Sie sind auf Seite 1von 4

STP SIZING CALCULATIONS

Given
Design Parameters Value Unit
Q (Capacity) 350 m3/day
BOD initial 350 mg/L

BOD final 50 mg/L


Detention Time(EQT) 6 hrs
Detention Time(CCT) 0.5 hrs
X(MLSS) 3000 mg/L
F/M 0.15
Sludge Age, Qc 10 days
Max Yield Coefficient, Yd 0.4 mg/mg
Kinematic Coefficient, Kd 0.06 /day
Density of Water, ρw 1000 kg/m3
Specific Gravity of Sludge, Ssl 1.02
Percent Soil as decimal, Ps 0.1
Sludge Growth Age (SGA) 0.6
Sludge Destruction Rate (SDR) 0.5
Sludge Concentration (SC) 0.02
Peak Factor 1.5
Equalization Tank
Formula

Volume of Influent Chamber (V)


87.5 m3
88 m3
Formula

Volume of EQT (V)


131.25 m3
132 m3
SBR Tank
Formula

Volume of SBR Tank (V)

233.33333 m3
234 m3
Chlorine Contact Tank
Formula

Volume of CCT (V)


7.2916667 m3
8 m3
Aerobic Sludge Digester
Formula

Sludge Production Rate (Px)


26.25 kg/day
27 kg/day

Yobs
0.25
0.25

Volume of Sludge Generated, Vb


0.2573529 m3/day
0.258 m /day
3

Volume of Sludge Digester, V


18.375 m3
19 m3
CALCULATIONS
Given
Assumptions

350 mg/L (For Residential);


800 mg/L (For Commercial)
50 mg/L DAO-2016-08 varies
6 hours varies
30 minutes varies
3000 mg/L varies
0.15 varies
10 days varies
0.4 mg/mg varies
0.06 per day varies

60%
50%
2%

zation Tank
Formula

Remarks:

Formula

Remarks:

BR Tank
Formula

Remarks:

Contact Tank
Formula

Remarks:

Sludge Digester
Formula

Remarks:

Remarks:

Remarks:

Remarks:

Das könnte Ihnen auch gefallen