverse)
Various characteristics IEC Curves for the Over Current protection as shown in below
figure:
Curve 1
Curve 2
Curve 3
Curve 4
Characteristic Equation
Curve 1
Curve 2
Curve 1
Curve 2
AEGIS F
PROTECTION FUNCTION
Three Phase O/C & E/F (50/51/50N/51N)
Three Phase Directional O/C & E/F (67/67N)
Three Phase O/V, U/V & NDR (27,59,59N)
Negative Phase Sequence (46)
A
Cold load Pick up & Inrush
CBFP (50BF) , Broken Conductor (46BC)
Power Measurement (P)
VTS & CTS
MODEL NO:
SERIAL NO:
CUSTOMER
PARAMETER
SETTINGS
CT PRIM :
CT SEC :
VT PRIM :
VT SEC :
SYS FRQ :
SETTING GROUP
CUSTOMER
PARAMETER
SETTINGS
3I> PROT :
3I>SET :
3I>Curve :
3I>TMS :
3I>RST DT :
3I>DT :
CUSTOMER
PARAMETER
SETTINGS
3I>>PROT:
3I>>SET :
3I>>DT :
3I>>RST DT :
CUSTOMER
PARAMETER
SETTINGS
Io> PROT :
Io>SET :
Io>Curve :
Io>TMS :
Io>RST DT :
Io>DT :
CUSTOMER
PARAMETER
SETTINGS
Io>>PROT:
Io>>SET :
Io>>DT :
Io>>RST DT :
CUSTOMER
PARAMETER
SETTINGS
3I> PROT :
3I>SET :
3I>Curve :
3I>TMS :
RST DT :
3I>DT :
CUSTOMER
PARAMETER
SETTINGS
3I>>PROT:
3I>>SET :
3I>>DT :
RSTDT :
CUSTOMER
PARAMETER
SETTINGS
DIR ANG :
Pol Type :
IL1 :
IL2 :
IL3 :
CUSTOMER
PARAMETER
SETTINGS
Io> PROT :
Io>SET :
Io>Curve :
Io>TMS :
Io>RST DT :
Io>DT :
CUSTOMER
PARAMETER
SETTINGS
Io>>PROT:
Io>>SET :
Io>>DT :
Io>>RST DT :
CUSTOMER
PARAMETER
SETTINGS
Io DIR ANG :
Io Pol Type :
F/R DIR :
CUSTOMER
PARAMETER
SETTINGS
PROT :
SET :
DT :
RST DT :
CUSTOMER
PARAMETER
SETTINGS
PROT :
SET :
DT :
RST DT :
CUSTOMER
PARAMETER
SETTINGS
3U> PROT :
3U>SET :
3U>Curve :
3U>TMS :
3U>RST DT :
3U>DT :
CUSTOMER
PARAMETER
SETTINGS
3U>>PROT:
3U>>SET :
3U>>DT :
3U>>RST DT :
CUSTOMER
PARAMETER
SETTINGS
3U< PROT :
3U<SET :
3U<Curve :
3U<TMS :
NV PROT :
NV VOLT :
3U<RST DT :
3U<DT :
CUSTOMER
PARAMETER
SETTINGS
3U<<PROT:
3U<<SET :
3U<<DT :
3U<<RST DT :
NV PROT :
NV VOLT :
CUSTOMER
PARAMETER
SETTINGS
PROT:
TYPE :
SET :
CURVE :
TMS :
RST DT :
DT:
CUSTOMER
PARAMETER
SETTINGS
BC PROT :
SET :
BC DT :
BC RST DT:
CUSTOMER
PARAMETER
SETTINGS
3I2f>PROT:
LOW SET :
HIGH SET :
DT :
If2/If1 :
If5/If1 :
If2 AND/OR If5 :
I>PROT :
I>>PROT :
I>PROT :
I>>PROT :
CUSTOMER
PARAMETER
SETTINGS
PROT :
Imax :
Imin :
DT :
RST DT :
CUSTOMER
PARAMETER
SETTINGS
PROT :
I2<SET :
U2>SET :
DT :
RST DT :
CUSTOMER
PARAMETER
SETTINGS
I2>PROT :
SET :
CURVE :
TMS :
K1 :
RST DT :
DT :
CUSTOMER
PARAMETER
SETTINGS
PROT
SET
DT :
RST DT :
CUSTOMER
PARAMETER
SETTINGS
PROT
SET
Topr :
CUSTOMER
PARAMETER
SETTINGS
No. of shot
DEAD TIME1 (tD1)
DEAD TIME2 (tD2)
DEAD TIME3 (tD3)
ReCLM TIME (tR)
AR ON PROT
PROGRESS LED
LOCKOUT LED
LOCKOUT RLY
CLR LOCKOUT
LOCKOUT STS
CUSTOMER
PARAMETER
SETTINGS
PROTOCOL :
BAUDRATE :
PARITY :
RLY ADRS :
PERIOD :
SCALING :
Registered Office
CG House, 6th Floor, Dr.Annie Besant Road, Worli, Mumbai-400 030
Visit us at: www.cgglobal.com Doc. No. : AEGIS-F-A-01